Types SSVT and SSMV oil-filled station

service voltage transformers


Auxiliary power from high voltage
transmission lines
ABB has been producing instrument transformers for
more than 60 years. Thousands of our products per form
vital functions in electric power networks around the
world – day after day, all year round. Their main applications
include revenue metering, control, indication and relay
protection.

All instr ument transformers supplied by ABB are tailormade


to meet the needs of our customers. An instrument
transformer must be capable of withstanding very high
stresses in all climatic conditions. We design and
manufacture our products for a service life of at least 30
years. Actually, most last even longer.

ABB’s family of Station Service Voltage Transformer (SSVT)


products combine the characteristics of voltage transformers
with the power r ating capability of dis tribution transformers.
This results in fully-insulated products, up to 362 kV, with
power performance up to 333 kVA.

Station Service Voltage Transformer (SSVT)


The SSVT is a line-to-ground connected single-phase
transformer that can be used either as an individual unit for
supplying single-phase loads, or in a three-phase bank to
support larger kVA three-phase loads. The high voltage
winding with graded insulation is applied line-to-ground on
grounded WYE systems, and is coupled to secondar y
windings through silicon steel cores.

This unique combination allows for a reliable, direct Standards - Electrical


connection to the high voltage transmission line in a The SSVT transformers can meet the applicable sections
convenient, economical installation using the pedestal (latest version) of the following standards respectively:
mounted transformer. The power transformation is taken
directly from the high voltage primary to the low voltage – IEEE C57.13 regarding Instrument transformers
output that supplies 125/250 VAC power, 277 VAC, 480 VAC, – IEEE C57.12.00 regarding Distribution/voltage transformers
or any output up to 600 VAC to supply lighting loads, pump – CAN/CSA C60044-2 regarding Inductive voltage
and motor loads, instrumentation and rural electrification transformer s
power needs. – IEC 60044 regarding Instrument, voltage and current
transformer s
Station Service Voltage Transformer for Medium Voltage – IEC 60076 regarding Distribution/power transformers
(SSMV)
This variation of the SSVT transforms power directly from the Standards - Quality
high voltage transmission line connetion and steps it down to – ISO 9001: 2000
a medium voltage output capable of transferring a reasonable
amount of power over immediate d istances (up to 8-10 kM). Standards - Environmental
This allows loads that are removed from the transmission right – ISO 13001: 2004
of way, to be powered with a cost effective transformer for
remote/rural locations The design consists of the same Standards - Occupational Health & Safety
construction as the original SSVT, but with medium voltage – OHSAS 18001
bushings in the low side compartment to provide clearance for the
increased voltage level.

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 3
Applications

Switching station application Remote cell tower site application


Many utilities maintain switching stations for interconnection Given the rapid expansion of the cellular telephone industry,
of transmission lines. Frequently, these substations do not it is vital that all possible points be reached with clear
have low voltage control power available from equipment communication signals. Given the limited distances that
inside the station, rather they rely on distribution feeders from cellular signals can be transmitted, it is often necessary to site
outside the substation (which may be owned by another utility cell towers in remote locations to enable repetition of phone
company). SSVT’s are mounted onto a pedestal, with the transmissions. When a selected cell tower site lacks nearby
primary tied to the incoming tr ansmission line with the output electrical secondary feeders, locating the cell tower adjacent
secondary control wiring connected to the station power to the high voltage transmission line is now an economical
panel. option. A tap can be taken from the transmission line to an
SSVT placed in a fenced-in area (a miniature substation) to
Benefits: energize the cell tower. Where permitted, the cell transceiver
- Eliminates the need for obtaining long-term power from an can be located directly on the tr ansmission tower.
outside supplier
- Reliable power for the substation with connection directly to Benefits:
the transmission line - Cost savings compared to installing a dedicated distribution
- Control power source self-contained within substation feeder over long distances (Evaluation shows break-even
boundary point to be approximately ½ to 1 mile of distribution line.)
- User advantage of economical power purchases at
Rural electrification application transmission level (with SSVT ownership)
In developing countries where transmission systems are - Avoid costs of tower permits when installing on existing
in place but a wide-spread distribution infrastructure is towers
lacking, SSVT’s can be used as a compact transformer to
greatly reduce the electrification costs for small villages or
compounds. SSVT’s can either be used with its low voltage
output to directly supply needed power for in-close loads near
the transmission right of way, or simply step up the SSVT low
voltage output through distribution transformers for a local
distr ibution network.

