Professional Documents
Culture Documents
Standby Batteries
ADVANTAGES OF SUNLIGHT OPzS
HIGH RELIABILITY AND ROBUSTNESS
ñ Compliant to DIN 40736 and EN 60896-1.
CONSTRUCTION SAFETY
ñ TUBULAR POSITIVE PLATES ñ Leak proof safety poles.
The positive plates are made of thick lead low antimony alloy tubes. ñ Explosion proof caps to prevent acid leakage
ñ NEGATIVE PLATES
ñ SEPARATORS APPLICATIONS
Microporous separators with a high porosity grade so as to ensure ñ Telecommunications
better ionic circulation and low internal resistance. ñ Control and monitoring systems in power plants and
ñ TERMINALS
ñ VENT PLUGS
Ceramic.
EASY UTILISATION
ñ Available in 2V cells, 6V and 12V monoblocks.
condition.
2
3
INSTALLATION
STANDARD TYPES
Available as:
1 row 1 row
2 row 2 row
1 floor 2 floor
3 row 3 row
.. row .. row
Available as:
2 step 2 step
4 step 4 step
SPECIAL TYPES
(for use in earthquake zones)
Available as:
1 row 1 row
.. row .. row
SUNLIGHT OPzS cells are suitable for all standard types of installation.
When installed in battery rooms EN 50272-2 standard must be applied.
4
General Characteristics
Positive plate Cell Dimensions (mm) Weight (kg) Volume of
Capacity (Ah)
separate
Type Designation acc. To
with without electrolyte
Size DIN 40736-1 h1 h2
No. a b e electrolyte electrolyte (lt)
(Ah)
(kg) (kg)
Monoblocks
6 V 3 OPzS 150 3x3 150 234 201 345,0 380 - 41.2 29.8 9,2
6 V 4 OPzS 200 3x4 200 272 205 350,0 388 - 47.1 35.2 9.6
6 V 5 OPzS 250 3x5 250 380 205 350,0 388 - 60.9 43.5 14.0
6 V 6 OPzS 300 3x6 50 300 380 205 350,0 388 - 67.1 50.5 13.4
12V 1 OPzS 50 6x1 50 272 205 350,0 388 - 37.7 24.4 10.7
12V 2 OPzS 100 6x2 100 272 205 350,0 388 - 49.4 37.7 9.4
12V 3 OPzS 150 6x4 150 380 205 350,0 388 - 69.8 53.0 13.5
2 V cells
2 OPzS 100* 2 100 103 206 355 380 - 13.8 8.4 4.4
3 OPzS 150* 3 150 103 206 355 380 - 15.7 10.7 4.0
4 OPzS 200 4 50 200 103 206 355 380 - 17.5 13.0 3.6
5 OPzS 250 5 250 124 206 355 380 - 21.4 15.4 4.8
6 OPzS 300 6 300 145 206 355 380 - 25.7 18.5 5.8
5 OPzS 350 5 350 124 206 471 496 - 28.4 20.7 6.2
6 OPzS 420 6 70 420 145 206 471 496 - 33.5 24.3 7.4
7 OPzS 490 7 490 166 206 471 496 - 38.6 27.9 8.6
5 OPzS 500* 5 500 145 206 646 671 - 42.0 28.8 10.6
6 OPzS 600 6 600 145 206 646 671 - 45.8 33.0 10.3
7 OPzS 700* 7 700 191 210 646 671 80 60.0 42.7 14.0
8 OPzS 800 8 100 800 191 210 646 671 80 63.8 46.8 13.7
9 OPzS 900* 9 900 233 210 646 671 110 73.0 53.0 16.1
10 OPzS 1000 10 1000 233 210 646 671 110 78.2 57.3 16.9
12 OPzS 1200 12 1200 275 210 646 671 140 91.3 66.2 20.2
11 OPzS 1400* 11 1400 275 210 796 821 140 110.5 76.0 27.8
12 OPzS 1500 12 1500 275 210 796 821 140 115.1 81.1 27.4
14 OPzS 1700* 14 1700 397 212 772 797 2x110 143.3 96.3 37.9
15 OPzS 1875 15 125 1875 397 212 772 797 2x110 148.9 102.6 37.3
16 OPzS 2000 16 2000 397 212 772 797 2x110 154.5 108.8 36.9
