You are on page 1of 40

GROUPEMENT TIMIMOUN Document Number:

Projet Surface 01SRF10-TIM-SP-XE-131002


SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 1 of 40

SOLID WASTE STORAGE AND DISPOSAL SYSTEM FACILITY


SPECIFICATION

Rev. Status Date Revision memo Issued by Checked by Approved by

03 AFD 03-May-11 Approved for Design CR JV


J VIVANT
Digitally signed by J VIVANT
DN: cn=J VIVANT, c=FR
Date: 2011.05.03 11:37:31 +02'00'
GL

02 AFD 08-Avr-11 Approved for Design ASou CR JV

01 IFA 11-Mar-11 Issued for approval ASou CR JV

00 IFR 17-Dec-10 Issued for Review ASou CR JV

This document has been generated by an Electronic Document Management System. When printed it is considered as a for information
only copy. The controlled copy is the screen version and it is the holder's responsibility that he/she holds the latest valid version.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 2 of 40

TABLE OF CONTENT
1 INTRODUCTION ...................................................................................................................................................... 4

2 SCOPE ....................................................................................................................................................................... 5

3 REFERENCES & ABBREVIATIONS.................................................................................................................... 6


3.1 REFERENCES ....................................................................................................................................................... 6
3.1.1 Local rules......................................................................................................................................... 6
3.1.2 Project documents ........................................................................................................................... 6
3.1.3 COMPANY Specifications .............................................................................................................. 7
3.1.4 Codes & Standards ......................................................................................................................... 7
3.2 ABBREVIATIONS.................................................................................................................................................... 8
4 HOLD LIST ................................................................................................................................................................ 9

5 WASTE MANAGEMENT POLICIES AND PRINCIPLES ................................................................................ 10


5.1 WASTE MANAGEMENT PLAN .............................................................................................................................. 10
5.1.1 Mitigation techniques..................................................................................................................... 10
5.1.2 Waste segregation......................................................................................................................... 11
5.1.3 Waste labelling and transport on site.......................................................................................... 11
5.1.4 Waste inventory ............................................................................................................................. 11
5.1.5 Waste handling............................................................................................................................... 12
5.1.6 Waste tracking system .................................................................................................................. 12
5.2 DUTY OF CARE.................................................................................................................................................... 13
5.3 USE OF BEST AVAILABLE TECHNOLOGY NOT ENTAILING EXCESSIVE COST (BATNEEC) ............................. 13
6 SOLID WASTE CLASSIFICATION AND PACKAGING.................................................................................. 14
6.1 DOMESTIC WASTE AND ASSIMILATED (MA) ....................................................................................................... 14
6.2 INERT WASTE (I) ................................................................................................................................................. 14
6.3 SPECIAL WASTE (S) ........................................................................................................................................... 14
6.4 HAZARDOUS SPECIAL WASTE (SD).................................................................................................................... 14
7 SOLID WASTES MITIGATION, DISPOSAL AND TREATMENT MEASURES........................................... 15

8 TREATMENT, STORAGE AND DISPOSAL SYSTEM .................................................................................... 23


8.1 STORAGE AND DRYING AREA FOR WASTE TO INCINERATE ................................................................................ 26
8.2 STORAGE AREA FOR SMALL CONTAINERS.......................................................................................................... 26
8.3 STORAGE AREA FOR HAZARDOUS WASTE IN LARGE CONTAINER ...................................................................... 27
8.4 STORAGE AREA FOR SPECIAL WASTE IN LARGE CONTAINER ............................................................................. 27
8.5 STORAGE AREA FOR INERT WASTE IN SKIP ........................................................................................................ 27
8.6 OUTDOOR STORAGE AREA ................................................................................................................................. 27
8.7 DECONTAMINATION FACILITIES .......................................................................................................................... 28
8.8 COMPACTION FACILITIES .................................................................................................................................... 28
8.9 WASTE STABILIZATION FACILITIES...................................................................................................................... 28
8.10 WASTE LANDFILL ON SITE .................................................................................................................................. 29
8.11 ORGANIC WASTE COMPOSTING ON SITE ............................................................................................................ 29
8.12 WASTE INCINERATION ON SITE .......................................................................................................................... 30
8.13 EVAPORATION BASIN .......................................................................................................................................... 31
8.14 SEWAGE TREATMENT ......................................................................................................................................... 31
8.15 HANDLING EQUIPMENT ....................................................................................................................................... 32

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 3 of 40

List of figures

Figure 1: Waste management for TIMIMOUN facilities .................................................................. 15


Figure 2: Accommodation camp waste location and arrangement facilities ................................... 23
Figure 3: CPF waste location and arrangement facilities................................................................ 24

List of tables

Table 1: Solid waste mitigation, disposal and treatment measures ................................................ 22


Table 2: Incinerator Capacity Evaluation ........................................................................................ 30

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 4 of 40

1 INTRODUCTION
Groupement TIMIMOUN (SONATRACH 51%, TOTAL 37.75%, and CEPSA 11.25%) is preparing the
development of the Timimoun gas fields, in south western Algeria.

Timimoun field has an extension of 13250 km². It is located at Algeria’s South West, 120 km to the
West from In Salah gas fields and at 100 km east from the route that links Timimoun to Tiberrhamine
and Oufrane palm groves and to Sbaa and Adrar village.

The entire field is located in a desert area.

The development will include a 5 MSm³/d (raw gas) gas processing treatment plant located in the CPF
(Central Processing Facility). A dew point unit will be included in order to reach the gas export
specifications.

This plant will be fed by 14 gas producing wells that will be drilled before plant start-up and 23 extra
wells that will be drilled later. The gas will be collected via 5 clusters, provided with production and test
manifolds, and sent through trunklines to the CPF to be treated.

The raw gas is a poor condensate gas with an estimated max CGR of 11.8 Sm³/MSm³. No free water
is foreseen with gas, only condensate water is present.

The CO2 content in the raw gas (7%) will be eliminated through an amine unit and reinjected in 2
disposal wells.

Treated gas will be exported through a 24’’ pipeline up to a tie-in point to a new pipeline to be installed
by Sonatrach as part of other project.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 5 of 40

2 SCOPE
This document presents the specification of the solid waste storage and disposal system facility of
TIMIMOUN Project (CPF, Accommodation Camp, Clusters, Gas Export Tie-In, Wells and Air Strip).

Only operational phase is covered. Drilling, Construction and dismantlement will be developed at a later
stage (Detailed Engineering).

For details about Catalyst / Chemical product, refer to “Catalyst Chemical storage and disposal system
specification”, Ref. [19]).

For details about quantification and type of wastes (Solid/Liquid/Gaseous), refer to “Effluent list”, Ref.
[20].

