You are on page 1of 64

User Manual

MCS 2200
Monitoring and Control System

System Operating Display - SOD 2200


Layout and Operating Instructions

Item No.: 815.000 401 Revision: – (2006-09)


© SAM Electronics GmbH 200X
The reproduction, distribution, and utilization of this document as well as the
communication of its content to others without explicit authorization is prohibited.
Offenders will be held liable for the payment of damages.
All rights reserved in the event of the grant of a patent, utility model, or design.
Alterations due to technical progress are reserved.

SAM Electronics GmbH


D - 22763 Hamburg

Service
Customer Support Center

Phone: + 49 (0) 18 03 00 85 53
Fax: + 49 (0) 18 03 00 85 54
E-mail: shipservice@sam-electronics.de
MCS 2200 - Monitoring and Control System
User Manual

List of Contents

1 Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


1.1 Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Alarm Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.2 Alarm List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.3 Cut-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.4 Field Processing Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.5 Main Control Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.6 Watch Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 SOD 2200 Main Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1 Personal Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.2 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.3 Keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.4 Pointing Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.5 Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3 SOD 2200 Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


3.1 SOD 2200 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.1 Track Ball / Mouse Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 SOD 2200 Lists and Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1 Header Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1.1 Stop Horn and Alarm Acknowledgment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1.2 Header Diagram Layout Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.2 Main Menu Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.3 Alarm Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.3.1 Alarm List Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.3.2 Alarm List Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.3.3 Alarm Acknowledgement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.3.4 Open Display Channel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.3.5 Alarm List State Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.4 Alarm Group Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.5 Additional Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.5.1 Suppression Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.5.2 Failure Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.5.3 High Priority Alarm List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.6 Display Channel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.6.1 Display Channel Diagram Sections and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.6.2 Toolbar Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2.7 Standard Function Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2.7.1 Digital Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
© SAM Electronics GmbH

3.2.7.2 Analog Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29


3.2.8 Mimic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2.9 Control Right Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2.10 Journals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.3 Spare Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

4 SOD 2200 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

815.000 401 / – (2006-09) 3


MCS 2200 - Monitoring and Control System
User Manual

4.1 Open Alarm Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35


4.2 Open Cut-Out Lists, Simulation Lists, Sensor Fail Lists, or Device Fail Lists . . . . . . . . 35
4.3 Open Alarm Group Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.4 Stop Horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.5 Acknowledge Oldest Unacknowledged Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.6 Alarm Acknowledgement .................................................... 36
4.6.1 Unacknowledged Alarms in Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.6.2 Unacknowledged Alarms in Mimic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.6.3 Unacknowledged Alarms in Display Channel Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7 Open Display Channel Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7.1 Menu Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7.2 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7.2.1 Lists (Alarm List, Alarm Group, Additional Lists, and Journals) . . . . . . . . . . . . . . . . . . . . . . . . 38
4.7.2.2 Mimic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.8 Alarm Limits, Delays, and Cut-Out State Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.9 Simulated Values for Monitoring Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.10 Open Mimic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.11 Control Right Change-Over for a Machinery Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.12 Journals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.12.1 Journal Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.12.2 Journal Printout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.12.3 Journal Creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.12.4 Automatic Printout of Journals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.12.4.1 Daily Printout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.12.5 Cyclic Printout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.12.5.1 Overall Enabling of Automatic Printout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.13 Spare Channel Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.13.1 Binary Channel Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.13.1.1 Analog Channel Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.14 Change Alarm Channel Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.14.1 Changes in Alarm Channel Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4.14.2 Adjust Time and Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

5 List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

6 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
© SAM Electronics GmbH

4 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 1 Terminology and Abbreviations
User Manual 1.1 Terminology

1 Terminology and Abbreviations

1.1 Terminology

1.1.1 Alarm Group

An alarm group is a logical grouping of related alarm channels. A single alarm channel can be included
in more than one alarm group.

1.1.2 Alarm List

The Alarm List is a list containing all standing and/or unacknowledged alarms.

1.1.3 Cut-Out

An alarm channel can be suppressed by a Cut-Out signal in order to prevent the Alarm System from
generating a new alarm in an unwanted situation.
Example: A signal exceeds the preset alarm generation limit, but an alarm is not desired (e.g. when the
physical device is stopped/not running). The alarm channel is "cut-out". A manually or automatically
generated Cut-Out signal suppresses the respective alarm channel.

1.1.4 Field Processing Device

Field Processing Devices FPD 2200 are cabinets which can be set-up in any location on a ship. They are
interconnected by different kinds of communication networks. An FPD 2200 contains the necessary
modules (e.g. Central Processing Module CPM 2200) which are needed to connect all required input and
output channels and interfaces.

1.1.5 Main Control Station

The Main Control Station is the Watch Station of the Main Alarm System. Only at this station, alarms can
be acknowledged after the horn has been silenced. If more than one location on board the ship is
equipped with full remote indication and control facilities to fulfil the Main Control Station requirements, it
is possible to select the Main Control Station location according to the ship’s current environment (Deck/
Ship’s Office when in harbor, Engine Control Room when at sea, etc.).
© SAM Electronics GmbH

1.1.6 Watch Station

Alarms are announced and acknowledged at the Watch Station. Each Alarm System can have its own
Watch Station at different selectable locations on board of a ship.

815.000 401 / – (2006-09) 5


1 Terminology and Abbreviations MCS 2200 - Monitoring and Control System
1.2 Abbreviations User Manual

1.2 Abbreviations

AEP 2200 Alarm Extension Panel


DAP 2200 Duty Alarm Panel
DAP 2200-Accommoda- Accommodation Duty Alarm Panel(s)
tion
DAP 2200-Bridge Bridge Duty Alarm Panel
DAP 2200-ECR Engine Control Room Duty Alarm Panel
ECR Engine Control Room
FPD 2200 Field Processing Device
LOP 2200 Local Operating Panel
MCS 2200 Monitoring and Control System - MCS 2200
PCM 2200 Personal Computer Module
SOD 2200 System Operating Display
WS Watch Station

© SAM Electronics GmbH

6 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 2 Introduction
User Manual 2.1 SOD 2200 Main Components

2 Introduction

The System Operating Display SOD 2200 is a control and supervision interface for the Monitoring and
Control System MCS 2200. It handles the alarms generated by the MCS 2200 and the operator
commands.
The SOD 2200 is based on a Windows operating system. In addition to its main window, the SOD 2200
provides pop-up windows and dialogs for informational and operational purposes.
See Section 3 for detailed information about the SOD 2200 layout.
The SOD 2200 operation is keyboard based, but the most functions can be executed by using a track
ball or a standard PC mouse.
See Section 3.1 for detailed information about the operation of the SOD 2200.
Operation processes by the SOD 2200 are kept simple without limiting the operator’s access to all system
information. In fact, the SOD 2200 is able to present complex data in a user-friendly way.
The operator has a clear view of sophisticated workflows and will be able to control even the most
advanced features after just a few hours of practice.

2.1 SOD 2200 Main Components

The SOD 2200 can either be desk-mounted or built into a console. Operation procedures and functions
are identical for both types. They only differ with respect to screen size and type of pointing device.
In the following sections you will read more about the main components of the SOD 2200.

2.1.1 Personal Computer

The PC is the central component of the SOD 2200. It stores all relevant programs on hard disc and has
an interface card for the communication to all FPD 2200.

2.1.2 Screen

The SOD 2200 screen requires standard SXGA resolution (1280x1024) and is able to display graphics
and text at the same time.

2.1.3 Keyboard

The SOD 2200 keyboard is a standard PC keyboard (104/105 keys or more). Function keys (F1..F12) are
dedicated to special SOD 2200 functions and operations.
© SAM Electronics GmbH

See Section 4 for SOD 2200 function key operation.

2.1.4 Pointing Device

The SOD 2200 can be equipped with either a track ball or a standard PC mouse.

815.000 401 / – (2006-09) 7


2 Introduction MCS 2200 - Monitoring and Control System
2.1 SOD 2200 Main Components User Manual

The track ball is permanently mounted on the SOD 2200 console type. It features two push buttons and
a ball. The operator has to roll the ball with his palm or thumb in order to move the cursor to an item and
select/activate it by pushing the respective buttons.
The SOD 2200 mouse is a standard PC mouse and is mounted and operated in the same way as the
track ball.
See Section 3.1.1 and Figure 3-2 for detailed information about the SOD 2200 track ball and mouse oper-
ation.

2.1.5 Printer

An optional printer for report or screen hard copy printing can be connected directly to the SOD 2200.
See Section 4.12 for information about the SOD 2200 printout functions.

© SAM Electronics GmbH

8 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual

3 SOD 2200 Layout

The GUI (Graphical User Interface) of the SOD 2200 is divided into a header, a tree and an application
area.
The header is always visible. It displays the SOD 2200 Header Diagram.
The tree is a navigation area for mimic diagrams, system lists and modules. The tree is always visible,
as well.
The application area displays various selectable diagrams for machinery (or other, for example cargo)
component control and supervision procedures, for example Alarms Lists or Mimic Diagrams.
At start of the SOD 2200, the working area displays the Main Menu Diagram. From here, the operator
can access the other diagrams and lists in the system.
In addition to the header, tree, and application area, the SOD 2200 features a menu bar. The menu bar
displays the different selectable SOD 2200 functions.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 9


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
User Manual

The following image shows an SOD 2200 start display.

Fig. 3-1 SOD 2200 start display.

