Professional Documents
Culture Documents
Line trap also is known as Wave trap. What it does is trapping the high
frequency communication signals sent on the line from the remote substation
and diverting them to the telecom/ teleportation panel in the substation
control room (through coupling capacitor and LMU).
This is relevant in Power Line Carrier Communication (PLCC) systems for
communication among various substations without dependence on the telecom
company network. The signals are primarily teleportation signals and in
addition, voice and data communication signals. Line trap also is known as
Wave trap. What it does is trapping the high frequency communication signals
sent on the line from the remote substation and diverting them to the
telecom/teleportation panel in the substation control room (through coupling
capacitor and LMU).
This is relevant in Power Line Carrier Communication (PLCC) systems for
communication among various substations without dependence on the telecom
company network. The signals are primarily tele protection signals and in
addition, voice and data communication signals.
The Line trap offers high impedance to the high frequency communication
signals thus obstructs the flow of these signals in to the substation bus
bars. If there were not to be there, then signal loss is more and
communication will be ineffective/probably impossible.
There are typically four types of disturbance or event records of interest to
a protection engineer.
These are categorized by the event duration as follows:
DR
1. Transient - These are very short in duration and typically include faults
that are cleared immediately by circuit breaker operation. These events are
generally no longer than 8 cycles for high speed clearing and 16 cycles for
sequential line clearing. These events are usually analyzed to determine
correct protection operation, fault location, or verification of system model
parameters.
2. Short Term - These generally include all other time-delayed fault clearing
and reclosing events where the system operation (stability) is not affected.
These events are typically 20 to 60 cycles in length but may be longer if
multiple protection operations are required to clear the fault. These events
are usually analyzed to determine correct protection operation, fault
location or verification of system model parameters.
3. Long Term- These include those events that affect system stability such as
power swings, frequency variations and abnormal voltage problems. These
events are usually analyzed to determine causes of incorrect system
operations. Data management techniques are employed to process a number of
samples and record the value for the parameter of interest. Record length
parameters may be defined.
4. Steady State - There are steady state disturbances where system operation
is not threatened, but power quality is affected. This may include harmonics
or sub-harmonics produced by the load and/or the interaction between power
system’s components. Depending upon the type of phenomena being analyzed,
higher sample rates may be required to capture the events and data of
interest. Record length parameters may be defined,
Tri-vector meter can measure active power, reactive power, apparent power
i.e. with the help of a single meter we can measure kva, kw, kvar. The power
triangle is sum of (kW , kVAR, kVA).
The basic difference between a Tri-vector meter and multi function meter is
that a Trivector meter cannot display the tariff it can display kWh and from
that reading the tariff and cost has to be calculated manually, where as a
multi function meter can display tariff also if programmed properly.
Different tariff at different interval of time for normal and peak time load
and also different tariff at same time by two different display is possible
in multi function meter.
TIME OF THE DAY (TOD) METER : This Energy Meter has built-in feature where
the 24 hour duration is divided into 4 zones, and peak price differences can
be used to reduce peaks in demand (load shifting or peak lopping), reducing
the need for additional power plants and in particular the higher polluting
and costly to operate natural gas powered peaked plants. The feedback they
provide to consumers has also been shown to cut overall energy consumption.
ICT
They are normally auto-transformers and they will have a delta connected
tertiary winding of about 33kV voltage rating, for providing a circulating
path for the zero-sequence currents. The spec would read: 400/132/33kV,
100MVA.
CT
Safety precautions
Burden
Burden class/saturation class
Rating factor
Load
External electromagnetic fields
Temperature and
Physical configuration.
The selected tap, for multi-ratio CTs
Phase change
For the IEC standard, accuracy classes for various types of measurement are
set out in IEC 60044-1, Classes 0.1, 0.2s, 0.2, 0.5, 0.5s, 1 and 3. The class
designation is an approximate measure of the CT's accuracy. The ratio
(primary to secondary current) error of a Class 1 CT is 1% at rated current;
the ratio error of a Class 0.5 CT is 0.5% or less. Errors in phase are also
important especially in power measuring circuits and each class has an
allowable maximum phase error for specified load impedance.
Rating factor is a factor by which the nominal full load current of a CT can
be multiplied to determine its absolute maximum measurable primary current.
Conversely, the minimum primary current a CT can accurately measure is "light
load," or 10% of the nominal current (there are, however, special CTs
designed to measure accurately currents as small as 2% of the nominal
current). The rating factor of a CT is largely dependent upon ambient
temperature. Most CTs have rating factors for 35 degrees Celsius and 55
degrees Celsius. It is important to be mindful of ambient temperatures and
resultant rating factors when CTs are installed inside padmount
transformers or poorly ventilated mechanical rooms. Recently, manufacturers
have been moving towards lower nominal primary currents with greater rating
factors. This is made possible by the development of more efficient ferrites
and their corresponding hysteresis curves.
Phase shift
Current transformers are used for protection, measurement and control in high
voltage electrical substations and the electrical grid. Current transformers
may be installed inside switchgear or in apparatus bushings, but very often
free-standing outdoor current transformers are used. In a switchyard, live
tank current transformers have a substantial part of their enclosure
energized at the line voltage and must be mounted on insulators. Dead
tank current transformers isolate the measured circuit from the enclosure.
Live tank CTs are useful because the primary conductor is short, which gives
better stability and a higher short-circuit current rating. The primary of
the winding can be evenly distributed around the magnetic core, which gives
better performance for overloads and transients. Since the major insulation
of a live-tank current transformer is not exposed to the heat of the primary
conductors, insulation life and thermal stability is improved.
conductor colliding with the ionic lattice of the conductor meaning that
electrical energy is converted into heat. Different materials have different
resistivity’s (a property defining how resistive a material of given
dimensions will be.
's and Faraday's laws which state mathematically that E=N*d(thi)/dt , where
this is the magnetic flux linkage). This means that when an AC current flows
through a conductor a small back emf or back current is induced reducing the
overall current.
As per present day transformer design practice, the peak rated value of the
flux density is kept about 1.7 to 1.8 Tesla, while the saturation flux
density of CRGD steel sheet of core of transformer is of the order of 1.9 to
2 Tesla which corresponds to about 1.1 times the rated value. If during
operation, an electrical power transformer is subjected to carry rather
swallow more than above mentioned flux density as per its design limitations,
the transformer is said to have faced over fluxing problem and consequent bad
effects towards its operation and life.
Depending upon the design and saturation flux densities and the thermal time
constants of the heated component parts, a transformer has some over
excitation capacity. I.S. specification for electrical power transformer does
not stipulate the short time permissible over excitation, though in a
roundabout way it does indicate that the maximum over fluxing in
transformer shall not exceed 110%.
The flux density in a transformer can be expressed by. cold rolled grain
oriented (CRGO).
B=CV/f,
where=A constant,
V=Induce voltage,
f = Frequency.
The condition arising out of over-fluxing does not call for high speed
tripping. Instantaneous operation is undesirable as this would cause tripping
on momentary system disturbances which can be borne safely but the normal
condition must be restored or the transformer must be isolated within one or
two minutes at the most.
The output from the first auxiliary element, which operates after fixed time
delay available between 20 to 120 secs. second output relay operates and
performs the tripping function.
It is already pointed out that high V/f occur in Generator Transformers and
Unit-Auxiliary Transformers if full exaltation is applied to generator before
full synchronous speed is reached. V/f relay is provided in the automatic
voltage regulator of generator. This relay blocks and prevents increasing
excitation current before full frequency is reached.
Structural steel parts which are nu-laminated and are not designed to carry
magnetic flux will heat rapidly. Flux flowing in unplanned air paths may link
conducing loops in the windings, loads, tank base at the bottom of the core
and structural parts and the resulting circulating currents in these loops
can cause dangerous temperature increase. Under conditions of excessive over
fluxing the heating of the inner portion of the windings may be sufficiently
extreme as the exciting current is rich in harmonies. It is obvious that the
levels of loss which occur in the winding at high excitation cannot be
tolerated for long if the damage is to be avoided.
Physical evidences of damage due to over fluxing will very with the degree of
over excitation, the time applied and the particular design of transformer.
The Table given below summarizes such physical damage and probable
consequences.
It may be seen that metallic support structures for core and coil, windings,
lead conductors, core lamination, tank etc. may attain sufficient temperature
with the evolution of combustible gas in each case due to over fluxing of
transformer and the same gas may be collected inBuchholz Relay with
consequent Alarm/Trip depending upon the quantity of gas collected which
again depends upon the duration of time the transformer is subjected to over
fluxing.
Due to over fluxing in transformer its core becomes saturated as such induced
voltage in the primary circuit becomes more or less constant. If the supply
voltage to the primary is increased to abnormal high value, there must be
high magnetizing current in the primary circuit. Under such magnetic state of
condition of transformer core linear relations between primary and secondary
quantities (viz. for voltage and currents) are lost. So there may not be
sufficient and appropriate reflection of this high primary magnetizing
current to secondary circuit as such mismatching of primary currents and
secondary currents is likely to occur, causing differential relay to operate
as we do not have over fluxing protection for sub-stn. transformers.
The over current relays cannot distinguish between external short circuit,
over load and internal faults of the transformer. For any of the above
fault, backup protection i.e. over current and earth fault
protection connected to in-feed side of the transformer will operate. Backup
protection is although generally installed at in feed side of the
transformer, but it should trip both the primary and secondary circuit
breakers of the transformer.
Over Current and Earth Fault protection relays may be also provided in load
side of the transformer too, but it should not inter trip the primary side
Circuit Breaker like the case of backup protection at in-feed side. The
operation is governed primarily by current and time settings and the
characteristic curve of the relay. To permit use of over load capacity of the
transformer and co- ordination with other similar relays at about 125 to 150%
of full load current of the transformer but below the minimum short circuit
current.
Backup protection of transformer has four elements; three over current relays
connected each in each phase and one earth fault relay connected to the
common point of three over current relays as shown in the figure. The normal
ranges of current settings available on IDMT over current relays are 50% to
200% and on earth fault relay 20 to 80%.
Another range of setting on earth fault relay is also available and may be
selected where the earth fault current is restricted due to insertion of
impedance in the neutral grounding. In the case of transformer winding with
neutral earthed, unrestricted earth fault protection is obtained by
connecting an ordinary earth fault relay across a neutral current
transformer.
The unrestricted over current and earth fault relays should have proper time
lag to co - ordinate with the protective relays of other circuit to avoid
indiscriminate tripping.
An external fault in the star side will result in current flowing in the
line current transformer of the affected phase and at the same time a
balancing current flows in the neutral current transformer, hence the
resultant electric current in the relay is therefore zero. So this REF relay
will not be actuated for external earth fault. But during internal fault the
neutral current transformer only carries the unbalance fault current and
operation of Restricted Earth Fault Relay takes place. This scheme
of restricted earth fault protection is very sensitive for internal earth
fault of electrical power transformer. The protection scheme is comparatively
cheaper than differential protection scheme
Differential protection relay for two line ends with 4-line display,
The 7SD610 relay is a differential protection relay suitable for all types of
applications and incorporating all those functions required for differential
protection of lines, cables and transformers. Transformers and compensation
coils within the differential protection zone are protected by means of
integrated functions, which were previously to be found only in transformer
differential protection. It is also well-suited for complex applications such
as series and parallel compensation of lines and cables.
It is designed to provide differential and directional back-up protection for
all voltage levels and types of networks. The relay features high speed and
phase-selective short circuit measurement. The unit is thus suitable for
single-phase and three-phase fault clearance.