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 6 of 40

3 REFERENCES & ABBREVIATIONS

3.1 References

3.1.1 Local rules


[1] Gestion, contrôle et élimination des déchets Loi n°01-19 du 12 décembre
2001
[2] Déchets d’emballage Décret exécutif n° 02-372 du 11
novembre 2002
[3] Réglementation de l'activité de traitement et de régénération des Décret exécutif n° 04-88 du 22
huiles usagées mars 2004
[4] Réglementation du déversement des huiles et lubrifiants dans le Décret exécutif n° 93-161 du 10
milieu naturel juillet 1993
[5] Conditions et modalités de récupération et de traitement des Décret exécutif n° 93-162 du 10
usagées juillet 1993
[6] Règles générales d’aménagement et d’exploitation des installations Décret exécutif n° 04-410 du 14
de traitement des déchets et les conditions d’admission de ces décembre 2004
déchets au niveau de ces installations
[7] Modalités de transport des déchets spéciaux dangereux Décret n°04-409 du 14 décembre
2004
[8] Modalités de déclaration des déchets spéciaux dangereux Décret n°05-315 du 10 septembre
2005
[9] Adhésion avec réserve, de la république algérienne, démocratique Décret présidentiel n° 98-158 du
et populaire, à la convention de Bâle sur le mouvement et le 16 mai 1998
contrôle des mouvements transfrontaliers de déchets dangereux et
de leur élimination
[10] Nomenclature des déchets, y compris les déchets spéciaux Décret exécutif n° 06-104 du 28
dangereux février 2006

3.1.2 Project documents


[11] Etude Initial d’Impact Environnemental et Sociétal – Rev4, Août Appendix 18
2008
[12] UFD – CPF Drainage system 01SRF10-CPF600-DB-C-070026
[13] UFD – CPF Hot Oil system 01SRF10-CPF480-DB-C-070128

[14] PID – CPF Evaporation Basin 01SRF10-CPF4K0-DC-C-070104


[15] TOTAL Climatological statistics Timimoun - Algeria Report n°10.32-V3- 06/10/2010
[16] Specification – Sewers & Drainage 01SRF10-TIM-SP-ZG-240016
[17] Specification – CPF Sewage Package 01SRF10-CPF460-SP-MU-084010
[18] Safety Concept 01SRF10-TIM-TP-X-100001
[19] Catalyst Chemical storage and disposal system specification 01SRF10-TIM-SP-XE-131001
[20] Effluent List 01SRF10-TIM-LO-XE-133001

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 7 of 40

3.1.3 COMPANY Specifications


[21] Environmental Requirements for Projects Design and E&P GS EP ENV 001 – Rev03
Activities
[22] Environmental specification for onshore pipeline construction GS-EP-ENV-011 – Rev02
[23] Baseline study environmental status of an onshore site GS-EP-ENV-111 – Rev03
[24] Environmental impact assessment of E&P activities GS-EP-ENV-120 – Rev00
[25] Landfill design and operation for E&P sites GS-EP-ENV-421 – Rev02

3.1.4 Codes & Standards


[26] Integrated Pollution Prevention and Control Reference Documents BAT, August 2006
on Best Available Technology for the Waste Treatment Industries

[27] Hazardous Waste Directive 91/689/EEC of 12


December 1991
[28] Basel Convention on the Control of Transboundary Movements of
Basel Convention, 1989
Hazardous Wastes and Their Disposal

[29] Guidelines for waste management with special focus on areas with International Association of Oil &
limited infrastructure Gas Producers - September 2008

[30] Environmental, Health, and Safety Guidelines – General Guidelines International Finance Corporation
/ World Bank Group – April 2007

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 8 of 40

3.2 Abbreviations
BATNEEC Best Available Technology Not Entailing Excessive Cost
CPF Central Processing Facility
EEC European Economic Community
EPC Engineering Procurement and Construction
FEED Front End Engineering Design
HSE Health, Safety and Environment
ISO International Organization for Standardization
MSDS Material Safety Data Sheets
MTA Million Tonnes per Annum
PPE Personal Protective Equipment
WMP Waste Management Plan
WRM Waste Reduction Management

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 9 of 40

4 HOLD LIST

HOLD 1 Deleted
HOLD 2 Waste incinerator capacity shall be confirmed at detailed engineering by CONTRACTOR
HOLD 3 Deleted
HOLD 4 Deleted
HOLD 5 Sewage sludge collection by specialized carrier for agricultural or land improvement
purposes to be confirmed at a later stage pending GTIM investigation ; a landfill option
has been considered in a conservative approach (refer to section 8.10),
HOLD 6 Stabilized hazardous sludge collection by specialized carrier for specific treatment to be
confirmed at a later stage pending GTIM investigation; a landfill option has been
considered in a conservative approach (refer to section 8.10).

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 10 of 40

5 WASTE MANAGEMENT POLICIES AND PRINCIPLES


5.1 Waste Management Plan
A Waste Management Plan shall be adopted for the project and shall take into account the “5 R
principle”, i.e.: Reduce, Recover, Re-use, Recycle, Residue disposal.

Waste Management Plan main objectives are:

• To ensure a full inventory of all wastes following environmental regulation.

• To identify the waste management practices to be employed in terms of mitigation,


collection, segregation, recycling, and disposal during project development.

• To meet the design targets required to maintain the local Permit requirements of discharges
and wastes that are known to have an impact on the environment.

• To provide detailed method statements for each element of the waste management
handling, treatment and disposal process.

• To identify any third party agreements for waste transfer or handling.

• To identify responsible use of materials to minimize waste.

• To enforce strict duty of care on the project managers and the contractors.

• To prohibit uncontrolled burning or burial of waste.

• To provide procedures for offsite disposal or long term storage of contaminated material.

5.1.1 Mitigation techniques

There will be an effort to minimize the amount expected waste to be generated, through waste
reduction management. The following actions are proposed during project implementation, as
reduction waste measures:

• Source as many materials as possible locally to reduce transport/import requirements, and


increase the restocking flexibility on the project of consumable materials;

• Use a “first in, first out” inventory method to minimize spoiled inventory;

• Purchase materials in bulk or in reusable/returnable containers to minimize packaging waste


or empty waste containers;

• Take appropriate measures to avoid or minimize leaks and spills, by providing adequate
shelter and secondary containment as appropriate.

All adequate measures will be taken to avoid waste generation and minimize both quantities and
hazards of waste generated.

Waste mitigation strategy shall be developed in order to involve personnel in reduction measures
such as segregation and recycling.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 11 of 40

In accordance with the waste management plan strategy, the contractor will ensure that project
recycled materials are either reused on the project or transferred to third party recycling facilities in
accordance with this Plan for recycling purposes.

5.1.2 Waste segregation

Recyclable materials (i.e. paper/cardboard, plastic, glass, metal, wood, and others) will, as far as is
practicable, be segregated from non-recyclable streams for recovery/recycling.

A key part of segregation will be to provide waste specific collection bins throughout the site.

