You are on page 1of 40

Aircon heat load calculation sheet

Project Name: Econ Medicare Centre (Upper Ease Coast Road)


Address:

Remarks
Assume glass value:
SC=0.70, U= 5.89w/m2k
ID: 23degC/60%RH, SF: 5%

26/July/2016
R0a_Sentron_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Heat load sum up table

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W] [Hr] [W] [kg/h] [Hr] [m2] [W/m2]

FCU 2-9 B1 1 1 655 1086 1140 15 5.9 193.3


1 1 1 0 0 0 1 0.0 0.0
Room 1 1 1 1 3641 4595 4825 15 18.2 265.1
Room 2 1 1 1 2492 3241 3403 11 15.0 226.9
Room 3 1 1 1 2070 2962 3110 15 13.8 225.4
Room 4 1 1 1 2612 3579 3758 15 19.1 196.8
Room 5 1 1 1 2257 3167 3325 15 15.1 220.2
Room 6 1 1 1 2213 3119 3275 15 14.8 221.3
Room 7 1 1 1 1966 2823 2964 15 11.4 260.0
Room 8 1 1 1 1937 2792 2932 15 11.2 261.8
Room 9 1 1 1 2384 3306 3471 15 15.9 218.3
Clinic Room 1 1 1 1756 2107 2212 11 5.5 402.2
Manager Room 1 1 1 3766 4323 4539 14 10.2 445.0
Reception Area 1 1 1 12374 14377 15096 16 37.0 408.0
Corridor (GL C-E) 1 1 1 3925 5439 5711 16 41.6 137.3
Corridor (GL E-F) 1 1 1 1801 2511 2637 17 20.7 127.4
Corridor (GL F-J) 1 1 1 3882 5848 6140 15 53.4 115.0
Room 10 1 1 1 3948 4945 5192 16 22.5 230.8
Room 11 1 1 1 2651 3518 3694 16 13.2 279.8
Room 12 1 1 1 2635 3499 3674 16 13.0 282.6
Room 12A 1 1 1 3241 4129 4335 16 14.7 294.9
1 1 1 0 0 0 1 0.0 0.0
NursingArea (GL A-E) 2 1 1 26110 41512 43588 15 195.6 222.8
Corridor (GL E-F) 2 1 1 798 1342 1409 15 15.5 90.9
NursingArea (GL F-J) 2 1 1 25607 40747 42784 16 195.3 219.1
2 1 1 0 0 0 1 0.0 0.0
NursingArea (GL A-E) 3 1 1 26110 41512 43588 15 195.6 222.8
Corridor (GL E-F) 3 1 1 798 1342 1409 15 15.5 90.9
NursingArea (GL F-J) 3 1 1 25607 40747 42784 16 195.3 219.1
3 1 1 0 0 0 1 0.0 0.0
NursingArea (GL A-E) 4 1 1 27116 41743 43830 15 187.0 234.4
Treatment Room 4 1 1 1641 2420 2541 15 8.8 288.8
FCU 4-3 4 1 1 2705 3480 3654 16 9.9 369.1
NursingArea (GL E-I) 4 1 1 18258 27571 28950 16 119.7 241.9
Store Room 4 1 1 2286 2717 2853 16 9.6 297.2
Physio Work Room 4 1 1 1743 2152 2260 16 7.2 313.8
4 1 1 0 0 0 1 0.0 0.0

