You are on page 1of 6

2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

Phase Comparison Protection for Distribution


Networks with High PV Penetration
Tan G. M. Alvin, Izham Z. Abidin, H. Hashim, A. A. Zainul Abidin
College of Engineering, Universiti Tenaga Nasional, Malaysia

Abstract - With the availability and reduced cost of renewable which subsequently causes the overcurrent relays to be less
energy sources such as Solar PV, distributed generation (DG) sensitive and produce a longer tripping time [3] [4]. Thus the
becomes an increasingly common practice in harnessing these coordination of the tripping time between the overcurrent relays
energy sources. However, a high level of penetration of the are disrupted and certain sections of the distributed network will
energy sources in the distribution network will cause issues be isolated incorrectly.
such as reverse power flow and the disruptions to the This issue becomes more critical when considering renewable
coordination of existing protection system. This paper looks energy sources such as PV and wind which have variable power
on how reverse power flow will affect the tripping times of outputs depending on the time of the day and climate condition.
overcurrent relays and its effect on the coordination of the While tropical countries such as Malaysia has solar irradiance
protection system. This paper also investigates on the between 800 to 1000 W/m2 and ambience temperature of up to
possibility of using the phase comparison protection method 40°C, making it ideal for Solar PV, this condition is not
to improve the coordination of the protection system in a maintained throughout the day [5]. Weather variables such as
high PV penetration environment. cloud cover and rain will further dampen the power output of PV
panels [6]. This creates a degree of unpredictability in the output
Index Terms – Distributed Generation, phase comparison of the PV. As a result, depending the time of the day and weather
protection, reverse power flow conditions, the network will have different direction of power
flow. High levels of PV penetration will cause drastic shifts in
I. INTRODUCTION the system condition between the period when the PV produces
With the cost of energy around the world steadily increases, no power and when the PV is operating at its peak capacity.
consumers are looking for cheaper alternative solutions for their
electrical needs. Renewable energy sources such as Solar PV and Current practice on DGs limits the output power of DG to
wind energy are becoming increasingly accessible and affordable minimize the effect of reverse power flow. Some research
to the consumers and are connected to the grid as distributed proposes the management of reverse power flow through the
generations (DG). The integration of DG into distribution brings application of controllable loads [7]. However, this translates to
some issues to the utilities such as reverse power flow and untapped potential energy supply. Considering the growing
disruption to the coordination of the protection system [1] [2]. demand for energy in the world and the increase of
environmental awareness among consumers, utilities should look
A typical distribution network has power flowing in a single into ways of increasing the adaptability of current protection
direction from the grid to the load. However, the introduction of system in anticipation of future distribution networks which
DG into the distribution network allows for the power to flow in consist of varying power flows.
the reverse direction when the power provided by the DG is
higher than the consumed power at the load. These distribution II. METHODOLOGY
networks are usually protected by a combination of fuses and
overcurrent relays. These protection devices are coordinated The simulation for this paper is done in MATLAB/Simulink.
through current discrimination. Overcurrent relays further down The test system network used for this simulation is a
the distribution line is more sensitive to a fault at the end of the representation of a typical radial 11kV distribution network
line compared to the relay closer to the source. The tripping time which is common in Malaysia. The network consists of five loads
of the relays are determined by the fault current flowing through each with its individual and unique load profile and two DGs
the relay. A lower fault current indicates a longer distance of the represented by the Solar PV blocks as shown in Figure 1. The
fault from the relay and thus the overcurrent relay produces a output power of the Solar PV is capped at 1 MVA which is the
longer tripping time. However, with DGs in the distribution typical limit for the distribution transformer in Malaysia to
network, distance from the fault may no longer be the sole reason simulate high levels of PV penetration. The Solar PV blocks are
for lower fault current levels. DGs may also contribute in feeding placed at the load block closest to the source (Load A) and the
the fault and thus lowering the fault current flowing from the grid load block in the middle of the distribution line (Load C). This is
to maximize the effect of reverse power flow on the grid source