20 OPzS 2500 20 2500 487 212 772 797 3x110 201.0 135.0 53.2
24 OPzS 3000 24 3000 576 212 772 797 3x140 230.0 158.0 58.1
6V 3OPzS 150 - 12V 1OPzS 50 - 2 OPzS 100 - 7 OPzS 700 - 14 OPzS 1700 - 20 OPzS 2500 -
6V 6OPzS 300 12V 3OPzS 150 6 OPzS 600 12 OPzS 1500 16 OPzS 2000 24 OPzS 3000
h1 h2 h1 h2
h1 h2
h1 h2
b 10
b 10
e
b 10
I B/L I B/L a 2 (10**) a e
e
b/w b/w
a
- -
a e e e
b
+ + + - + -
Above mentioned dimensions and weights are subject to the usual manufacturing tolerances
5
End of discharge voltage: 1,90 V/cell in Amps
30 min 1h 2h 3h 5h 8h 10h
Monoblocks
6 V 3 OPzS 150 61.7 48.8 35.8 28.3 20.3 14.6 12.5
6 V 4 OPzS 200 82.2 65.0 47.7 37.7 27.1 19.5 16.6
6 V 5 OPzS 250 102.8 81.3 59.6 47.2 33.9 24.4 20.8
6 V 6 OPzS 300 123.4 97.5 71.6 56.6 40.7 29.3 24.9
12 V 1 OPzS 50 20.6 16.3 11.9 9.4 6.8 4.9 4.2
12 V 2 OPzS 100 41.1 32.5 23.9 18.9 13.6 9.8 8.3
12 V 3 OPzS 150 61.7 48.8 35.8 28.3 20.3 14.6 12.5
2 V cells
2 OPzS 100 41.1 32.5 23.9 18.9 13.6 9.8 8.3
3 OPzS 150 61.7 48.8 35.8 28.3 20.3 14.6 12.5
4 OPzS 200 82.2 65.0 47.7 37.7 27.1 19.5 16.6
5 OPzS 250 102.8 81.3 59.6 47.2 33.9 24.4 20.8
T y p e
Monoblocks
6 V 3 OPzS 150 71.3 55.5 39.9 31.4 22.4 16.1 13.7
6 V 4 OPzS 200 95.1 74.0 53.3 41.8 29.9 21.4 18.2
6 V 5 OPzS 250 118.9 92.5 66.6 52.3 37.4 26.8 22.8
6 V 6 OPzS 300 142.7 111.0 79.9 62.8 44.9 32.2 27.3
12 V 1 OPzS 50 23.8 18.5 13.3 10.5 7.5 5.4 4.6
12 V 2 OPzS 100 47.6 37.0 26.6 20.9 15.0 10.7 9.1
12 V 3 OPzS 150 71.3 55.5 39.9 31.4 22.4 16.1 13.7
2 V cells
2 OPzS 100 47.6 37.0 26.6 20.9 15.0 10.7 9.1
3 OPzS 150 71.3 55.5 39.9 31.4 22.4 16.1 13.7
4 OPzS 200 95.1 74.0 53.3 41.8 29.9 21.4 18.2
5 OPzS 250 118.9 92.5 66.6 52.3 37.4 26.8 22.8
T y p e
6
End of discharge voltage: 1,83 V/cell in Amps
30 min 1h 2h 3h 5h 8h 10h
Monoblocks
6 V 3 OPzS 150 83.7 63.8 44.2 34.3 24.2 17.2 14.6
6 V 4 OPzS 200 111.6 85.0 58.9 45.7 32.2 22.9 19.4
6 V 5 OPzS 250 139.6 106.3 73.6 57.1 40.3 28.7 24.3
6 V 6 OPzS 300 167.5 127.5 88.4 68.5 48.4 34.4 29.1
12 V 1 OPzS 50 27.9 21.3 14.7 11.4 8.1 5.7 4.9
12 V 2 OPzS 100 55.8 42.5 29.5 22.8 16.1 11.5 9.7
12 V 3 OPzS 150 83.7 63.8 44.2 34.3 24.2 17.2 14.6
2 V cells
2 OPzS 100 55.8 42.5 29.5 22.8 16.1 11.5 9.7
3 OPzS 150 83.7 63.8 44.2 34.3 24.2 17.2 14.6
4 OPzS 200 111.6 85.0 58.9 45.7 32.2 22.9 19.4
5 OPzS 250 139.6 106.3 73.6 57.1 40.3 28.7 24.3
T y p e
Monoblocks
6 V 3 OPzS 150 90.6 69.0 46.7 35.9 25.1 17.8 15.0
6 V 4 OPzS 200 120.8 92.0 62.3 47.8 33.5 23.7 20.0
6 V 5 OPzS 250 151.0 115.0 77.8 59.8 41.9 29.6 25.0
6 V 6 OPzS 300 181.2 138.0 93.4 71.8 50.3 35.5 30.0
12 V 1 OPzS 50 30.2 23.0 15.6 12.0 8.4 5.9 5.0
12 V 2 OPzS 100 60.4 46.0 31.1 23.9 16.8 11.9 10.0
12 V 3 OPzS 150 90.6 69.0 46.7 35.9 25.1 17.8 15.0
2 V cells
2 OPzS 100 60.4 46.0 31.1 23.9 16.8 11.9 10.0
3 OPzS 150 90.6 69.0 46.7 35.9 25.1 17.8 15.0
4 OPzS 200 120.8 92.0 62.3 47.8 33.5 23.7 20.0