Menu bar: The menu bar incorporates several drop-down menus with selectable SOD
2200 functions, for example File, Edit, View, etc.

© SAM Electronics GmbH

10 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.1 SOD 2200 Operation

Header Diagram: The Header Diagram can display different header information, depending on
the Alarm System definition of the SOD 2200 location.
The Header Diagram holds important Alarm System information, including
number of alarms, number of unacknowledged alarms, oldest unacknowl-
edged alarm, Watch Station location, and duty officer selection.
The Header Diagram also contains short-cuts (selection buttons) to frequently
used functions, for example [MAIN MENU], [ALARM LIST], [STOP HORN],
etc.
For information about short-cut buttons, see Section 3.2.1.
The Header Diagram displays the date and the time, either in UTC or local
time. The indication of the time display type (UTC, LT) is optional.
For information about time and date adjustments, see Section 4.14.2
Application area: The application area can display different lists or diagrams.
Lists:
- Alarm List
- Alarm Group
- Failure Lists (sensor fail, device fail)
- Suppression Lists (Cut-Out List, Simulated Channel List)
- Journals
Diagrams:
- Mimic Diagram
- Function Block Diagram
- Graph Diagram
- Bar Graph Diagram
Tree area: - t.b.d.!!!

3.1 SOD 2200 Operation

Although the SOD 2200 operation is kept simple, some basic rules have to be observed.
An SOD 2200 diagram consists of a static background and dynamic objects. The latter can indicate
alarms, measurements, and states of machinery component.
Some dynamic objects are also active elements which can be used to carry out different actions, for
example opening diagrams, alarm acknowledgment, or sending commands to machinery components.

3.1.1 Track Ball / Mouse Operation

Most SOD 2200 operations can be carried out by use of a track ball (or a standard computer mouse
which offers the same functionalities).
© SAM Electronics GmbH

815.000 401 / – (2006-09) 11


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.1 SOD 2200 Operation User Manual

The track ball consists of a ball housed in a socket containing sensors to detect rotation of the ball about
two axes (like an upside-down mouse) and three push-buttons ([LEFT], [CENTER], [RIGHT]. Only [LEFT]
and [RIGHT] are used during SOD 2200 operation). The following figure shows a standard SOD 2200
tracker ball.
Left button
Used to select diagrams and objects

Center button
Not used

Right button
Used to acknowledge and open "Display
Channel" dialogs

Ball
Used to move the cursor

Fig. 3-2 SOD 2200 track ball.

The operator rolls the ball with his thumb or the palm of his hand to move the cursor on the display.
In this manual, to select or to left/right-click means to move the cursor on to a desired item and push the
left/right track ball or mouse button in order to mark the element (for example an Alarm List line) or to
execute an SOD 2200 function.
Active elements in mimic diagrams (see Section 3.2.8) can be selected by use of the track ball push
buttons.
Active elements will be highlighted by a frame when pointed at with the cursor.
The following actions can be carried out (examples):

Active Element Type Push-Button Function


Open new diagram [LEFT] Opens the respective new diagram
Component object [LEFT] Opens command menu
Alarm indication [RIGHT] Opens the alarm menu

Table 3-1 SOD 2200 track ball functions.

In order to display all available active elements in a mimic diagram


• Select Edit in the menu bar.
Select Select All Objects.
© SAM Electronics GmbH

12 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

3.2 SOD 2200 Lists and Diagrams

3.2.1 Header Diagram

The Header Diagram displays vital information about the Alarm System(s) accessible by the SOD 2200,
for example the number of (acknowledged/unacknowledged) alarms, the location of the Watch Station,
the selected duty officer, etc.
The MCS 2200 can include up to four Alarm Systems (one Main Alarm System and 3 Sub-Alarm
Systems) for example for machinery alarms, or cargo alarms. Each SOD 2200 can have access to one
or more of these Alarm Systems. The specific access rights are location dependend and assigned during
customizing the SOD 2200. Access rights cannot be changed by the operator.
The Header Diagram incorporates selectable short-cut buttons for some of the most frequently used SOD
2200 functions.
• Select a button with the tracker ball or the mouse in order to execute the respective function.
The following short-cut buttons are available:

Short-Cut Button Function


[EVENT LOG] Displays the Event Log
[STOP HORN] Stops the horn
[ACKN.] Acknwoledges the oldest unacknowledged alarm
[CTRL RIGHTS] Displays Control Rights
[ALARM LIST] Displays Alarm List
[WATCH/DUTY] Displays Alarm System Status
[MAIN MENU] Displays main menu

Table 3-2 SOD 2200 Header Diagram short-cut buttons.

3.2.1.1 Stop Horn and Alarm Acknowledgment

Button Function Action


The red horn symbol indicates an active horn signal. Select this
[STOP HORN] button to silence the horn.

The red lamp symbol indicates an unacknowledged alarm. Select


this button to acknowledge the oldest unacknowledged alarm.
[ACKN.] The alarm text of the respective alarm will be displayed in the
bottom line of the header. Only visible alarms can be acknowl-
edged.
© SAM Electronics GmbH

The buttons [STOP HORN] and [ACKN.] will only function if the respective SOD 2200 is the Watch
Station of the Alarm System which has generated the new alarm.
For more information about stopping the horn, see also Section 4.4.
For more information about alarm acknowledgement, see also Section 4.5 and Section 4.6.

815.000 401 / – (2006-09) 13


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.1.2 Header Diagram Layout Examples

The following figure displays a Header Diagram of an SOD 2200 with one Alarm System. All relevant
information is displayed in one section.

Fig. 3-3 SOD 2200 Header Diagram with one Alarm System.

The next figure displays a Header Diagram of an SOD 2200 with two Alarm Systems. The line which
holds information about the Alarm System (Alarm Sys., Alarms, Man. Supp., Watch, Duty, Backup) is
divided into two parts. The left part dispalys information from the "Machinery Alarm System" and the right
part displays information from the "Bridge Alarm System". The "Oldest Unacknowledge Alarm" indicaton
is from both Alarm Systems.

Fig. 3-4 SOD 2200 Header Diagram with two Alarm Systems.

The next figure displays a Header Diagram of an SOD 2200 with three Alarm Systems. The line which
holds information about the Alarm System (Alarm Sys., Alarms, Man. Supp., Watch, Duty, Backup) is
divided into three parts. The left part dispalys information from the "Machinery Alarm System", the middle
part displays information from the "Bridge Alarm System", and the right part displays information from the
"Cargo Alarm System". The "Oldest Unacknowledge Alarm" indicaton is from all three alarm system.

Fig. 3-5 SOD 2200 Header Diagram with three Alarm Systems.

The following figure displays a Header Diagram for an SOD 2200 with four Alarm Systems. The line
which holds information about the Alarm System (Alarm Sys., Alarms, Man. Supp., Watch, Duty, Backup)
is divided into four parts. The left part displays information from the "Machinery Alarm System", the next
part displays information from the "Bridge Alarm System", the next part displays information from the
"Cargo Alarm System" and the right part displays information from the "Reefer Alarm System". The
"Oldest Unacknowledge Alarm" indicaton is from all four alarm system.
© SAM Electronics GmbH

Fig. 3-6 SOD 2200 Header Diagram with four Alarm Systems.

14 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

3.2.2 Main Menu Diagram

The Main Menu Diagram is the most important diagram in the system diagram hierarchy. From here, the
operator can access all other mimic diagrams in the system. Depending on the system size (number of
selectable diagrams), it is possible to open mimic diagrams, Alarm Groups, or other sub-system overview
diagrams directly from the Main Menu Diagram.
Each Alarm Group, mimic diagram, or sub-system overview diagram is displayed by an active element in
the Main Menu Diagram:

Active element for Fuel Oil System diagram.

Fig. 3-7 Active element in Main Menu Diagram.

• Select either the diagram title or the box in order to display the corresponding diagram.
In case of unacknwoledged alarms in the diagram, the box will flash red. In case of acknowledged and
no unacknowledged alarms in the diagram, the box will be steadily red.
The Main Menu Diagram layout can be customized to meet special requirements. Your actual SOD 2200
Main Menu Diagram may differ from the example in Figure 3-1.

3.2.3 Alarm Lists

An Alarm List displays all standing alarms (acknowledged and unacknowledged) in an Alarm System. The
MCS 2200 can include up to four Alarm Systems (one Main Alarm System and three Sub-Alarm Systems)
for example for machinery alarms, or cargo alarms. Each Alarm System has its own Alarm List. Each line
in an Alarm List displays an individual alarm. The alarms are sorted by their starting time with the oldest
© SAM Electronics GmbH

815.000 401 / – (2006-09) 15


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

alarm on top and the newest alarm at the bottom of the Alarm List. If an alarm is older than 24 hours,
the starting date will be displayed instead of the starting time. The following figure displays a typical SOD
2200 Alarm List.

Fig. 3-8 SOD 2200 Alarm List.


© SAM Electronics GmbH

For more information about opening Alarm Lists, see also Section 4.1.

16 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

3.2.3.1 Alarm List Buttons

Button Function Action

[SELECT NEW ALARM LIST] Select this button to select a new Alarm List.

Select this button to update the Alarm List (acknowl-


[UPDATE LIST] edged and not active alarms are removed from the
list).

Select the respective button to scroll up or down in


[PAGE UP / PAGE DOWN]
the Alarm List.