978-1-4799-1300-8/14/$31.00 ©2014 IEEE 216


2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

Figure 1. Test system network

and to create a scenario where the power will flow both upstream protection zone of both relays, the phase comparison protection
and downstream from the PV. will detect almost no difference in phase between the relays. As
such the relays will not trip in the event of a through fault. While
There are 10 relays in the test system network. Relay A, B, C, this relay provides an excellent unit protection and fault locating
D, and E are overcurrent relays which will collect data from the method, it does not coordinate with other protection devices in
distribution network and determine the tripping time for its the system as it does not detect faults outside its own protection
corresponding circuit breaker. Relay H, I, J, K, and L only zone.
collects data from the network for analysis purposes.
However, by taking advantage of the communication
The test system network is simulated to mimic the system capabilities of a Smart Grid, this protection system could be
condition at the time of 12.00 p.m. when the Solar PV is modified to perform coordinated tripping in a distributed
operating at its maximum capacity. The simulation is done for 20 network. Data collection through the use of Smart Grid will
seconds with the fault triggered at 5 seconds after simulation
become essential in determining the health of the power system
starts. Two types of faults will be simulated, ground fault and network. The concept protection system proposed in this paper is
high impedance fault. The high impedance fault will have a fault one way Smart Grid technology could be utilized to provide
impedance of 40 ohms which will not create a voltage drop low protection to the power system network. High speed
enough to trip the PV breakers which have been configured in communication between electrical installations will enable a
accordance to the recommended settings in IEEE Std 929-200 complete overview of the system condition and allow a
IEEE Recommended Practice for Utility Interface of centralized control system provide the appropriate response to
Photovoltaic (PV) System. The tripping time for overcurrent any system anomalies.
relays will be measured and analyzed.
Conventional phase comparison relays will compare the
III. PHASE COMPARISON PROTECTION phase difference to a set value determined by the protection
In response to the need of a protection system capable of engineer. However, in a distribution network with renewable DG,
adapting to changing power flows, this paper proposes a new the phase difference between two relays may exceed the set value
protection system which is a hybrid of overcurrent and phase even when fault does not occur. In the case of having a DG in the
comparison protection. Phase comparison protection is a form of middle of a radial distribution network as shown in Figure 1,
differential protection which is generally used in the protection of Relay C and D will show a large difference in its current phases
transmission lines and transformers. Phase comparison protection even when fault does not occur as the power is flowing both
operates by comparing the phase difference between two relays upstream and downstream from the PV. Therefore, in this paper,
[8]. When fault occurs between the two relays, there is a the phased difference measured will be compared with another
measurable difference in phase between the two relay. The phase value which is the value of the phase difference before the fault.
comparison protection detects this difference and trips the circuit Simulation results from Figure 2 to 7 will show the proof behind
breakers at both relays. When the fault occurs outside the

217
2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

Figure 2. Phase difference between Relay B and C with ground fault Figure 5. Phase difference between Relay B and C with high
impedance fault

