You are on page 1of 3

POWER TRANSFORMER

INRUSH AND CONTROLLED


SWITCHING

INTRODUCTION
Random power transformer energization the direction of current flow for one half
can lead to large flux asymmetries and as cycle is in one direction and for other half
a consequence to core saturation. The life the direction reverses. So the
saturation of a core can drive currents of direction magnitude of Field applied to
high amplitude and harmonics, known as the core of the Transformer also alters for
inrush currents, which can result to every half cycle. Consider the core is
undesirable effects including equipment magnetized by the magnetic field (H)
damages and loss of life. called magnetizing force. The magnetic
flux density (B) of the core of
The protection engineers when dealing Transformer will increase and saturates
with those currents prefer to de- at the knee point and then starts
sensitizing or even blocking the decreasing as magnetizing force (H)
protection schemes. Those tactics are of decreases. An instant (D in fig.) will arise
high risk as it is shown from statistics that where the magnetizing force (H) will
failures during energization are quite become zero i.e, no magnetic field force is
common occurrences. applied to the material (This arise due to
the current wave during passing from one
half cycle to other half cycle it touches
THEORETICAL APPROACH zero point) but still magnetic flux density
is not zero in the material but have some
value. This is called Magnetic Retentivity.
The value of H at zero B is called
Corrective Force( C in fig.). Coercive Force
required making the magnetic flux (B)
zero by applying the magnetic field in
opposite direction. When the flux applied
in the opposite direction to the material in
opposite direction in another cycle the
same phenomenon takes place. This
complete loop is called hysteresis loop.
Typical hysteresis curve Hysteresis loop is significant because the
area under the hysteresis loop gives the
total Hysteresis Loss of the Magnetic
In an AC Transformer voltage and current Material.
waveforms vary in cycles, means when

1|Page

www.engineering-services.gr -White papers


The transformer normal core flux is given and depending on the voltage level hard
by the Faraday low of induction: to utilize.

| |= | |. A modern approach is to reduce or even


eliminate the transient energizing
Integrating the applied voltage we can currents by selecting the instant and
calculate the flux at the specific instance. sequence of opening or closing the
From the above equation it is obvious that feeding circuit breaker. This method of
the flux waveform is sinusoidal with π/2 transient elimination is also applicable for
phase shift compared to voltage in such a power capacitors and transmission lines.
way that when voltage is in its maximum
the flux is zero.

When a transformer is de-energized a CASE A, IGNORING THE REMANENCE


permanent magnetization of the core FLUX
remains due to hysteresis of the magnetic In cases where the inrush current
material. This permanent magnetization phenomenon is not severe or the
is called “residual flux” and it is mainly switching element is a three pole
influenced by the core materials and simultaneous interrupting device, we can
geometry, winding or other external improve the network transient response
connected capacities as also circuit by selecting the closing time instant to be
breaker chopping characteristics. when the voltage amplitude has its
maxima value. When the voltage passes
During transformer re-energization the through the maximum, the induced flux is
instantaneous magnitude of the core flux zero. One of the requirements of this
at the instant of energization is the vector technique is the measurement of the
summation between residual flux and circuit breaker closing time in order to
applied sinusoidal flux. Depending of the calculate the close command timing.
instances of energization and de-
energization the peak transient core flux Here to mention that, most of the circuit
can reach values more than two times the breakers out in the market, interrupts the
rated peak flux which can generate power networks at zero current passing
transient currents of high amplitude and time, so someone can insist that there
rich of harmonics superimposed on a dc would be no residual flux at the core at
offset. the next energization. This is not actually
the case, as the breakers are chopping the
current waveforms at values other than
exactly zero.
CONTROLLED SWITCHING
A common practice of reducing the
inrush currents of power transformers is
by introducing power resistors in series CASE B , TAKING IN ACCOUNT THE
or specially designed energizing circuits. REMANENCE FLUX
Those solutions are often too expensive In the cases that severe inrush transient
phenomena occurs the residual flux must

2|Page

www.engineering-services.gr -White papers


be supervised and measured by
integrating the applied voltage at the
moment of opening in order to calculate
the closing time so that the victorious
summation of the sinusoidal and residual
flux is equal to zero. This is actually the
case when the breaker is opened by a
protection. In the case of maintenance or
scheduled opening no monitoring is
needed if we reassured the opening at
zero current crossing time.
Typical inrush current wave form taking in
This solution is best applied when account the residual flux
individual pole opening is available (i.e.
three single phase breakers), so that the
pole closing is happened after a time REFERENCES
delay (120o) in order to avoid
· Moraw, G., et al, “Point-ON-Wave
asymmetries in the core flux. Controlled switching of High Voltage
Circuit-Breakers,” CIGRE paper 13-02, pp.
Depending on the needed result the above 1-6, 28 August-3 September 1988.
concepts can be utilized via existed · Brunke, J.H., “Elimination of Transient
numerical protection and control relays Inrush Currents When Energizing
Unloaded Power Transformers” ETH
or by using dedicated market solutions.
Zurich 1998
· Holmgren, R., Jenkins, R.S., Riubrugent, J.,
“Transformer Inrush Current,” CIGRE
paper 12-03, CIGRE Paris, pp. 1-13, 1998
· John H. Brunke, Klaus J. Frohlich,
“Elimination of transformer currents by
controlled switching Part I – Theoretical
Considerations”

Typical inrush current wave form without


taking in account the residual flux

3|Page

www.engineering-services.gr -White papers

You might also like