Small substations can be sited specific to the load


requirements without a large distribution network. Tapping
the high voltage transmission line and connecting SSVT’s with
a small footpr int substation will provide affordable, readily-
available electricity to millions of people presently without
power.

Benefits:
- Cost of electrification can be greatly reduced for developing
countries with limited size load requirements and small
substations
- Output can be tailored to each specific voltage and load
requirement using the flexible SSVT capability
- Modular substations using the SSVT as the main
transformer can be pre-packed, shipped in containers, and
quickly erected on site to reduce time and costs

4 Types SSVT and SSMV oil-filled statio n ser vice vo ltage transformers | ABB product bu lletin
Applications (cont‘d)

Substation aux iliary power application without using power Transmission switch automation application
transformer tertiary To improve the service of a substation which feeds a 69 kV
In normal tr ansmission substation installations, power radial tap line, switches can be automated to sectionalize
transformers are typically equipped with tertiary windings the line in the event of a fault. A distribution feeder may not
in order to supply distribution transformers with 15 or 25 always be available in order to power the SCADA RTU, radio,
kV primar y voltages for substation load. The distribution and motor-operated switches, so by supplying a 69 kV SSVT
transformers supply control power for the substation location. with 10 kVA power rating and a measuring winding, utilities
In substations where the power transformers do not have can achieve both control power and tap voltage indication for
tertiary windings, control power must be supplied by alternate monitoring circuits. If necessary, additional standard voltage
means. SSVT’s can be mounted on the bus, as both a bus transformers can be supplied on the loop line to monitor
potential transformer with measuring winding, and a control voltages on both sides of the switches.
power source.
Benefits:
Benefits: - Savings from reduced space and installation times on
- Control power is supplied from within the substation directly compact switch structure arrangement
from the transmission bus, improving reliability - Self-contained power from transmission line, reliability
- Power transformer tertiary can remain buried, which assured by transmission connection
prevents connection abuse and improves power quality - Could be used as part of a measuring circuit if primary
control measuring where needed
- Power from transmission line is less susceptible to weather-
related outages
- Dual functions incorporated, with SSVT’s acting as a power
source and voltage control winding

Transmission line lighting application


Transmission towers which span a body of water require
overhead lighting be supplied for safety and security
purposes. ABB has designed a 46 kV, 5 kVA power rating
transformer with hanger brackets for pole-mounting, and
fusing in the control cabinet for mounting atop a transmission
pole adjacent to the transmission line. This arrangement
eliminated the need to maintain control wiring at near ground
level from distribution tr ansformers high up the transmission
tower. SSVT’s safely provide lighting power directly on the
tower.

Benefits:
- Small footprint allowing restricted installation in a compact
space near transmission line
- Short distance control wiring to reduce losses
- Self-contained fusing and mounting format for quicker
installation and reduced costs

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 5
Features and benefits

The SSVT and SSMV feature rugged transformer designs


incorporating high creepage insulators and high over-voltage
capability with impedance protection to limit fault currents.

Features and benefits of the transformer designs include:

Incorporated inductive voltage transformer insulation and


magnetic performance.
- Readily accommodates high momentary and maximum
continuous operation voltage relative to power transformers.
- Fully-rated impulse levels provide improved withstand to HV
transients.

Low profile, compact overall size and weight relative to power


transformers.
- Units do not require expensive concrete pad, simply a
support stand and small foundation.
- Minimal substation footprint.

Low cost alter native to distribution feeder construction.


- Self-contained power source within substation fence, not
subject to weather related outages.
- Simplest power source for reliable station p ower.

Power ratings up to 333 kVA per phase (1 MVA bank),


available with isolated measuring winding option.
- Ample single-phase power ratings for any station power
need, as well as for limited power applications.
- Line voltage information and control power needs from one
source. High seismic withstand capability.
- Most designs are rated for high seismic withstand per IEEE
Reliable transmission voltage access for substation power. 693 via dynamic analysis.
- Very reliable control power access available directly from - Mechanically robust to withstand transportation and
the transmission lines. handling.
- Eliminates need to bring in outside distribution voltage.
- Not typically subject to line outages. Short lead-time Station Ser vice Voltage Transformer.
- Produced using lean manufacturing techniques to provide
Special designs easily accommodate for different low voltages short lead times and to prevent project delays.
and outputs.
- Quick transformer availability with customer-specified
design to meet site needs.