Digital data communication for differential current measurement is effected
via fiber optic cables, networks or pilot wires connections, so that the line
ends can be quite far apart. The serial protection data interface (R2R
interface) of the relay can flexibly be adapted to the requirements of all
existing communication media. If the communication method is changed,
flexible retrofitting of communication modules to the existing configuration
is possible.
Apart from the main protection function, i.e. the differential protection,
the 7SD610 has a full range of configurable emergency and / or back-up
protection functions such as phase and earth over current protection with
directional elements if voltage transformers are connected. Overload, under
and over-voltage/frequency and breaker failure protection round off the
functional scope of the 7SD610.
Multi-end differential protection relay for two to six line ends, 4-line
backlit display
Description
Power system configurations need to be adjusted onto changing needs. New
challenges, like multi-circuit and multivendor overhead lines, embedded
generation etc. require alterations of traditional transmission line relaying
concepts. Apart from technical issues, the utility has to survive in a
competitive environment. The challenge is sustaining system reliability at
lower costs.
Features:
The protected differential zone may be easily extended from 2 up to 6 line
ends. Complex system configurations receive clearly defined protection zones
and maximum fault coverage. The high-speed distance relay operates fully
independent from the differential relay. Back-up zones provide remote back-up
for upstream and downstream lines and other power system components. Contrary
to traditional measurement approaches, the distance-to-fault locator uses
measurement quantities from both line terminals. This results in precise
readings, even under difficult system conditions, e.g. parallel lines or
resistive line faults fed from both line terminals. The readings are
available right after fault clearance for quick line clearance and system
restoration.
The high-speed distance relay operates fully independent from the
differential relay. Back-up zones provide remote back-up for upstream and
downstream lines and other power system components.
Contrary to traditional measurement approaches, the distance-to-fault locator
uses measurement quantities from both line terminals. These results in
precise readings, even under difficult system conditions, e.g. parallel lines
or resistive line faults fed from both line terminals. The readings are
Available right after fault clearance for quick line clearance and system
restoration.
The relays provide optical ports for relay-to-relay (R2R). The adjustment to
other communication media takes place via media converter. They accept all
traditional and modern communication media, i.e. fibers, commas networks and
pilot wires. The relays remain unchanged.
For multi-ended lines the communication links may be operated in open or
closed rings. The latter provides communication even if one link is broken.
Kf = form Constant.
Copper loss can simply be denoted as,
Where, IL = I2 = load of transformer, and R2′ is the resistance of transformer referred to secondary.
Now we will discuss Hysteresis loss and Eddy Current loss in little bit more details for better understanding the topic of losses in
transformer
The magnetic core of transformer is made of ′Cold Rolled Grain Oriented Silicon Steel′. Steel is very good ferromagnetic
material. This kind of materials is very sensitive to be magnetized. That means whenever magnetic flux passes through,it will
behave like magnet. Ferromagnetic substances have numbers of domains in their structure. Domain are very small region in the
material structure, where all the dipoles are paralleled to same direction. In other words, the domains are like small permanent
magnet situated randomly in the structure of substance. These domains are arranged inside the material structure in such a random
manner, that net resultant magnetic field of the said material is zero. Whenever external magnetic field or mmf is is applied to that
substance, these randomly directed domains are arranged themselves in parallel to the axis of applied mmf. After removing this
external mmf, maximum numbers of domains again come to random positions, but some few of them still remain in their changed
position. Because of these unchanged domains the substance becomes slightly magnetized permanently. This magnetism is called
“Spontaneous Magnetism". To neutralize this magnetism some opposite mmf is required to be applied. The magneto motive force or
mmf applied in the transformer core is alternating. For every cycle, due to this domain reversal there will be extra work done. For
this reason, there will be a consumption of electrical energy which is known as Hysteresis loss of transformer.
Consider a ring of ferromagnetic specimen of circumference L meter, cross - sectional area a m2 and N turns of insulated wire as
shown in the picture beside,
Let us consider, the electric current flowing through the coil is I amp,
Magnetizing force,
As the electric current flowing through the solenoid is alternating, the flux produced in the iron ring is also alternating in
nature, so the emf (e′) induced will be expressed as,
According to Lenz,s law this induced emf will oppose the flow of electric current, therefore, in order to maintain the
current I in the coil, the source must supply an equal and opposite emf. Hence applied emf ,
Energy consumed in short time dt, during which the flux density has changed,
Thus, total work done or energy consumed during one complete cycle of magnetism,
Now aL is the volume of the ring and H.dB is the area of elementary strip of B - H curve shown in the figure above,
= total area enclosed by Hysteresis Loop.
Therefore, Energy consumed per cycle = volume of the ring X area of hysteresis loop.
In the case of transformer, this ring can be considered as magnetic core of transformer. Hence this work done is nothing but
electrical energy loss in transformer core and this is known as hysteresis loss in transformer.
In transformer we supply alternating current in the primary, this alternating current produces alternating magnetizing flux in the core
and as this flux links with secondary winding there will be induced voltage in secondary, resulting current to flow through the load
connected with it. Some of the alternating fluxes of transformer may also link with other conducting parts like steel core or iron body
of transformer etc. As alternating flux links with these parts of transformer, there would be an locally induced emf. Due to these emfs
there would be currents which will circulate locally at that part of the transformer. These circulating current will not contribute in
output of the transformer and dissipated as heat. This type of energy loss is called eddy current loss of transformer. This was a
broad and simple explanation of eddy current loss. The detail explanation of this loss is not in the scope of discussion in that
chapter.
The Electrical power system load current always flows through current transformer primary; irrespective of whether the Current
Transformer is open circuited or connected to burden at its secondary.
If CT secondary is open circuited, all the primary current will behave as excitation current, which ultimately produce huge voltage.
Every Current Transformer has its won non - Linear magnetizing curve, because of which secondary open circuit voltage should be
limited by saturation of the core. If one can measure the rms voltage across the secondary terminals, he or she will get the value
which may not appear to be dangerous. As the CT primary current is sinusoidal in nature, it zero 100 times per second.(As
frequency of the electric current is 50Hz). The rate of change of flux at every current zero is not limited by saturation and is high
indeed. This develops extremely high peaks or pulses of voltage. These high peaks of voltage may not be measured by
conventional voltmeter. But these high peaks of induced voltage may breakdown the CT insulation, and may case accident to
personnel. The actual open - circuit voltage peak is difficult to measure accurately because of its very short peaks. That is why CT
secondary should not be kept open.
Is a device whose principal function is to connect a machine to its source
of running or
Operating voltage. This function may also be used for a device, such as a
contractor, that is used in series with a circuit breaker or other fault
protecting means, primarily for frequent opening and closing of the circuit.
Lenz’s law
Back emf
There were many other oddities that have been explained by the production of eddy currents,
including the back emf produced in electric motors. When a motor starts up, the coils are rotating
through an external magnetic field and so there is an induced back emf.
The net emf is the sum of the supply emf and the opposing back emf (the minus sign indicates it is
against the direction of the supply emf).
When current is flowing through the armature conductor of dc motor, it starts rotating inside the
magnetic field of stator pole. As the armature conductors move inside the magnetic field there will
be an induced emf in the armature conductor. This emf would be due to Faraday law of
electromagnetic induction. The direction of the induced emf will be as per Fleming right hand rule
and the induced emf will oppose the applied voltage across the armature terminals. In other words
in dc motor the rotating armature will generate an emf as it is rotating under magnetic field, in
opposite of the applied voltage and this generated emf in dc motor is called back emf.
Supply Unbalance & Sequence components :
When the power supply to the motor is unbalanced, the unbalanced voltage and the resulting
unbalanced currents in the three phases can be resolved into three balanced components as follows :
Positive Sequence component: This component is in the same phase sequence as that of the motor
current. All its three phases are perfectly balanced - they are equal in magnitude and are displaced by
120 degrees. The positive sequence component represents the amount of balance in the power supply
and consequently is instrumental in delivering useful power.
Negative Sequence component: This component has a phase sequence opposite to that of the motor
current hence the name negative sequence. It represents the amount of unbalance in the feeder. All its
three phases are perfectly balanced - they are equal in magnitude and are displaced by 120 degrees.
This component does not produce useful power - however by being present it contributes to the losses
and causes temperature rise.
Zero Sequence components: This, if present, represents extent of earth fault in the feeder. All its three
phases are in the same direction.
Negative Sequence
When the load on the generator becomes unbalanced, negative
phase sequence currents flows. The negative sequence
components produce a rotating magnetic field which rotates
at synchronous speed in a direction opposite to the
direction of rotor field. Hence effectively the relative
speed between the two is double the synchronous speed. Thus
double frequency currents are induced in the rotor. These
currents cause severe heating of the rotor and can cause
damage to the rotor. The unbalanced stators currents also
cause sever vibration and heating of stator. Hence it is
necessary to provide the negative sequence protection to
the generators against the unbalanced load condition.
Single phasing :
Single phasing causes worst kind of unbalance - it produces equal amount of positive and negative
sequence components. The prime causes for single phasing are :
broken or burn out of connecting leads to motor
blown fuses
faulty contact in switching element
To understand the effect of single phasing in motors, consider the condition shown below .
It can be seen that the current in winding C will be larger than that in A and B and consequently it will
burn out. Typical currents in the windings are shown below >
Phase reversal :
Phase reversal in a motor can be very dangerous - the motor will run in the opposite direction resulting
in severe damage to gear boxes, material flow problems and hazard to operating personnel.
Phase reversal in a motor feeder produces a negative sequence of nearly 100% and is well detected by a
relay with negative sequence protection.
Considering the above details, it can be easily concluded that a motor protection relay will
provide an effective protection to the motor only when it is equipped to measure the
negative sequence component level in the motor feeder.
What is a Protocol?
A standard set of regulations and requirements that allow two electronic items to connect to and exchange information with
one another. Protocols regulate data transmission among devices as well as within a network of linked devices through both
error control and specifying which data compression method to use. In particular, protocols decide: the method of error
checking, how to compact data (if required), how the transmitting device signals that it has concluded sending data, and
how the receiving device signals that it has completed receiving data.
As a rule, true power is a function of a circuit's dissipative elements, usually resistances (R). Reactive power
is a function of a circuit's reactance (X). Apparent power is a function of a circuit's total impedance (Z).
Since we're dealing with scalar quantities for power calculation, any complex starting quantities such as
voltage, current, and impedance must be represented by their polar magnitudes, not by real or imaginary
rectangular components. For instance, if I'm calculating true power from current and resistance, I must use
the polar magnitude for current, and not merely the “real” or “imaginary” portion of the current. If I'm
calculating apparent power from voltage and impedance, both of these formerly complex quantities must
be reduced to their polar magnitudes for the scalar arithmetic.
There are several power equations relating the three types of power to resistance, reactance, and
impedance (all using scalar quantities):
Please note that there are two equations each for the calculation of true and reactive power. There are
three equations available for the calculation of apparent power, P=IE being useful only for that purpose.
Examine the following circuits and see how these three types of power interrelate for: a purely resistive
load in Figure below, a purely reactive load in Figure below, and a resistive/reactive load in Figure below.
Resistive load only:
True power, reactive power, and apparent power for a purely resistive load.
Resistive/reactive load:
True power, reactive power, and apparent power for a resistive/reactive load.
These three types of power -- true, reactive, and apparent -- relate to one another in trigonometric form.
We call this the power triangle: (Figure below).
Power triangle relating appearant power to true power and reactive power.
Using the laws of trigonometry, we can solve for the length of any side (amount of any type of power),
given the lengths of the other two sides, or the length of one side and an angle.