Waste segregation strategy presented in Table 1 is in accordance with company specification GS-
EP-ENV-011, Ref. [22].

5.1.3 Waste labelling and transport on site

Each waste shall be labelled with adequate colour code giving appropriate category of waste
(Categories / Types of waste, Any associated hazards) in order to facilitate the identification and
collection.
Waste collection bins will be clearly labelled in both French and Arabic.
All hazardous waste must be transported in sealed containers with labels to clearly identify the types
of waste, and the associated hazards. Vehicles carrying hazardous waste must also carry spillage
containment and clean-up equipment, and the driver must be trained in its use.
Each chemical product shall be supplied with its own MSDS (Material Safety Data Sheet).

5.1.4 Waste inventory

Site specific inventory of waste will be managed by the site environment department.

Management of the waste inventory will be established by the site environmental team with input
from the site manager. In managing the inventory at waste collection sites, particular attention will
be paid to:
• Description and classification of the waste streams i.e., inert (I), hazardous (DS) and non-
hazardous (S and MA);
• Identification of storage arrangements at collection sites;
• Identification of disposal methods and contractors used;

• Quantification of waste generated – on an annual, quarterly or monthly basis, as appropriate;


and
• Waste stream volumes and their sources.

Proper waste labelling is essential to managing the inventory and tracking of waste.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 12 of 40

5.1.5 Waste handling

All personnel who are involved in the handling of hazardous and non-hazardous waste will undergo
specific induction in:
• Project HSE policy
• Procedures for adequate segregation;
• The duty of care system and how to complete forms and other required documentation
correctly;
• Waste handling Personal Protective Equipment (PPE) requirements;

• Waste treatment; and


• Waste storage.
The method of waste handling, particularly for hazardous waste will be specific to each waste type.

Material Safety Data Sheets (MSDS) will be available at appropriate locations. Relevant sections,
e.g. substance description, handling instructions, PPE requirements, etc. will be presented in both
French and Arabic.

5.1.6 Waste tracking system


A spreadsheet based tracking system shall be used to record and track the inventory of waste
(hazardous and non hazardous) generated in TIMIMOUN Facilities, with as minimum:
• Waste name / type / category / packaging,
• Quantity (kg),
• Date,

• Point of origin of waste generated,


• Chemical contains,
• Handling, fire intervention and HSE information,
• Intended means of reuse, recycling, treatment and/or disposal of each waste type;

For hazardous waste, information listed in the spreadsheet shall give the information to facilitate
filling of:
• “movement document” (Refer to Appendix 1) which shall be delivered by the transporter of
hazardous waste, to treatment installation (as per executive decree n° 04-410, Ref. [6], and
presidential decree n°98-158, Ref. [9]),
• “Special hazardous waste declaration” (see Appendix 2) which shall be sent to
administration in charge of environment each year (as per executive decree n°05-315, Ref.
[8]).
The project waste manager will manage the waste tracking system in coordination with the site
environment department which will maintain site specific records.
When collecting the waste, the Waste Contractor driver must confirm that the information is correct
by signing and dating the appropriate movement document. Movement document and special
hazardous waste declaration copies must be kept on file for management purpose.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 13 of 40

5.2 Duty of care


The Duty of Care principle states that a producer of waste (for either hazardous or non-hazardous
waste) has a duty to ensure that waste is properly managed even after transfer to a third party.
The Duty of Care system categorises and identifies the nature and quantities of waste from “cradle
to grave” (i.e. from generation to treatment and final disposal including handling) of the waste.
The Duty of Care concept moreover requires that producers of waste select appropriate third party
waste handlers justifiably and transparently, while assessing their capabilities, and monitoring their
activities with respect to the management of the waste.
The Duty of Care requirements can be summarised as follows:
• Hazardous Waste consigned to a disposal contractor or transporter is accompanied by a
movement document for tracking the safe handling, treatment, and disposal of the waste.

• Waste is consigned only to authorised entities, i.e. licensed waste contractors, local authority
waste collectors, entities dealing with waste in ways that are exempt from licensing, or
project authorized waste landfill / treatment facility.
• Waste is securely contained to prevent escape to the environment both during storage,
handling, and transit.

• Appropriate measures are taken to ensure that others involved in the handling and disposal
of the waste do so in accordance with respective laws and the project environment
guidelines.

5.3 Use of Best Available Technology Not Entailing Excessive Cost (BATNEEC)
For the purposes of waste management the BATNEEC principle shall apply. The BATNEEC
principles states that waste shall be managed by the Best Available Technology (BAT) that does not
Entail Excessive Cost, in other words the costs of moving from one technology to a better performing
one plus the associated energy costs are not disproportionate to the overall benefit achieved.
Important considerations for BAT, bearing in mind the likely costs and benefits of a measure and the
principles of precaution and prevention are:
1. the use of low-waste technology if there is a choice in procurement;
2. the use of less hazardous substances if there is a choice in procurement;
3. the furthering of recovery and recycling of substances generated and used in the process
and of waste, where appropriate;
4. comparable processes, facilities or methods of operation which have been tried with success
on an industrial scale;

5. technological advances and changes in scientific knowledge and understanding;


6. the nature, effects and volume of the emissions concerned;
7. the length of time needed to introduce the best available technique;

8. the consumption and nature of raw materials (including water) used in the process and their
energy efficiency;
9. the need to prevent or reduce to a minimum the overall impact of the emissions on the
environment and the risks to it;
10. the need to prevent accidents and to minimize the consequences for the environment;
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 14 of 40

6 SOLID WASTE CLASSIFICATION AND PACKAGING


Waste hazardous classification is given in the article 5 of low n°01-19, Ref. [1]. Waste nomenclature
given in the executive decree n°06-104, Ref. [10], details category of waste for every industrial
activity and for each one, classification and hazardous criteria.

Classification of TIMIMOUN waste is showed in the following section 7.

6.1 Domestic waste and assimilated (MA)


Definition: All waste from households and similar waste from industrial, commercial, craft, and
others, who, by their nature and composition are similar to household waste.

Examples: paper, cartoons, wood, food waste, etc.

Packaging: shall insure good waste confinement and protection (from soiling/pollution), facilitate
segregation and handling.

6.2 Inert waste (I)


Definition: All waste including wastes coming from quarrying, mining, demolition, construction or
renovation that does not undergo any significant physical, chemical or biological at their landfill, and
are not contaminated by hazardous substances, or other nuisance generating waste which can
damage the health and / or the environment.

Examples: Insulation material, topsoil, concrete, etc.

Packaging: Excavated materials shall be temporarily stockpiled if required for backfill or construction
purposes and disposed in approved locations.

6.3 Special waste (S)


Definition: All waste from industrial, agricultural, medical care, services and other activities which,
due to their nature and composition of the material they contain, may not be collected, transported
and processed under the same conditions as household waste and treated as inert waste.