Isolated windings for flexibility in making various required


secondary connections.
- Access to the full kVA regardless of voltage is needed.
- Standard design can be used for both single phase
installation, as well as three-phase needs.

6 Types SSVT and SSMV oil-filled statio n ser vice vo ltage transformers | ABB product bu lletin
Product details

4 The ABB Station Service Voltage Transformer (SSVT)


1
incorporates an integral inner condenser bushing connected
2
to a layer wound coil (except 50 and 100 kVA 230 kV unit
which is a disk wound design).
3

5 6 1 NEMA 4-hole stainless steel 4”x4” (100 mm x100 mm)


pad primary terminal
2 Gas cushion (dry air or dry nitrogen cushion)
3 Pressure relief valve to prevent pressure buildup
4 Shrader gas valve for cushion application / fillcap
5 Magnetic oil level gauge
6 Powder-coated polyester paint on mild steel dome
7 7 Glazed porcelain with major-minor shed patter n for high
creepage distance
8 Condenser graded inner bushing
8 9 Stainless and bronze corrosion-resistant hardware
10 Powder-coated polyester paint on mild steel cover and
tank
11 High contrast aluminum schematic and nameplates (not
shown)
9 12 Power conduit box with 12” x 20” (305 mm x 508 mm)
removable bottom plate
13 10
13 Aluminum 2-hole lugs for standard low voltage terminals
17 14 Measuring conduit box (if measuring winding is specified)
with three (3) 1-1/2” (38 mm) NPT openings (not shown)
15 Measuring low voltage ¼”-20 (6 mm) copper alloy
14
15 terminals (not shown)
16 High visibility ratio and kVA stencils
17 5 kV rated isolated H0 bushing connected to dedicated
tank ground
19
18 ½” (13 mm) bronze drain ball valve with stainless steel
pipe plug
19 Two (2) NEMA 2-hole stainless steel ground pads
12 20 20 Four (4) 2” (51 mm) and four (4) ¾” (19 mm) lifting holes

Optional Accessories
16 - One (1) or two (2) measur ing windings
18
- Special low voltage lugs or connectors (NEMA 4-hole, stud
or cable connectors, etc.)
- Special low voltage output ratings (277 VAC, 347 VAC,
480 VAC, any voltage up to 600 VAC)
- Special medium voltage output ratings (voltates up to 15 kV
class output)
- Extra strike and creep insulators
- Polymer insulators in lieu of porcelain designs
- Cor rosion-resistant stainless steel housings
- Secondary terminal box heaters
- Sudden pressure relay
- CTs to power secondary monitoring
- Oil sampling valve

For needs or features not listed, contact the factory.

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 7
SSVT technical data

SSVT product rating matrix


10 25 50 100/125 160/167 200 250 315/333
Type System MSV kV BIL Style kVA(1) kVA(1) kVA(1) kVA(1) kVA(1) kVA (1) kVA(1) kVA(1)

Power windings
SSVT-250 48 kV 250 kV Measuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-350 72 kV 350 kV Measuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-550 123 kV 550 kV Measuring windings (2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-650 145 kV 650 kV Measuring windings (2) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-650 170 kV 650 kV Measuring windings (2) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-750 170 kV 750 kV Measuring windings (2) Cl 0.2(3) Cl 0.2(3)

Power windings
SSVT-900 245 kV 900 kV Measuring windings (2) Cl 0.5(4)

Power windings
SSVT-1050 245 kV 1050 kV Measuring windings (2) Cl 0.5(4)

Power windings
SSVT-1300 362 kV 1300 kV

1. k VA ratings shown are ba sed on a 30° C ave rage a mbie nt condition a nd a 65° C ris e. 4. Tw o m ea suring w indings are standa rd w ith a cc urac y c lass 0. 5% at 400 VA or 0.3%
2. M easuring windings, w here available, may be quantity of one or tw o w indings, ex cept at 400 VA ( ZZ).
as noted. 5. O ne or two mea suring windings are a va ila ble w ith ac curacy cla ss 0.5% a t 400 VA or
3. A c curac y of 0.2% at 400 VA or 0.15% a t 400 VA (ZZ) . 0.3% a t 400 VA (ZZ) .