[ACKNOWLEDGE ONE SELCTED Select this button to acknowledge one selected


ALARM] alarm on the Alarm List page.

Select this button to acknowledge all alarms on the


[ACKNOWLEDGE ALL ALARMS] Alarm List page.

The Alarm List is able to display all types of alarms defined in the Alarm System. Normally, up to 20
alarms can be displayed on one page.
Example: Figure 3-8 displays an Alarm List with 13 alarms, indicated by the text Entry 1-13 of 13 in the
lower right corner of the Alarm List display. If 26 alarms were present, the information would be Entry 1-
20 of 26. In order to display alarms 21 to 26, you would have to left-click the [PAGE DOWN] button. In
order to return to alarms 1-20 again, you would have to select the [PAGE UP] button.

3.2.3.2 Alarm List Priorities

The Alarm List font is usually green. However, the State column font depends on the alarm priority:

Color Alarm Priority


Red 1
Magenta 2
Yellow 3

3.2.3.3 Alarm Acknowledgement

• Right-click an alarm line in order to display a pop-up menu.


Select Acknowledge in order to acknowledge an unacknowledged alarm.
© SAM Electronics GmbH

Acknowledge will be disabled under the following conditions:


• The alarm is already acknowledged.
• The horn is not silenced.
• The SOD 2200 has not the rights to acknowledge this alarm.

815.000 401 / – (2006-09) 17


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.3.4 Open Display Channel Diagram

• Right-click an alarm line in order to display a pop-up menu


• Select Display Channel in order to open the corresponding Display Channel Diagram
The Display Channel Diagram provides detailed information about the alarm channel set-up, such as
alarm delay, alarm limits, connection terminals, Cut-Out and Simulation status. It is also possible to
change parts of the alarm channel set-up from the Display Channel Diagram, for example delay times
and limits. For detailed information about the layout of the Display Channel Diagram, see Section 3.2.6.
For detailed information about the operation of the Display Channel Diagram, see Section 4.7.

3.2.3.5 Alarm List State Indication

The following table describes the different states of SOD 2200 Alarm List lines in Figure 3-8.

Alarm List Line Alarm Type Description


State: ALM (flashing, red)
UTC (Starting time): 10:14:13
Select the [ACKNOWLEDGE ALL ALARMS] button in order to
New, unacknowl-
A. acknowledge this and all other currently unacknowledged
edged
alarms visible on the Alarm List page.
Please note that alarms cannot be acknowledged as long as
the horn is not silenced.
Selected and highlighted alarm (blue background)
Select the [ACKNOWLEDGE ONE SELECTED ALARM]
New, unacknowl-
B. button in order to acknowledge only the selected alarm.
edged, selected
Please note that alarms cannot be acknowledged as long as
the horn is not silenced.
State: NORM (flashing, red)
UTC: removed
Unacknowl- Select the [ACKNOWLEDGE ONE SELECTED ALARM] or
C. edged, turned to [ACKNOWLEDGE ALL ALARMS] button as described in A and
normal again B, in order to acknowledge this alarm.
Please note that alarms cannot be acknowledged as long as
the horn is not silenced.
State: ALM (steady, red), standing, acknowledged
D. Standing
UTC (staring time): 10:12:22.0 (format: hh:mm:ss.c)
State: ALM (steady, red), standing, acknowledged
UTC (starting time): 1999/01/23 (format: yyyy/mm/dd)
Standing, older This alarm is older than 24 hrs, hence the starting date is
E.
than 24 hrs displayed instead of the starting time.
The starting time can be found in the alarm channel’s Event
Log.
State: NORM (steady, grey)
UTC (starting time): removed
In order to avaoid confusion with other alarm lines, this alarm
Turned to normal
F. will only be removed if:
again - [UPDATE LIST] is selected
© SAM Electronics GmbH

- another Alarm List page is opened


- the Alarm List is closed

Table 3-3 SOD 2200 Alarm List layout.

18 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

3.2.4 Alarm Group Lists

An Alarm Group List displays all alarms assigned to one Alarm Group, regardless of individual alarm
states. The MCS 2200 can display up to 100 Alarm Groups.
The layout of the Alarm Group List and lines is the same as the Alarm List layout. However, in an Alarm
Group List, the entries are listed in alphabetical order of their ID.
An Alarm Group List displays more channels than an Alarm List because some channel have states there
are not listed in the Alarm List, for example Cut-Out channels or simulated channels.
The following table displays the possible alarm channel states in an Alarm Group List:

State Indication Description


NORM Steady, green Alarm channel in normal state, i.e. no alarms and no failures
ALM Flashing, red Unacknowledged alarm, priority 1
ALM Steady, red Acknowledged standing alarm, priority 1
ALM Flashing, magenta Unacknowledged alarm, priority 2
ALM Steady, magenta Acknowledged standing alarm, priority 2
ALM Flashing, yellow Unacknowledged alarm, priority 3
ALM Steady, yellow Acknowledged standing alarm, priority 3
FAIL Flashing, red Unacknowledged sensor fail alarm
FAIL Steady, red Acknowledged sensor fail alarm, outside normal range
Alarm channel with standing alarm. The alarm is suppressed by a
NORM/CA Steady, blue Cut-Out signal.
One of the following MCS 2200 hardware failures has occured for
this alarm channel:
- Field Processing Device FPD 2200 hardware failure
? Steady, white - FPD 2200 power failure
- Connection failure between SOD 2200 and FPD 2200
In this state, the complete Alarm Group List line is displayed
steadily white.

Table 3-4 Alarm Group List channel states and indication.

All State texts can be extended with a preceding "S", for example "S NORM" or "S ALM". This indicates
an alarm channel in simulation mode. In this mode, displayed values are entered manually without
connection to the sensor input.
For information about opening Alarm Group Diagrams, see also Section 4.3.

3.2.5 Additional Lists

Additional Lists are a specific set of alarm channel state lists. Each Alarm System has a set of Additional
© SAM Electronics GmbH

Lists. The Additional Lists’ layout is the same as the Alarm List layout.
For more information about opening Additional Lists, see also Section 4.2.

815.000 401 / – (2006-09) 19


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.5.1 Suppression Lists

Simulated Channels List: List of all channels in simulation mode


Automatic Suppressed List: List of all channels suppressed by Automatic Cut-Out
Manual Suppressed List: List of all channels suppressed by Manual Cut-Out

3.2.5.2 Failure Lists

Device Fail List: List of all channels with device failure (FPD 2200 hardware or power
failure)
Sensor Fail List: List of all channels with sensor failure (sensor input exceeds defined
range)

3.2.5.3 High Priority Alarm List

Alarm List Priority 1: Alarm List including Priority 1 alarms


Alarm List priority 1&2: Alarm List including Priority 1 and 2 alarms

3.2.6 Display Channel Diagram

The Display Channel Diagram provides detailed alarm channel information. From here, some of the alarm
channel parameters can be adjusted (password level 1 protected).

© SAM Electronics GmbH

20 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

The Display Channel Diagram is divided into sections corresponding to the various functions. The two
following figures show Display Channel Diagrams of a binary and an analog alarm channel.

Fig. 3-9 Display Channel Diagram of binary alarm channel.


© SAM Electronics GmbH

Fig. 3-10 Display Channel Diagram of analog alarm channel.

815.000 401 / – (2006-09) 21


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.6.1 Display Channel Diagram Sections and Functions

In this section you will learn about the different sections and functions of the Display Channel Diagram.

3.2.6.1.1 Display Channel Diagram Buttons

Button Function Action

[OPEN ALARM GROUP] Select this button to open an Alarm Group Diagram.

[OPEN LIST] Select this button to open a drop-down list.

[ADJUST] Select this button to open the Adjust dialog.

3.2.6.1.2 Headline Section

The Display Channel Diagram headline is identical to the Alarm List and Alarm Group List headline. It
includes the following entries:
• Alarm channel ID
• Alarm channel Description
• Alarm Channel State
• Message Text
• Alarm channel Value (analog channels only)
• UTC (alarm starting time, if available)

3.2.6.1.3 Configuration Section

Type: Analog / binary alarm


Alarm System: Name of the Alarm System which generated the alarm
FPD 2200: Name of Field Processing Device FPD 2200 location
Addr. FPD 2200 address (unit number) in the System Net
© SAM Electronics GmbH

3.2.6.1.4 Alarm Groups Section

Each alarm channel can be included in 0 to 4 Alarm Groups. The Alarm Groups section displays the
Alarm Groups in which the selcted alarm is included.

22 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

Select the [OPEN ALARM GROUP] button next to an Alarm Group entry in order to open the corre-
sponding Alarm Group Diagram.

3.2.6.1.5 Channel Parameters Section

Limit: Binary alarm channels have only one limit (1).