Examples: Medical care waste, sludge from water treatment package, from sewage treatment
package, industrial non hazardous waste, etc.

Packaging: As per law n°01-19, Ref. [1], medical care wastes shall have a specific packaging and
must be stored in closed safe packaging (polyethylene box, drum or container)

6.4 Hazardous special waste (SD)


All special waste that, by their composition or characteristics of hazardous materials they contain,
are likely to harm public health and / or the environment.

Examples: Batteries, Maintenance Waste (painting packaging, etc.), lubricating oil, etc.

Packaging: As a minimum, must be stored in closed safe packaging (polyethylene box, drum or
container) and if required, in a hermetically sealed container (drum or tank type).

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 15 of 40

7 SOLID WASTES MITIGATION, DISPOSAL AND TREATMENT


MEASURES
The following figure presents the waste management for TIMIMOUN facilities.
Food waste
Open ground Compos-ting pit
protected with fence and a Provide handling
Green waste mosquito net on the surface equipment for sludge
mixing, pit filling and
short transport
Polluted packaging
INCINERATION

Oily rag / filters


Drying

Ash STABILISATION
Soft Medical (LIME)
waste
Stabilized
Plastic packaging sludge
Treated wood

LANDFILLING
Industrial Bottom STORAGE
HOLD 6
Sludge Offsite

TRANSPORT
Treatment
Soil and concrete STORAGE

Non recyclable
plastic
HOLD
Offsite 5
Sewage sludge Valorization
Isolation wool STORAGE
Tyres
Stockpile / Valorisation
/ Material reuse
Wood Palettes
Compaction

Cardboard CARDBOARD Alger

Recyclable plastic PLASTIC Alger

Used oil OIL Oran

Used batteries BATTERY Gharda

Metallic wastes
TRANSPORT
STORAGE
Compaction
Cleaning

Metallic Empty Metallic


Metallic waste METAL Bouira
container empty
container

GLASS Oran
Glass

Sharp medical Offsite


MEDICAL
wastes Treatment

Domestic battery,
mercury lamp Export
SPECIAL
Used ink

Legend : Process Storage


Inert waste Hazardous waste Special waste Domestic waste

Figure 1: Waste management for TIMIMOUN facilities


The following table gives the main mitigation, disposal and treatment measures of wastes produced in
TIMIMOUN facility during project operation phase. Waste sources and quantity are specified in “Effluent
list”, Ref. [20].

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 16 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Excavated Inventory control and Use of Segregation of wood, Onsite: landfill or burial of not Onsite landfill - Shall be collected and
Inert waste
(I) material / management inert paper, metals for reused inert waste Refer to section 8.10 treated in accordance
Topsoil Segregation of constructi recycling Offsite: Operator will use with law n°01-19,
on Ref. [1].
Concrete and components for specialized carrier to send waste
rubble recycling or reuse material in dedicated authorized
as infill installation (landfill, reuse,
recycle)
Insulation Inventory control and No Segregation of wood, Onsite: Landfill on site Outdoor storage before Operator will use specialized Shall be collected and
material management paper, metals for offsite recycling carrier to send waste in treated in accordance
Offsite: Operator will use
Segregation of recycling specialized carrier to send waste Refer to section 8.6 dedicated authorized with law n°01-19,
installation Ref. [1].
components for in dedicated authorized
recycling or reuse installation (recycling / landfilling)
Non Inventory control and No Segregation for Offsite: Operator or commune Compacted and stored in Operator or commune will use Shall be collected and
Domestic
waste and contaminated management recycling will use specialized carrier to container before offsite specialized carrier to send treated in accordance
paper and Improved send waste in dedicated recycling waste in dedicated authorized with law n°01-19,
assimilated
cardboard authorized installation (for installation (for recycling in Ref. [1] and executive
(MA) housekeeping Refer to sections 8.8 and 8.4
recycling in Algeria) Algeria) decrees n°02-372, Ref.
Compacting in waste [2]
Collected with other Onsite: Incineration in Refer to Appendix 3
baler
burnable waste accommodation camp
incinerator in a safe and
controlled manner
Plastic Inventory control and No Segregation for Offsite: Operator or commune • Incineration onsite of non • Operator or commune will Bottle consumption may
packaging: drink management recycling will use specialized carrier to recyclable plastic – Refer to use specialized carrier to be limited by using
bottles, Improved send waste in dedicated sections 8.1 and 8.12 send waste in dedicated cisterns rechargeable
polystyrene, authorized installation (for authorized installation (for by client.
housekeeping • Recyclable plastic
polyethylene … recycling in Algeria) recycling in Algeria) - Refer to Shall be collected and
Compacting in waste compacted and stored in
Excepted for PVC which Onsite: Incineration in Appendix 3 treated in accordance
baler container before offsite
produce toxic gas, may accommodation camp recycling – Refer to • Refer to incinerator ash with law n°01-19,
be collected with other incinerator in a safe and sections 8.8 and 8.4 treatment and disposal Ref. [1] and executive
burnable waste controlled manner options decrees n°02-372, Ref.
[2]

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 17 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Metal waste Inventory control and No Segregation for Offsite: Operator or commune • Metal waste stored in open Operator or commune will use Shall be collected and
(ferrous and non management recycling will use specialized carrier to floor skip before offsite specialized carrier to send treated in accordance
ferrous): food Improved send waste in dedicated recycling - Refer to section waste in dedicated authorized with law n°01-19,
and drink cans, authorized installation (for 8.8 installation (for recycling in Ref. [1].
housekeeping
scrap, drums, recycling in Algeria) Algeria)
• Metallic drums compacted
electric cables Refer to Appendix 3
and stored in dedicated

area before offsite recycling
Glass Inventory control and No Segregation for Offsite: Operator or commune - Refer to section 8.5
management recycling will use specialized carrier to
send waste in dedicated
authorized installation (for
recycling in Algeria)
Treated wood / Inventory control and Reuse for Collected with other Onsite: Incineration in Incineration onsite Refer to incinerator ash Shall be collected and
pallet debris management do-it- burnable waste (Food accommodation camp treatment and disposal treated in accordance
Refer to sections 8.1 and
yourself waste and green incinerator in a safe and 8.12 options with law n°01-19,
work wastes, used controlled manner Ref. [1].
paper/card-board)
Offsite: Operator will use
Segregation for specialized carrier to send waste
recycling in dedicated authorized
installation (for recycling,
incineration, heat recovery)
Non treated Inventory control and Reuse for Segregation for recover Onsite: incineration of non reuse Outdoor storage before Operator will use specialized Shall be collected and
wood management handling / pallet in accommodation camp offsite valorization / reuse carrier to send waste in treated in accordance
transportation storage incinerator in a safe and Refer to section 8.6 dedicated authorized with law n°01-19,
pallet purpose controlled manner installation (for reuse / Ref. [1].
Offsite: recycling)