Product winding options


The standard Station Ser vice Voltage Transformer (power only) These extra windings supply r ated accuracy and burden
has two (2) isolated secondary power windings that can be support only when the power winding is loaded at 10% or
either series or parallel connected for different voltage output. less of its power rating, otherwise these measuring windings
Also, one (1) or two (2) additional tapped measuring windings will become less accurate as the power winding is loaded
can be supplied for measurement and control application above 10% of r ating.
with some isolation from the power coils to minimize voltage
fluctuations.

Power winding options Measurement winding options

High vol tage windi ng High vol tage windi ng


Ô·²»

Ô·²»

ײ¬»®²¿´ ­¸·»´¼­ ײ¬»®²¿´ ­¸·»´¼­

Low vo ltage wind ings Low vo ltage wind ings

Series / Parallel Measuring Sing le

б©»® ï б©»® î íðß


or or
Y or Delta Measuring Dual

б©»®

or
Auxiliary
Series / Parallel

8 Types SSVT and SSMV oil-filled statio n ser vice vo ltage transformers | ABB product bu lletin
Power conduit box Measuring conduit box

Power co nduit box intern al view Measuring condu it box internal view
(7 50 kV BIL r ating and lo wer) (7 50 kV BIL r ating and lo wer)

Conduit bo x inter nal view


(9 00 kV BIL r ating and h igher)

Typical nameplate layout ßÞÞ ÕË ØÔÓßÒ


The supplied nameplates are laser-etched aluminum ÌÇÐÛ ÍÍÊÌóêë ðóïðð ÊÑÔÌßÙ Û ÌÎßÒ ÍÚÑÎÓÛÎ

and contain product technical details, as well as winding ÝÎÇÍÌßÔ ÍÐÎ×ÒÙÍ


Ó×ÍÍ×ÍÍ×ÐÐ×
ÝßÌßÔÑÙ ÒÑò
schematics. A power winding nameplate is affixed ÍÛÎ×ßÔ
ÒËÓÞÛÎæ ÐñÒ æ
ÔççÒê ëêïðð Ý
îîë éççíð ðï
near the power conduit box and, where applicable, a ÒÍÊ æ
ïíè ÕÊ
ÐÎ ×ÓßÎÇ
ÊÑ ÔÌÍ
ÎßÌÛÜ
ÍÛÝ ÊÑ ÔÌÍ
ÝÑ ÒÒÛÝÌ×Ñ Ò ÎßÌ×Ñ ÌØÛÎ ÓßÔ
ÎßÌ×ÒÙ
û
×ÓÐ ÛÜßÒÝÛ
Ñ×Ô Ê ÑÔæ
èë ÙßÔ
separate nameplate for measuring windings is provided Þ×Ôæ
êëð ÕÊ èðë ðð
ïîí ÈïóÈî ×× ÈíóÈì êëê ïðð ÕÊß çòð û ÌÑÌò É Ìò
ïîí ñîìê ÈïóÈì íîè ïðð ÕÊß çòð û íðé ë ÔÞ
near the measuring terminals. The example shown is for êð ØÆ êëpÝ Î ×ÍÛ ÓßÈò ÌÑ ÌßÔ ï ðð Õ Êß

