Professional Documents
Culture Documents
ABB
1MDB08222-YN
Preliminary information
April 2013
Application: The tripping relays type PQ.... are used for High burden tripping relays PQ8nC2JW are
all kinds of control and protection circuits suitable for applications where initiating
in power stations and industrial contacts are coming from remote.
installations, where a high degree of
reliability and a high contact rating are The high burden provides immunity
stipulated, with minimal internal to capacitance discharge currents,
consumption. which can result at the inception of
an earth fault on battery wiring and
Acting as instantaneous switching immunity to the subsequent leakage
element, relay provides galvanic current.
separation and contact multiplication in
tripping circuits of protective applications. Both low as well high burden relays are
suitable for relay coil supervision through
Low burden tripping relays PQ8nCH2J and either LED lamp or trip circuit supervision
PQ5nCH2J are suitable for HV, MV and relay type TCS.
LV installations where immunity to
capacitance discharge and high minimum
operation currents are not required.
Design and The relay type PQ.... is specially designed contact bar directly. When the coil is de-
Principle: for high speed operation and mechanical energized, the armature of the magnet and
latching. It has flag indicator which the contact bar are forced back into their
indicates trip status when the relay latches. initial position by spring action when relay is
The relay can be hand reset by pressing in resetted.
and resetting the operation indicator.
The contacts are arranged symmetrically in
The trip relays type PQ.. are two rows, on either side of the magnet,
instantaneous, plunger type relay with clearly visible and readily accessible.
4/6/7 contacts with double interruption.
They are designed to operate from d.c. The high burden relays have 2 cutoff contacts
The low burden relays can also operate in series with coil, which ensures momentory
from a.c. when preceded by rectifier. high burden during pick up which is cut off
after relay operation.
The relay has a magnet system which
comprises a fixed core and a moving, The terminals on 1/2’S’ flush mounting case
plunger-type armature, actuating the have an opening which can accommodate
two wires with a crosssection of 1.5mm².
Type and
designation
of relays:
Technical Rated auxiliary voltage, Uaux ( Low : 24 ,30, 48, 110, 125, 220, 250 V DC
data burden) : 110, 240 V AC (with rectifier)
Rated auxiliary voltage, Uaux ( High : 24-30, 48, 110-125, 220-250V DC
burden)
Operating range : 70% to 110% of Uaux
Frequency : 50 Hz, ±5%
Pick-up voltage (%Uaux) : < 70%
Operation time at Uaux : 12-15 ms
Maximum power consumption :
Low burden varient : 9W for DC, 7.5 VA for AC
High burden varient : 150W for DC
Mechanical life : 1 x 10⁴
Switching rate : Up to 500 times per hour at full breaking
current or 5000 times per hour with redu-
ced breaking current
Insulation tests As per IEC 60255-5
Dielectric test : 2kV, 50Hz, 1min
Impulse voltage test : 5kV, 1.2/50micro sec. 0.5J
Insulation resistance : >100 M ohms at 500V DC
Contacts
Rated voltage 250V DC / AC
Rated current 5A
Max. making current 50 A, 0.5 sec
Max. Breaking capacities
Environment tests
Dry heat test : IEC 60068-2-2 +55˚C and +70˚C
Dry cold test : IEC 60068-2-1 -10˚C and -25˚C
Damp heat cyclic test : IEC 60068-2-30 12hrs+12hrs cycle at
+55˚C / +25˚C with RH98% for 6 days
Storage test : IEC 60068-2-8 +70˚C for 72hrs and -25˚C
for 72 hrs
Vibrations test IEC 60255-21-1 Class-1
Vibration response : 10-150Hz; 0.5g; 3 axis
Endurance test : 10-150Hz; 1.0g; 3 axis
Electromagnetic compatibility :
requirements
High frequency disturbance test : IEC 60255-22-1 1MHz 2.5kV common
mode, and 1 kV differential mode
Weight: : 0.95 Kg. Approx
Connection
diagram and
Contact
configuratio
n
Connection
diagram for
relay coil
supervision
Fig 5 - Relay PQ8nC2JW coil supervision Fig 6 - Relay PQ8nC2JW coil supervision
with supervision relay TCS with LED lamp
Ordering Refer type designation for selection and tick appropriate boxes
data
Type : PQ8nCH2J
Quantity :
Item no. :
24V DC 7NO + 0 NC
30V DC 6NO + 1 NC
48V DC 5NO + 2 NC
110V DC 4NO + 3 NC
220V DC
250V DC
110V AC
240V AC
Type : PQ5nCH2J
Quantity :
Item no. :
24V DC 4NO + 0 NC
30V DC 3NO + 1 NC
48V DC
110V DC
220V DC
250V DC
110V AC
240V AC
24-30V DC 6NO + 0 NC
48V DC 5NO + 1 NC
110-125V DC 4NO + 2 NC
220-250V DC
125V DC
220V DC
250V DC