Analog alarm channels can have three limits (1, 2, and 3).
If more than one limit is active at the same time, the Alarm List automatically displays
the message text for the highest limit.
Type: BINARY / LOW LIMIT / HIGH LIMIT
Message: Displays the limit message text (defined during customizing)
Prio.: Alarm channel priority
Priorities 1, 2, and 3 are reserved for alarms.
Priority 4 is reserved for events.
The Alarm channel priority defines the color of the Alarm State text and the indication
in Mimic Diagrams.
- Priority 1: Red text
- Priority 2: Magenta text
- Priority 3: Yellow text
- Priority 4: White text
The priority defines also which alarms will be inluded in the Alarm List if Only priority
1 alarms or Only priority 1 + 2 alarms is selected in the Additional List dialog.
Priority 4 alarms will not be displayed in the Alarm List but can be included in an
Alarm Group List and in a Mimic Diagram.
Value: Limit value for analog channels (not used for binary channels).
Select the [ADJUST] button in order to open the Adjust dialog.
Delay on/off: Delay on defines the period of time between limit overstepping (analog channel ) or
input activation (binary channel) and announcement (horn) and display of an alarm in
the Alarm List.
Delay off defines the period of time between the end of limit overstepping (analog
channel) or input passivation (binary channels) and the removal of the alarm from the
Alarm List.
Select the [ADJUST] button in order to open the Adjust dialog.
M.cut: Manual Cut-Out displays ON if an alarm is suppressed by a Manual Cut-Out. The
Manual Cut-Out function allows deliberate alarm suppression in order to avoid
unwanted alarms (for example in case of a sensor fail or during servicing)
Select the [ADJUST] button in order to open the Adjust dialog and activate/deactivate
the Manual Cut-Out function.
Normally, Cut-Out procedures are carried out from channel limit 1. In this case, ON/
OFF will only be displayed for limit 1. However, separate Cut-Outs for each limit are
possible. This will be indicated by On/Off for each limit.

The following figure displays the Adjust dialog for channel limit 1.
© SAM Electronics GmbH

Fig. 3-11 Adjust dialog for Channel Limit 1.

815.000 401 / – (2006-09) 23


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.6.1.6 Channel Calculation Section

The Channel Calculation section displays the signal which is used for alarm state calculation.
The following three input signals (1, 2, 3) can be used for analog channels:
• Main signal
• A signal which is added to main signal
• A signal which is subtracted from main signal
For binary channels, 1 or 2 signals can be used. The calculated signal is a logical operation between the
two signals. The following signals can be used:
• AND
• OR
• XOR
• XNOR
Each signal is displayed in an individual line with the following information:

Signal: Defines the use of this signal during calculation:

Analog channels:
- MAIN
- ADD
- SUBTRACT

Binary channels:

- MAIN
- NOT
- AND
- OR
- XOR
- XNOR
Type: Indicates the signal type:

- SENSOR INPUT
- MONITORING CHANNEL
- CONSTANT
- SERIAL INPUT
- SLS POINT
- ALARM GROUP
ID/Name: Signal ID and name
Mod. ID: Defines the Field Processing Device FPD 2200 input module ID (only for
sensor inputs)
Terminal: Defines the connection terminals on the FPD 2200 input module (only for
sensor inputs)
Range: Defines the sensor range
© SAM Electronics GmbH

3.2.6.1.7 Channel Time Section

The Channel Time section displays the time of an alarm channel’s latest change of state.
The following changes will set the channel time:

24 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

• Alarm occurrence
• Alarm turns normal
• Cut-Out activated
• Channel set in simulation mode

3.2.6.1.8 Simulation Section

All alarm channels can be set to simulation mode. In this mode, there is no connection to the alarm
channel input signals. However, the input value can be set manually.
For example, this feature can be used to enter the proper value in case of a sensor failure.
• Select the [ADJUST] button to open the Channel Simulation Adjust dialog
Tick the On radio button in Simulation
Enter the proper value in Value
Select OK

Fig. 3-12 Channel Simulation dialog.

3.2.6.1.9 Data Log Section

The Data Log function offers the possibility to print a log of all selected actual alarm channel values.
• Select the [ADJUST] button in order to open the Data Log Adjust dialog and change the
selected alarm channel.
Each Alarm System has one Data Log.
© SAM Electronics GmbH

Fig. 3-13 Data Log selection dialog.

Data Log printouts can only be initiated from the Duty Alarm Panel DAP 2200:
• Press the [PRINTER CONTROL] key

815.000 401 / – (2006-09) 25


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

Press [MORE] softkey


Press [DATALOG] softkey

3.2.6.2 Toolbar Section

The toolbar is located at the bottom of the Display Channel Diagram. The following figure displays a
Display Channel Diagram toolbar.

Fig. 3-14 Display Channel Diagram toolbar.

The following actions can be carried out from the toolbar:

Button Function Action


Select this button to display the data of the last channel
in the system.
[CHANGE TO LAST CHANNEL]
Channels are sorted alphabetically according to their
channel ID.
Select this button to display the data of the next channel
in the system.
[CHANGE TO NEXT CHANNEL]
Channels are sorted alphabetically according to their
channel ID.
Select this button to display the data of the previous
[CHANGE TO PREVIOUS channel in the system.
CHANNEL] Channels are sorted alphabetically according to their
channel ID.
Select this button to display the data of the first channel
[CHANGE TO FIRST in the system.
© SAM Electronics GmbH

CHANNEL] Channels are sorted alphabetically according to their


channel ID.
Select this button to acknowledge an alarm in the
[ACKNOWLEDGE ALARM] selected channel.
In case of unacknowledged alarms, the exclamation
mark symbol will be red.

26 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

Button Function Action


Select this button and enter password level 1.
All Display Channel Diagram data can be adjusted
ENTER ADJUST MODE without further password entries.
The entered password will be disabled when the Display
Channel Diagram is closed.
Select this button in order to open the Mimic Diagram
which includes the selected channel. In case of multiple
FIND MIMIC DIAGRAM
Mimic Diagrams, the desired diagram can be selected
from a Mimic Diagram List.

Select this button in order to open a list of all monitoring


OPEN CHANNEL SELECTION
channels in the system. The desired monitoring channel
LIST
can be selected from the list.

Select this button and enter password level 3 in order to


change the channel parameters in a new window.
The following parameters can be changed:
- Channel name
- Membership of Alarm System
- Membership of Alarm Groups
EDIT CHANNEL PARAMETERS - Input definition NO or NC for binary channels
- Input scaling block for analog channels
- Message text
- Alarm priority
Some parameters may be blocked for certain channels
(Example: a channel is used by the MCS 2200)
For further details, please refer to Section 4.14.

3.2.7 Standard Function Block Diagrams

A Standard Function Block Diagram is divided into 12 sections. Each section represents one Standard
Function Block. One Standard Function Block represents a corresponding machinery component.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 27


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

The following figure displays the layout of a Standard Function Block Diagram. It includes Standard Func-
tion Blocks for pumps, stand-by pumps, valves, and tank measurements.

Fig. 3-15 Standard Function Block Diagram.

A Standard Function Block normally consists of several objects.


Example: Three objects in a Standard Function Block of a pump device:

Object 1: State (Stopped/Running/Failure)


Object 2: Control mode (Local/Remote/Automatic control mode)
Object 3: Interlocks/failures (Interlocks/blocked pump due to failure)

Standard Function Blocks display dynamic information of machinery components (valves, pumps, etc.)
and consist of one or more dynamic objects. A dynamic object indicates the state or value of a machinery
component. Dynamic objects can be an icon (graphical representation), a text, or a numerical value.
Dynamic objects can be either digital or analog obejects.

3.2.7.1 Digital Objects

Digital objects indicate the state of a machinery component, for example a pump device.
A digital object can indicate a number of different states, for example Stopped and Running.
© SAM Electronics GmbH

A digital object can display one static indication and two dynamic indications in a Standard Function Block
Diagram.
The ID/name of a machinery component is displayed as a static indication.

28 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

Both dynamic indications display the actual state of a machinery component. One displays the state as
a text, and the other displays it as an icon. Due to the state of the machinery component, the icon
changes its graphical appearance and color. In case of an alarm, the icon is highlighted by a red back-
ground color.

Stopped pump

Running pump

Fig. 3-16 Examples of icon/text indication.

One, two, or all three indicators (name, state, icon) can be displayed. Normally, all three indicators will
be included in Standard Function Block Diagrams.
It is possible to send commands from a digital object to a machinery component. The name, state text,
and icon are ective elements.
• Select one element in order to open the Command menu
Select the desired command in order to send it to the respective machinery component

Command menu of pump device.

Fig. 3-17 Command menu.

3.2.7.2 Analog Objects

Analog objects indicate a numerical measurement value or an adjustable Field Processing Device FPD
2200 value.
An analog object can display one static indication and two dynamic indications in a Standard Function
Block Diagram.
© SAM Electronics GmbH

The ID/name of an object (measurement) is displayed as a static indication.


Both dynamic indications display the value of the measurement. One displays the value as a number, the
other displays a graphical representation (for example a bar graph or pie chart).
It is possible to display one, two, or all three indicators (name, state, icon). Normally, all three indicators
will be displayed in Standard Function Block Diagrams.

815.000 401 / – (2006-09) 29


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

3.2.8 Mimic Diagrams

Mimic Diagrams provide a clear overview of specific components of a machinery system. Dynamic
objects in the diagram represent individual machinery components and system measurements on a static
background.
Normally, the dynamic objects are Standard Function Blocks. However, the system may be customized
to display other objects.
Usually, digital object icons and analog object values will be displayed in order to guarantee clarity and
legibility.
The following figure displays a Mimic Diagram of a Fuel Oil Supply System.

Fig. 3-18 Mimic Diagram of Fuel Oil Supply System.

• Select an object in order to view its ID.


For detailed information about Mimic Diagrams, see also Section 4.10.

