© OMICRON Page 1 of 7
What’s New in the VOTANO Hardware?
No changes
The new 2.10 version of the VOTANO software offers new features including:
VOTANO 100 now offers two different test options for inductive as well as for capacitive voltage
transformers. The VT/CVT test is designed to efficiently determine the most important parameters of the
assets and check the integrity and proper electrical functionality of the assets. This test is ideal for
commissioning, GIS testing and in-production testing.
The Advanced VT/CVT test provides more results, parameters and subsequently a result assessment. This
is an ideal tool for on- and off-site calibration and failure root cause analysis. The advanced VT/CVT test is
equal to the VT/CVT test known from previous VOTANO versions.
After setting the basic test and asset parameters during test preparation, the test can be operated with only
one single connection. No reconnection is required.
As a result of this test mode, information about load and no-load ratio error and phase displacement,
capacitive divider ratio (for CVT only), ratio, polarity and short circuit impedance are shown for the
corresponding test voltage.
The VT/CVT test does not provide a class assessment per IEC and IEEE standards.
Please refer to the updated user manual for further information about the VT/CVT test, the connections and
safety relevant information.
Ratio test
ԑ [%] Δϕ [min] ԑ [%] Δϕ [min]
Winding % of Upr Ratio Polarity
(no load) (no load) (@Sr) (@Sr)
1a-1n 35% 199,77 Ok 0,118% 2,89 -0,032% 4,13
2a-2n 35% 199,78 Ok 0,113% 2,82 -0,036% 3,77
da-dn 35% 340,37 Ok 1,775% 2,76 -0,396% 25,43