Peak load of building 37 217211 326007 342307 15 1527.2 0.0

SH : Sensible heat

-1- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016

Table of System heat load

System

[Cooling Load] [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

1 25.5 79.2 7722 2314 3783 3516 6556 1359 7891 15720 22911 5386 3615 0 49971 30802 29386 110159
2 25.3 79.2 6156 2018 3466 3396 6032 1244 7617 15720 22911 5386 2435 0 45853 30528 28161 104542
3 25.1 79.2 5128 1807 3158 3275 5514 1139 7358 15720 22911 5386 2435 0 43562 30269 26989 100820
4 25.0 79.2 4349 1661 3027 3213 5239 1087 7218 15720 22911 5386 2435 0 42117 30129 26392 98638
5 24.9 79.6 3893 1550 2870 3152 4974 1030 7193 15720 22911 5386 3615 0 42190 30104 26130 98424
6 24.8 79.6 3437 1444 2728 3091 4717 981 7070 15744 22944 8936 5975 0 47053 30014 25571 102638
7 25.1 79.2 3304 1610 3158 3275 7948 1139 7358 15794 23012 17872 9591 0 63691 30370 26989 121050
8 25.8 78.8 4567 2131 4228 3700 46113 1521 8177 15946 23218 14492 12178 0 104876 31395 30819 167090
9 26.9 78.2 9532 3340 5888 4365 64923 2116 9547 16198 23560 9446 12555 0 128363 33107 37063 198533
10 28.2 77.3 15792 5084 7845 5150 78389 2823 11194 16198 23560 5896 12555 0 149732 34754 44536 229022
11 29.7 76.1 22122 7239 10113 6059 84254 3638 13141 16198 23560 5896 12555 0 168074 36701 53301 258076
12 31.0 75.0 27703 9399 12081 6846 82017 4340 14909 16198 23560 5896 6655 0 171135 38469 61162 270766
13 32.1 70.0 31827 11350 13735 7511 80424 4942 14700 16198 23560 5896 6655 0 178538 38260 62397 279195
14 32.8 70.0 34582 12767 14796 7934 89329 5318 15922 16198 23560 9446 6655 0 197025 39482 67473 303980
*15 33.0 70.0 37707 13435 15102 8054 99286 5428 16274 16198 23560 9446 12555 0 217211 39834 68962 326007
16 32.8 70.0 40151 13356 14796 7934 98940 5318 15922 16198 23560 9446 12555 0 218694 39482 67473 325649
17 32.1 70.0 41039 12462 13735 7511 87848 4942 14700 16198 23560 14775 12555 0 211065 38260 62397 311722
18 31.1 75.3 39730 10945 12224 6906 68729 4398 15195 16198 23560 14775 12555 0 186460 38755 62250 287465
19 29.8 76.0 35649 8960 10275 6118 23404 3693 13263 15946 23218 18042 12555 0 134642 36481 53861 224984
20 28.5 76.8 28524 6910 8309 5334 14420 2986 11484 15794 23012 17872 12178 0 112327 34496 45956 192779
21 27.5 77.6 21943 5328 6792 4728 11792 2443 10233 15794 23012 17872 9591 0 96283 33245 40270 169798
22 26.8 77.8 16690 4191 5734 4302 9967 2063 9277 15744 22944 14265 9591 0 82547 32221 36024 150792
23 26.2 78.8 12828 3341 4840 3940 8391 1736 8740 15744 22944 8936 5975 0 65731 31684 33283 130698
24 25.8 78.8 9935 2743 4228 3700 7336 1521 8177 15720 22911 8936 5975 0 60094 31088 30819 122001

-2- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name FCU 2-9 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No B1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 5.9
Depth of underground wall(m) 4.4
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 5.9 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 5.9 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 -2.7 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 2.2 2.7 2.2 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Underground earth floor 0.28
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-3- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 0.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 0
Floor area(m2) 0.0
Depth of underground wall(m) 0.0
Ceiling height(m) 0.0 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(without ceiling board) 0.93 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(without ceiling board) 2.05
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-4- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 1 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 18.2
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 18.2 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 18.2 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 4.1 4.7 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 4.8 3.4 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 4.7 0.0 0.0 4.1 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-5- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 2 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 15.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 15.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 15.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 3.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 4.3 0.9 4.3 4.1 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-6- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 3 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 13.8
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 13.8 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 13.8 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 2.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 4.3 0.9 4.3 3.8 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-7- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 4 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 19.1
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 19.1 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 19.1 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 0.0 3.9 5.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-8- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 5 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 15.1
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 15.1 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 15.1 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 3.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 0.0 3.9 3.9 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-9- Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK
Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 6 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 14.8
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 14.8 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 14.8 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 3.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 0.9 3.9 4.4 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-10-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 7 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 11.4
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 11.4 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 11.4 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 2.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.4 1.0 3.4 3.9 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-11-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 8 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 11.2
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 11.2 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 11.2 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 2.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.4 1.0 3.4 3.8 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-12-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 9 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 15.9
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 15.9 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 15.9 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.4 0.7 3.4 5.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-13-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Clinic Room Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 5.5
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 5.5 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 5.5 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 2.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 2.1 0.0 2.1 2.6 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-14-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 20.4
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Manager Room Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 10.2
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 10.2 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 10.2 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 3.6 2.8 0.0 0.0 0.0 0.0 0.0 0.0 2.8
Roof(with ceiling board) 0.58 II
Window area on <1> 5.4 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 163 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-15-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 74.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Reception Area Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 7
Floor area(m2) 37.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 37.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 37.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 5.7 0.0 0.0 5.6 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 15.1 0.0 0.0 20.1 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 5.6 7.3 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 592 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-16-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 45.7
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Corridor (GL C-E) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 4
Floor area(m2) 41.6
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 41.6 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 41.6 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 2.5 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 6.0 15.0 6.0 12.5 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-17-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 22.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Corridor (GL E-F) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 20.7
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 20.7 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 20.7 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 2.2 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 5.9 5.1 5.9 2.9 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-18-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 58.7
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Corridor (GL F-J) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 53.4
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 53.4 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 53.4 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.6 25.0 0.0 25.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-19-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 10 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 22.5
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 22.5 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 22.5 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 5.4 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 5.4 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 6.4 3.9 1.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-20-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 11 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 13.2
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 13.2 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 13.2 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 3.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 4.1 3.9 1.1 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-21-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 12 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 13.0
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 13.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 13.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 3.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 3.9 3.9 0.9 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-22-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Room 12A Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 14.7
Depth of underground wall(m) 0.0
Ceiling height(m) 3.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 14.7 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 14.7 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 3.4 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 5.4 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.9 4.4 3.9 1.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-23-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 0.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 1
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 0
Floor area(m2) 0.0
Depth of underground wall(m) 0.0
Ceiling height(m) 0.0 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(without ceiling board) 0.93 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(without ceiling board) 2.05
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-24-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL A-E) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 2
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 39
Floor area(m2) 195.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 195.6 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 195.6 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 9.4 21.2 0.0 18.4 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 12.9 25.2 0.0 21.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 2.9 9.4 5.7 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1400 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-25-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 17.1
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Corridor (GL E-F) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 2
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 15.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 15.5 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 15.5 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 2.6 5.8 2.6 5.8 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-26-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL F-J) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 2
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 39
Floor area(m2) 195.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 195.3 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 195.3 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 12.2 9.4 24.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 14.4 16.0 28.8 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 9.4 11.8 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-27-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 0.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 2
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 0
Floor area(m2) 0.0
Depth of underground wall(m) 0.0
Ceiling height(m) 0.0 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(without ceiling board) 0.93 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(without ceiling board) 2.05
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-28-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL A-E) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 3
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 39
Floor area(m2) 195.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 195.6 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 195.6 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 9.4 21.2 0.0 18.4 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 12.9 25.2 0.0 21.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 2.9 9.4 5.7 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1400 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-29-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 17.1
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Corridor (GL E-F) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 3
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 15.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 15.5 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 15.5 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 2.6 5.8 2.6 5.8 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-30-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL F-J) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 3
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 39
Floor area(m2) 195.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 195.3 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 195.3 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 12.2 9.4 24.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 14.4 16.0 28.8 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 9.4 11.8 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-31-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 0.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 3
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 0
Floor area(m2) 0.0
Depth of underground wall(m) 0.0
Ceiling height(m) 0.0 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(without ceiling board) 0.93 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(without ceiling board) 2.05
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-32-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL A-E) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 37
Floor area(m2) 187.0
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 187.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 187.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 9.4 21.2 0.0 12.8 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 12.9 25.2 0.0 18.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 2.6 9.4 8.4 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1400 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-33-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Treatment Room Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 8.8
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 8.8 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 8.8 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 2.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 3.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.7 0.0 3.7 2.4 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-34-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name FCU 4-3 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 9.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 9.9 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 9.9 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 2.7 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 5.2 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.7 2.7 3.7 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-35-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name NursingArea (GL E-I) Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 24
Floor area(m2) 119.7
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 119.7 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 119.7 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 16.1 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 28.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 6.1 24.3 6.1 8.2 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 1400 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-36-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Store Room Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 9.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 9.6 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 9.6 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 3.1 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 3.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.1 3.1 3.1 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-37-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h person)
Outer wall assembly Normal Concrete Summer 19.8
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.40
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Physio Work Room Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Hospital