1-Returned to vendor/supplier
(recover)
2- Operator will use specialized
carrier to send waste in
dedicated authorized installation
(for reuse)

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 18 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Food waste Inventory control and Segregatio Segregation for Onsite: Composted on site • Composted on site – Refer - Shall be collected and
management n for valorization to section 8.11 treated in accordance
Green wastes Offsite: Operator or commune
animals with law n°01-19,
Mass reduction in a will use specialized carrier to • Incineration shall be
feeding Ref. [1].
dehydration unit send waste in dedicated considered as alternative to
authorized installation (for composting in order to
composting, animals feeding) avoid sanitary problems –
Collected with other Onsite: Incineration in food waste and green
burnable waste (used accommodation camp waste shall be considered
paper and cardboard) incinerator in a safe and for definition of incinerator
controlled manner capacity – Refer to
sections 8.1 and 8.12
Offsite:
Disposed by commune for
incineration

Contaminated Inventory control and No Collected with other Onsite: Incineration in Incineration onsite – Refer to Refer to incinerator ash Shall be collected and
burnable management burnable waste (used accommodation camp sections 8.1 and 8.12 treatment and disposal treated in accordance
domestic waste paper and cardboard) incinerator in a safe and options with law n°01-19,
(cardboard, controlled manner Ref. [1].
paper, Offsite:
packaging, …)
Disposed by commune for
incineration

Special
Medical care Inventory control and No Segregation for specific Onsite: Incineration in • Onsite incineration of soft • Operator will use specialized Shall be collected and
wastes management treatment : accommodation camp medical waste – Refer to carrier to send needles in treated in accordance
waste (S)
- Soft waste incinerator in a safe and sections 8.1 and 8.12 dedicated authorized with law n°01-19,
controlled manner installation Ref. [1].
- Needles • Needles and sharp medical
Offsite: Operator will use wastes stored in dedicated • Refer to incinerator ash
specialized carrier to send waste box before offsite treatment treatment and disposal
in dedicated authorized – Refer to section 8.2 options
installation

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 19 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Used filters and Inventory control and No Segregation for Offsite: Incineration onsite and Refer to incinerator ash Shall be collected and
seals (polluted management recycling or specific stabilization of hazardous treatment and disposal treated in accordance
1- Disposed by vendor for
with non treatment recover / recycling ash – Refer to sections 8.1 options with law n°01-19,
hazardous and 8.12 Ref. [1].
facilities) 2- Operator or commune will use
specialized carrier to send waste
in dedicated authorized
installation (for crushing /
incineration)
Sewage sludge Reduce by No Segregation for land- Offsite: Operator or commune • Offsite treatment (HOLD 5) Operator or commune will use
dehydration in spreading will use specialized carrier to – Refer to section 8.13 specialized carrier to send
dehydration cell send waste in dedicated waste in dedicated authorized
• OPTION : landfill onsite
authorized installation (for installation (for agricultural /
(dehydration) – Refer to
agricultural / land improvement land improvement purposes,
section 8.10
purposes, incineration) incineration) - HOLD 5

Hazardous
Incinerator ash No No No Onsite: Landfill on site • Stabilization and storage in Operator or commune will use Shall be collected and
container before offsite specialized carrier to send treated in accordance
special Offsite: Operator will use
waste (SD) specialized carrier to send waste treatment after stabilization stabilized incinerator ash in with law n°01-19,
(HOLD 6) – Refer to dedicated authorized Ref. [1].
in dedicated authorized
sections 8.8 and 8.3 installation (for landfill in
installation (for landfilling, reuse)
Algeria) - HOLD 6
• OPTION : landfill onsite in
tight cell – Refer to section
8.10
Old battery Inventory control and No Segregation for Offsite: Operator will use Stored in container before Operator will use specialized Specific containers will
management recycling specialized carrier to send waste offsite recycling carrier to send waste in be provided in the
Substitution with in dedicated authorized Refer to section 8.3 dedicated authorized vehicle maintenance
installation (for specific treatment installation (for specific areas for collection of
longer life products
in Algeria) treatment in Algeria) waste oil, used oil filters
Refer to Appendix 3 and batteries.
Used mercury- Inventory control and No Segregation for Offsite: Operator will use Stored in small container
containing management recycling specialized carrier to send waste before offsite treatment Shall be collected and
lamps in dedicated authorized treated in accordance
Substitution with Refer to section 8.2
installation (for specific with law n°01-19,
longer life products
treatment) Ref. [1], executive
decrees n°04-409, Ref.
[7], n°05-315, Ref. [8]

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 20 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Used print Inventory control and No Segregation for recover Offsite: Operator will use Offsite treatment Operator will use specialized Shall be collected and
cartridge management / recycling specialized carrier to send waste carrier to send waste in treated in accordance
Refer to section 8.2
Old small in dedicated authorized dedicated authorized with law n°01-19, Ref.
installation (for recover by installation (for recover by [1], executive decrees
battery
vendor at export) vendor at export) n°04-409, Ref. [7], n°05-
Refer to Appendix 3 315, Ref. [8], n°98-158,
Ref. [9]
Used cartridge, Inventory control and No Segregation for Offsite: • Onsite Incineration of non • Operator will use specialized Shall be collected and
seals, filters management recycling or specific Operator will use specialized metallic filters – Refer to carrier to send waste in Shall be collected and
(polluted with treatment sections 8.1 and 8.12 dedicated authorized treated in accordance
carrier to send waste in
hazardous installation (for recycling, with law n°01-19,
dedicated authorized installation • Offsite treatment of metallic
products) (for recycling, recover, crushing, recover, crushing, landfilling) Ref. [1], executive
filters – Refer to section 8.2
decrees n°04-409, Ref.
incineration, landfilling) • Refer to incinerator ash
[7], n°05-315, Ref. [8].
treatment and disposal
options
Used resin Inventory control and No Segregation for Offsite: Recycling offsite – Refer to Operator will use specialized Shall be collected and
impregnated management recycling / specific Operator will use specialized section 8.2 carrier to send waste in treated in accordance
with glass fiber treatment dedicated authorized with law n°01-19,
carrier to send waste in
cartridge installation (for recycling, Ref. [1], executive
dedicated authorized installation
(for recycling, recover, landfilling) recover, landfilling) decrees n°04-409, Ref.
[7], n°05-315, Ref. [8].
Empty container Inventory control and Reused Segregation for Offsite: Operator will use Metallic drums cleaning / Operator will use specialized Shall be collected and
/ drum / can management for recycling / specific specialized carrier to send waste Compaction (waste carrier to send waste in treated in accordance
polluted with hazardou treatment in dedicated authorized reduction) / Offsite recycling dedicated authorized with law n°01-19, Ref.
fresh chemical s waste installation (for recycling, recover installation (for recycling, [1], executive decrees
Refer to sections 8.7, 8.8
products (TEG, storage in Algeria / at export) and 8.5 recover in Algeria / at export) n°04-409, Ref. [7], n°05-
amine, 315, Ref. [8] n°98-158,
antifoam, foam Ref. [9]
concentrate,
activated
alumina,
solvent…)