Figure 3. Phase difference between Relay C and D with ground fault


Figure 6. Phase difference between Relay C and D with high
impedance fault

Figure 4. Phase difference between Relay D and E with ground fault

Figure 7. Phase difference between Relay D and E with high


impedance fault

218
2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

this concept. The simulation is done by introducing a fault at calculate the tripping time for their corresponding circuit breaker.
Load C where the PV is connected. The phase difference Instead, it will be sensors for the central control unit. Data from
between the relays where the fault is located is measured and relays all over the network could be collected to provide a more
compared with the phase difference at other sections of the complete analysis of the system condition. The zones will be
network. Two types of fault will be simulated, a ground fault and determined from the location of the relay sensors.
a high impedance fault.
The algorithm which determines the fault location needs to
From the simulation results, it can be observed that the difference check each section of the line in sequence from upstream to
in phase difference before and after the fault is minimal for both downstream of the radial distribution line. This is due to the
types of faults when the relays are upstream from the fault. The unreliable nature of the data downstream from the fault. Once the
difference in phase difference is less than 0.5 rads for both cases. fault location has been determined, the centralized protection
However, we can see that the difference in phase difference is system could assign the correct tripping times for each circuit
notably larger when the fault is in between two relays. Both cases breaker in the system. The circuit breaker closest to the fault will
display shifts in phase difference of between 2 to 4 rads. In the location will be assigned with the shortest tripping time while the
case of relays downstream for the fault, huge shifts in phase next closest circuit breaker will be tripped after a predetermined
difference in some phases could be observed for the ground fault grading margin and so forth.
simulation while no observable difference in phase difference
could be seen in the high impedance fault. This shows that the Compared to existing methods of distribution network
system is experiencing instability during ground fault protection systems, this method is unique as it provided a varying
downstream from the fault. reference value to determine the location of the fault. Existing
methods compare values such as current and phase with a
By taking advantage of this difference in phase difference predetermined set value to determine the location of the fault.
before and after the fault, fault location could be easily However, with the integration of renewable DGs such as Solar
determined. In this paper, fault location is determined by these PV, the system will experience reverse power flows and
three conditions. reduction of fault current levels which will render the existing
methods ineffective. The proposed method uses a historical
1. Current magnitude exceeds overcurrent limit. comparison to compare the phase difference before and after the
2. Difference in phase difference between two relays before fault which creates a dynamic reference value which changes
and after the fault exceeds a certain threshold. with the system. This allows the protection to be more adaptable
3. Phase difference between two relays exceeds through and provide better system security.
fault threshold.
The proposed protection will consist of three parts. The first IV. SIMULATION RESULTS
part will be the overcurrent module which will detect fault The test system network in Figure 1 is simulated under with
currents above acceptable operating levels. This module will both the standard overcurrent protection and the phase
detect the fault in the system and starts the operation of the other comparison protection. Both protection systems will be tested
modules which will determine the location of the fault. The under ground fault and high impedance faults conditions. Faults
second module will be the through fault module which will are simulated at 2 locations, Load E and Load C.
determine the location of the fault in most cases. Similar to how
conventional phase comparison relay works, it compares to phase
difference between two relays with a predetermined reference
value. Fault location is determined when the phase difference is
greater than the reference value. The third module is to determine
fault locations which the second module could not accurately
detect. This module will periodically sample and store the phase
difference value between two relays. When fault occurs and
signal is sent from the first module, this module will compare the
new phase difference value with the most recent stored phase
difference value. Fault location is determined when the
difference of the two values is greater than 0.5 rads. The fault
location is determined when the output from the three modules
are TRUE.
Since this method is only effective within the protection zone
of two relays, a centralized control unit is required to coordinate
the tripping time between the circuit breakers. This is where Figure 8. Overcurent relay tripping times for ground fault at Load E
Smart Grid communication technologies will play a part. The
relays in this method will not be individual devices which

219
2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

Figure 9. Overcurrent relay tripping times for high impedance fault Figure 12. Overcurrent relay tripping times for ground fault at Load C
at Load E

Figure 10. Phase comparison relay tripping times for ground fault at Figure 13. Overcurrent relay tripping times for high impedance fault
Load E at Load C

Figure 11. Phase comparison relay tripping times for high impedance
fault at Load E
Figure 14. Phase comparison relay tripping times for ground fault at
Load C

220
2014 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA)