LOAD ENCROCHMENT
Abstract - Cascaded tripping of power lines due to mal-operation
of zone 3 distance relays was one of the main causes of many
previous blackouts worldwide. Encroachment of load into the
zone 3 characteristics is one of the main causes for the mal-operation
of the relays. By improving the operation of zone 3 of
distance relays it is possible to prevent such mal-operations so
that cascaded line tripping can be avoided.
A new algorithm that utilizes
Synchronized Phasor Measurements (SPM) to control the
operation of distance protection zone 3. Based on the proposed
algorithm, several improvements in operation of zone 3 can be
achieved. For instance, the relay can differentiate between actual
system faults and load encroachment.
Types of protection
Protection schemes can be divided into two major groupings:
1. Unit schemes
2. Non-unit schemes
The unit protection a scheme is based on Kirchhoff’s Current Law – the sum of the currents entering an area of the system must
be zero.
Any deviation from this must indicate an abnormal current path. In these schemes, the effects of any disturbance or
operating condition outside the area of interest are totally ignored and the protection must be designed to be stable above the
maximum possible fault current that could flow through the protected area.
The non-unit schemes, while also intended to protect specific areas, have no fixed boundaries. As well as
protecting their own designated areas, the protective zones can overlap into other areas. While this can be very beneficial for
backup purposes, there can be a tendency for too great an area to be isolated if a fault is detected by different non unit schemes.
The most simple of these schemes measures current and incorporates an inverse time characteristic into the protection operation
to allow protection nearer to the fault to operate first.
2 Phase to Phase fault Not with Ground Related Phase Over current relays
3 Double phase to Ground fault Related Phase Over current relays and Earth Fault
relays
For feeder protection, there would be more than one over current relay to protect different sections of the feeder. These over
current relays need to coordinate with each other such that the relay nearest fault operates first.
Use time, current and a combination of both time and current are three ways to discriminate adjacent over current relays.
1. Phase faults
2. Earth faults
3. Winding faults
Short-circuit currents are generally several times (5 to 20) full load current. Hence fast fault clearance is always desirable on
short circuits.
If the interrupting rating is not properly selected, a serious hazard for equipment and personnel will exist.
Current limiting can be considered as another overcurrent protective device rating, although not all overcurrent protective devices
are required to have this characteristic
Voltage Rating: The voltage rating of the overcurrent protective device must be at least equal to or greater than the circuit
voltage. The overcurrent protective device rating can be higher than the system voltage but never lower.
Ampere Rating: The ampere rating of a overcurrent protecting device normally should not exceed the current carrying capacity of
the conductors As a general rule, the ampere rating of a overcurrent protecting device is selected at 125% of the continuous load
current.
The overcurrent protection is a bigger concept So that the overload protection can be considered as a subset of overcurrent
protection.
The overcurrent relay can be used as overload (thermal) protection when protects the resistive loads, etc., however, for motor
loads, the overcurrent relay cannot serve as overload protection Overload relays usually have a longer time setting than the
overcurrent relays.
Modern relays may contain more than one stage of protection each stage includes each own current and time setting.
1. For Operation of Definite Time Over current Relay operating time is constant
2. Its operation is independent of the magnitude of current above the pick-up value.
3. It has pick-up and time dial settings, desired time delay can be set with the help of an intentional time delay mechanism.
4. Easy to coordinate.
5. Constant tripping time independent of in feed variation and fault location.
Drawback of Relay:
1. The continuity in the supply cannot be maintained at the load end in the event of fault.
2. Time lag is provided which is not desirable in on short circuits.
3. It is difficult to co-ordinate and requires changes with the addition of load.
4. It is not suitable for long distance transmission lines where rapid fault clearance is necessary for stability.
5. Relay have difficulties in distinguishing between Fault currents at one point or another when fault impedances between
these points are small, thus poor discrimination.
Application:
Definite time over current relay is used as:
1. Back up protection of distance relay of transmission line with time delay.
2. Back up protection to differential relay of power transformer with time delay.
3. Main protection to outgoing feeders and bus couplers with adjustable time delay setting.
Discrimination by both ‘Time’ and ‘Current’. The relay operation time is inversely proportional to the fault current.
Inverse Time relays are also referred to as Inverse Definite Minimum Time (IDMT) relay.
Inverse Definite Minimum Time (IDMT)
The operating time of an over current relay can be moved up (made slower) by adjusting the ‘time dial setting’. The lowest time
dial setting (fastest operating time) is generally 0.5 and the slowest is 10.
Operates when current exceeds its pick-up value.
Operating time depends on the magnitude of current.
It gives inverse time current characteristics at lower values of fault current and definite time characteristics at higher values
An inverse characteristic is obtained if the value of plug setting multiplier is below 10, for values between 10 and 20
characteristics tend towards definite time characteristics.
Widely used for the protection of distribution lines.
Based on the inverseness it has three different types:
Inverse types
3.1. Normal Inverse Time Overcurrent Relay
The accuracy of the operating time may range from 5 to 7.5% of the nominal operating time as specified in the relevant
norms. The uncertainty of the operating time and the necessary operating time may require a grading margin of 0.4 to 0.5
seconds.
It’s used when Fault Current is dependent on generation of fault not fault location.
Normal inverse time Overcurrent Relay is relatively small change in time per unit of change of current.
Application:
Most frequently used in utility and industrial circuits. especially applicable where the fault magnitude is mainly dependent on the
system generating capacity at the time of fault.
Three conditions must be satisfied for its operation: current magnitude, time delay and directionality. The directionality of current
flow can be identified using voltage as a reference of direction.
Application of over current Relay
Motor Protection:
Used against overloads and short-circuits in stator windings of motor.
Inverse time and instantaneous over current phase and ground
Over current relays used for motors above 1000 kW.
Transformer Protection:
Used only when the cost of over current relays are not justified.
Extensively also at power-transformer locations for external-fault back-up protection.
Line Protection:
On some sub transmission lines where the cost of distance relaying cannot be justified.
Primary ground-fault protection on most transmission lines where distance relays are used for phase faults.
For ground back-up protection on most lines having pilot relaying for primary protection.
Distribution Protection:
Over current relaying is very well suited to distribution system protection for the following reasons:
Quiescent Current
The term given to describe the amount of current consumed by a circuit when it is not performing any work
(sometimes referred to as standby current). This is a particularly important concept in designing battery-operated
systems such as wireless belt pack transmitters. Battery life is determined by the total current drain composed of
quiescent current and load current. Usually battery-operated devices are in standby mode more than in operation
mode so the quiescent current consumption is the more dominant consideration. Quiescent current consumption
should be as low as possible in order to prolong the battery’s life.
Class A amplifiers have the general property that the output device(s) always carry a significant current level, and
hence have a large quiescent current. The quiescent current is defined as the current level in the amplifier when it is
producing an output of zero. Class A amplifiers vary the large quiescent current in order to generate a varying current
in the load hence they are always inefficient in power terms.
A Restricted Earth Fault (REF) means an earth fault from a restricted/localized zone of a
circuit. The term "REF protection method” means not to sense any earth faults outside this
restricted zone. REF is a type of "unit protection" applied to transformers or generators and
is more sensitive than the method known as differential protection. An REF relay works by
measuring the actual current flowing to earth from the frame of the unit. If that current
exceeds a certain preset maximum value of milliamps (mA) then the relay will trip to cut off
the power supply to the unit. Differential protection can also be used to protect the windings
of a transformer by comparing the current in the power supply's neutral wire with the current
in the phase wire: if the currents are equal then the differential protection relay will not
operate; if there is a current imbalance then the differential protection relay operates.
However, REF protection is also applied to transformers in order to detect ground faults on a
given winding much more sensitively than differential protection can do. Read more:
http://wiki.answers.com/Q/What_is_restricted_earth_fault_protection_and_how_is_it_provided
#ixzz1sjyn901n Re: what is the diff. b/w restricted earth fault relay & standby earth fault relay
and where they are used? Answer# 1Restricted earth fault (REF) relay is a unit protection
intended for one winding of a transformer (neutral winding) the input of which is from a
neutral bushing CT and in some applications, balanced by the output of three line CTs in the
Y-winding directly connected to neutral. This provides accurate sensing of zero-sequence
leakage currents for a fault within its zone of protection, i.e., on the windings. Whereas,
standby EF relay is a back-up over current ground protection usually connected on the HV
side and its main purpose is to provide local back-up protection in case for a failure of main
protections of the LV feeder/line ports., bus ports., and the transf. main protections. Re: what
is the diff. b/w restricted earth fault relay & standby earth fault relay and where they are
used? Answer# 2i agree with this answer with little correction Standby Earth Fault relay is also
connected to star side the difference between SEF and REF is REF operates in In Zone only
SEF operates in In and Out Zones. If there is an earth fault in outgoing feeders and the feeder
protection is not
Phase to phase fault in the transformer are rare. If such a fault does occur, it will give rise to substantial current to
operate instantaneous over current relay on the primary side as well as the differential relay.
Accuracy class of 0.2 means +/ - 0.2 % error. But, the declared accuracy is guaranteed only
between 100% & 120%
rating. And, with some increased error, the CT performance
can be guaranteed from 5% loading. Below this load, the
error is not guaranteed. It can be anything.
Accuracy class:0.2S more accurate, for protection s ee data sheet. CT s, accuracy class is
typically, 0.2, 0.5, 1 or 3. This means that the errors have to be within the limits specified in
the standards for that particular accuracy class. The metering CT has to be accurate from 5%
to 120% of the rated primary current, at 25% and 100% of the rated burden at the specified
power factor. In the case of protection CT s, the CT s should pass both the ratio and phase
errors at the specified accuracy class, usually 5P or 10P, as well as composite error at the
accuracy limit factor of the CT.
But in an actual CT, errors with which we are connected can best be considered through a study of phasor diagram
for a CT,
Is – Secondary current.
Es – Secondary induced emf.
Ip – Primary current.
Ep – Primary induced emf.
KT – Turns ratio = Numbers of secondary turns/number of primary turns.
I0 – Excitation current.
Im – Magnetizing component of I0.
Iw – Core loss component of I0.
Φm – Main flux.
Let us take flux as reference. EMF Es and Ep lags behind the flux by 90°. The magnitude of the passers Es and Ep are
proportional to secondary and primary turns. The excitation current Io which is made up of two components Im and Iw.
The secondary current I0 lags behind the secondary induced emf Es by an angle Φ s. The secondary current is now
transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The total current flows through the
primary Ip is then vector sum of KT Isand I0.
From above passer diagram it is clear that primary current Ip is not exactly equal to the secondary current multiplied
by turns ratio, i.e. KTIs. This difference is due to the primarycurrent is contributed by the core excitation current.
The error in current transformerintroduced due to this difference is called current error of CT or some times ratio
error incurrent transformer.
It is an
electro-mechanical relay with a consistent positive action, a
XR351
In some applications of high Impedance relays a non-linear metrosil resistor is required to limit the current
transformer secondary voltage to a safe level during maximum internal fault condition. The metrosil
chosen depends on the relay setting voltage and the maximum secondary internal fault current.
Three phase power transmission has become the standard for power distribution. Three phase
power generation and distribution is advantageous over single phase power distribution.
Three phase power distribution requires lesser amount of copper or aluminium for transferring the
same amount of power as compared to single phase power
The size of a three phase motor is smaller than that of a single phase motor of the same rating.
Three phase motors are self starting as they can produce a rotating magnetic field. The single phase
motor requires a special starting winding as it produces only a pulsating magnetic field.
In single phase motors, the power transferred in motors is a function of the instantaneous current
which is constantly varying. Hence, single phase motors are more prone to vibrations. In three phase
motors, however, the power transferred is uniform through out the cycle and hence vibrations are
greatly reduced.