illustration purposes; actual nameplates will reflect the Øï Øð


ïîí Ê ïîíñîìê Ê

specification for each site application. ÐßÎßÔ ÔÛÔ ÝÑÒÒÛÝÌ ×ÑÒ


ÍÌßÌ×Ý
ÍØ×Û ÔÜ
ÍÛ Î×Û Í ÝÑ ÒÒÛÝÌ×Ñ Ò

Èï Èí Èï Èí
ÌßÒÕ
Èî Èì Èî Èì
Èï Èî Èí Èì
ÍËÞÌÎßÝÌ×ÊÛ ÐÑÔßÎ×ÌÇ
ÍÛÛ ÕËØÔÓßÒ ×ÒÍÌÎËÝÌ×ÑÒ ÓßÒËßÔ ÞÛÚÑ ÎÛ Û ÒÛÎÙ× Æ×Ò Ùò
ØÛÎÓÛ Ì×ÝßÔÔÇ ÍÛßÔÛÜæ Ü Ñ ÒÑÌ Ì×ÔÌ ÑÊ ÛÎ î ëp ÚÎÑ Ó ÊÛÎ Ì×ÝßÔò
Ú×ÔÔÛÜ É×Ì Ø ÒÑÒóÐ ÝÞ Ó×Ò ÛÎßÔ Ñ×Ô ÉØÛÒ ÓßÒËÚßÝÌËÎÛÜ øÔÛÍÍ Ì ØßÒ ï Ð ÐÓ÷
ÇÛßÎ ÝÑ ÑÔ×Ò ÙóÑÒßÒ ÓßÜÛ ×Ò ËòÍò ßò

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 9
Dielectric ratings
In general, the SSVT (low voltage output only) is produced The unit can be configured for IEC dielectric ratings as well as
according to IEEE C57.13 relative to the dielectric ratings and for 50 her tz systems.
for 60 her tz performance.

The information shown below reflects the IEEE specification.

Rating Product voltage levels


SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300

NSV 46 kV 69 kV 115 kV 138 kV 161 kV 161 kV 230 kV 230 kV 345 kV

MSV 48 kV 72 kV 123 kV 145 kV 170 kV 170 kV 245 kV 245 kV 362 kV

BIL 250 kV 350 kV 550 kV 650 kV 650 kV 750 kV 900 kV 1050 kV 1300 kV

MCOV (power only) 115% 115% 115% 115% 115% 115% 110% 115% 115%

MCOV (power + mea sure) 140% 140% 140% 140% 140% 140% 106% N/A N/A

MMOV (power only) 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min

MMOV (power + mea sure) 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 120% - 1 min N/A N/A

PF Withstand 460 kV - 1 min 575 kV - 1 min


- Dry 95 kV - 1 min 140 kV - 1 min 230 kV - 1 min 275 kV - 1 min 275 kV - 1 min 325 kV - 1 min 395 kV - 1 min 445 kV - 10 575 kV - 10
- Wet 95 kV - 10 sec 140 kV - 10 sec 230 kV - 10 sec 275 kV - 10 sec 275 kV - 10 sec 315 kV - 10 sec 350 kV - 10 sec sec sec

PD f ree @ 37 kV 54 kV 93 kV 109 kV 124 kV 124 kV 186 kV 186 kV 300 kV

H0 bushing 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV

H0 BIL 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV

**E xtra c ree p a nd s trike insulators a va ila ble , c onta ct f ac tory.


Creep** in. (mm) 37 (940) 52 (1321) 130 (3302) 147 (3734) 147 (3734) 199 (5055) 267 (6782) 351 (8915) 391 (9931)

Strike** in. (mm) 17 (432) 23 (584) 42 (1067) 49 (1245) 49 (1245) 54 (1372) 72 (1829) 79 (2007) 98 (2489)

10 Types SSVT and SSMV o il-filled station service voltage tran sformer s | ABB product bu lletin
Dimensions and weights
SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300

MSV / BIL kV 48 / 250 72 / 350 123 / 550 145 / 650 170 / 650 170 / 750 245 / 900 245 / 1050 345 / 1300

A - Height in. (mm) 66.39 (1686) 75.00 (1905) 94.05 (2389) 101.73 (2584) 101.73 (2584) 124.29 (3157) 175.20 (4450) 177.56 (4510) 207.48 (5270)

B - Width in. (mm) 30.50 (775) 30.50 (775) 30.50 (775) 31.00 (787) 31.00 (787) 34.25 (870) 70.08 (1780) 70.08 (1780) 70.08 (1780)

C - De pth in. (mm) 44.82 (1138) 44.82 (1138) 44.82 (1138) 48.97 (1244) 48.97 (1244) 53.96 (1371) 68.30 (1735) 66.00 (1676) 75.00 (1905)

D - Highest Gnd Part


in. (mm) 34.37 (873) 34.37 (873) 34.37 (873) 35.19 (894) 35.19 (894) 39.81 (1011) 61.42 (1560) 66.07 (1678) 69.53 (1766)

E - Insulator Le ngth
13.88 (353) 22.21 (582) 40.65 (1032) 47.64 (1210) 47.64 (1210) 58.38 (1483) 75.79 (1925) 74.80 (1900) 98.80 (2510)
in. (mm)