V. CONCLUSION
From the simulation results shown above, it can be observed
that the existing overcurrent protection is insufficient to provide
total protection to the distribution network when DG is
introduced. During high impedance fault conditions, the fault
current level is low enough that the current feeding from the DG
is significant enough to effect the calculation of the tripping time
by the overcurrent relay. This paper shows that existing
impedance based protections are no longer appropriate when
DGs are integrated into the distribution network.
However, with some modifications to existing phase
comparison relays, it is possible to provide such a protection with
the help of Smart Grid communication technologies. This paper
shows how a centralized protection system could be realized
using Smart Grid and its improvements to the efficiency and
Figure 15. Phase comparison relay tripping times for high impedance fault at reliability of the protection system.
Load C
ACKNOWLEDGEMENT
From Figure 8 and 12, it can be seen that under ground fault The research team would like to acknowledge the Ministry
condition, the overcurrent relays work as intended. The relay of Energy, Green Energy and Water Malaysia (KeTTHA) and
closest to the fault will produce the shortest tripping time and it is Department of Higher Education for funding this research
closely followed by the next closest relay. However, we can see (20120230 FRGS). The team would also like to extend their
that the coordination of the relays is compromised under the high thanks to Universiti Tenaga Nasional for providing the facilities
impedance fault condition as shown in Figure 9 and 13. The fault and making this research possible.
current provided by the DG lowers the fault current detected by
Relay C1 which causes the tripping time it produces is longer REFERENCES
than the tripping time of Relay B1. Relay A1 does not even trips [1] Cipcigan, L.M., Taylor, P.C., "Investigation of the reverse power flow
as the relay is unable to detect the fault current due to the DGs requirements of high penetration of small-scale embedded generation," IET
feeding into the fault. Journal of Renewable Power Generation, vol. 1, no. 3, 2007.
The phase comparison relays on the other hand works as [2] Driesen, J., Belmans, R., "Distributed Generation: Challenges and Possible
Solutions," Power Engineering Society General Meeting, vol. IEEE, p. 8,
intended for both the ground fault and high impedance fault as
2006.
shown in Figure 10, 11, 14 and 15. The fault location is correctly
[3] Boljevic, S.; Conlon, M. F., "Fault Current Level Issues for Urban
determined by the centralized protection system and the correct
Distribution Network with High Penetration of Distributed Generation,"
tripping times could be assigned to each circuit breaker. Since the
Energy Market, 2009. EEM 2009. 6th International Conference on the
tripping times are definite in nature, the tripping time could be
European, pp. 1-6, 2009.
assigned as short as possible to ensure fast tripping in the event [4] Lin Xia; Lu Yu-ping; Wang Lian-he, "The study of the protection revision
of a fault. The phase comparison protection system are also method based on the DG effect to protection sensitivity," Sustainable
unaffected by the varying value of fault current and is able to Energy Technologies, 2008. ICSET 2008. IEEE International Conference
provide the same tripping times for both the ground fault and on, pp. 186 - 191, 2008.
high impedance fault. [5] Rahman, H. A., K. M. Nor, M. Y. Hassan, S. Thanakodi, M. S. Majid, F.
Another feature provided by the phase comparison relay is Hussin, "Modeling and simulation of grid connected Photovoltaic System
this ability to isolate the faulted section of the line from the rest for Malaysian climate using Matlab/Simulink," Power and Energy
of the system. In a typical distribution network, fault is fed by the (PECon), 2010 IEEE International Conference, vol. IEEE, pp. 935-940,
2010.
grid upstream. However, with the addition of DGs into the
[6] Phimmasone, V.; Kondo, Y.; Kamejima, T.; Miyatake, M., "Evaluation of
system, there is a possibility of fault being fed by a DG located
extracted energy from PV with PSO-based MPPT against various types of
downstream from it. Overcurrent relays are not designed to
solar irradiation changes," Electrical Machines and Systems (ICEMS),
detect downstream fault and does not trip the circuit breaker
2010 International Conference on, p. 2010, 487-492.
downstream from the fault. Phase comparison relays on the other
[7] Hatta, Hiroyuki, Masahiro Asari, and Hiromu Kobayashi, "Study of energy
hand trips both ends of its protected zone. As shown in Figure 14 management for decreasing reverse power flow from photovoltaic power
and 15, both relay C1 and D1 trips at the same time and isolates systems," Sustainable Alternative Energy (SAE), 2009 PES/IAS
the faulted section. This ensures the DG is able to continue to Conference, vol. IEEE, pp. 1-5, 2009.
operate in a microgrid environment until supply is reconnected [8] Kasztenny, B.; Voloh, I.; Udren, E.A., "Rebirth of the phase comparison
from the grid. line protection principle," Protective Relay Engineers, 2006. 59th Annual
Conference for, p. 60, 2006.

221

You might also like