You are on page 1of 5

TRANSIENT OVERVOLTAGES AND DISTANCE

PROTECTIONS: PROBLEMS AND SOLUTIONS

Leonardo Torelli*, Selva Moorthy

*HTC, Level 25 Collins St, Melbourne VIC, Australia - leonardo.torelli@hydro.com.au

Keywords: transient overvoltage, distance protection, Capacitor Voltage Transformer and transient
polarisation, CVT, protection settings. response
The results of this analysis are discussed to determine the
Abstract impact of a disturbed voltage signal fed to the distance relay,
with particular attention to the polarisation and CVT transient
This paper investigates the relationship between post fault mitigation techniques.
transient overvoltages and the functionality of the numerical Finally, this paper provides recommendation for the design of
distance protection. The study is conducted on a 66kV the protection settings of the distance relay implemented on
network with a neutral earth resistor as method to earth the short lines, high SIR and weak source.
power system.
This paper begins by performing an extensive power system 2 Phase to Ground Fault: Overvoltage Study
analysis on ground fault transient overvoltages. The study is
conducted by using the PSCAD-EMTC software package. The system model is represented by a basic radial
The results of this analysis are discussed to determine the subtransmission system and analysed using PSCAD-EMTC
impact of a disturbed voltage signal fed to the distance relay, software.
with particular attention to the polarisation and CVT transient
II
mitigation techniques as implemented by modem relays. 66W Subtransrrission Line �

Finally, this paper provides recommendation for the design of


the protection settings of the distance relay.
The results of this study show that fault current limitation and
Figure I: PS CAD-E M T C Model
consequent reduction of the thermal stress and aging of the
equipment are successfully supported by modem distance
relays. The model contains a 220kV source, one 220166kV delta/star
power transformer grounded via a resistor and one 66 kV
overhead line. Phase to ground faults were simulated to
1 Introduction
investigate the transient overvoltage which is the
Phase to ground faults represent the majority of faults in the superposition of the peak of the temporary overvoltage at
power system. Recent statistics found out that these types of power frequency and the transient overvoltage with higher
faults represent between 80 and 90% of the faults in a given and lower frequency components[4].
power system[I-3]. A large majority of these faults involving
overhead lines are of transitory nature and therefore self Power freq. V + Natural freq. V = Measured V (I)
extinguish in a short period of time when deenergised.
A fault in the system can be represented and analysed as the The maximum overvoltage value out of the three phases was
closing of a switch. This change in the power system selected for the analysis. Steady state overvoltage for a given
develops a new redistribution of stored energy in the system value of the neutral earth resistor was calculated by applying
and a consequent transient overvoltage[3]. symmetrical components theory and using Ko and K2 factors.
The method of earthing system does not have any effect on K2=Z2/Z0 (2)
the system during normal operation. However, during the post KO=ZO/ZI (3)
fault transient period, the method of earthing has an impact on The factor KO gives us a prompt understanding of the
the system response and magnitude of the transient overvoltage on the healthy phases during a ground fault.
overvoltage. Faults were simulated at the end of line. The length of the line
This paper begins by performing an extensive power system was set to 100km, lOkm and O.2km.
analysis on ground fault transient overvoltages. The study is 3.0 -,------,
conducted by using the PSCAD-EMTC software package. � 2.5
i t:::=:=��.' �===��
+---,====
/
��- �---------- 7'1

t
The research was conducted by using the experimental 2.0
�'
-F--
. . - . -
1.5
method that involves the scientific manipulation of the � +-----------------l-i
• 1.0
- L-10okm
1
variables involved in the process and the systematic study of 8 0.5 ----:-: � 0 . ���
t==============�==:=�
=

the behaviour of the system. The following disturbances are 0.0


1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0
investigated: I fault with NER/I fault solidly earthed (pu)

Line faults and overvoltages Figure 2: Measured Overvoltage- Fault at the end o f the line
implementing the PSCAD-EMTC Fast Fourier Transform
3.0
2.5 1------------;==;::;:;::;:::
i-��== --_I
��___=c=__
- --

L 100km :=:;-
1 (FFT) function.
g: 2.0 I � �=O���� � Base frequency was set to 125 Hz to detect noise elements
'i 1.5 - - .. ....
_ • • "•
-- .........
' ----'\
� 1.0 i------'-.;,-
<tI
\.--------
-- .......... -.:------j
-"' .....
with a frequency component lower than power frequency

voltage. Referring to the snapshot on Figure 5, the frequency
� O.5 1------ ---'-�.-._- _\.-.-----....��
. -\ . ...L/