The ripple factor of rectified DC produced from three phase power is less than the DC produced from
single phase supply.
Three phase motors have better power factor regulation.
Motors above 10HP are usually three phase.
The impedance of a transformer is defined as the percentage of the drop in voltage to the at full load to
the rated voltage of the transformer. This drop in voltage is due to the winding resistance and leakage
reactance.
Alternatively, the percentage of a transformer can be described as the percentage of the nominal
voltage in the primary that is required to circulate the rated current in the secondary.
The secondary of the transformer whose percentage impedance is to be measured is shorted. The
voltage on the primary is gradually increased from zero till the secondary current reaches the
transformer's rated value.
Thus a transformer with a primary rating of 110V which requires a voltage of 10V to circulate the rated
current in the short-circuited secondary would have an impedance of 9%.
A reverse power relay is a directional power relay that is used to monitor the power from a generator
running in parallel with another generator or the utility. The function of the reverse power relay is to
prevent a reverse power condition in which power flows from the bus bar into the generator. This
condition can occur when there is a failure in the prime mover such as an engine or a turbine which
drives the generator.
Causes of Reverse Power
The failure can be caused to a starvation of fuel in the prime mover, a problem with the speed controller
or an other breakdown. When the prime mover of a generator running in a synchronized condition fails.
There is a condition known as motoring, where the generator draws power from the bus bar, runs as a
motor and drives the prime mover. This happens as in a synchronized condition all the generators will
have the same frequency. Any drop in frequency in one generator will cause the other power sources to
pump power into the generator. The flow of power in the reverse direction is known as the reverse
power relay.
Another cause of reverse power can occur during synchronization. If the frequency of the machine to be
synchronized is slightly lesser than the bus bar frequency and the breaker is closed, power will flow from
the bus bar to the machine. Hence, during synchronization (forward), frequency of the incoming
machine is kept slight higher than that of the bus bar i.e. thesynchroscope is made to rotate in the "Too
fast" direction. This ensures that the machine takes on load as soon as the breaker is closed.
The df/dt protection is used to identify abnormal changes in system frequency and take remedial actions
in order to prevent generator overload and the resulting blackout. The df/dt operates faster than
ordinary under frequency relays as it is able to predict the under frequency much earlier.
df/dt relays are also known as ROCOF relays (Rate Of Change of Frequency Relays) The df/dt is usually
wired to a load sheddingsystem which trips select breakers to isolate loads.
The df/dt functions by measuring the rate of change of frequency. When the frequency changes too
fast, it is an indicator of a forthcoming under frequency. The setting of the df/dt relay is in
Frequency/Time in seconds. e.g. 0.3Hz/second or 0.4 Hz/.5 seconds.
Some manufacturers provide a more reliable setting involves specifying two frequency set points and
the time taken for the frequency to cross the two limits. For instance, a df/dt relays can be programmed
to operate if the system frequency crosses 48.5 Hz and 48 Hz in 0.4 seconds
POWER SWING
A transmission line trip during a power swing may cause instability of a power system. It is
necessary to recognize the power swing from fault. Based on stability boundary, the power
swing blocking relays must be set. To do that, first power swing should be analyzed. Second
a way of probability of occurrence of fault must be found. Third, the critical condition under
which the stability of a power system not disturbed is recognized. Finally the settings of the
power swing relays are calculated. In this paper, analysis of the power swing occurrence
has been made. By defining transmissions and generators sensitivities coefficients, the way
of making the line under consideration full load is found. The way of minimization of
distance between load impedance and the last zone of distance protection is given and the
settings of the power swing relays are calculated.
https://www.youtube.com/watch?v=JkYSsbFoyI0
Introduction
Three phase transformer consists of three sets of primary windings, one for each phase, and three sets of secondary
windings wound on the same iron core.
Separate single-phase transformers can be used and externally interconnected to yield the same results as a 3-phase unit.
The primary windings are connected in one of several ways. The two most common configurations are the delta, in which
the polarity end of one winding is connected to the non-polarity end of the next, and the star, in which all three non-polarities
(or polarity) ends are connected together. The secondary windings are connected similarly. This means that a 3-phase transformer
can have its primary and secondary windings connected the same (delta-delta or star-star), or differently (delta-star or star-delta).
It’s important to remember that the secondary voltage waveforms are in phase with the primary waveforms when the primary and
secondary windings are connected the same way. This condition is called “no phase shift.”
But when the primary and secondary windings are connected differently, the secondary voltage waveforms will differ from the
corresponding primary voltage waveforms by 30 electrical degrees. This is called a 30 degree phase shift. When two transformers
are connected in parallel, their phase shifts must be identical; if not, a short circuit will occur when the transformers are energized.”
When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages can be in phase or displaced
as above with the coils connected in star or delta and, in the case of a star winding, have the star point (neutral) brought out to an
external terminal or not.
There are mainly two schemes available for protection against loss of field or excitation of a generator. In
1st scheme, we use an undercurrent relay connected in shunt with main field winding circuit. This relay will
operate if the excitation current comes below it predetermined value. If the relay is to operate for
complete loss of field along, it must have a setting lies well below the minimum excitation current value
which can be 8% of the rated full load current. Again when loss of field occurs due to failure of exciter but
not due to problem in the field circuit (field circuit remains intact) there will be an induced current at slip
frequency in the field circuit. This situation makes the relay to pick up and drop off as per slip frequency
of the induced current in the field. This problem can be overcome in the following manner.
In this case a setting of 5% of normal of full load current is recommended. There is a normally closed
contact attached with the undercurrent relay. This normally closed contact remains open as the relay coil
is energized by shunted excitation current during normal operation of the excitation system. As soon as
there is any failure of excitation system, the relay coil becomes de-energized and the normally closed
contact closes the supply across the coil of timing relay T1. As the relay coil is energized, the normally
open contact of this relay T 1 is closed. This contact closes the supply across another timing relay T 2 with
an adjustable pickup time delay of 2 to 10 seconds. Relay T 1 is time delayed on drop off to stabilize
scheme again slip frequency effect. Relay T 2 closes its contacts after the prescribed time delay to either
shut down the set or initiate an alarm. It is time delayed on pickup to prevent spurious operation of the
scheme during an external fault. For larger generator or alternator, we use a more sophisticated scheme
for that purpose. For larger machines, it is recommended to trip the machine after a certain prescribed
delay in presence of swing condition resulting from loss of field. In addition to that there must be
subsequent load shedding to maintain stability of the system. In this scheme of protection, an automatic
imposition of load shedding to the system is also inherently required if the field is not restored within is
described time delay. The scheme comprises an offset mho relay, and an instantaneous under voltage
relay. As we have said earlier that it is not always required to isolate the generator immediately in the
event of loss of field, unless there is a significant disturb in system stability. We know that system voltage
is the main indication of system stability. Therefore the offset mho relay is arranged to shut the machine
down instantaneously when operation of generator accompanied by a system voltage collapse. The drop
in system voltage is detected by an under voltage relay which is set to approximately 70% of normal rated
system voltage. The offset mho relay is arranged to initiate load shedding to the system up to a safe value
and then to initiate a master tripping relay after a predetermined time.
Power Swing
Power Swing which is basically caused by the large disturbances in the power system which if
not blocked could cause wrong operation of the distance relay and can generates wrong or
undesired tripping of the transmission line circuit breaker.
Power swings can cause the change in load impedance which under steady state conditions,
whereas within the relay’s operating characteristic, to induce unwanted relay operations at
different network locations. These undesirable measurements may aggravate the power-system
disturbance and cause major power outages, or even power blackout. Particularly, distance
relays should not trip unexpectedly during dynamic system conditions such as stable or
unstable power swings, and allow the power system to return to a stable operating condition.
Thereby, a Power Swing Block (PSB) function is adopted in modern relays to prevent unwanted
distance relay element operation during power swing. The main purpose of the PSB function is
to differentiate between power faults and power swings, and block distance or other relay
elements from operations during a power swing.
The power system disturbances cause big oscillations in active and reactive power, low voltage,
voltage instability and phase or angular instability between the generated and consumed power
which results in loss of generation and load which effected both the power generation and the
end customers. During the steady state condition, power systems operate on the nominal
frequency (50Hz or 60Hz). The complete synchronism of nominal frequency and voltage at the
sending and receiving ends cause complete balance of active and reactive power between
generated and consumed active and reactive powers. In steady state operating condition
Frequency= Nominal frequency (50 or 60 Hz) +/– 0.02 Hz and Voltage=Nominal voltage +/– 5%
[1].
Power system faults, line switching, generator disconnection, and the loss or application of large
blocks of load result in sudden changes to electrical power
The electrical power, Pg transferred from the generator, an electric machine, to the load is given
by the equation:
where:
El = Load Voltage
Pa = Accelerating Power
The mechanical power, Pm, is provided by the turbine and the average mechanical power must
be equal to the average electrical power. When a system disturbance occurs there is a change
in one of the parameters of the electrical power equation. For faults, typically the reactance
between the generator and the load (X), the load voltage (El), or some combination of these two
parameters causes the electrical power to change. For example, for a short circuit the load
voltage is reduced, for a breaker opening the reactance increases. When a generation unit trips,
the required electrical power from the remaining generators increases. In this case, the
instantaneous mechanical power provided by the turbine is no longer equal to the instantaneous
electrical power delivered or required by the load. When the load on a unit is suddenly
increased, the energy furnished by the rotor results in a decrease in the rotor angular velocity.
And this decrease in rotor velocity will cause oscillations in rotor angle and can result in severe
power flow swings.
Suppose we have two generators G1&G2 in parallel, and both the generators are sharing load.
On the sudden disconnection of G2, there will be an increase in load on G1 and due to this
there will be the oscillations in the rotor angle of G1, which is represented in Fig.
In Fig, d is the steady state rotor angle and d’ is the change in rotor angle due to oscillations
which will result in
The oscillation of nominal voltage and this oscillation in the nominal voltage cause loss of
synchronism between the generators in parallel or between the generation and load.
Depending on the severity of the disturbance and the actions of power system controls, the
system may remain stable and return to a new equilibrium state experiencing what is referred to
as a stable power swing. Severe system disturbances, on the other hand, could cause large
separation of generator rotor angles, large swings of power flows, large fluctuations of voltages
and currents, and eventual loss of synchronism between
groups of generators or between neighboring utility systems. Stable Power Swing: Small
disturbances which can be control by the action of Power System and the system remain in its
steady state condition. Unstable Power Swing: Severe disturbances can produce a large
separation of System Generator Rotor angles, large swings of power flow, large fluctuations of
voltages and currents, and eventually lead to lose synchronism.
Distance or other relays should not trip during such as stable or unstable power swings, and
allow the power system to return to a stable operating condition. Distance relay elements prone
to operate during stable or transient power swings should be temporarily inhibited from
operating to prevent system separation from occurring at random or in other than pre-selected
locations. A Power Swing Block (PSB) function is available in modern relays to prevent
unwanted distance relay element operation during power swings. The main purpose of the PSB
function is to differentiate between faults and power swings and block distance or other relay
elements from operating during a power swing. However, faults that occur during a power swing
must be detected and cleared with a high degree of selectivity and dependability. Severe
system disturbances could cause large separation of the rotor angles between groups of
generators and eventual loss of synchronism between groups of generators or between
neighboring utility systems. When two areas of a power system, or two interconnected systems,
lose synchronism, the areas must be separated from each other quickly and automatically to
avoid equipment damage and power blackouts. Ideally, the systems should be separated in
predetermined locations to maintain a load-generation balance in each of the separated areas.