3.2.9 Control Right Diagrams

The MCS 2200 provides a Control Right function for machinery components (Standard Function Blocks).
Please note that this function is optional and may not be included in your installation.
© SAM Electronics GmbH

The Control Right function will allow a machinery component (for example a pump, a valve, or a controller
set point) to be controlled from only one location at a time.
Example: If the control right for a specific machinery component is assigned to the Engine Control Room,
all control functions from other SOD 2200 on the ship will be blocked.

30 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.2 SOD 2200 Lists and Diagrams

The control functions of the Local Operating Panels LOP 2200 (if included) are not influenced by the
Control Right function. It is always possible if groups from panels control >>> Rest of this sentence is
misssing in all source documents <<< This I don’t understand.
Control rights are always assigned to a location, not to individual SOD 2200, hence two SOD 2200 in the
same location have the same control rights.
Machinery components are classified in machinery groups. The control rights for all components in one
group are always assigned to the same location.
The control rights for different machinery groups can be assigned to the same location or to different loca-
tions.
Control rights for one machinery group can alternate between different locations. The Control Right
System can handle up to five individual control locations and up to 50 machinery groups.
During customizing, each machinery group is assigned to its legal control locations.
The change-over of machinery group control rights to a new location is carried out from the new location
without any change-over procedure. This way, only the new location needs to be manned.
Example: If only one officer is on duty, he can change over the control rights to any location required
during his watch. Control right change-over can be carried out even if the present location is out of order
or blocked, for example due to a fire.
Please note that it is impossible to change over machinery group control rights if the new location is an
illegal location for a specific machinery group.
• Select a desired machinery component in order to open the Command menu
If the control rights for a specific component are not assigned to the new location, the commands will be
unavailable.
The following figures display available and unavailable commands in a Command menu.

Available pump control commands.

Unavailable pump control commands (control rights are


not assigned to new SOD 2200 location)
© SAM Electronics GmbH

Fig. 3-19 Control Right Command menu.

An overview of the current control right locations is provided by a Control Right Change-Over Diagram.
• Select the [CTRL.RIGHT] short-cut in the header in order to display the Control Right Change-
Over Mimic Diagram

815.000 401 / – (2006-09) 31


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.2 SOD 2200 Lists and Diagrams User Manual

From here, it is also possible to change the location of new machinery groups.
The table is defined by the number of control stations (columns) and the number of machinery groups
(rows) in the Control Right System. Please refer to Figure 3-20.
The column Machinery Group Name displays the name of the machinery group (for example PMS 2200,
AUX ENGINES, BALLAST TANKS, etc.). The column Actual Control Location displays the currently
selected control location of the respective machinery groups. The column Select Location displays all
other legal/available control locations.
• Select the resective button to change over the control functions to the desired location.
The following figure displays a Control Right Change-Over Diagram.

Fig. 3-20 Control Right Change Over Diagram.

This example diagram contains 9 machinery groups (PMS 2200, AUX ENGINES, BALLST TANKS, etc.)
and 4 control stations (Engine Control Room, Ship’s Office, Bridge, Cargo Control Room).
Example: The Power Management System PMS 2200 is currently controlled from the Engine Control
Room. Other legal PMS 2200 control locations are the ECR and the Ship’s Office.
• Select Ship’s Office in the PMS 2200 row in order to change the PMS 2200 control from the
ECR to the Ship’s Office.
This will change the entry in the Actual Control Location column from ECR to Ship’s Office. The control
functions from the Engine Control Room will be disabled and changed over to the Ship’s Office.
For information about Control Right Change-Over functions, see also Section 4.11.
© SAM Electronics GmbH

3.2.10 Journals

Jounals are lists or sets of lists of monitoring channels. The Journal layout is identical to the Alarm List
layout.
The Journal content is defined online by an operator. One Journal can include up to 10 pages, each with
32 monitoring channels on display. A maximum of 15 individual Journals can be defined.

32 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 3 SOD 2200 Layout
User Manual 3.3 Spare Channels

Journals are assigned to individual SOD 2200. This means that the total number of possible journals is
15 multiplied with the total number of SOD 2200 in the system. Journals designed on one SOD 2200
cannot be displayed on another SOD 2200.

Fig. 3-21 Journal.

Journals can either be displayed on screen or printed by a printer assigned to the respective SOD 2200.
Journal printout can be carried out either manually (tractor feed printer or graphical printer) or automati-
cally (only tractor feed printer). Automatic printouts can be carried out cyclically or at pre-determined
points in time.
For detailed information about Journal printout, see also Section 4.12.

3.3 Spare Channels

Input modules are equipped with 8, 16, or 32 inputs. In most installations, some input channels are not
being used. These channels are called spare channels.
Spare channels can be activated (optional). Activating means to connect a physical switch or analog
sensor to the input channel and create a monitoring channel (alarm) for this switch or sensor.
Activation can be carried out in a running system. The new channel will function immediately on FPD
2200 or SOD 2200 restart.
© SAM Electronics GmbH

Binary switches can be either NO (normally open) or NC (normally closed).


Input from analog sensors can be current (mA), voltage, Pt100, potentiometer, NiCrNi, or FeCo.
Please note that only sensor types already included in the system can be used. It is not possible to define
new sensor types in a running system.
• Select Diagrams in the menu bar to open a drop-down list of diagrams.

815.000 401 / – (2006-09) 33


3 SOD 2200 Layout MCS 2200 - Monitoring and Control System
3.3 Spare Channels User Manual

Select Spare Channels... in the Maintenance window.


If the Spare Channel function is not included in your system, Spare Channels... will be disabled and spare
channels will be unavailable for activation in a running system.

Fig. 3-22 Maintenance dialog.

For detailed information about spare channel activation, see Section 4.13.

© SAM Electronics GmbH

34 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.1 Open Alarm Lists

4 SOD 2200 Operating Instructions

In this chapter, you will learn about the operation and the functions of the SOD 2200.

4.1 Open Alarm Lists

The Alarm List can be opened in the following ways:


• Select the [ALARM LIST] button in the header.
• Press the <F2> function key on the keyboard.
• Select Diagram in the menu bar in order to open a drop-down list of diagrams.
Select AlarmList.

4.2 Open Cut-Out Lists, Simulation Lists, Sensor Fail Lists, or Device Fail Lists

These lists are included in the Additional Lists dialog. Additional Lists can be opened in the following way:
• Select the [ADD. LISTS] button in the header.
• Press the <F5> function key on the keyboard.
• Select Diagram in the menu bar in order to open a drop-down list of diagrams.
Select AddList.

4.3 Open Alarm Group Diagrams

The most important Alarm Groups are listed in the Main Menu Diagram.
• Select the active element (text and white box), e.g. Fuel Oil System, in order to open the
respective Alarm Group Diagram.
If the desired Alarm Group is not displayed in the Main Menu, a list of all available Alarm Groups in the
system can be opened in two ways:
• Select Diagram in the menu bar in order to open a drop-down list of available diagrams.
Select AlarmGroup.
• Press the <F4> function key on the keyboard.
Select the desired Alarm Group.
Select OK.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 35


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.4 Stop Horn User Manual

The following figure displays an Alarm Group selection dialog.

Fig. 4-1 Alarm Group selection dialog.

4.4 Stop Horn

The horn can be stopped in the following ways:


• Press the <F11> function key on the keyboard.
• Select the [STOP HORN] button in the header.
• Select the [STOP HORN] key on the Duty Alarm Panel DAP 2200.

4.5 Acknowledge Oldest Unacknowledged Alarm

The oldest unacknowledged alarm is always displayed in the header (in case of a multiple Alarm System
header, it will be displayed in the bottom line). The oldest unacknowledged alarm can be acknowledged
in the following ways:
• Press the <F12> function key on the keyboard.
• Select the [ACKN.] button in the header.

4.6 Alarm Acknowledgement

4.6.1 Unacknowledged Alarms in Lists

Unacknowledged alarms in lists are indicated by a flashing State text. Unacknowledged alarms can be
© SAM Electronics GmbH

acknowledged in two ways:


• Select and right-click an alarm line in order to open a pop-up menu.
Select Acknowledge.
• Select the alarm line (background color will change to blue).
Select the [ACKNOWLEDGE ONE SELECTED ALARM] button.

36 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.7 Open Display Channel Diagrams

Please note that the SOD 2200 has to be the Watch Station of the actual Alarm System in order to
acknowledge an alarm. Alarms can only be acknowledged if the horn is silenced. For information about
silencing the horn, see Section 3.2.1.1 and Section 4.4.

4.6.2 Unacknowledged Alarms in Mimic Diagrams

Unacknowledged alarms in Mimic Diagrams are indicated by a flashing icon background. Unacknowl-
edged alarms in Mimic Diagrams can be acknowledged in the following way:
• Right-click the icon in order to display a pop-up menu
Select Acknowledge
Please note that the SOD 2200 has to be the Watch Station of the actual Alarm System in order to
acknowledge an alarm. Alarms can only be acknowledged if the horn is silenced. For information about
silencing the horn, see Section 3.2.1.1 and Section 4.4.

4.6.3 Unacknowledged Alarms in Display Channel Diagrams

Unacknowledged alarms in Display Channel Diagrams are indicated by a flashing State text.
• Select the [ACKNOWLEDGE ONE SELECTED ALARM] button.

4.7 Open Display Channel Diagrams

Display Channel Diagrams of specific channels can be opened in different ways, depending on the
currently open diagram.