O.O +--�-��-�� .\
-_'=�_ -�_,_� """"4 on the left hand side refers to 125Hz component. On the right
5 0.4 0.3 0.2 0.1 0 0
.0.51 0 0.9 0.8 0.7 0.6 0. hand side, the spectrum refers to the 3225 HZ noise band.
Ifault with NER/lfault solidly earthed (pu)

-� I II
Figure 3: Transient Overvoltage Co mponent- Fault at the end o f the line
60.0

The maximum overvoltage, which reaches 25 times the value


of the normal phase to earth voltage, was recorded with the
longest subtransmission line of 100km. The characteristic is --------=�;;�;;-----------
due to the larger line capacitance and inductance which are Figure 5: Frequency Co mponents - NER 20 Oh m- 10 ms after fault
proportional to the length of the line. As the capacitance
increases, the energy stored in the electric field increases From the graphs we note that the major frequency
producing larger transient phenomena if a sudden change components of the noise are in the band close to 50 Hz.
takes place in the power system. The increase of the resistor Therefore, noise filtering could be problematic and slow
size slightly increases the measured overvoltage due to the down the operation of the digital relay.
highest contribution of the power frequency overvoltage. This
characteristic is common with previous studies [3-5]and tests 3 CVT Study
with a miniature circuit test [5]. These results suggest that
power system analysis and related transient studies should be Capacitive voltage transformer represents the most common
considered for long subtransmission line as is usually done form of voltage source for distance protection relays.
for transmission lines. There is also a consistent similarity of In order to provide precise impedance measurement, the relay
results for line length of 10km and O.2km. We can explain needs to be fed with correct voltage signals. During a fault,
this characteristic by referring to plots of overvoltages as ideally, the low voltage source provided by the CVT should
functions of system parameters[4]. The different line length be an exact copy of the primary voltage. Unfortunately this is
does not have a particular impact on the Xco/Xl. For both not the reality. CVT contains a large number of stored energy
line lengths, the ratio is larger than 100. Beyond this value the components which must be charged and discharged during
expected overvoltage is considered constant. This voltage changes. As the stored energy element requires some
characteristic should be taken into consideration to optimize time to change their stored energy during fault, the CVT
planning and design work activities for short and medium introduces some transients that affect the magnitude and
length subtransmission line. Similar results have been shape of the voltage signal.
recorded with fault at the end of the line. The main component of the CVT are the capacitive voltage
A further investigation was conducted to identify any relevant divider , a tuning reactor , a voltage transformer, a
relation between overvoltage responses on healthy and faulty ferroresonance suppression circuit and the burden made by
phase. On PSCAD-EMTC software phase to ground fault the relay. The CVT transient performance was investigated
takes place on phase a. using PSCAD-EMTC software. The CVT model was
Line=10Qkm simplified and represented as in [6, 7]:

I AJ.1 1.--- � 9 v
v, --t �reJ�
C L R
Phase a

�=r--
1,
Phase b
I - Phase c L1.
__--.-R.
------:;;

.... .... - -

... � Figure 6 - CVT si mplified model

Fault simulation from SOlidly earthed to isolated system


Simulations were conducted at zero crossing of the primary
50 wo 200 250 300 350
voltage. At this time the energy store in the capacitor is at the
Figure 4: Transient Overvoltage - Phase co mparison maximum. The line model was set to 2 km. NER was
increased to generate the required Source Impedance Ratio
This investigation shows that maximum overvoltage can be (SIR). Simulations results are shown in Figure 7.
recorded in the healthy phase following fault clearing. The
figure also shows a common overvoltage pattern throughout Transient Overvoltage- 2krn IIno- Initial SIR 1

the resistor spectrum and among the three phases. There are 50.00
-
45.00
,
regular overvoltage "bumps" according to the highest voltage a
40.00
35.00
SIR 1

