You are on page 1of 4

Smart

GSM+SMS
GPRS+3G
M2M RTU

Register Assignment Table

Register Assignment
Ver 2.0

S270
Date Issued: 2016-06-07

All rights reserved by


www.GPRS-M2M.com
GSM 3G M2M RTU
Automation solution
Table of contents
1. Table of Contents -------------------------------------------------------------------------------------------------2

2. Typically Applications ----------------------------------------------------------------------------------------3

3. System Schematic Diagram ----------------------------------------------------------------------------3

4. Register Assignment Table ---------------------------------------------------------------------------4

5. En d -- - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - -- - - - - -- - - - - - - - - -- -- 5

This handbook has been designed as a guide to the installation and operation of GSM 3G RTU S270.
Statements contained in the handbook are general guidelines only and in no way are designed to supersede the
instructions contained with other products.
We recommend that the advice of a registered electrician be sought before any Installation work commences.
King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for any loss or damage
including consequential damage due to reliance on any material contained in this handbook.
King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for GSM/3G Network
upgrading or SIMCard upgrading due to the technology specifications contained in this handbook.

Model GSM/3G Precision DIN AIN PT100 DO T/H Register Record Port
S270 V 12bit 2 2 0 2 1 X 200 USB
S271 V 12bit 4 4 0 4 1 X 200 USB
S272 V 12bit 8 6 0 4 1 X TF Card USB/RS232/RS485
S273 V 12bit 8 6 0 4 1 64 TF Card USB/RS232/RS485
USB/RS232/RS48
S275 V 16bit 8 6 0 4 1 64 TF Card
5/RJ45
1. For 3G Version, the model should plus C or W, C stands for inbuilt module is CDMA2000. W
stands for inbuilt module is WCDMA;
2. T/H: temperature & humidity input for environment monitoring, Range: -40~80°C, 0~100%RH.
Notice 3. The standard package:
1x RTU, 1x GSM Antenna, 1x AC/DC Adaptor,1x Android APP, 1x PC Configuration Software,
1x USB cable, 1x User Manual, 1x Backup battery inside, Terminals for Connection.
4. The standard package not includes: SIMCard , Temperature+Humidity sensor AM2301.

Warning Tips:

This Register Assignment is for King Pigeon RTU S270 ONLY!

S270 GSM 3G M2M RTU Register Assignment Table Page 2 of 4 Ver 2.0 WWW.GPRS-M2M.COM
GSM 3G M2M RTU
Automation solution
1. Typically Applications

2. System Schematic Diagram

A: I/O port connections;


B: Through GPRS or 3G to HMI, OMC, the TCP/IP protocol is KingPigeon Definition Protocol.
C: Through GPRS or 3G to SCADA,HMI, DCS, OPC Server, Under this condition, the RTU performs Modbus
Slave. And the TCP/IP Protocol is Modbus TCP.
D: Using SMS to control the RTU, or receive SMS alarm alert, or through voice communication to open the door
or receive alarm calling.

S270 GSM 3G M2M RTU Register Assignment Table Page 3 of 4 Ver 2.0 WWW.GPRS-M2M.COM
GSM 3G M2M RTU
Automation solution
3. Register Assignment Table
1. Relay:
Read: Function code 3
Write: Function code 6(Data format:short[int],MSB first)
Address Definition Data Description
00FAH Relay 0 The DOUT0 Digital output:=0,open;=1,close.
00FBH Relay 1 The DOUT1 Digital output:=0,open;=1,close.

2. Analog: Function 4 (Data format:float,MSB first)


Address Definition Data Description
0000H AIN0 high 16 bit Current value =Real Value*100,Measuring range:
0001H AIN0 low 16 bit -3.40E+38~+3.40E+38
0002H AIN1 high 16 bit Current value =Real Value*100,Measuring range:
0003H AIN1 low 16 bit -3.40E+38~+3.40E+38

3. External power voltage, and backup battery voltage: Function code 4.


(Data format:short[int],MSB first)
Address Definition Data Description
000E External Power Voltage Current value =Real Value*100,Measuring range:
-32535-~32536
000F Backup Battery Voltage Current value =Real Value*100,Measuring range:
-32535-~32536

4. Digital input: Function code 4.(Data format:short[int],MSB first)


Address Definition Data Description
0010H DIN0 =0000:Close or high level(3V-30V);
=0001:Open or low level(0V-0.5V).
0011H DIN1 =0000:Close or high level(3V-30V);
=0001:Open or low level(0V-0.5V).

5. Temperature and humidity current value for AM23xx sensors only.


Function code 4, (Data format:Integer,MSB first)
Address Definition Data Description
0018H Temperat Current value =Real Value*100 , Measuring range :
ure -32535-~32536
0019H Humidity Current value =Real Value*100 , Measuring range :
-32535-~32536

6. Use DIN0 as pulse counter,current value.


Function code 4, (Data format:float,MSB first)
Address Definition Data Description
001AH Current value high 16 bit
Current value,range:0-999999.
001BH Current value low 16 bit
The End!