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 21 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Out-of-date / Inventory control and No Segregation for Offsite: Storage in dedicated area Operator will use specialized Shall be collected and
used chemical management recycling / specific (retention for each type of carrier or vendor to send treated in accordance
1- Disposed by vendor for
products treatment recycling waste, shelter) before offsite waste in dedicated authorized with law n°01-19,
treatment installation (for incineration / Ref. [1], executive
2- Operator will use specialized treatment / recycling) decrees n°04-409, Ref.
Refer to Catalyst chemical
carrier to send waste in [7], n°05-315, Ref. [8]
storage and disposal system
dedicated authorized installation
(for incineration / treatment) facility specification, Ref.
[19]
Empty paint Inventory control and No Segregation for Offsite: Operator will use Stored in container before Operator will use specialized Shall be collected and
drums and other management recycling / specific specialized carrier to send waste offsite treatment carrier to send waste in treated in accordance
coating wastes treatment in dedicated authorized Refer to section 8.2 dedicated authorized with law n°01-19,
installation (for specific installation (for specific Ref. [1], executive
treatment) treatment) decrees n°04-409, Ref.
[7], n°05-315, Ref. [8]
Oily rags and Inventory control and No No Offsite: Operator will use Incineration onsite of oily Refer to incinerator ash Shall be collected and
other solid management specialized carrier to send waste rags – Refer to sections 8.1 treatment and disposal treated in accordance
hydrocarbon in dedicated authorized and 8.12 options with law n°01-19,
contaminated installation (for incineration, Ref. [1], executive
products recover at export) decrees n°04-409, Ref.
Cleaning [7], n°05-315, Ref. [8]
products

Oil, Hot oil, No Reused in No Process recycling Process recycling - -


Methanol (from process
Refer to:
closed drains)
• UFD – CPF Drainage
system, Ref. [12]
• UFD – CPF Hot Oil System,
Ref. [13]

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 22 of 40

Mitigation techniques Preferred GTIM option


Solid
Treatment / Disposal
waste Waste list Note
options Onsite facilities (treatment
class Reduce Reuse Recycle / Recover Disposal option
/ storage)

Waste lube oil No No Segregation for Offsite: Operator will use specialized Shall be collected and
recycling / specific carrier (with agreement) to treated in accordance
Oil change Operator will use specialized
(mobile treatment carrier (with agreement) to send Stored in container before send waste oil in dedicated with executive decrees
offsite treatment authorized installation (for n°93-161, Ref. [4] and
equipment waste oil in dedicated authorized
recycling, incineration) n°93-162, Ref. [5]
waste) installation (for recycling, Refer to section 8.3
incineration) Refer to Appendix 3
Oily waste (from
open drain)
Used frying oil Inventory control and No No Onsite: Incineration in Incineration onsite of frying Refer to incinerator ash Shall be collected and
management accommodation camp oil – Refer to sections 8.1 treatment and disposal treated in accordance
incinerator in a safe and and 8.12 options with law n°01-19,
controlled manner Ref. [1], executive
Offsite: Operator will use decrees n°04-409, Ref.
[7], n°05-315, Ref. [8]
specialized carrier to send waste
in dedicated authorized
installation (for incineration, heat
recovery)
Open drain, Improved No No Offsite: Operator will use Offsite treatment after Operator or commune will use Shall be collected and
evaporation housekeeping specialized carrier to send waste stabilization and storage in specialized carrier to send treated in accordance
basin, tank and in dedicated authorized container (HOLD 6) – Refer stabilized sludge in dedicated with law n°01-19,
vessel bottom installation (for incineration with to sections 8.9 and 8.3 authorized installation (for Ref. [1], executive
wastes proper pollution control device) landfill in Algeria) - HOLD 6 decrees n°04-409, Ref.
OPTION : landfill onsite in
Water treatment tight cell – Refer to section [7], n°05-315, Ref. [8]
packages 8.10
sludge

Table 1: Solid waste mitigation, disposal and treatment measures

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 23 of 40

8 TREATMENT, STORAGE AND DISPOSAL SYSTEM


Waste treatment and storage facilities will be located on 2 dedicated areas depending on waste
source:
• 1 close to accommodation camp with an incinerator, an area dedicated to storage and dry
waste to incinerate and a composting area,
• 1 close to CPF evaporation basins, an area dedicated to storage and CPF waste
(containers, sludge, etc…).

Waste arrangement location and facilities are showed on the figures below:

• In Accommodation Camp:
Legend

Water supply (local tank)


Non hazardous wastes
facility
Drainage system
Slope
Impermeable floor
Plane surface (no
concrete floored)
Wire mesh
Wire mesh & mosquito
net
Fences
Gate
Handling equipment

4m

Storage Sewage treatment


area
area

Incinerator
Drying 2m
25 m
area

Composting
1.5 m area in pits
1.5 m

35 m

Figure 2: Accommodation camp waste location and arrangement facilities

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 24 of 40

• In CPF:
Legend

Water supply (local tank)


Non hazardous wastes
facility
Hazardous wastes facility
Stabilized hazardous
sludge facility
Drainage system
Sump
Slope
Impermeable floor
Plane surface (no
concrete floored)
Sheltered area
Fences
Safety shower / Eye bath
unit
Gate
Handling equipment

20 m
10 m

OPTION : Stabilized
Non burnable plastic
hazardous wastes

OPTION :
Sand Sewage
stockpile sludge

Excavated material /
OPTION : Stabilized Topsoil / Concrete
hazardous wastes and rubble

Waste landfill on site

100 m

Lime
stockpile Storage area for inert waste in skip
Hazardous Shed
sludge
Hazardous
Metal Glass Spare
sludge Parking area
Hazardous Waste Plateform
sludge stabilization

Used oil
Cardboard

Plastic

Compactor
Spare

50 m Used oil 6m
Used
battery
Storage area for special wastes Compaction area

Storage area for Cleaning unit for


hazardous waste metal container
Small 10 m
ContainersBoxes Outdoor storage area

Insulation
Spare Cables Tires Pallets
material

30 m
100 m
Figure 3: CPF waste location and arrangement facilities
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 25 of 40

Except for landfill area, waste treatment and storage area shall have a lockable fence surrounding it
to prevent entry by unauthorized personnel and offsite movement of wind blown rubbish.

Car park will be located outside waste treatment and storage area fence.

Overall area will be:


• Flat and not concrete floored,
• Allowing vehicles circulation (truck, handling equipment),
• Provided with:

o Waste description panel mentioning safety signs,


o Safety shower and eye wash unit,
o Water tank for stabilization and decontamination units supply (Refer to section 8.7
and 8.9).