-SIRS

J
30.00
magnitude at the fault inception or clearing time. 25.00
SIR 10


-SIR20

==
20.00

To determine the harmonic components of the overvoltage a 15.00


-SIR30

SIR 60
-=
10.00

further analysis was conducted on the frequency spectrum by 5.00


0.00
10 30 so 70

ThTle (lTls)
Figure 7: Peak overvoltage after fault- Initial SIR 1- Line length 2 km impedance leading to overreach or underreach measurements.
Reference [ 10] provides a complete background of the
According to the SIR, transient overvoltage decays between 2
purpose and characteristics of the fIlters. Modem digital
and 4 cycles. The transient time to decay is related to the
fIltering techniques have dramatically improved the
magnitude difference between the pre fault and post fault performance of the distance protection relays by improving
steady state voltage. the following:
Acceptable results in terms of transient decay are provided • Quality of the voltage input to the relay
with SIR of 30 or below. These results are in line with the
• Operating time
relay manufacturer's technical data which specify zone reach
• Cost
accuracy, usually ± 3 of reach setting, and operating time in
Although the latest fIltering techniques improve the
respect of SIR. It is also noted that some relay manufacturers
performance, relay manufactures do not guarantee that the
are expanding the SIR limit to 60 [8, 9] with only an error
voltage used for the impedance computation will be noise free
increase to ± 5 %.
[8, 9, 1 1- 13]. Therefore, further engineering techniques are
Referring to the snapshot in Figure 8, Er is the voltage at the
required to enhance the performance of the protection relay.
CVT output. Ea is the voltage at the CVT input.

4.1 Polarisation Technique

'� �
��--==J
'.0

2.0
In the Mho characteristic relay, the basic of the distance
protection is achieved by comparing two voltage signals,
_4.0

-6.0
commonly known as operating signal, S 1, and polarising
Figure 8: Peak overvoltage - Line length 2 krn -SIR 30 signal, S2.