5 OPzS 250 151.0 115.0 77.8 59.8 41.9 29.6 25.0
T y p e
7
End of discharge voltage: 1,75 V/cell in Amps
30 min 1h 2h 3h 5h 8h 10h
Monoblocks
6 V 3 OPzS 150 105.0 76.5 50.2 38.1 26.4 18.5
6 V 4 OPzS 200 140.0 102.0 67.0 50.9 35.2 24.7
6 V 5 OPzS 250 175.0 127.5 83.7 63.6 44.0 30.9
6 V 6 OPzS 300 210.0 153.0 100.4 76.3 52.8 37.1
12 V 1 OPzS 50 35.0 25.5 16.7 12.7 8.8 6.2
12 V 2 OPzS 100 70.0 51.0 33.5 25.4 17.6 12.4
12 V 3 OPzS 150 105.0 76.5 50.2 38.1 26.4 18.5
2 V cells
2 OPzS 100 70.0 51.0 33.5 25.4 17.6 12.4
3 OPzS 150 105.0 76.5 50.2 38.1 26.4 18.5
4 OPzS 200 140.0 102.0 67.0 50.9 35.2 24.7
5 OPzS 250 175.0 127.5 83.7 63.6 44.0 30.9
T y p e
Monoblocks
6 V 3 OPzS 150 115.5 81.8 52.5 39.5 27.2
6 V 4 OPzS 200 154.0 109.0 70.0 52.7 36.2
6 V 5 OPzS 250 192.5 136.3 87.5 65.9 45.3
6 V 6 OPzS 300 231.0 163.5 105.0 79.1 54.3
12 V 1 OPzS 50 38.5 27.3 17.5 13.2 9.1
12 V 2 OPzS 100 77.0 54.5 35.0 26.4 18.1
12 V 3 OPzS 150 115.5 81.8 52.5 39.5 27.2
2 V cells
2 OPzS 100 77.0 54.5 35.0 26.4 18.1
3 OPzS 150 115.5 81.8 52.5 39.5 27.2
4 OPzS 200 154.0 109.0 70.0 52.7 36.2
5 OPzS 250 192.5 136.3 87.5 65.9 45.3
T y p e
Electrical values are approximate, Alterations can be made in the view of technical improvements without prior notice. 8
2 30 500 1 2 79 59 1
? team
guess who
Head Office: Sunlight Factory: Sunlight Bulgaria LTD creative
www.sunlight.gr
Moskow Sales Office: Sunlight Cairo Sales Office:
24,Pereulok Smolensi 15 El - Hassan Str. Dokki
Moskow, Russia Giza, Egypt
Doc No 8.03/ b
Data in this document are subject to change without notice and become contractual only after written confirmation.
Germanos S.A.
SUNLIGHT FACTORY
History: It was established in 1977, as a Zinc - Carbon battery production unit and acquired
by GERMANOS in 1991. Since then, following an intensive development plan, it has been
tranformed to one of the most advanced factories in Europe.
Present status: It covers an area of more than 30.000 m2 in a field of total area 80.000m2
it employs more than 170 specialized engineers, technicians and workers and it has
currently installed the following production and/or assembly lines:
Quality Assurance:
SUNLIGHT factory has established and maintains a Quality Assurance System according to ISO 9001/AQAP 110
that has been certified by TUV CERT. The Quality Control Department ensures the highest quality
and the outmost performance of the final product, while the R&D Dept focuses its
activities on the development of new products and improvement of the
existing manufacturing procedures.
Environmental Control:
SUNLIGHT Factory has established and maintains an Environmental Pollution Prevention System according
to EN 14001 that has been certified by TUV CERT. Special engineering and expensive
machinery ensure absolutely clean working conditions as well as
protection of the natural environment.