System separation may not always achieve the desired load-generation balance. In cases
where the separated area load is in excess of local generation, some form of load shedding is
necessary to avoid a complete blackout of the area. Uncontrolled tripping of circuit breakers
during an Out-of- Step (OOS) condition could cause equipment damage, pose a safety concern
for utility personnel, and further contribute to cascading outages and the shutdown of larger
areas of the power system.
*Unless a burden (i.e. meters, relays, etc.) is connected to the CT, current transformers should
always be shorted across the secondary terminals. The reason is very high voltages will be
induced at the terminals. Think of the CT as a transformer, with a 1 turn primary and many turns
on the secondary. When current is flowing through the primary, the resulting voltage induced in
the secondary can be quite high, on the order of kilovolts. When a CT fails under open circuit
conditions, the cause of failure is insulation breakdown, either at the shorting terminal strip, or at
the feed through (in the case of oil filled apparatus), because the distances between terminals
are not sufficient for the voltages present.
*Basically act is a step up transformer, normally in the primary of a ct high currents are flowing.
If the secondary is opened then as it's a step up transformer.
A high voltage is induced in the secondary, the induced secondary voltage is very high, it may
damage the instrument itself or it may damage the observer or the insulation may break down
so it must be shorted with an ammeter of suitable range or must be shorted.
A CT has large number of turns on its secondary winding, but very few turns on its primary winding. The primary winding is connected in
series with the load so that it carries full load current. A low voltage range ammeter (0-5A) is connected across the secondary winding
terminals. Secondary of the CT is practically short circuited since the ammeter resistance is very low. It should be remembered that
secondary of the CT should not be made open as it draws heavy current and damages the primary winding of the CT
A PT has large number of turns in the primary and fewer turns in the secondary and hence it steps down the voltage. The primary winding is
connected across the supply voltage and low range voltmeter (0-110V) is connected across the secondary winding terminals
Some of the main difference between current transformers (CT) and potential transformers (PT) are given below:
The secondary of the CT is almost short circuit, whereas the secondary of the PT is practically a open circuit
The primary winding of the CT is connected in series with the load so that it carries the full line current, but there is only a small
voltage across it. However the primary winding of the PT has the full supply voltage applied across it
In CT the excitation current I0 and flux density vary over a wide range whereas in PT, they vary over a limited range only.
Current transformer: Secondary current is proportional to Primary current. Secondary voltage depends upon the current as well as
load resistance
Potential transformer: Secondary current is proportional to Primary current. Secondary current depends upon the voltage as well as
load resistance.
Current transformer: Secondary can be short circuited. Open secondary may result in failure of the transformer.
Potential transformer: Secondary can be opening circuited. Short secondary may result in failure of the transformer.
Current transformer: Primary of current transformer should be connected in series of the circuit of which current needs to be
measured.
Potential transformer: Primary of voltage transformer should be connected in parallel of the circuit of which voltage needs to be
measured.
Current transformer: Used for measurements and operating protective relays. Never used as power source.
Potential transformer: Used as power source as well as for measurements and operating protective relays.
Current transformer: Primary impedance is very low as compared to impedance of the circuit of which current needs to be measured.
Potential transformer: Primary impedance is very high.
Shunt reactors are designed for connection to the ends of high voltage transmission lines or to high-voltage cables for
the purpose of controlling the line voltage by absorbing reactive power. Let us look at the equivalent circuit of the transmission line
and see shunt reactor effect on the line parameters.
A shunt reactor is an absorber of reactive power, thus increasing the energy efficiency of the system. It is the most compact device
commonly used for reactivepower compensation in long high-voltage transmission lines and in cable systems
Main Power System parameters are System Voltages and Frequency which normally indicate the healthiness level (they indicate
the level of Generated active and reactive Powers against the load power requirement). In a healthy system, Voltage and
frequency are close to the rated system values.
Increased active and reactive power load tends to decrease the system frequency and voltage levels respectively. It then becomes
essential to generate additional active and reactive power. Synchronous Generators respond to the demand by means of
Governor/AVR control systems.
In order to preserve MVA capability of Generators (stator thermal limit) it is preferred to have reactive load support from other
sources of reactive power like fixed Capacitor banks or other FACTS .
Shunt Reactors are Inductive device commonly used in HV and EHV Systems for compensating the excess capacitive VArs in a
power system.
Due to their inductive nature of the Shunt Reactor, it is used whenever there is need for compensation of capacitive
reactance. Power System loads are predominantly inductive in nature and Capacitor banks are used to compensate for the
inductive loads. During system light load condition, often voltages increase beyond the normal operating levels and such a
condition demands additional inductive loads to maintain system voltage levels within the normal range.
Generators have limited capacity with regard to under and over excitation operation. Typical Generators have rated power factor
(pf) of between 0.8 to 0.85 (lead and lag) at rated MVA. At different MVA loading, Synchronous Generators can be operated wit hin
its limit of stability, stator/rotor thermal capacity as over and under-excited.
These limiting values of under and over excitation are given as Generator capability curves by the Generator Manufacturer.
As mentioned above, during light load condition there is risk of system instability due to generated VAr larger than system can
absorb. When system VAr generation is higher than the required VAr load, Generators tend to go to under-excitation. Under
excitation limit of AVR is used to prevent level of under- excitation below stability limit.
Voltage rise due to increased total system generated VAr is dependent on the source impedance of the system. Source
impedances are inductive in nature and weaker system has larger inductive reactance. It is known that inductive reactance and
capacitive reactance are opposite in sign.
Series reactors are used as current limiting reactors to increase the impedance of a system. They are also used for neutral
earthing. Such reactors are also used to limit the starting currents of synchronous electric motors and to compensate Reactive
Power in order to improve the transmission capacity of power lines.
*A shunt reactor is an absorber of reactive power, thus increasing the energy efficiency of the system. It is the most compact device
commonly used for reactive power compensation in long high-voltage transmission lines and in cable systems. The shunt reactor
can be directly connected to the power line or to a tertiary winding of a three-winding transformer.
The shunt reactor could be permanently connected or switched via a circuit breaker. To improve the adjustment of the consumed
reactive power the reactor can also have a variable rating. If the load variation is slow, which it normally is (seasonal, daily or
hourly), a variable shunt reactor (VSR) could be an economical solution for some customer applications.
To find the lead resistance Rleads (two leads – supply, return) we can use the standard formulae for resistivity:
Rleads = 2 ρ l /a = 2 x 0.0175 x 50 / 6 = 0.3 Ω
Numerical relays have low burdens, typically 0.1 Ω (where possible the relay manual should be consulted).
Rb = 15 VA / 1 A2 = 15 Ω
R’b = Rleads + Rrelay = 0.3 + 0.1 = 0.4 Ω
K’scc = Kscc (Rct + Rb)/(Rct + R’b)
= 20 (4 + 15 )/ (4 + 0.4) = 86.4
In this case the effective K’scc of 86.4 is greater than the required K’scc of 50 and the CT meets the stability criteria.
The factor Kssc is relatively easy to understand and relates to the liner portion of a CT characteristic. The voltage and current across a CT are linear only up till a
certain value (normally specified as a multiple of the nominal rating), after which the CT will saturate and the curve will level off. A CT rated at say 5P20 will stay
linear to approximately 20 times its nominal current. This linear limit is the Kssc (i.e. Kssc = 20). As a reminder, the 5 [in the 5P20] would be the CT accuracy class
and the ‘P’ signifies a protection class CT.
Slightly more complicated is the effective factor, K’scc. This is a calculated value which takes into account the burden (resistance) of the relay, resistance of the CT
windings and resistance of the leads:
Connection Leads
In the sizing of protection transformers, the resistance (burden) of the connection leads can have a considerable effect. In calculations, the resistance of the
connection leads can be estimated from:
where:
The standards adopted the concept of knee voltage and it is still common to find knee voltage voltage being used as a CT sizing parameter.
Knee voltage is defined as the point at which a 10% increase in voltage across the terminals, causes a 50% increase in excitation current
Utilising the British Standards, CTs were defined by the knee point voltage UKN and the internal secondary resistance Ri. To convert an IEC design the following
can be used:
ANSI/IEEE C57.13
The IEEE standard C57.13 covers the requirements for CT sizing in the North American markets.
Class C of the standard defines CTs by their secondary terminal voltage at 20 times nominal current (for which the ratio error shall not exceed 10%). Standard
classes are C100, C200, C400 and C800 for 5 A nominal secondary current.
This terminal voltage can be calculated from the IEC data as follows:
with
and
If anyone has any questions, comments or suggestions on how to improve the post, please add them below.
Principle of operation of CT
A current transformer is defined as “as an instrument transformer in which the secondary current is substantially
proportional to the primary current (under normal conditions of operation) and differs in phase from it by an angle
which is approximately zero for an appropriate direction of the connections.”
Current transformers are usually either “measuring” or “protective” types.
Some Definitions used for CT:
Bar type current transformers are insulated for the operating voltage of the system.
Bar-type CTs operate on the same principle of window CTs but have a permanent bar installed as a primary
conductor
2) Wound CT’s:
Capacity: There are designed to measure currents from 1 amp to 100 amps.
the most common one is the wound type current transformer. The wound type provides excellent performance
under a wide operating range. Typically, the wound type is insulated to only 600 volts.
Since the load current passes through primary windings in the CT, screw terminals are provided for the load and
secondary conductors. Wound primary CT’s are available in ratios from 2.5:5 to 100:5.
Wound CTs have a primary and secondary winding like a normal transformer. These CTs are rare and are usually
used at very low ratios and currents, typically in CT secondary circuits to compensate for low currents, to match
different CT ratios in summing applications, or to isolate different CT circuits. Wound CTs have very high burdens,
and special attention to the source CT burden should be applied when wound CTs are used.
3) Window:
Window CTs are the most common. They are constructed with no primary winding and are installed around the
primary conductor. The electric field created by current flowing through the conductor interacts with the CT core to
transform the current to the appropriate secondary output. Window CTs can be of solid or split core construction.
The primary conductor must be disconnected when installing solid window CTs. However, split core CTs can be
installed around the primary conductor without disconnecting the primary conductor
The primary and secondary currents are expressed as a ratio such as 100/5. With a 100/5 ratio CT, 100A flowing
in the primary winding will result in 5A flowing in the secondary winding, provided the correct rated burden is
connected to the secondary winding. Similarly, for lesser primary currents, the secondary currents are
proportionately lower.
It should be noted that a 100/5 CT would not fulfil the function of a 20/1 or a 10/0.5 CT as the ratio expresses the
current rating of the CT, not merely the ratio of the primary to the secondary currents.
The rated secondary current is commonly 5A or 1A, though lower currents such as 0.5A are not uncommon. It
flows in the rated secondary load, usually called the burden, when the rated primary current flows in the primary
winding.
Increasing or Decreasing Turns Ratio of CT:
Increasing Number of Turn: Increasing the number of primary turns can only decrease the turn’s ratio. A current
transformer with a 50 to 5 turn’s ratio can be changed to a 25 to 5 turn’s ratio by passing the primary twice through
the window.
Increasing or Decreasing Turns Ratio:
The turn’s ratio can be either increased or decreased by wrapping wire from the secondary through the window of
the current transformer.
Increasing the turn’s ratio with the secondary wire, turns on the secondary are essentially increased. A 50 to 5
current transformer will have a 55 to 5 ratio when adding a single secondary turn.
Decreasing the turn’s ratio with the secondary wire, turns on the secondary are essentially decreased. A 50 to 5
current transformer will have a 45 to 5 ratio when adding a single secondary turn.
Decreasing the turn’s ratio with the primary, accuracy and VA burden ratings are the same as the original
configuration.