As in the previous section, an extensive analysis was done to SI= Operating V = I fault* Z settings - V meas. (4)
determine the frequency components of the disturbance. Base S2= Polarising signal = V measured (5)
frequency has been set to 12.5 Hz with 3 1 harmonics setting.
A snapshot of the result is shown on Figure 10. As the fault gets closer to the relay location, the voltage signal
fed to the protection relay becomes so small that it will not
allow a reliable computation of the phase comparison
algorithm. In particular, the voltage measured could not be
suffIcient to determine if the fault is on the line side or on the
bus side of the voltage transformer placing at risk the inherent
directionality of the Mho characteristics [ 1, 2, 7, 14, 15]. For
Figure 9: SIR 30 - Frequency response 45 ms after the fault
the old electromagnetic relays the minimum requirement to
This study confIrms that relevant transient overvoltages have operate correctly was about 1 V [2]. For the modem digital
a frequency component near the power frequency. The noise relays the lower limit is approximately 0. 1 V[2].
is more relevant with high SIR. To overcome this issue, protection engineers have developed
several techniques to manipulate the polarizing signal to
ensure correct determination of the direction of the fault.
3 Numerical Distance Relays: Solutions These techniques have been known as" polarisation signal
Distance protection scheme is extensively implemented in techniques". The end result of all these engineering methods
subtransmission and transmission lines. The popularity of this is to expand the Mho circle to protect the impedance area
protection scheme is due to its inherent simplicity of around the X-R origin without affecting the inherent
implementation, the relative cost and the speed of operation. directionality of the Mho characteristic. There are many
The protection function requires voltage and current papers on the available polarising techniques which also take
measurements only from one end of the line to calculate the into consideration critical factors such as fault resistance, load
short circuit fault impedance, based on the ratio between the flow and single pole auto-reclose function [2, 7, 15, 16].
voltage and the current. In theory, if correct current and
x
voltage are fed to the relay, and the relay is set with the
correct impedance data, the distance protection scheme is
immune from malfunction or incorrect measurement.
It is illustrated in the previous section that, after fault
inception, the power frequency voltage fed to distance
protection relay is superimposed by transients generated by
R
the power system and the CVT. As the impedance settings are
defIned at the power frequency, it is required that the
protection relay shall be able to keep the fundamental
frequency and reject the other frequency components before I
Figure 10: Mho Characteristics expansion with the polarising techniques
data processing is initiated. If a distorted signal is fed to the
relay, the relay will perform an incorrect computation of the
This study would like to pay attention to the polarising Modem relays use parallel and different computation to
technique implemented in five modem digital relays [8, 9, 11- crosscheck the measured impedance during high SIR
13]. condition[2]. Latest technology also provide CVT transient
Siemens 7SA522 offers to the User the ability to determine compensation function using customised CVT transient
the percentage of self and memorized voltage for the filtering and impedance estimation techniques. These filtering
polarising signal. The memory polarisation is only used if the methods include Finite Impulse Response filter with a longer
available voltage is above 40% of the nominal phase to window length in the pre-filtering area of the relay and full
ground voltage. Below this threshold the algorithm uses the cycle Fourier algorithms and least square methods for the
cross polarisation voltage. phasor estimation [ 16].
Even Areva P543 uses a combination of memorizing and self Another technique includes applying a time delay to CB trip
polarized voltage. The User shall determine the right in the zone before the Z l setting reach. This zone is the most
composition during relay configuration. The memorizing critical area for relay accuracy. An error on the computation
voltage can vary between 16 % to 83 % of the overall of the fault impedance could lead to maloperation as the relay
polarising signal. The memorizing voltage is taken from two could "overreach" or underreach".
cycles before fault and is used for 16 cycles after the loss of
the voltage supply. After this period, cross polarised voltage 4.3 Setting Advice
is used.
Schweitzer SEL 3 1 1 relay fully implements the memorizing Modem filtering techniques, CVT adaptive algorithms and
voltage to perform the distance relay computation. the use of memorised voltage as a polarising signal have
ABB-REL 670 employs a memorizing voltage. The dramatically improved the performance of the distance
memorized voltage is maintained for 2 cycles. protection relays. In relation to the protection settings, the
General Electric- Multilin D30 uses the memory voltage if the following items should also be considered:
actual voltage is below 80% of the nominal voltage. After the • Liaise with the planning engineer to determine the size
memory timer elapsed the voltage is checked. If the voltage is of the neutral earth resistor and consequent SIR. For
above 10%, the actual voltage is used. Otherwise, the instance, a SIR below 25 will usually ensure adequate
memorised voltage is still used. relay performance
There is a clear choice to use the entire or a percentage of the • Estimate the expected post fault transient overvoltages (
voltage memory as polarising signal. The use of this voltage magnitude and time to decay), based on system
will also prevent the relay being fed by a voltage signal which earthing, power system characteristics, SIR, CVT, and
contains the transient disturbance on the healthy and faulty relay performance. Although a precise figure can't be
phases. The voltage sample used refers to 2 cycles before the determined unless a power system study is performed,
fault inceptions. This time gap is considered satisfactory as a the above data and the existing literature as listed in the
compromise between two different requirements: Reference should be sufficient to complete the exercise.
• Using a sample as close as possible to the fault • Select the polarising technique according to the
inception. This will prevent that a frequency change in estimation above and the SIR at the end of zone 1 reach.