4.7.1 Menu Bar

• Select Diagram in the menu bar in order to open a drop-down list of diagrams
Select Display Channel.
This will open the Display Channel Diagram and a list of all channels.
• Select a channel line.
Select OK (alternatively, double-click the respective channel).

4.7.2 Function Keys

• Press the <F8> function key on the keyboard.


© SAM Electronics GmbH

This will open the Display Channel Diagram and a list of all channels.
• Select a channel line.
Select OK (alternatively, double-click the respective channel line).

815.000 401 / – (2006-09) 37


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.8 Alarm Limits, Delays, and Cut-Out State Adjustment User Manual

4.7.2.1 Lists (Alarm List, Alarm Group, Additional Lists, and Journals)

• Right-click the channel line in order to open a pop-up menu.


Select Display Channel.

4.7.2.2 Mimic Diagram

• Right-click an icon in order to open a pop-up menu.


Select Display Channel.

4.8 Alarm Limits, Delays, and Cut-Out State Adjustment

Monitoring channel limits and delay times can be changed from the Display Channel Diagram. Further-
more, the Manual Cut-Out state can be enabled or disabled.
The following figure shows a Display Channel Diagram for an analog alarm channel.

Fig. 4-2 Display Channel Diagram for an analog alarm channel.

• Open the Display Channel Diagram of the desired channel (see Section 4.7).
Select the [ADJUST] button next to the desired limit in Channel Parameters.
© SAM Electronics GmbH

Enter password level 1.


Adjust the desired entries in the Channel Limit Adjust dialog.

38 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.9 Simulated Values for Monitoring Channels

Select OK in order to activate your changes.

Fig. 4-3 Adjust dialog for limit 1.

4.9 Simulated Values for Monitoring Channels

A monitoring channel can be set to simulation mode. In this mode, the channel will not display the actual
input sensor value but a simulated value. This simulated value can be entered in the Simulation dialog.
• Open the Display Channel Diagram of the desired channel (see Section 4.7)
Select the respective [ADJUST] button in the Simulation section.
Enter password level 1.
Select the On radio button in Simulation.
Enter Channel Simulation value.
Select OK.

Fig. 4-4 Channel Simulation dialog.

4.10 Open Mimic Diagrams

The Main Menu Diagram provides access to all Mimic Diagrams in the SOD 2200. Access can be made
either directly by use of active elements or indirectly by use of sub-diagrams. An alarm situation in an
inferior diagram object will will be relayed to the active element of the superior diagram in the diagram
hierarchy. This way, all alarms in Mimic Diagrams will be displayed in the Main Menu Diagram.
© SAM Electronics GmbH

• Select an active element in the Main Menu Diagram or any other diagram in order to open the
corresponding diagram, for example Fuel Oil System.
It is also possible to open a diagram by its name:
• Select Edit in the menu bar to open a drop-down list.
Select Open by Name to open the Open by Name dialog.

815.000 401 / – (2006-09) 39


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.11 Control Right Change-Over for a Machinery Group User Manual

Select the Diagram radio button in Types.


Open the Name list.
Select the desired diagram name in the list.
• Select OK

Fig. 4-5 Open by Name dialog.

4.11 Control Right Change-Over for a Machinery Group

The change-over of a machinery group’s control rights is carried out from the Control Right Change-Over
Diagram.
• Select the [CTRL.RIGHT] button in the header in order to open the Control Right Change-Over
Diagram.
Select the button of the new control right location in the respective machinery group row.
The name in Actual Control Station Location will change to the new location. All control functions of the
old location will be disabled and changed over to the new location.

4.12 Journals

4.12.1 Journal Display

In order to display a Journal, the journal function has to be activated first.


© SAM Electronics GmbH

• Select Diagram in the menu bar to open a drop-down list of diagrams.


Select Journals.
This will open an empty Journal window and add the buttons Open and Edit to the menu bar.
• Select Open in the menu bar to open a drop-down list of defined Journals.

40 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.12 Journals

Place the cursor on one of the Journals in the list to display a list of the pages of the respective
Journal.
Select the desired page to fill the Journal window with the content of the selected page.

Fig. 4-6 Journal page selection.

4.12.2 Journal Printout

In order to print a Journal manually, the Journal has to be opened first (see also Section 4.12.1).
• Select Diagram in the menu bar to open a drop-down list of diagrams.
Select Journals.
Either select Open in the menu bar and left-click Print, or press <CTRL> and <P> simultane-
ously on the keyboard.
Only the displayed page will be printed.

4.12.3 Journal Creation

Journals can be defined by the operator in online mode.


• Select Diagram in the menu bar to open a drop-down list of diagrams.
Select Journals.
This will open an empty Journal window and add Open and Edit to the menu bar.
• Select Edit in the menu bar to display a drop-down list.
Select Password.
Enter password level 1.
Select OK.
Select Edit again to display a drop-down list of already defined Journals (below the parting line).
© SAM Electronics GmbH

Fig. 4-7 New Journal creation 1.

815.000 401 / – (2006-09) 41


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.12 Journals User Manual

Select Add group... to create a new Journal.


Enter the name of the new Journal in the dialog window.
• Select Edit again.
Now, the name of the new Journal (here: NewJournal) is added to the Journal list.

Fig. 4-8 New Journal creation 2.

• Select NewJournal.
Select Add page...
Enter the name of the page in the dialog.
This will display the Select Monitoring Channels dialog. It contains the Available Monitoring Channels List
in the left section, and a list of already Selected Monitoring Channels in the right section.

© SAM Electronics GmbH

Fig. 4-9 Select Monitoring Channels dialog.

• Select the monitoring channel that shall be included in the Journal in Available Monitoring Chan-
nels.
Select Add.

42 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.12 Journals

The selected channel will be removed from the list of Available Monitoring Channels and added to the list
of Selected Monitoring Channels. Repeat this procedure with all channels to be included in the Journal.
In order to remove a channel from the Selected Monitoring Channels list and from the Journal:
• Select the channel in the Selected Monitoring Channels List.
Select Remove.
In order to change the order in the Selected Monitoring Channels List and in the Journal:
• Select the desired channel and move it up or down by the [UP] and [DOWN] buttons.
In order to change the name of a page:
• Enter the new name in the Name field.
• Select OK when the Selected Monitoring Channels List is complete.
This will display the final Journal page.

4.12.4 Automatic Printout of Journals

Each Journal can be assigned to an individual automatic printout definition.


Example:
• Journal 1 is printed out automatically daily at 8:00 am.
• Journal 2 is printed out every 4 hours.
• Journal 3 is only printed out manually.
In order to determine the automatic Journal printout definitions, the respective Journals must be opened
for editing.
• Select Diagram in the menu bar to open a drop-down list of diagrams.
Select Journals.
This will open an empty Journal window and add the buttons Open and Edit to the menu bar.
• Select Edit in the menu bar to open a drop-down list.
Select Password.
Enter password level 1.
Select OK.
Select Edit to display the following drop-down list:
© SAM Electronics GmbH

Fig. 4-10 Journal printout selection 1.

815.000 401 / – (2006-09) 43


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.12 Journals User Manual

In order to define automatic printout of a Journal:


• Select Edit in the menu bar.
Place the cursor onto the Journal that shall be printed out automatically (here: NewJournal).
Select Printout to open the Printout Schedule dialog.

Fig. 4-11 Journal printout selection 2.

In the Printout Schedule dialog, you can select between Cyclic or Daily printout [UTC].
• Tick the Enable Printout check box before setting the printout parameters

4.12.4.1 Daily Printout

• Check the Daily Printouts radio button.


Select Add in Daily Printouts [UTC] and enter the printout time (multiple printout times are
possible).

© SAM Electronics GmbH

44 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.12 Journals

Select OK.

Fig. 4-12 Daily Journal printout.

4.12.5 Cyclic Printout

• Check the Cyclic radio button.


Enter printout Start [UTC] and End [UTC] time by using the [UP] and [DOWN] buttons.
Printout will only be carried out within this interval.
• Enter the interval between printouts by using the [UP] and [DOWN] buttons.
• Select OK.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 45


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.12 Journals User Manual

In the Journal printout example in following figure, printouts will be executed out at 01:00, 05:00, 09:00,
13:00 and 17:00.

Fig. 4-13 Cyclic Journal printout.

4.12.5.1 Overall Enabling of Automatic Printout

Automatic Journal printout will only be carried out if the Scheduled Printout function is enabled. Sched-
uled Printout will activate automatic printout of all Journals with Cyclic or Daily Printout definitions.
• Select Diagram in the menu bar to open a drop-down list of diagrams.
Select Journals.
This will open an empty Journal window and add the buttons Open and Edit to the menu bar.
• Select Edit in the menu bar.
Select Scheduled printout.
Automatic printout is enabled when Scheduled Printout is checked in the drop-down menu.

© SAM Electronics GmbH

Fig. 4-14 Scheduled Journal printout.

46 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.13 Spare Channel Activation

4.13 Spare Channel Activation

In order to activate a spare channel, the Spare Channel List has to be opened.
• Select Diagram in the menu bar to open the drop-down list of diagrams
Select Maintenance
This will open the Maintenance dialog.

Fig. 4-15 Maintenance dialog.

• Select Spare Channels... in the Main tab (the Spare Channels... button is disabled if the Activate
Spare Channel option is not included in the system).
This will open the Spare Channel List.
© SAM Electronics GmbH

Fig. 4-16 Spare Channel List.