Increasing the turn’s ratio with the secondary will improve the accuracy and burden rating.
Decreasing the turn’s ratio with the secondary will worsen the accuracy and burden rating.
When using the secondary of a current transformer to change the turn’s ratio, the right hand rule of magnetic fields
comes into play. Wrapping the white lead or the X1 lead from the H1 side of the transformer through the window to
the H2 side will decrease the turn’s ratio. Wrapping this wire from the H2 side to the H1 side will increase the
turn’s ratio.
Using the black or X2 lead as the adjustment method will do the opposite of the X1(white) lead. Wrapping from the
H1 to the H2 side will increase the turns ratio, and wrapping from the H2 to the H1 side will decrease the turns
ratio.
2) Burden of CT:
Total burden of Measuring CT = Sum of Meters Burden in VA (Ammeter, Wattmeter, Transducer etc.)
connected in series to the CT secondary circuit + Connecting Secondary Circuit Cable Burden in VA.
Cable burden = I2 x R x2 L, where I = CT secondary current, R = cable resistance per length, 2L is the tro &fro
distance of cable length L from CT to metering circuits. If the proper size and short length of wire is used, cable
burden can be ignored.
The CT secondary circuit load shall not be more than the CT VA rating. If the load is less than the CT burden, all
meters connected to the measuring CT should provide correct reading.
In the case of Measuring Current transformer, the burden depends on the connected meters and quantity of meters
on the secondary i.e. no of Ammeters, KWh meters, Kvar meters, Kwh meters, transducers and also the
connection cable burden (I2 x R x2 L) to metering shall be taken into account.
Note Meters burden can be obtained from manufacturer catalogue.
Selected CT burden shall be more than the calculated burden
Burden for Protecting CT:
In the case of Protection CTs the burden is calculated in the same way as above except the burden of individual
protective relays burden shall be considered instead of meters. The connecting cable burden is calculated in the
same way as metering CT
Total burden of Protection CT=Connecting cable Burden in VA + sum of Protective relays Burden in VA.
All manufacturers can supply the burden of their individual devices. Although not used very often these days,
induction disk over-current devices always gave the burden for the minimum tap setting. To determine the
impedance of the actual tap setting being used, First Square the ratio of minimum divide by the actual tap setting
used and, second multiply this value by the minimum impedance.
Suppose an impedance of 1.47 + 5.34j at the 1A tap. To apply the relay at the 4A tap the engineer would multiply
the impedance at the 1A taps setting by (1/4)2. The impedance at the 4A tap would be 0.0919 + 0.3338j or 0.3462
Z at 96.4 power factor.
The CT burden impedance decreases as the secondary current increases, because of saturation in the
magnetic circuits of relays and other devices. Hence, a given burden may apply only for a particular value of
secondary current. The old terminology of volt-amperes at 5 amperes is most confusing in this respect since it is
not necessarily the actual volt amperes with 5 amperes flowing, but is what the volt-amperes would be at 5
amperes
If there were no saturation. Manufacturer’s publications give impedance data for several values of over current for
some relays for which such data are sometimes required. Otherwise, data are provided only for one value of CT
secondary current.
If a publication does not clearly state for what value of current the burden applies, this information should be
requested. Lacking such saturation data, one can obtain it easily by test. At high saturation, the impedance
approaches the DC resistance. Neglecting the reduction in impedance with saturation makes it appear that a CT
will have more inaccuracy than it actually will have. Of course, if such apparently greater inaccuracy can be
tolerated, further refinements in calculation are unnecessary. However, in some applications neglecting the effect
of saturation will provide overly optimistic results; consequently, it is safer always to take this effect into account.
It is usually sufficiently accurate to add series burden impedances arithmetically. The results will be slightly
pessimistic, indicating slightly greater than actual CT ratio inaccuracy. But, if a given application is so borderline
that vector addition of impedances is necessary to prove that the CTÕs will be suitable, such an application should
be avoided.
If the impedance at pickup of a tapped over current-relay coil is known for a given pickup tap, it can be estimated
for pickup current for any other tap. The reactance of a tapped coil varies as the square of the coil turns, and the
resistance varies approximately as the turns. At pickup, there is negligible saturation, and the resistance is small
compared with the reactance. Therefore, it is usually sufficiently accurate to assume that the impedance varies as
the square of the turns. The number of coil turns is inversely proportional to the pickup current, and therefore the
impedance varies inversely approximately as the square of the pickup current.
Whether CT is connected in wye or in delta, the burden impedances are always connected in wye. With wye-
connected CT the neutrals of the CT and of the burdens are connected together, either directly or through a relay
coil, except when a so-called zero phase-sequence-current shunt is used.
It is seldom correct simply to add the impedances of series burdens to get the total, whenever two or more CT are
connected in such a way that their currents may add or subtract in some common portion of the secondary circuit.
Instead, one must calculate the sum of the voltage drops and rises in the external circuit from one CT secondary
terminal to the other for assumed values of secondary currents flowing in the various branches of the external
circuit. The effective CT burden impedance for each combination of assumed currents is the calculated CT terminal
voltage divided by the assumed CT secondary current. This effective impedance is the one to use, and it may be
larger or smaller than the actual impedance which would apply if no other CTÕs were supplying current to the
circuit.
If the primary of an auxiliary CT is to be connected into the secondary of a CT whose accuracy is being studied,
one must know the impedance of the auxiliary CT viewed from its primary with its secondary short-circuited. To this
value of impedance must be added the impedance of the auxiliary CT burden as viewed from the primary side of
the auxiliary CT; to obtain this impedance, multiply the actual burden impedance by the square of the ratio of
primary to secondary turns of the auxiliary CT. It will become evident that, with an auxiliary CT that steps up the
magnitude of its current from primary to secondary, very high burden impedances, when viewed from the primary,
may result.
Burden is depending on pilot lead length
For Metering Class CTs burden is expressed as ohms impedance. For Protection-class CTs burden is
express as volt-amperes (VA).
VA Applications
Burden (VA) of copper wires between instrument & current transformer for 1A and 5A secondary’s
Cross CT 1 Amp Secondary Burden in VA (Twin Wire)
Section
(mm2) Distance
10 20 40 60 80 100
meter meter meter meter meter meter
The Actual burden is formed by the resistance of the pilot conductors and the protection relay(s). The resistance of
a conductor (with a constant cross-sectional area) can be calculated from the equation:
R =ƿxL / A
where ƿ = resistivity of the conductor material (given typically at +20°C) ,L= length of the conductor , A = cross
sectional area
If the resistivity is given in μΩm, the length in meters and the area in mm2, the equation 1 will give the resistance
directly in ohms.
Resistivity: Copper 0.0178 µΩm at 20 °C and 0.0216 µΩm at 75 °C
Burden of CT for 4 or 6 wire connection:
If 6-wire connection is used, the total length of the wire, naturally, will be two times the distance between the CT
and the relay. However, in many cases a common return conductor is used as shown in figure then, instead of
multiplying the distance by two, a factor of 1.2 is typically used. This rule only applies to the 3-phase connection
only. The factor 1.2 allows for a situation, where up to 20% of the electrical conductor length, including terminal
resistances, uses 6-wire connection and at least 80% 4-wire connection.
Example: the distance between the CT and the relay is 5 meters the total length is 2 x 5 m = 10 meter for 6-wire
connection, but only 1.2 x 5 m = 6.0 meter when 4-wire connection is used.
Burden of the relay:
Example: The Distance between the CTs and the protection relay is 15 meters, 4 mm2 Cu conductors in 4-wire
connection are used. The burden of the relay input is less than 20 mΩ (5 A inputs). Calculate the actual burden of
the CT at 75°C , the input impedance is less than 0.020 Ω for a 5 A input (i.e. burden less than 0.5 VA) and less
than 0.100 Ω for a 1 A input (i.e. less than 0.1 VA):
Solution:
ƿ = 0.0216 µΩm (75°C) for copper conductor.
R =ƿxL / A ,R = 0.0216 µΩm x (1.2 x 15 m) / 4 mm2 = 0.097 Ω
Burden of CT = 0.097 Ω + 0.020 Ω = 0.117 Ω.
Using CTs of burden values higher than required, is unscientific since it leads to inaccurate reading (meter) or
inaccurate sensing of fault / reporting conditions.
Basically, such high value of design burden extends saturation characteristics of CT core leading to likely damage
to the meter connected across it under overload condition. e.g. When we expect security factor (ISF) to be 5, the
secondary current should be restricted to less than 5 times in case primary current shoots to more than 5 times its
rated value.
In such an overload condition, the core of CT is desired to go into saturation, restricting the secondary current thus
the meter is not damaged. However, when we ask for higher VA, core doesn’t go into saturation due to less load
(ISF is much higher than desired) which may damage the meter.
To understand the effect on Accuracy aspect, let’s take an example of a CT with specified burden of 15 VA, and
the actual burden is 2.5 VA:15 VA CT with less than 5 ISF will have saturation voltage of 15 Volts (15/5×5), and
actual burden of 2.5 VA the saturation voltage required shall be ( 2.5/5 x 5) 2.5 Volts against 15 Volts resulting ISF
= 30 against required of 5.
Example: Decide Whether 5A,20VA CT is sufficient for following circuit
The CT accuracy is determined by its certified accuracy class which is stamped on nameplate. For example, CT
accuracy class of 0.3 means that the CT is certified by the manufacturer to be accurate to within 0.3 percent of its
rated ratio value for a primary current of 100 percent of rated ratio.
CT with a rated ratio of 200/ 5 with accuracy class of 0.3 would operate within 0.45 percent of its rated ratio value
for a primary current of 100 amps. To be more explicit, for a primary current of 100A it is certified to produce a
secondary current between 2.489 amps and 2.511 amps.
Accuracy is specified as a percentage of the range, and is given for the maximum burden as expressed in VA. The
total burden includes the input resistance of the meter and the loop resistance of the wire and connections
between the current transformer and meter.
Example: Burden = 2.0 VA. Maximum Voltage drop = 2.0 VA / 5 Amps = 0.400 Volts.
Maximum Resistance = Voltage / Current = 04.00 Volts / 5 Amps =0.080 Ohms.
If the input resistance of the meter is 0.010Ω, then 0.070Ω is allowed for loop resistance of the wire, and
connections between the current transformer and the meter. The length and gauge of the wire must be considered
in order to avoid exceeding the maximum burden.
If resistance in the 5 amp loop causes the burden to be exceeded, the current will drop. This will result in
the meter reading low at higher current levels.
As in all transformers, errors arise due to a proportion of the primary input current being used to magnetize the
core and not transferred to the secondary winding. The proportion of the primary current used for this purpose
determines the amount of error.
The essence of good design of measuring current transformers is to ensure that the magnetizing current is low
enough to ensure that the error specified for the accuracy class is not exceeded.
This is achieved by selecting suitable core materials and the appropriate cross-sectional area of core. Frequently in
measuring currents of 50A and upwards, it is convenient and technically sound for the primary winding of a CT to
have one turn only.
In these most common cases the CT is supplied with a secondary winding only, the primary being the cable or bus
bar of the main conductor which is passed through the CT aperture in the case of ring CTs (i .e. single primary
turn) it should be noted that the lower the rated primary current the more difficult it is (and the more expensive it is)
to achieve a given accuracy.