F - Lowest live part


52.51 (1334) 62.25 (1581) 81.82 (2078) 89.50 (2273) 89.50 (2273) 89.70 (2278) 137.21 (3485) 140.87 (3578) 168.30 (4275)
in. (mm)

G - Conduit box
11.50 (292) 11.50 (292) 11.50 (292) 12.25 (311) 12.25 (311) 16.63 (422) 31.10 (790) 31.10 (790) 27.96 (710)
height in. (mm)

H - Mtg Holes front-


ba ck in. (mm) 30.38 (772) 30.38 (772) 30.38 (772) 34.75 (883) 34.75 (883) 40.88 (1038) 48.00 (1219) 48.00 (1219) 48.00 (1219)

I - Mtg Hole s left- 57.00 (1448) 57.00 (1448) 57.00 (1448)


right in. (mm) 28.75 (730)) 28.75 (730) 28.75 (730) 28.87 (733) 28.87 (733) 32.25 (819)
66.00 (1676) 66.00 (1676) 66.00 (1676)

Shipping Volume 60x46x75 60x46x83 60x46x102 60x46x102 60x46x102 60x46x102 66x70x142 66x70x145 196.5x80x125
(l x w x h) in. ( mm) (1524x1168x1905) (1524x1168x2108) (1524x1168x2591) (1524x1168x2591) (1524x1168x2591) (1524x1168x2591) (1676x1778x3595) (1676x1778x3683) (4991x2032x3175)

Unit Weight lb. (kg) 2255 (1009) 2470 (1120) 2550 (1156) 2960 (1343) 2960 (1343) 3500 (1588) 9500 (4318) 9910 (4505) 11084 ( 5038)

Shipping Weight
2325 (1055) 2570 (1166) 2650 (1202) 3060 (1388) 3060 (1388) 3600 (1633) 11480 ( 5281) 11500 ( 5227) 14291 ( 6496)
lb. (k g)

Oil Volume gal. (liter) 69 (261) 75 (284) 80 (303) 105 (397) 105 (397) 120 (453) 541 (2048) 550 (2082) 550 (2082)

Informa tion s how n herein is for informa tiona l purpos es a nd is subje ct to cha nge w ithout notice .
For c onstruction purp os es , conta c t fa ctory f or updated informa tion.

íòðð
Ò
Øï
øéê÷
×Ô ×Ë
ÏÜ
ÔÛ Ê
Û Ô
ÔÑ

ïòéë
øìì÷

ïòéë òêî ¨ ïòîë


íòëð
ðòëê øìì÷ øïëòç ¨ íïòè÷
ß
øèç÷ Ø
øïì÷ ÓÑËÒÌ×ÒÙ ÓÌÙ
ÑÊÛ ÎßÔÔ øì÷ ØÑÔÛÍ ÍÔÑÌ ØÑÔÛÍ
ØÛ×Ù ØÌ
øì÷ ÐÔÝÍ Ú®±²¬
ëð ³³ ¸±´» ­°¿½·²¹ ¿ª¿·´¿¾´» ¬± Þ¿½µ
ÒÛÓß ìóر´» Ý
Û Ú ÑÊÛÎßÔÔ
×ÒÍ ËÔßÌÑÎ
Ю·³¿®§ Ì»®³·²¿´ ÜÛÐÌØ
ÔÑÉÛÍÌ êòðð ¨ îðòðð
ÍËÎÚßÝÛ Ô×ÊÛ ÐßÎÌ
ÕÒÑÝÕÑËÌ
ØÛ×Ù ØÌ ÚÑÎ ÝÑÒÜË×Ì
ÛÒÌÎÇ ú
îòðð
øëï÷ ïñîóïí ÒÝ éòîë ¨ îïòéë
øî÷ ØÑÔÛÍ ÎÛÓÑÊßÞÔÛ
ÐÔßÌÛ ßÔ
×
øÒÑÌ ÍØÑÉÒ÷ ÓÌÙ ØÑÔÛÍ
Ü íòëð ïòéë ÒÑÒóÜÎ×ÔÔÛÜ Ô»º¬ ¬± η¹¸¬
Ø×Ù ØÛÍÌ øèç÷ øìì÷
ÙÎÑË ÒÜ Ê×ÛÉ ÚÎÑÓ ÞÑÌÌÑÓ
Ø ·¹ ¸ ª± ´¬ ¿
¹ » ò
ݲ ¿ ½ ¿ ­« »
­ ª» ®» » ²
· «¶ ô§® ¼ » ¸
¬¿
± ®¼ ¿ ³ ¿
¹ » ¬® ¿
² ­º ±
® ³»
® ò