Specific handling and transport equipment shall be provided for sludge mixing, pit filling, waste or
ground moving, or short transport of waste (Refer to section 8.15 for details).

The waste storage design for TIMIMOUN facilities shall be in accordance with CPY specifications
(Environmental specification for onshore pipeline construction Ref. [22] and Landfill design and
operation for E&P sites [25]) and will include:
• A storage and drying area for waste to incinerate,
• A storage area for small containers,
• A storage area for hazardous waste in large container,
• A storage area for special waste in large container,
• A storage area for inert waste in skip,
• A storage area for stabilized sludge,
• An outdoor storage area (tyres, pallets, cables, insulation material).

Storage defined in this section refers to an area that will be used during the operation of the facility
as a short term storage facility prior to the final treatment and/or disposal of wastes.

Due to the isolation of TIMIMOUN project facility, waste storage and treatment facility will be sized
according to logistic constraint (one container / box / skip waiting for transportation, a second one
filled during transportation of the first one).

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 26 of 40

Some waste may be dehydrated, decontaminated, stabilized, compacted, landfill, incinerated or


composted on site in the following units:
• Dehydration : drying waste to be incinerated,
• Decontamination : metallic empty container cleaning unit,
• Stabilization : vessel bottom waste, basin cleansing sludge,
• Compaction : recyclable waste compaction unit, metallic container compaction unit,
• Landfilling : inert wastes, insulation material, non recyclable plastic, stabilized sludge (HOLD
6), sewage sludge (HOLD 5)
• Incineration : incineration of contaminated packaging / cardboard / paper, plastic packaging,
oily rags, medical soft wastes,
• Composting : Composting pits for biodegradable wastes,
In addition, evaporation basin (refer to section 8.13) and sewage treatment (refer to section 8.14)
have been mentioned for sludge collection aspects.

For TIMIMOUN facilities defined ahead, the following requirement shall be respected.

8.1 Storage and drying area for waste to incinerate


Waste dedicated to incineration will be stored and dryed in dedicated areas:
• 1 area for fresh waste arrival and one for dryed waste pending incineration,
• The 2 areas shall be designed to allow good incinerator feeding and to avoid early fire from
incinerator,
• Each area surface (L = 4 m x W = 2 m x H = 3 m) shall allow continuous incinerator feeding
for 10 hours,
• Each area shall be entirely close with:
o wire mesh to avoid bird and rodent access,
o an access gate to ensure total enclosing,
o a concrete floor to allow collection of waste effluent,
o a fresh water supply to allow cleaning,
o a device that prevents access to reptiles (low smooth wall around storage area and
smooth plate under the gate).

8.2 Storage area for small containers


Storage area for waste in small containers shall be:
• Roofed and closed,.
• Provided for 30 plastic containers open top on face, and a storage area for box.
• Provided with:
o 20 containers with stickers (safety signs),
o 10 box for inks and lamps storage.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 27 of 40

8.3 Storage area for hazardous waste in large container


Hazardous waste shall be stored:
• In containers (L =6 m x W = 2,44 m x H = 2,59 m) :
o 2 for oil storage,
o 1 for used battery storage,

o 3 for stabilized hazardous sludges (incinerator ash, vessel bottom wastes, drainage
basins sludge) - HOLD 6.
• Disposed on drip pan.

8.4 Storage area for special waste in large container


Special waste (cardboards, recyclable plastic, …) shall be stored:

• In containers (L =6 m x W = 2,44 m x H = 2,59 m) :

o 1 for cardboard,
o 1 for recyclable plastics,
o 1 for spare,
• Disposed on ground.

8.5 Storage area for inert waste in skip


Glass and metal shall be stored:

• In skip open on top:

o 1 for glass,
o 1 for metal,
o 1 for spare,
• Each skip shall have a permeable floor allow rain water circulation,

• A platform will be provided to allow waste loading on the same level,

• The opposite side will allow loading by truck.

In addition to waste metal skip, a storage area will be provided for metallic containers to be reused or
decontaminated.

8.6 Outdoor storage area


An outdoor area shall be provided for tires, pallets, cables and insulation materials storage, before
their collection by a dedicated transporter for valorization. The area shall be:
• Installed on a plane surface,
• Surrounded with fences in order to prevent the offsite movement of wind blown rubbish,
• Divided in 5 units (for tires, pallets, cables, insulation material, and one spare).
• Unit surface area (around 5 m x 10 m), equivalent to waste volume transportable by truck
and allowing a valorization.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 28 of 40

8.7 Decontamination facilities


In order to reduce waste volume quantity and allow metal recycling, a cleaning unit for metallic
container will be provided close to the metallic container compaction unit.

This unit shall be designed with the following requirement:

• Supplied with fresh water,


• Allow aspersion from the bottom through the plughole,
• Watertight,
• Provided with a filter for solid material collection,
• Connected to non hazardous open drain OD2 (after filtration).

8.8 Compaction facilities


Metallic container compaction unit:

This equipment shall be located close to the container cleaning unit and shall reduce container
volume of at least 60%.

Recyclable waste compaction unit:

This equipment shall be designed to allow compaction and tie recyclable plastic or carboard in bale
of less than 50 kg (in order to allow their transport by 2 persons).

2 sheltered storage (one for recycling plastic and one for cardboard) shall be provided for waiting
non compacted material.

8.9 Waste stabilization facilities


In order to be stored or transported in safe conditions, incinerator ash, hazardous sludge (i.e. from
evaporation basin, observation basin, API basin, …) and bottom wastes from vessels (i.e. slug
catchers, LP separator, hazardous liquid drums / tank, …) shall be stabilized (mix with lime) in a
dedicated facility with the following requirement :
• Floor of the facility shall be constructed with an impermeable material that is resistant to
waste hazardous substances and lime action,
• Facility (including lime storage and waste stabilization area) shall be sheltered,
• Shall be designed for 2 m3 sludge with a slope oriented to the back of facility,
• A drainage valve shall be provided at the lowest point for liquid collection in dedicated
containers,
• Design of unit (i.e. unit front) shall allow waste handling with dedicated equipment (truck,
waste and lime mixing),
• Lime storage area shall be enough for 2 pallets that should be transported easily to the
stabilization area,

• A fresh water supply shall be available for waste humidification purpose.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 29 of 40

8.10 Waste landfill on site


According to the law n° 01-19, Ref. [1], authorization of inert waste landfill, shall be initiated by
commune, and authorized by the president of commune popular assembly.

Waste landfill required for inert waste such as insulation material, concrete and rubble, shall be
provided on site and designed in accordance with GS-EP-ENV-421, Ref. [25].

The landfill will be subdivided into several cells (cell dimension: L = 20 m x W = 10 m x H = 3 m) to


facilitate waste management:
• 3 cells will be dedicated to inert waste:
o Excavated material / Topsoil / Concrete and rubble,
o Non burnable plastic,
o OPTION : Sewage sludge (HOLD 5).
• OPTION : 2 cells will be dedicated to stabilized hazardous waste (HOLD 6).