the network could cause a phase error in the calculation The design shall consider the SIR excursion under
• Use a sample recorded well before fault inception to minimum and maximum fault levels. For the minimum
fully prevent a post fault noise being memorised in the fault level, the worst case scenario of a single ( N- 1) or
relay double contingencies (N-2) should be adopted according
It has been noted that some relays allow the users to to the project/client requirements
determine the composition of the polarising signal [8, 13]. • Implement multiple group protection settings in the
The authors suggest that this capability be implemented by all relay to adapt the protection scheme to different system
the relay manufacturers in their next series of distance digital configuration and different SIR
relays. • To Zone 1, apply a constant time delay longer than the
CVT transient. This solution is not dynamic and
4.2 CVT Techniques penalizes fast fault clearing time for close in faults or
low SIR condition
Modem distance digital relays employ a wide variety of • Reduce the distance reach of Zone l(instantaneous trip)
techniques to reduce the negative impact created by the CVT to less than the traditional 80-85 %
transients. Precise details of the algorithms are not published • Limit the use of distance protection, where practicable,
by the Manufacturers possibly to protect their intellectual to transmission line with a SIR of less than 25 [2] or
properties. higher if specific type of relays are implemented
Areva P543 allows the User to enable or disable the CVT • Modem relays offer the capability to implement 4 or 5
filters and select the type of ferroresonance suppression used zones. According to the application a zone could be used
in the CVT. to divide zone 1 into two zones, a fast zone and a slow
SEL 3 1 1 detects CVT transient detection to delay the zone. The first zone covers the safe reach area of the
operating time of Zone 1 reach to 30 ms if SIR detected is line, for instance 60% of the line. The second zone, ZI
above 5. "slow", will cover the reach between 60% and 85% with
a time delay longer than the CVT transient. The time implementation of modem distance protection relays on short
delay could vary between 20 and 80 ms lines, ineffective grounding system and weak impedance
• CVT transient performance is improved if the source as a valuable alternative solution to the differential
transformer is adequately loaded. Considering that protection scheme.
modem digital relays have a small burden, it is good
engineering practise to increase the load connected to Acknowledgements
the CVT by using a resistor. The load shall be above 50
% the nominal rating of the CVT[2] The Presenter Hydro Tasmania Consulting for funding the
• Protection settings shall consider the system stability participation at the conference.
requirement. In Australia, the Australian National
Electricity Rules, NER, Chapter 5,[2] Clause S5. 1a.8 References
[28], requires that the primary protection system during
a faults should operate within the relevant time as [ 1] Alstom, Network Protection & Automation. Vol. 1.
detailed in Column 2 of Table 1: 2002.
[2] Ziegler, G., Numerical Distance Protection, ed.
TABLE I -NER- Fault Clearing Time Siemens. 2008: Public Corporate Publishing.
[3] Greenwood, A., Electrical transients in power systems
No minal voltage Ti me( milliseconds) 2nd ed. ed. 199 1, New York: New York : Wiley
kV Interscience.
Pri mary End o f line Back up Prot [4] IEEE, IEEE guide for the application of neutral
Prot Prot
grounding in electrical utility systems, part V -
400 kV and above 80 100 175
At least 250kV but 100 120 250 transmission systems and subtransmission systems
less than 400 IEEE Std C62.92.5- 1992, 1993.
kV [5] Peterson, H.A., Transients in Power Systems. 195 1, New
More than 100 kV 120 220 430
York: John Wiley & Sons,lnc. New York -Chapman &
but less than
250kV
Hall,LTD.London.
Less than or equal As necessary to prevent plant da mage and meet [6] Hou, D. and J. Roberts. Capacitive voltage transformer:
100kV stability require ments transient overreach concerns and solutions for distance
relaying. in Electrical and Computer Engineering, 1996.
On the 66 kV network the application of a time delay Canadian Conference on. 1996.
between 60 and 85 % of ZI reach will not affect system [7] Kasztenny, B. and D. Finney. Fundamentals of Distance
stability and the overall performance of the overall Protection. in Protective Relay Engineers, 2008 61st
protection scheme. For instance, in Melbourne Annual Conference for. 2008.
metropolitan area, system stability could be affected [8] Areva, P543 Relay Manual, Areva, Editor. 2008.
only if a fault is not cleared within 600 ms. The critical [9] Schweitzer, SEL 311 Manual. 2008.
fault clearing time exceeds 1000 ms in the Victorian [ 10] Schweitzer, E.O. and D. Hou. Filtering for Protective
regional area. Relays. in 46th Annual Conference For Protective Relay
In a 220 kV network, a small time delay could also be Engineers. 1993. Texas A&M University.
applied. For instance, applying a 20 ms time delay with [ 1 1] ABB, REL 670 Manual, ABB, Editor. 2007.
a modem CB and protection relay, the total CB [ 12] Multilin, G., D30 Protection Relay Manual, G. Multilin,
operating time would be still within the 120 ms limit. Editor. 2008.
• Test the protection settings using different SIR to verify [ 13] Siemens, 7SA522 Relay Manual. 2007.
and ensure that the performance of the relay are not [ 14] Alexander, G. and G. Andrichak. Ground Distance
affected by the reduced input voltage Relaying: Problems and Principles. in 19th Annual
Western Protective Relay Conference. 199 1. Spokane,
5 Conclusion Washington.
[ 15] Cigre, Modern Distance Protection Functions and
Phase to ground fault generates transient overvoltage in the Applications, Cigre, Editor. 2007.
power system and the capacitor voltage transformers. The [ 16] Schweitzer, E.O. and J. Roberts. Distance Relay
results are in line with the existing body of knowledge. Element Design. in 46th Annual Conference For
Modem digital distance relays are provided with digital Protective Relay Engineers. 1993. Texas A&M
filters, adaptive algorithm and voltage memory to overcome University.
the issues created by these disturbances. The source
impedance ratio, SIR, provides a correct indication of how the
relay performs under transient overvoltage conditions.
Modem digital relays provide accurate and fast operation with
SIR below 25. Sizing of the NER which produces a SIR
above 25 should be evaluated in the early stage of a project.
This study also offers some design advice to support the

You might also like