815.000 401 / – (2006-09) 47


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.13 Spare Channel Activation User Manual

By default, the Spare Channel List will display all spare channels, both currently vacant and previously
activated channels.
• Left-click the Activated check box in Spare Channels to remove the check mark.
This will display only vacant channels.
• In order to determine which sensor type you want to connect, left-click and deselect the check
boxes of all other sensor types in the Sensor Type section.
This will display a list of spare channels for the selected sensor type in all Field Processing Devices FPD
2200.
In case you know to which FPD 2200 the sensor shall be connected to, it is possible to display only spare
channels for a particular FPD 2200.
• Select the bottom check box in the FPD 2200 section.
Adjust the number of FPD 2200 by use of the [UP] and [DOWN] keys.

Fig. 4-17 FPD 2200 selection.

4.13.1 Binary Channel Activation

When you have selected the binary sensor type and the FPD 2200 it shall be connected to, the Spare
Channel List will look like this:

© SAM Electronics GmbH

Fig. 4-18 Vacant binary Spare Channel List for FPD 2200 1.

48 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.13 Spare Channel Activation

• Select a channel you want to activate.


Select Edit in order to open the Channel Definition dialog.

Fig. 4-19 Channel Definition dialog.

• Check the Activate box to open the first page of the Channel Definition dialog.
© SAM Electronics GmbH

Fig. 4-20 Channel Definition page 1 of binary monitoring channel.

815.000 401 / – (2006-09) 49


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.13 Spare Channel Activation User Manual

On Channel Definition page 1, the following fields can be edited:

ID: Enter the new channel ID (max. 8 characters).


Name: Enter the new channel name (max. 30 characters).
Type: Select BINARY or BACKUP.
- a binary channel is a normal monitoring channel (alarm channel).
- a backup channel will immediately call the backup officer in case a time delay
is exceeded.
Example: The captain is the backup officer on the bridge. If the duty officer
presses a button which is defined as backup channel, the captain will be
informed.
Alarm System: Select the Alarm System in which the new monitoring channel shall be
included.
Included in data Check this box if the channel shall be included in the printer’s data log. The
log: channel is always included in the Alarm/Even List.
Available Alarm Select the Alarm Groups in which the channel shall be included. Select a
Groups: desired Alarm Group and left-click Add. One channel can be included in 0 - 4
different Alarm Groups.

• Select Next to access the next page.

Fig. 4-21 Channel Definition page 2 of binary monitoring channel.


© SAM Electronics GmbH

50 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.13 Spare Channel Activation

On the Channel Definition page 2, the following fields can be edited:

Input definition: Select between Open Contact = Alarm and Closed Contact = Alarm
Message text / Normal Open the drop-down menu and select one of the available texts. This text will
state: be displayed when the channel is in normal state.
Message Text (limit 1): Open the drop-down menu and select one of the available texts. This text will
be displayed when the channel is in alarm state due to Limit 1.
Normally, there is only one alarm limit for a binary channel. However, it is
possible to define more limits with different delays and priorities.
Priority: Open the drop-down menu and select priority 1, 2, 3, or 4.
Priority 1: Highest priority, indicated by red alarm font in the Alarm List.
Priority 2: Second highest priority, indicated by magenta alarm font in the
Alarm List.
Priority 3: Third highest priority, indicated by yellow alarm font in the Alarm
List.
Priority 4: Fourth highest priority, indicated by white alarm font in the Alarm/
Event List. Priority 4 is only an event indication and will not be included in the
Alarm List or alarm announcement procedures.
Delay on: Delay time between the contact’s change to alarm state and the alarm
announcement. The delay time can be set from 0 to 650 seconds.
Delay off: Delay time between a contact’s change to normal state and the alarm
channel’s change to normal state. The delay time can be set from 0 to 650
seconds.

• Left-click Finish when all entries in the Channel Definition dialog are complete.
The new monitoring channel definition will be transferred to the Field Processing Device FPD 2200 and
to the other operating displays. The new monitoring channel will be active immediately.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 51


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.13 Spare Channel Activation User Manual

4.13.1.1 Analog Channel Activation

After the selection of the analog sensor type and the FPD 2200 it shall be connected to, the Spare
Channel List will be displayed.

Fig. 4-22 Spare Channel List of vacant analog spare channels in FPD 2200 1.

• Select the channel you want to activate.


Select Edit.
This will display the Channel Definition dialog:

© SAM Electronics GmbH

Fig. 4-23 Channel Definition dialog.

52 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.13 Spare Channel Activation

• Tick the Activate check box to open the first page of the Channel Definition.

Fig. 4-24 Editing an analog monitoring channel, page 1.

In this window, the following fields can be edited:

ID: Enter the new channel ID (max. 8 characters).


Name: Enter the new channel name (max. 30 characters).
Type: ANALOG.
Alarm System: Select the Alarm System in which the new monitoring channel shall be included.
Incl. in Data Log: Check this box if the channel shall be included in the printer’s data log. The
channel is always included in the Alarm/Even List.
Alarm Group: Select the Alarm Groups in which the channel shall be included. Select a desired
Alarm Group and left-click Add. One channel can be included in 0 - 4 different
Alarm Groups.

• Select Next when all entries in the Channel Definition dialog are complete.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 53


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.13 Spare Channel Activation User Manual

This will display the Channel Definition - Input/Limits dialog.

Fig. 4-25 Editing an analog monitoring channel, page 2.

On this page, the following fields can be edited:

Input scaling block: Select one of the predefined scaling blocks.


Message text/Normal state: Select one of the texts. The selected text will be displayed when
the channel is in normal state.
Alarm Limit 1
Type: Select the function type for this alarm (NOT USED, LOW LIMIT,
and HIGH LIMIT).
- NOT USED means that there is no alarm based on this limit.
- LOW LIMIT means that an alarm is generated if the monitoring
channel value falls below the value of this limit longer than
determined in Delay on.
- HIGH LIMIT means that an alarm is generated if the moni-
toring channel value exceeds the value of this limit longer than
specified in Delay on.
Message Text: Select one of the texts. The selected text will be displayed when
the channel is in alarm state due to Limit 1.
© SAM Electronics GmbH

54 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.14 Change Alarm Channel Definitions

Priority: Select priority 1, 2, 3, or 4.


Priority 1: Highest priority, indicated by red alarm font in the
Alarm List.
Priority 2: Second highest priority, indicated by magenta alarm
font in the Alarm List.
Priority 3: Third highest priority, indicated by yellow alarm font
in the Alarm List.
Priority 4: Fourth highest priority, indicated by white alarm font
in the Alarm/Event List. Priority 4 is only an event indication and
will not be included in the Alarm List or alarm announcement
procedures.
Limit Value: The value of this limit.
An alarm will be generated if the monitoring channel value
exceeds this limit:
Type LOW LIMIT: Lower value alarm
Type HIGH LIMIT: Higher value alarm
Delay on: Delay time between the contact’s change to alarm state and the
alarm announcement. The delay time can be set from 0 to 650
seconds.
Delay off: Delay time between a contact’s change to normal state and the
alarm channel’s change to normal state. The delay time can be
set from 0 to 650 seconds.
Limit 2: A monitoring channel can include up to 3 alarm limits.
If the Limit 2 type is other than NOT USED, the parameters for
the second alarm limit can be entered, and Limit 3 will be
displayed.
The meaning of parameters for Limit 2 and 3 is the same as for
Limit 1 described above.
• Select Finish when all entries in the Channel Definition - Input/Limits dialog are complete.
The new monitoring channel definition will be transferred to the Field Processing Device FPD 2200 and
to the other operating displays. The new monitoring channel will be active immediately.

4.14 Change Alarm Channel Definitions

It is possible to change the definitions of alarm channels in online mode.


The following parameters can be changed:
• Channel name
• Alarm System membership
• Alarm Group membership
• Input definition NO or NC for binary channels
• Input scaling block for analog channels
• Message text
• Alarm priority
© SAM Electronics GmbH

Some channel parameters can be locked, for example channels which are currently used by the MCS
2200.
All changes will be effective immediately when the OK button in the Channel Definition dialog is selected.
The changes will be transferred to the Field Processing Devices FPD 2200 and to the other operating
displays (for printer and panel indication).

815.000 401 / – (2006-09) 55


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.14 Change Alarm Channel Definitions User Manual

Changes can be uploaded by a service engineer and imported into the system database (changes of
alarm limits, delays and hour counter values can be uploaded and imported, as well). This means that
changes will not be lost in case of a new generation and download of the database.
Note: Changes are not included in the back-up of the FPD 2200 code
displayed on the SOD 2200. This means that changes will be lost if an
FPD 2200 is loaded from the System Status Diagram on the operating
display, for example after replacement of a faulty FPD 2200.
However, this feature can be useful when cleaning up a system, for
example if some unsuccessful changes have been made.
Make sure to always write down all changes made online in order to be
able to remake the changes in case of a new download.

4.14.1 Changes in Alarm Channel Definition

• Open the Display Channel Diagram of the desired channel (see Section 4.7).
Select the [EDIT CHANNEL PARAMETERS] button in the tool bar in order to display the
Channel Definition dialog.

Fig. 4-26 Channel Definition Main tab.


© SAM Electronics GmbH

On the Main tab, the fields Name, Alarm System, Included in data log, and Alarm Groups can be
changed.

56 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.14 Change Alarm Channel Definitions

• Select the Input/Limits tab.