An access way shall be provided upstream side of landfill area.

Storage capacity must be designed for an operating life of no longer than 10 years. As project length
is 25 years, 2 extensions shall be planned.

Waste landfill for inert waste (HOLD 5)

Due to its location in a non sensitive area (poor ecosystem, unconfined aquifer not close to the
surface (depth > 3 m), no groundwater use by local population, and no population near the site
area), and an arid climate (Rain water precipitation less than 200 mm/year), requirement for inert
waste landfill will be limited (i.e. no requirement of lining / drainage system).

OPTION: Waste landfill for hazardous waste (HOLD 6)

Stabilized hazardous waste cells shall be designed with:


• Compacted clay at bottom,
• Geotextile membrane,
• Leachate collection drain system for each cell.

8.11 Organic waste composting on site


A composting area will be provided on site near accommodation camp, and close to the incinerator
for treatment of food and green waste only. This will enable the reused of “composted material” as
fertilizer within TIMIMOUN facilities.

Composting area will be designed with the following requirement:


• 20 pits located side by side to allow an easy access with a dedicated vehicle (5 pits per year
cleaned after 4 years of composting)
• Dimensions of each pit : 1.5 m x 1.5 m x 1.5 m
• 5 pits will be equipped with easily movable structures movable to the closest pit on the same
row. Such structure will prevent access to rodents / birds (wire netting) and flies (mosquito
nets), but allow the solar radiation and air circulation. The area will be equipped with a
device that prevents access to reptiles (low wall).

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 30 of 40

8.12 Waste incineration on site


According to the law n° 01-19, Ref. [1], authorization of non hazardous waste incineration, shall be
initiated by commune, and authorized by the wali territorially conversant with MA waste.

A waste incinerator will be provided on site near accommodation camp for heat treatment of mixed
non hazardous burnable waste, with the following minimum requirement:
• Allow complete combustion of the following wastes: contaminated paper and cardboard,
plastic packaging, textile, Wood treated crumb, Oily rags, Used filters (non metallic), Soft
medical wastes, Green/food wastes and Used frying oil,
• Allow high availability rate and easy maintenance (list of wear part to provide),
• A specific air supply system will be provided to allow optimal hanging waste and gas
combustion,
• Combustion will be assist with a fuel supply,
• Allow smoke temperature higher than 600°C,
• Fixed Emission Monitoring System (EMS) to follow the levels of pollutants and to prevent
adverse impacts,
• Disposal requirements for ash without combustion deterioration.

Incinerator capacity will be designed for minimum treatment capacity to allow continuous supplying
during long periods. Waste quantities to be considered are summarized in the table below (for further
details, refer to Effluent List, Ref. [20]):
Solid waste quantity ( kg / day )
Accommodation camp CPF TOTAL
Contaminated paper and 10 3.8
cardboard (20% of cardboard and (20% of cardboard and 13.8
paper production) paper production)
Non hazardous mixed 1
waste (plastic packaging, 36 37
textile, ...) (20% of plastic production)

Wood treated crumb 0.8 1.3


(10% of wood pallets (10% of wood pallets 2.1
production) production)
Oily rags - 5 5
Used filters - 0.5 0.5
Soft medical wastes 0.5 0.2 0.7
Food waste
58 22 80
Used frying oil
Green wastes 6.6 - 6.6
TOTAL 111.9 33.8 145.7 (HOLD 2)

Table 2: Incinerator Capacity Evaluation

In a conservative approach, Incinerator will be designed for 150 kg / day (HOLD 2).
A crusher shall be provided for wood and plastic piece, in order to allow optimum incinerator
performance.
Ash produced by the incinerator may be stored in landfill under on meter soil / inert waste for fly
prevention.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 31 of 40

8.13 Evaporation basin


In order to avoid potential pollution due to effluent release to environment, 2 Evaporation basins will
be provided to collect effluent from:

• Reverse osmosis package


• Produced Water Treatment Package
• Drainage system (observation basin)

Each evaporation basin will be designed:


• Inlet flowrate : based on the maximum flow from produced water treatment and continuous
flow from reverse osmosis
• To avoid overflow, the following hypothesis has been considered:
o > 100% evaporation of inlet nominal flow (in the worst evaporation conditions, i.e. in
march at a reference temperature of 20°C and a wind velocity of 5m/s)
o Water temperature is equal to air temperature
o Capacity shall allow 3 months of production without evaporation (during winter when
average ambient temperature is less than 20°C, Ref. [15])
o 20% margin on calculated evaporation basin volume
• To avoid infiltration : watertight
• Dimensions : square area (75 x 75m) with a depth of 1.5m
• Orientation : basin shall be oriented downwind and effluent feeding shall be upwind
• With an easy access to allow good collect and transport of evaporation basin sludge.

For further details, refer to “PID – CPF Evaporation Basin”, Ref. [14].

Evaporation basin sludge shall be stabilized (refer to sections 8.9 and 8.3) before transport by
specialized carrier and authorized offsite treatment (HOLD 6).

8.14 Sewage treatment


Two sewage treatment facilities designed to treat 250L/pers/day will be provided in Timimoun
facilities (one in CPF and one close to Accommodation Camp).

For further details refer to “specification – Sewers & Drainage”, Ref. [16], and “Specification – CPF
Sewage Package”, Ref. [17], and Effluent list, Ref. [20].

Sewage sludge will be collected from each sewage treatment facility by specialized carrier and sent
in dedicated authorized installation for agricultural / land improvement purposes (HOLD 5).

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 32 of 40

8.15 Handling equipment


The following equipment shall be provided:

• Handling equipment equipped for moving sludge or soil,

• Adaptable handling vehicle (truck type or towing) for transport of containers (minimum
capacity of 4 containers),

• 2 towing 1 m3 tank for use with TIMIMOUN vehicles including fire man vehicles,

• 2 electric vacuum pumps for waters or effluent (i.e. sewage, oily water, treated water),

• Mobile containers for oil collect.

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 33 of 40

Appendix 1: Information to provide for movement document filling (Ref. [9])

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 34 of 40

Appendix 2: Hazardous waste declaration (Ref. [8])

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 35 of 40

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 36 of 40

Appendix 3: List and location of Algerian specialized company for wastes

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 37 of 40

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 38 of 40

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 39 of 40

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
GROUPEMENT TIMIMOUN Document Number:
Projet Surface 01SRF10-TIM-SP-XE-131002
SOLID WASTE STORAGE AND DISPOSAL SYSTEM Class: 1
FACILITY SPECIFICATION Revision: 03 Status: AFD
Document Type: SP System / Subsystem: NA Discipline: XE Rev. Date: 03-May-11
CONTRACTOR Doc. Number: - Page 40 of 40

This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.