ÐßÎÌ
ØÛ×Ù ØÌ ÓÑËÒÌ×ÒÙ Ü×ßÙÎßÓ
ÒÛÓß îóر´»
Ù Ù®±«²¼ п¼
ÈÈÈñÈÈÈæï
ÝÑÒÜË× Ì ÈÈ ÕÊ ß
ÞÑÈ
ØÛ×Ù ØÌ
×Ú Ô Ü

Óß
É Ì× Ò
Ôø ÍÛ Ø
Ë

ï
î
ëð
Ú Ý Ë
ÌÍ ß Ò Ð

í
êï
Û ß ÌØ Û
×Ì Ó
Û ÑÚ
Òß Ì ÛÎ
Ø Ñ óÒ Ý
ï Ó
Ð Þ
Ð ÷
Ü ×ÔÛ ÛÝ ÌÎ ×Ý ÚÔ Ë ×Ü Fo r SSVTs with 90 0 kV B IL and higher ratin gs,
a sin gle conduit bo x co ntains both the power
windings as well as the mea sur in g windings
Þ
(w hen su pplied) an d has a fixed 3 ” con duit open-
É×ÜÌØ
ing for power o utlet.

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 11
SSMV technical data

SSMV product rating matrix


100 125 167 200
Type System MSV kV BIL Style Frequency kVA(1) kVA(1) kVA(1) kVA(1)

60 Hz
SSVT-350 72 kV 350 kV Power windings 50 Hz

60 Hz
SSVT-550 123 kV 550 kV Power windings 50 Hz

60 Hz
SSVT-650 145 kV 650 kV Power windings 50 Hz

60 Hz
SSVT-650 170 kV 650 kV Power windings 50 Hz

1. k VA ratings shown are ba sed on a 30° C ave rage a mbie nt condition a nd a 65° C ris e.

SSVT Medium Voltage ( SSMV) winding r ating design SSMV (secondary) dielectric ratings
This design has been developed to aid siting the product
Product voltage leve ls
anywhere there is a transmission line to allow connection.
The design will facilitate power tap off of transmission lines for Rating SSVT-350 SSVT-550 SSVT-650

mining sites, rural electrification projects or remote loads of Frequency 60 Hz 60 Hz 60 Hz


any description.
Thermal rating range 100-200 100-200 100-200

A distribution class surge arrester is supplied on the side of the Standa rd the rmal ratings
tank wall for direct protection of the low side winding. Take off NS V 69 kV 115 kV 138 kV
options can be overhead directly from the medium voltage
MS V 72 kV 123 kV 138 kV
bushings (with protective box cover removed) or sub-surface via
BIL 350 kV 550 kV 650 kV
conduit entrance at the bottom of the box.
MCOV powe r only 115% 115% 115%

Unit provided for medium voltage power output cannot be MMOV power only 125%, 1 min 125%, 1 min 125%, 1 min

Power f requenc y withstand

Dry 140 kV, 1 min 230 kV, 1 min 275 kV, 1 min

Wet 140 kV, 10 sec 230 kV, 10 sec 275 kV, 10 sec

PD free upto 54 kV 93 kV 109 kV

Product winding schematic and protection arrangement H0 bushing 25 kV 25 kV 25 kV

H0 bushing BIL 125 kV 125 kV 125 kV

Sec ondary voltage 7200 V 7200 V 7200 V

X1 - X2 bushing class 25 kV 25 kV 25 kV

X1 - X2 bushing BIL 125 kV 125 kV 125 kV

HV cree p in. (mm) 52 (1321) 130 (3302) 147 (3734)

HV strike in. (mm) 23 (584) 40.9 (1040) 48 (1219)