Fig. 4-27 Channel Definition Inputs/Limits tab.

On the Input/Limits tab, Input Scaling Block and Message Text can be changed.
The Channel Definition dialogs are the same dialogs used for spare channel activation. For parameter
details, please refer to Section 4.13.1 (Binary channel activation) and Section 4.13.1.1 (Analog channel
activation).

4.14.2 Adjust Time and Date

The MCS 2200 is able to display both UTC and local time.
During all logging routines, internal UTC will be used. However, the operator can select either UTC or
local time as the SOD 2200 display time.
Display time selection and adjustment of time and date display can be executed from the Maintenance
Diagram (alternatively, selections and adjustments can be carried out from a Duty Alarm Panel DAP
2200).
• Select Diagram in the menu bar to open a drop-down list of diagrams.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 57


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.14 Change Alarm Channel Definitions User Manual

Select Maintenance to open the Maintenance dialog.

Fig. 4-28 Maintenance dialog.

• Select Adjust Date/Time...


Enter password level 1 to open the Time/Date Adjust dialog.

Fig. 4-29 Time/Date Adjust dialog.

UTC time and date can be adjusted in the UTC section.


• Use the [UP] and [DOWN] buttons to adjust Time and Date.

Fig. 4-30 UTC adjustment.


© SAM Electronics GmbH

58 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 4 SOD 2200 Operating Instructions
User Manual 4.14 Change Alarm Channel Definitions

Local time and date can be adjusted in the LT section.

• Use the [UP] and [DOWN] buttons to adjust Local Time and Date.
• Select -20 min in Offset in order to set back Local Time by 20 minutes.
• Select +20min in Offset in order to advance Local Time by 20 minutes.
In the Display section, you can select either UTC or LT display for lists and printouts.
• Check either the UTC or Local Time radio button

Fig. 4-31 Time and Date Display.

The title bar time (top of the screen) will not be affected by this selection.
In order to select the title bar time display:
• Select View in the menu bar.
Select the desired title bar time format.

If UTC Date/Time has a check mark, the title bar time will be UTC.
If Time Zone has a check mark, the current time zone will be displayed in addition to the title bar time.
© SAM Electronics GmbH

815.000 401 / – (2006-09) 59


4 SOD 2200 Operating Instructions MCS 2200 - Monitoring and Control System
4.14 Change Alarm Channel Definitions User Manual

This page is intentionally blank.

© SAM Electronics GmbH

60 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 5 List of Figures
User Manual

5 List of Figures

Fig. 3-1 SOD 2200 start display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


Fig. 3-2 SOD 2200 track ball. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fig. 3-3 SOD 2200 Header Diagram with one Alarm System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fig. 3-4 SOD 2200 Header Diagram with two Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fig. 3-5 SOD 2200 Header Diagram with three Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fig. 3-6 SOD 2200 Header Diagram with four Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fig. 3-7 Active element in Main Menu Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fig. 3-8 SOD 2200 Alarm List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 3-9 Display Channel Diagram of binary alarm channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 3-10 Display Channel Diagram of analog alarm channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 3-11 Adjust dialog for Channel Limit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fig. 3-12 Channel Simulation dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fig. 3-13 Data Log selection dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fig. 3-14 Display Channel Diagram toolbar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig. 3-15 Standard Function Block Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fig. 3-16 Examples of icon/text indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fig. 3-17 Command menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fig. 3-18 Mimic Diagram of Fuel Oil Supply System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig. 3-19 Control Right Command menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fig. 3-20 Control Right Change Over Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fig. 3-21 Journal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fig. 3-22 Maintenance dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Fig. 4-1 Alarm Group selection dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fig. 4-2 Display Channel Diagram for an analog alarm channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Fig. 4-3 Adjust dialog for limit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Fig. 4-4 Channel Simulation dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Fig. 4-5 Open by Name dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fig. 4-6 Journal page selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Fig. 4-7 New Journal creation 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Fig. 4-8 New Journal creation 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Fig. 4-9 Select Monitoring Channels dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Fig. 4-10 Journal printout selection 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Fig. 4-11 Journal printout selection 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig. 4-12 Daily Journal printout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Fig. 4-13 Cyclic Journal printout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Fig. 4-14 Scheduled Journal printout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Fig. 4-15 Maintenance dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Fig. 4-16 Spare Channel List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Fig. 4-17 FPD 2200 selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Fig. 4-18 Vacant binary Spare Channel List for FPD 2200 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Fig. 4-19 Channel Definition dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fig. 4-20 Channel Definition page 1 of binary monitoring channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fig. 4-21 Channel Definition page 2 of binary monitoring channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Fig. 4-22 Spare Channel List of vacant analog spare channels in FPD 2200 1. . . . . . . . . . . . . . . . . . . . 52
Fig. 4-23 Channel Definition dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
© SAM Electronics GmbH

Fig. 4-24 Editing an analog monitoring channel, page 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


Fig. 4-25 Editing an analog monitoring channel, page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fig. 4-26 Channel Definition Main tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Fig. 4-27 Channel Definition Inputs/Limits tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Fig. 4-28 Maintenance dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Fig. 4-29 Time/Date Adjust dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Fig. 4-30 UTC adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

815.000 401 / – (2006-09) 61


5 List of Figures MCS 2200 - Monitoring and Control System
User Manual

Fig. 4-31 Time and Date Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

© SAM Electronics GmbH

62 815.000 401 / – (2006-09)


MCS 2200 - Monitoring and Control System 6 Index
User Manual

6 Index

A H
Abbreviations 6 Header Diagram 9, 11, 13
Additional Lists 19
Failure Lists 20
High Priority Alarm List 20 J
Suppression Lists 20 Journals 32
Alarm Acknowledgement 36 Automatic Printout 43, 46
Unacknowledged Alarms in Display Channel Dia- Cyclic Printout 45
grams 37 Daily Printout 44
Unacknowledged Alarms in Lists 36 Journal Creation 41
Unacknowledged Alarms in Mimic Diagrams 37 Journal Display 40
Alarm Channel Definitions 55 Printout 41
Adjust Time and Date 57
Change Definitions 56
Alarm Groups 5 M
Alarm Group Lists 19 Main Control Station 5
Open Alarm Group Diagrams 35 Main Menu Diagram 9, 15
Alarm Lists 5, 15 Mimic Diagrams 30
Buttons 17 Open Mimic Diagrams 39
High Priority Alarm Lists 20 Monitoring Channel
Open Alarm Lists 35 Simulated Values 39
Mouse Operation 11
C
Control Rights S
Control Right Change-Over Diagram 31, 40 Sensor Fail Lists
Control Rights Diagram 30 Open Sensor Fail Lists 35
Machinery Group Control Rights 40 Simulation Lists
Cut-Out 5 Open Simulation Lists 35
Open Cut-Out Lists 35 SOD 2200
Header Diagram 9, 11
Layout 9
D Lists and Diagrams 13
Device Fail Lists Additional Lists 19
Open Device Fail Lists 35 Alarm Group Lists 19
Display Channel Diagram 20 Alarm Lists 15
Alarm Groups Section 22
Control Rights Diagram 30
Buttons 22
Channel Calculation Section 24 Display Channel Diagram 20
Channel Parameters Section 23 Header Diagram 13
Channel Time Section 24 Journals 32
Configuration Section 22 Main Menu Diagram 15
Data Log Section 25 Mimic Diagrams 30
Headline 22 Standard Function Block Diagrams 27
Open Display Channel Diagram 37 Main Components 7
Open Display Channel Diagram by Function Key 37 Keyboard 7
Open Display Channel Diagram from Lists 38 Personal Computer 7
Open Display Channel Diagram from Menu Bar 37 Pointing Device 7
Open Display Channel Diagram from Mimic Diagram
Printer 8
38
Opening Display Channel Diagram from Lists 37 Screen 7
Sections and Functions 22 Main Menu Diagram 9
Simulation Section 25 Menu Bar 9, 10
© SAM Electronics GmbH

Toolbar 26 Operating Instructions 35


Acknowledge Oldest Unacknowledged Alarm 36
Alarm Acknowledgement 36
F Alarm Limits, Delays, and Cut-Out States Adjust-
Field Processing Device FPD 2200 5 ment 38
Change Alarm Channel Definitions 55
Device Fail Lists 35
Machinery Group Control Rights Change-Over 40

815.000 401 / – (2006-09) 63


6 Index MCS 2200 - Monitoring and Control System
User Manual

Open Alarm Groups 35


Open Alarm Lists 35
Open Cut-Out Lists 35
Open Display Channel Diagram 37
Open Mimic Diagrams 39
Open Sensor Fail Lists 35
Open Simulation Lists 35
Spare Channels 47
Stop Horn 36
Operation 11
Spare Channels 33
Start Display 10
Tree Area 11
Working Area 9, 11
Spare Channels 33
Activation 47
Activation (Analog Spare Channels) 52
Activation (Binary Channels) 48
Standard Function Block Diagrams 27
Analog Objects 29
Digital Objects 28

T
Terminology 5
Alarm Groups 5
Alarm Lists 5
Cut-Out 5
Field Processing Device FPD 2200 5
Main Control Station 5
Watch Station 5
Toolbar 26
Tracker Ball Operation 8, 11

W
Watch Station 5
Working Area 9

© SAM Electronics GmbH

64 815.000 401 / – (2006-09)

You might also like