Considering a core of certain fixed dimensions and magnetic materials with a secondary winding of say 200 turns
(current ratio 200/1 turns ratio 1/200) and say it takes 2 amperes of the 200A primary current to magnetize the
core, the error is therefore only 1% approximately. However considering a 50/1 CT with 50 secondary turns on the
same core it still takes 2 amperes to magnetize to core. The error is then 4% approximately. To obtain a 1%
accuracy on the 50/1 ring CT a much larger core and/or expensive core material is required
Accuracy Class of Metering CT:
Metering Class CT
Class Applications
3 OR Approximate measurements
5
Protective CT
VA Class
System Secondary
High
impedance Class PX use relay
1A or 5A
differential manufacturers formula
impedance
High speed
Class PX use relay
feeder 1A or 5A
manufacturers formula
protection
Motor
1A or 5A 5 5P10
protection
B Metering Purpose
Protection Class CT
C CT has low leakage flux.
Current error is an error that arises when the current value of the actual transformation ratio is not equal to rated
transformation ratio.
Current error (%) = {(Kn x Is – Ip) x 100}/Ip
Kn = rated transformation ratio, Ip = actual primary current, Is = actual secondary current
Example: In case of a 2000/5A class 1 5VA current transformer
Kn = 2000/5 = 400 turn, Ip = 2000A, Is = 4.9A
Current error = ((400 x 4.9 – 2000) x100)/2000 = -2%
For protection class current transformer, the accuracy class is designed by the highest permissible percentage
composite error at the accuracy limit primary current prescribed for the accuracy class concerned.
Accuracy class includes: 5P, 10P
By phase angle
Phase error is the difference in phase between primary & secondary current vectors, the direction of the vectors to
be zero for a perfect transformer.
You will experience a positive phase displacement when secondary current vector lead primary current vector.
Unit of scale expressed in minutes / cent radians.
Circular measure = (unit in radian) is the ratio of the distance measured along the arc to the radius.
Angular measure = (unit in degree) is obtained by dividing the angle subtended at the center of a circle into 360
deg equal division known as “degrees”.
Limits of current error and phase displacement for measuring current transformer (Classes 0.1 To 1)
Accur +/- Percentage Current (Ratio) +/- Phase Displacement at % Rated Current
acy Error at % Rated Current
Class Minutes Centi radians
5 20 10 12 5 2 10 12 5 20 10 12
0 0 0 0 0 0 0
0.1 0.4 0.2 0. 0. 15 8 5 5 0.4 0.2 0.1 0.1
1 1 5 4 5 5
0.2 0.7 0.3 0. 0. 30 1 10 10 0.9 0.4 0.3 0.3
5 5 2 2 5 5
0.5 1.5 0.7 0. 0. 90 4 30 30 2.7 1.3 0.9 0.9
5 5 5 5 5
1.0 3 1.5 1 1 18 9 60 60 5.4 2.7 1.8 1.8
0 0
limits of current error and phase displacement for measuring current transformer For special application
Ac +/- Percentage Current (Ratio) +/- Phase Displacement at % Rated Current
cur Error at % Rated Current
acy Minutes Centi radians
Cla 1 5 2 1 1 1 5 2 1 1 1 5 2 1 1
ss 0 0 2 0 0 2 0 0 2
0 0 0 0 0 0
0.2 0 0 0 0 0 3 1 1 1 1 0 0 0 0 0
S . . . . . 0 5 0 0 0 . . . . .
7 3 2 2 2 9 4 3 3 3
5 5
0.5 1 0 0 0 0 9 4 3 3 3 2 1 0 0 0
S . . . . . 0 5 0 0 0 . . . . .
5 7 5 5 5 7 3 9 9 9
0 5
limits of current error for measuring current transformers (classes 3 and 5)
Accuracy Class +/- Percentage Current (Ratio) Error at
% Rated Current
50 120
3 3 3
5 5 5
Class X current transformer is use in conjunction with high impedance circulating current differential protection
relay, eg restricted earth fault relay. As illustrated in IEC60044-1, the class X current transformer is needed.
The following illustrates the method to size a class X current transformer.
Step 1: calculating knee point voltage Vkp
Vkp = {2 x Ift (Rct+Rw)}/ k
Vkp = required CT knee point voltage, Ift = max transformer through fault in ampere
Rct = CT secondary winding resistance in ohms, Rw = loop impedance of pilot wire between CT and the
K = CT transformation ratio
Step 2: calculate Transformer through fault Ift
Ift = (KVA x 1000)/ (1.732 x V x Impedance)
KVA = transformer rating in kVA , V = transformer secondary voltage, Impedance = transformer impedance
Step 3: How to obtain Rct
To measure when CT is produce
Step 4: How to obtain Rw
This is the resistance of the pilot wire used to connect the 5th class X CT at the transformer star point to the relay
In the LV switchboard. Please obtain this data from the Electrical contractor or consultant. We provide a table
toServe as a general guide on cable resistance.
Example:
Transformer Capacity: 2500kVA
Transformer impedance: 6%
Voltage system : 22kV / 415V 3phase 4 wire
Current transformer ratio: 4000/5A
Current transformer type: Class X PR10
Current transformer Vkp : 185V
Current transformer Rct : 1.02½ (measured)
Pilot wire resistance Rw : 25 meters using 6.0mm sq cable
= 2 x 25 x 0.0032 = 0.16½
Ift = (kVA x 1000) / (1.732 x V x impedance) = (2500 x 1000) / (1.732 x 415 x 0.06)= 57,968 (Say 58,000A)
Vkp = {2 x Ift (Rct+Rw)} / k= {2 x 58000 (1.02+0.16)} / 800= 171.1½.
4) Accuracy Limit Factor:
Measurements must have the same polarity to keep the power factor and direction of power flow measurements
accurate and consistent.
Most CTs are labelled that shows which side of the CT should face either the source or the load.
Primary Side : The Primary of CT is marked with H1 and H2 ( or only marking dot on one side)
The label “H1” or dot defines the direction as flowing current into the CT (H1 or the dot should face the Power
source side). H2 side to load facing direction
Secondary Side: The Secondary (The output wires) of CT is marked with X1 and X2.
X1 corresponds to H1, or the input side.The X1 secondary terminal is the polarity terminal. The polarity marks of a
current transformer indicate that when a primary current enters at the polarity mark (H1) of the primary, a current in
phase with the primary current and proportional to it in magnitude will leave the polarity terminal of the secondary
(X1).
Normally CT’s should not be installed on live services. The power should be disconnected when the CT’s are
installed. Many times this is not possible because of critical loads such as computers, laboratories, etc. that cannot
be shut down. Split core CT’s should not be installed on live un insulated bus bars under any conditions.
Modification of Primary & Secondary Turns Ratio:
The nameplate current ratio of the current transformer is based on the condition that the primary conductor will be
passed once through the transformer opening. If necessary, this rating can be reduced in even multiples by looping
this conductor two or more times through the opening.
A transformer having a rating of 300 amperes will be changed to 75 amperes if four loops or turns are made with
the primary cable.
The ratio of the current transformer can be also modified by altering the number of secondary turns by forward or
back-winding the secondary lead through the window of the current transformer.
By adding secondary turns, the same primary amperage will result in a decrease in secondary output.
By subtracting secondary turns, the same primary amperage will result in greater secondary output. Again using
the 300:5 example, adding two secondary turns will require 310 amps on the primary to maintain the 5 amp
secondary output or 62/1p = 310p/5s.
Subtracting two secondary turns will only require 290 amps on the primary to maintain the 5 amp secondary output
or 58s/5p = 290p/5s. The ratio modifications are achieved in the following manner:
To add secondary turns, the white lead should be wound through the CT from the side opposite the polarity mark.
To subtract turns, the white lead should be wound through the CT from the same side as the polarity mark.
1) Modifications in Primary Turns Ratio of CT:
The ratio of the current transformer can be modified by adding more primary turns to the transformer. By adding
primary turns, the current required to maintain five amps on the secondary is reduced.
Ka = Kn X (Nn/Na)
Ka= Actual Turns Ration.
Kn=Name Plate T/C Ratio.
Nn=Name Plate Number of Primary Turns.
Na=Actual Number of Primary Turns.
Example: 100:5 Current Transformers.
2) Modifications in Secondary Turns Ratio of CT:
Formula : Ip/Is = Ns/Np
Ip = Primary Current , Is = Secondary Current , Np = No of Primary Turns, Ns = No of Secondary Turns
Example: A 300:5 Current Transformer.
The ratio of the current transformer can be modified by altering the number of secondary turns by forward or back
winding the secondary lead through the window of the current transformer.
By adding secondary turns, the same primary current will result in a decrease in secondary output. By subtracting
secondary turns, the same primary current will result in greater secondary output.
Again using the 300:5 example adding five secondary turns will require 325 amps on the primary to maintain the 5
amp secondary output or: 325 p / 5s = 65s / 1p
Deducting 5 secondary turns will only require 275 amps on the primary to maintain the 5 amp secondary output or:
275p / 5s = 55s / 1p
The above ratio modifications are achieved in the following manner:
Current Transformer Ratio Modification:
Number of Primary
CT Ratio Modified Ratio
Turns
100:5A 2 50:5A
200:5A 2 100:5A
300:5A 2 150:5A
100:5A 3 33.3:5A
200:5A 3 66.6:5A
300:5A 3 100:5A
100:5A 4 25:5A
200:5A 4 50:5A
300:5A 4 75:5A
A primary turn is the number of times the primary conductor passes through the CT’s window. The main advantage
of this ratio modification is you maintain the accuracy and burden capabilities of the higher ratio. The higher the
primary rating the better the accuracy and burden rating.
You can make smaller ratio modification adjustments by using additive or subtractive secondary turns.
For example, if you have a CT with a ratio of 100:5A. By adding one additive secondary turn the ratio modification
is 105:5A, by adding on subtractive secondary turn the ratio modification is 95:5A.
Subtractive secondary turns are achieved by placing the “X1” lead through the window from the H1 side and out
the H2 side. Additive secondary turns are achieved by placing the “X1” lead through the window from the H2 and
out the H1 side.
So, when there is only one primary turn each secondary turn modifies the primary rating by 5 amperes. If there is
more than one primary turn each secondary turn value is changed (i.e. 5A divided by 2 primary turns = 2.5A).
The following table illustrates the effects of different combination of primary and secondary turns:
CT RATIO 100:5A
PRIMARY SECONDARY
RATIO ADJUSTMENT
TURNS TURNS
1 -0- 100:5A
1 1+ 105:5A
1 1- 95:5A
2 -0- 50:5A
2 1+ 52.5:5A
2 2- 45.0:5A
3 -0- 33.3:5A
3 1+ 34.97:5A
3 1- 31.63:5A
Advantages of using a CT having 1A Secondary:
The standard CT secondary current ratings are 1A & 5A,The selection is based on the lead burden used for
connecting the CT to meters/Relays.5A CT can be used where Current Transformer & protective’s device are
located within same Switchgear Panel.
1A CT is preferred if CT leads goes out of the Switchgear.
For Example if CT is located in Switch Yard & CT leads have to be taken to relay panels located in control room
which can be away.1A CT is preferred to reduce the load burden. For CT with very High lead length, CT with
Secondary current rating of 0.5 Amp can be used.
In large Generator Circuits, where primary rated current is of the order of few kilo-amperes only,5A CTs are used,
1A CTs are not preferred since the turns rations becomes very high & CT becomes unwieldy.
Danger with Current Transformer:
When a CT secondary circuit is closed, current flows through it, which is an exact proportion of the primary current,
regardless of the resistance of the burden. In the CT have a ratio of 1OOO/5A and to have 1OOOA flowing in the
primary is carrying exactly 5A.
If the secondary terminals S1 and S2 are short- circuited, there is no voltage between them.