Ceiling board Available Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 7.2
Depth of underground wall(m) 0.0
Ceiling height(m) 2.4 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 1.0
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 7.2 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 7.2 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 0.58 II
Window area on <1> 0.0 0.0 0.0 2.6 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.31
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 3.6 2.0 3.6 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 30 30 30 30 30 50 100 80 50 30 30 30 30 50 50 50 80 80 100 100 100 80 50 50
Persons 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Equipments 30 20 20 20 30 50 80 100 100 100 100 50 50 50 100 100 100 100 100 100 80 80 50 50

OHTC : Overall heat transfer coefficient

-38-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK


Econ Medicare Centre (Upper Ease Coast Road) 26/July/2016
Room data(Input data)

Project name Econ Medicare Centre (Upper Ease Coast Road) Design room temperature in summer(CDB) 23.0
Design room humidity in summer(%RH) 60.0
Address Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Singapore/Singapore
Fresh air intake Air volume(m3/h)
Outer wall assembly Normal Concrete Summer 0.0
Winter ----
Max. fresh air temp.
33.0
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 4
Window type <1> Assume
System No 1 Blind type No
Shading factor/OHTC 0.70/5.89
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 0.0


Incandescent lamp(W/m2) 12.0
Method of
Common ventilation fan
fresh air intake
No of persons 0
Floor area(m2) 0.0
Depth of underground wall(m) 0.0
Ceiling height(m) 0.0 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.84 II

N E S W NE SE SW NW Shade Inner Wall <1> 2.33


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(without ceiling board) 0.93 II
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(without ceiling board) 2.05
outer wall(m2) Mezz floor(with air layer) 1.31
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.05
wall length(m) Pilotis 2.62
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.91
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.46
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 1:00 to 24:00

Internal heatgaing schedule(%) Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Lighting 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 10
Persons 5 5 5 5 5 10 20 50 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10 5
Equipments 10 10 10 10 10 10 20 50 100 100 100 100 100 100 100 100 100 100 100 50 20 20 10 10

OHTC : Overall heat transfer coefficient

-39-Z:\Project 2016\Econ Medicare Centre (Upper Ease Coast Road)_HL_R0a_Hooi Fu_JK