DESIGN OF

TWO-STOREY REINFORCED-CONCRETE RESIDENTIAL


STAAD.Pro & STAAD Advanced Concrete

Main objectives
1) Calculate Wind Pressure for Components and Claddin
2) Design the Roof Truss and Purlins per NSCP 2015/AIS
3) Derive dead load and live load values per NSCP 2015
4) Discuss NSCP 2015/UBC 97 Seismic parameters input
5) Design the concrete elements in STAAD Advanced Co
(beams, slabs, columns and footings)
STRUCTURE USING
Designer RCDC

g per NSCP 2015/ASCE 7-10


C 360-10 by LRFD Method

to STAAD
ncrete Designer RCDC
Purlin spacing 0.8 m
truss spacing 2.5 m

STORIES (LEVELS)

Levels Storey Height (m)

Footing to GF 1.8
GF to 2F 3
2F - Roof Beam 3
Roof Beam - Apex 2
9.8
Roof mean Height for wind load calculation
7.00 m
Roof Slope = 22.62deg
40km

Seismic Source Type A


Malolos City Bulacan
Bulacan = 250 kph
SAMPLE REINFORCED-CONCRETE BUILDING PROJECT USING
STAAD.Pro & STAAD Advanced Concrete Designer

STORIES (LEVELS)
Levels Storey Height (m)
Footing to GF 1.8
GF to 2F 3
2F - Roof Beam 3
Roof Beam - Apex 2
9.8
PROPERTIES
Beams Columns Slabs fc' fy
RB250x400 RC300X300 S115 20.68 Mpa 275 Mpa
(3000psi) (Gr40)

LOADS
Dead Load
1) Selfweight
Concrete unit weight = 24 kN/m3

2) Member Load
150mm CHB 3.11 kN/m per meter height
100mm CHB 2.98 kN/m per meter height

Floor Load Floors Roof


115mm slab 2.76 - kN/m2
roof framing - 0.41 kN/m2
corrugated roofing sheet - 0.10 kN/m2
Floor finish 1.10 - kN/m2
Ceiling 0.10 0.10 kN/m2
MEP 0.10 0.10 kN/m2
Interior Partition 1.00 - kN/m2
Water proofing - - kN/m2
5.06 0.71
Live Load
1.9 kN/m2 0.60 kN/m2

Seismic Parameters
UBC 97 / NSCP 2015
Zone = 4
Seismic Source Type = A
Importance Factor ( I ) = 1.0 (Standard
Occupancy) R = 8.5 - Special Moment Frame
Structure is located 40km from seismic source
Ct = 0.0731

Wind Parameters
Wind (ASCE 7-10 / NSCP 2015)
Vwind = 250 kph
I = 1.0
Exposure = B (typical residential structure in urban area)
2.63 0.24 0.24 3.11
2.5 0.24 0.24 2.98
Low-Rise Buildings : Component and Cladding
Simplified Procedure
ASCE 7-10
PURLINS (EFFECTIVE AREA

1
1.09
-1.85
PURLIN SP
0.872
-1.48
Pnet = λ Kzt Pnet9

1 1 TRUSS (EFFECTIVE AREA =


Zone
1
0.85

-1.72
TRUSS SPA

2.13
-4.3
PURLINS (EFFECTIVE AREA = 2.08 m2)
250kph
Zone
2 3
1.09 1.09 kn/m2
-3.04 -4.57 kn/m2
PURLIN SPACING = 0.8M

0.872 0.872 kn/m


-2.432 -3.656 kn/m

FECTIVE AREA = 24m2)


250kph
Zone
2 3
0.85 0.85 kn/m2
-2.44 -3.83 kn/m2
TRUSS SPACING = 2.5M

2.13 2.13 kn/m 10% least horizontal dimension 0.8


-6.1 -9.575 kn/m 0.4h 2.8
4% least horizontal dimension 0.32
0.9 0.9 governs
TRUSS 1.635 KN 2.5 9.6 24 0.068125 KN/M2

PURLINS 0.681 KN 0.8 2.5 2 0.3405 KN/M2

0.408625 KN/M2
UBC 1997
T = Ct (hn)
0.75
PARAMETERS sec UBC Eq. (30-8)

Z 0.4 = 0.341 sec


I 1 < 0.70 sec therefore Ft = 0;
Rwx 8.5
Rwz 8.5
Na 1
Nv 1 V= CvIW KN UBC Eq. (30-4) S
4 RT
Ct 0.0731 = 386.90 KN
hn 7.8
W 1753.2
Cv 0.64
Ca 0.44

Total design base shear need not exceed:


V = 2.5Ca IW KN UBC Eq. (30-5) R
= 226.88 KN DESIGN BASE SHEAR IS TOO LARGE!
USE THIS VALUE!

Design base shear shall not be less than:


V = 0.11CaIW KN UBC Eq. (30-6)
= 84.85 KN OK!

V = 0.8ZNvIW KN UBC Eq. (30-7)


R
= 66.00 KN OK!

If Ft≠ 0:
Ft = 0.07TV UBC Eq. (30-14)
= 9.24 KN
< 0.25V = 96.73

ENGR JOHN PAUL DELA ROSA (CE)


LICENSE # 98600_PRC MANILA
0.004202
1.2 DL + 1.00 E + 0.5 LL

1 1.400 D
1 1.200 D + 1.600 Lp
1 1.420 D + 0.500 Lp + 1.250 E1
1 1.420 D + 0.500 Lp + 1.250 E2
1 1.420 D + 0.500 Lp - 1.250 E1
1 1.420 D + 0.500 Lp - 1.250 E2
1 1.420 D + 1.250 E1
1 1.420 D + 1.250 E2
1 1.420 D - 1.250 E1
1 1.420 D - 1.250 E2
1 0.680 D + 1.250 E1
1 0.680 D + 1.250 E2
1 0.680 D - 1.250 E1
1 0.680 D - 1.250 E2
E = ρ Eh + Ev
1.25

= 1.25 Eh

Ev = 0.5 Ca I DL
0.5 0.44 1 DL
= DL

= 0.22 DL