If now the short-circuit be replaced by a resistance of, say, 0.5 ohm the same 5A will flow through, causing a volt-
drop of 2.5V and a burden of 5 x 2.5 = 12.5V A. If the resistance were increased to 5 ohms the terminal voltage
with 5A flowing would rise to 25V and the burden to 125V A.
The greater the resistance, the greater would be the voltage and burden until, as it approached infinity (the open-
circuit condition), so also in theory would the voltage (and burden) become infinite. This cannot of course happen
in practice because the CT would saturate or the terminals flash over due to the very high secondary voltage
between them. But it does show the danger of open-circuiting the secondary of running CT. lethal voltages can be
produced at the point of opening. This is why CT secondaries are never fused.
The danger from an open-circuited CT is twofold. It can produce lethal voltages and so is a very real danger to
personnel. The high voltage across the secondary winding could also cause insulation failure in that winding,
leading at best to inaccuracy and at worst to burn- out or fire.
Before ever an instrument or relay is removed from the secondary loop of a running CT (if such a thing had to be
done), the wires feeding that instrument must first be securely short- circuited at a suitable terminal box or, better,
at the CT itself. Similarly, if a running CT is ever to be taken out of circuit, it must first be firmly shorted. CTs with 1
A secondary’s are more dangerous than those with 5A, as the induced voltages are higher.
Ammeter resistance is very low ,the current transformer normally works short circuited.
If for any reason the ammeter is taken out of secondary winding then the secondary winding must be short
circuited with the help of short circuit switch .
If this is not done, then due to high m.m.f. will set up high flux in the core and it will produces excessive core loss
which produce heat and high voltage across the secondary terminals
Hence the secondary of current transformer is never left open
Sizing of CT for Building:
New construction: size the CT to handle about 80% of the circuit breaker capacity. If the building is served by a
2000 amp breaker, use 1600 amp (2000 x 0.8) CT’s.
Older buildings: the peak demand can generally be determined from the power company or from past billings. In
this case add 20 to 30% to the peak demand and size the CT’s for this load. If the peak demand was 500 kW, the
peak current on a 480/3/60 system would be 500,000 / (480 x 1.73 x 0.9 pf) = 669 amps. This assumes a 0.9
power factor. (Peak current would be higher with a lower power Factor.) Use CT’s about 20% larger. 800:5 CT’s
would be a good selection.
For older buildings with no demand history, size the CT’s the same as for new construction. Where possible, use
multi-tap CT’s so that the ratio can be reduced if the maximum load is much less than 80% of the breaker size.
CT’s that are used to monitor motor loads can be sized from the nameplate full load motor amps.
It is a device in the circuit breaker that prevents multiple closures of the breakers. Multiple breaker closures can
damage the closing mechanism of the breaker. The anti-pump function is a very important feature of control circuits.
Without the anti-pump function, if the user connected a maintained contact in the close circuit, and the circuit
breaker were closed into a fault current, the protective relays would cause an immediate trip action, but the
maintained contact in the close circuit would initiate closing (again) into the fault. This process is called pumping,
and would lead to ultimate catastrophic failure of some element in the system, perhaps the conductors leading to the
fault, perhaps the circuit breaker, or elsewhere in the system. Therefore, anti-pump control is one of the fundamental
requirements for every medium-voltage circuit breaker. Anti-pumping relay is used to prevent multiple breaker
closures. The effect of continuous closing of circuit breaker is called breaker hunting effect. Anti-pumping relay
insures that the breaker closes only once and removes the hunting effect of the breaker. It is also called trip free
mechanism of the circuit breaker. Sometimes anti-pumping relay is built-in in the circuit breaker and sometimes it
works as auxiliary relay with circuit breaker.
Note that the anti-pump function is reset if the control power supply is removed for some reason. When this
happens, the anti-pump relay contact in the close circuit closes to complete the close circuit. Then, if a maintained
contact in the user’s control circuit is closed, and the control power is restored, the circuit breaker will close.
However, after this initial close operation, the anti-pump relay will be sealed in, and further closing operations will
be prevented until the maintained contact is opened or the control power supply is interrupted.
Multiple closure of circuit breaker can cause damage to breaker and it can be avoided by using 52 relay (circuit
breaker anti-pumping relay). The main function of this relay is to cut off the supply to 52C (circuit breaker closing
coil) coil in case of TNC (trip neutral close push button) switch spring failure and prevent multiple closure of circuit
breaker (hunting effect of CB).
Closing coil circuit with 52 present is as shown in above figure below. Path 1 in the figure shows how 52C (CB
closing coil) will be energized when we press TNC switch. If switch comes to its original state once we release it
then 52 will not come in picture. If switch does not comes to its original state then 52 will be energized as shown in
path 2. Then 52-NC (normally closed) contact present in path 1 will be got opened up and prevents extension of
supply. The auxiliary contacts and anti-pumping relay contacts are shown in the figure with blue arrow.
We have the concept that initially for the energization of 52 80% to 90% of 110V is required. But once after
energization 60-70% of 110V is sufficient to maintain its energization state. This logic is achieved by introducing a
resistance in 52 energization maintenance path.
Trip-free mechanism or anti-pumping control is an important safety feature, as it assures that the decision to open a
circuit breaker dominates over the command to close.
For residual compensation of an earth-fault distance relay, a compensation method using only a reactive
compensation factor (X0/X1) for the transmission line or a compensation method using both a reactive
compensation factor (X0/X1) and a resistive compensation factor (R0/R1) which are widely used in Japan. In this
paper, we present the reason why measuring distance errors of earth-fault distance relays occur even when these two
residual current compensation methods are used. Furthermore, with the compensation method that uses both reactive
and resistive compensation factors, we have shown that depending upon whether the ratio, (RG/RA) of the line to
earth resistance (RG) to line to line resistance (RA) is larger or smaller than the resistive compensation factor
(R0/R1) that an earth-fault distance relay will respectively either overreach or under reach for a double line to earth
fault.
Charging Current in Transmission Line
In a transmission line, air acts as a dielectric medium between the conductors. When the voltage is
applied across the sending end of the transmission line, current starts flowing between the conductors
(due to imperfections of the dielectric medium). This current is called the charging current in the
transmission line. In
other words, we can say, the current associated with the capacitance of a line is known as the charging
current. The strength of the charging current depends on the voltage, frequency, and capacitance of the
line. It is given by the equations shown below.
Also, reactive
volt-ampere generated by the line = charging volt-amperes of the lines
For a three phase line, the charging current phase
1. It reduces the load current, due to which line losses decreases, and hence the efficiency of the line is
increased.
2. It improves the power factor of the transmission line.
3. Charging current improves the load capacity of the line.
4. It improves the voltage regulation of the line because the voltage drop is quite small.
All digital circuits work on logic. that is logic of zero and one. Everything in digital electronics is
summarized in 1 and 0. Here 1 represents +5 voltage and and 0 represents 0 voltage or ground level.
DC voltages/ current :
are ideally steady. i.e there is no fluctuation in it. Like battery. it gives 1.5 V if it is rated for 1.5V.
AC current :
where as ac current i.e. Alternating Current as name suggests varies with time. Means for every given
moment the voltage is changing and so is current. It is like if as time increases voltage and current
increases and after reaching certain top level it goes down again to level 0 and then it further goes down
in -ve to certain lowest level and then again it goes up to 0 level and this goes on.
It has sinusoidal wave form. We have in India 60 hz (hertz) current that means voltage changes from 0 -
230-0- -230 -0 sixty times in a second.
Now how can a digital circuit work for its requirement of constant ± 5 V status if the current is varying
every moment ? So dc is the only source for digital circuits. AC voltages are converted to dc voltage by
using rectifier circuits comprising of diode, capacitor so some voltage stabilizer ICs etc.. as per need.
Now how the electricity is produced? DC or direct current is available in lightning happening in sky or
the by converting from AC to DC or by using battery [ NICD, Lead Acid ect ]. And ac is produced by the
rotation of copper coils in the magnetic field.i.e. nutshell. You may have heard of wind electricity / coal
electricity / water electricity etc.... ultimately all they do is to rotate the copper coils in the magnetic
field to produce electricity. And this method is far cheaper than producing DC current. So it is widely
used in producing electricity world wide.
The resistance-change factor per degree Celsius of temperature change is called the temperature
coefficient of resistance. This factor is represented by the Greek lower-case letter “alpha” (α). A positive
coefficient for a material means that its resistance increases with an increase in temperature.
You might have noticed on the table for specific resistances that all figures were specified at a
temperature of 20o Celsius. If you suspected that this meant specific resistance of a material may
change with temperature, you were right!
Resistance values for conductors at any temperature other than the standard temperature (usually
specified at 20 Celsius) on the specific resistance table must be determined through yet another
formula:
The “alpha” (α) constant is known as the temperature coefficient of resistance, and symbolizes the
resistance change factor per degree of temperature change. Just as all materials have a certain specific
resistance (at 20o C), they also change resistance according to temperature by certain amounts. For
pure metals, this coefficient is a positive number, meaning that resistance increases with increasing
temperature. For the elements carbon, silicon, and germanium, this coefficient is a negative number,
meaning that resistance decreases with increasing temperature. For some metal alloys, the
temperature coefficient of resistance is very close to zero, meaning that the resistance hardly changes
at all with variations in temperature (a good property if you want to build a precision resistor out of
metal wire!). The following table gives the temperature coefficients of resistance for several common
metals, both pure and alloy:
Firmware is programming that's written to the read-only memory (ROM) of a computing device.
Firmware, which is added at the time of manufacturing, is used to run user programs on the
device.
Why Neutral Grounding Transformer is used for generator?
Sunday, January 18, 2015
A Neutral Grounding Transformer is NOT a three phase transformer, but a single phase
transformer, with the primary (HV) rated voltage equal to the system phase-to-neutral
voltage and the secondary (LV) rated voltage either 110V or 240V.
Why is it required? For economic reasons. Let us see how. Supposing you have an 11kV
System, whose neutral you want to ground through a resistance. The desired ground fault
current, let us say, is 10A. Now, if you want to connect a resistor directly in the path
between the system neutral and earth, the value of the resistor would be (6350/10 = 635
Ohms) and the voltage rating of the resistor would be 6350V. A 6350V, 635 Ohms resistor
would not be cheap.
Now, if you opt for a single phase 6350V/240V, neutral grounding transformer, whose
6350V winding is connected in the neutral to ground path, you can connect a simple 0.9
Ohms resistor across the 240V secondary of this neutral grounding transformer. This 0.9
Ohms resistor at 240V side will reflect multiplied by the square of the turn’s ratio, at the HV
side (i.e.) 6350/240 is 26.45 whose square is 700. The 0.9 Ohms resistor connected across
the 240V secondary of the neutral grounding transformer would appear as (700 x 0.9 =
about 630 Ohms). And, the added advantage is that this resistor needs to be insulated only
for 240V. A reduced Ohmic value resistor, with a reduced insulation rating is cheaper. And,
the neutral grounding transformer can be short-time rated, to optimize on the size & cost of
the neutral grounding transformer.
The limited fault current and fast response time also prevent over-heating and mechanical
stress on conductors. Low resistance grounding resistors are typically rated up to 400 amps for
10 seconds, and are commonly found on medium voltage systems. Ground fault protection for
high voltage transformer and generator grounding applications typically require a grounding
transformer to lower the voltage reflected to the neutral grounding resistor.
Post Glover’s GT product line is designed for applications up to 15kV primary. Secondary
voltage is typically 240 V, and resistors are designed according to customer specification.
Typical construction is a dry type transformer with a secondary resistor mounted in a common
enclosure.
Features
Maxim provides a wide range of products designed for implementing and protecting 4-20mA communication
links.