(This spreadsheet is to calculate wind loading on the roof as per IS 875)
Dimensions of the Building:
Length 27 m
Width 24 m
Height 10.2 m
Roof Type: Hipped
Life of structure 50 years
2 Wind Data:
1 Wind Zone (Sec 5.2) :‐ 39 m/sec
2 Terrane category (Sec 5.3.2.1): ‐ Terrain Catogry 1 A
3 Design Factors:
Risk coefficient factor, k1 (Sec 5.3.1, Table 1):‐ 1.05
Building category : A
Terrain and Height factor, k2 (Sec 5.3.2.2, Table 2):‐ 1.18
Tophography Factor, k3 (Sec 5.3.3.1):‐ 1
Importance factor for cyclonic region, k4 (Sec 6.3.4) 1
Wind directionatlity factor, kd (Sec 6.1.1):‐ 1
Tributory area for purlins: 13
Area Avg factor: ka 1
Combination factor :kc (sec 6.3.13) 1
F = (Cpe‐Cpi) x A x pd
Building with opening: Small
Cpi = 0.2
‐0.2
h/w = 0.43
External Coefficients: Table 9 with = 0 with 25 deg slope
Wind =0 Wind =90
Angle EF GH EG FH
25 ‐0.2 ‐0.4 ‐0.7 ‐0.6
Windward Leeward
M & N ‐0.7 ‐0.2 ‐0.4
Hipped slope
So, pressure on each area: kN/m2
c/c distance 2m
UDL
=0 =90 =0 =90
EF GH EG FH MN MNwi MNlee
‐1.12 ‐1.68 ‐2.52 ‐2.24 ‐2.02 ‐0.90 ‐1.34
0.00 ‐0.56 ‐1.40 ‐1.12 ‐1.12 0.00 ‐0.45
Inclined rafter =
‐1.569066 ‐1.84926 ‐1.70916 ‐1.93331
‐0.560381 ‐0.84057 ‐0.70048 ‐0.92463