Sec ondary arre ste r ra ting

Freque nc y 50 Hz 50 Hz 50 Hz

Thermal rating range 100-200 100-200 100-200

Standa rd thermal ratings 25 kVA, 50 kVA , 100 kVA, 125 k VA, 167 kVA

Sec ondary voltage 6600 V 6600 V 6600 V

HV arreste r 60 kV 102 kV 120 kV

MV arrester 60 kV 60 kV 60 kV

12 Types SSVT and SSMV o il-filled station service voltage tran sformer s | ABB product bu lletin
Dimensions and weights
SSVT-350 SSVT-550 SSVT-650

MSV / BIL kV 72 / 350 123 / 550 145 / 650

A - Height in. (mm) 75.05 (2261.87) 108.52 (2756) 116.33 (2955)

B - Width in. (mm) 33.75 (857) 33.75 (857) 34.25 (870)

C - Depth in. (mm) 66.18 (1681) 66.21 (1681) 70.56 (1792)

D - Highest Gnd Part in. (mm) 41.83 (1062) 42.91 (1090) 43.71 (1110)

E - Insula tor Length in. (mm) 22.91 (582) 40.65 (1033) 47.64 (1210)

F - Lowe st live pa rt in. ( mm) 64.93 (1649) 83.74 (2127) 91.55 (2325)

G - Conduit box height in. (mm) 11.50 (292) 11.50 (292) 12.25 (311)

H - Mtg Holes front- back in. (mm) 36.40 (925) 36.40 (925) 40.77 (1038)

I - Mtg Hole s left- right in. (mm) 32.13 (816) 32.13 (816) 32.25 (819)

80x48x72 80x48x92 85x50x98


Shipping Volume (l x w x h) in. ( mm) (2032x1219x1829) (2032x1219x2337) (2159x1270x2489)

2 crates 24x24x26 24x24x26 24x24x26


(610x610x660) (610x610x660) (610x610x660)

Unit Weight lb. (kg) 3513 (1593) 3593 (1629) 4343 (1970)

Shipping Weight lb. (k g) 3620 (1642) 3700 (1678) 4450 (2023)

Oil Volume gal. (liter) 150 (568) 75 (284) 180 (681)

Inf ormation shown herein is for informa tional purposes a nd is subje ct to c hange without notice .
For construc tion purpose s, contact fa ctory for updated inf ormation.

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 13
Inquiry and order information sheet

Copy form as needed.

ABB Statio n Service Volt ag e Transformers Quot e requests : HV IT@us. ab b.com


Type SSV T: Sing le Phas e, Single Bus hing

Customer / Project

Size / L oad R ating kVA 10, 25, 50, 100, 167 or higher

Primary Voltage Volt Line-to-Neutral a verage, actua l, not nominal

MMOV Volt 30 seconds or 60 seconds maximum over voltage, L-N

MCOV Volt Continuous maximum over voltage, L-N

Primary Protection kV BIL 250 - 1300 kV

SEC. Pow er Voltages V nominal 110/220, 120/240, 240/480, 277, 347, other (600 V class)

or Limits NLV high / FLV low (V or ratio)

Ratio s: PRI . L-N:SEC :1 for ea ch Sec onda ry Powe r Voltage at no load

Lo ad Power F actor % at maximum powe r loading

Measuring Ou tputs None Single with tap Dual with tap Spec ia l

High accuracy is standard

Elev > 3000 f t. 24 hr. avg.


Operating Enviro nment

STANDARD FEATURES SPECIAL FEATURES

Primary Bushing ANSI 70 Gray Brown Inc re ased / Reduced BIL ra ted

H-spade terminal standard

Type o f Secon dary Terminals 2-hole g spade 4-hole h spade


2-hole lug

Tan k Material Mild steel 304L SST or Other:

Dome Material Mild steel 304L SST or Other:

Finish Coating ANSI 70 Gray polye ster powder Other:

Tan k Gro und Pads 1 on side 1 in T.B. Other:

Cable Conn ector Optio n Y/N Size Range

Primary Terminal MCM

Tan k Gro und MCM

Other o ption s available - Oil sampling device - Export crating


- 1 or 2 CTs in terminal box - Tempe rature gauge
- Heater in terminal box - Mounting rise r stand

Comments: ____ ______ _______ ______ _______ ______ ______ _______ ______ _______ ______ _______ ______ _______ ______ _______ ______ ______ __
____ ______ _______ ______ _______ ______ ______ _______ ______ _______ ______ _______ ______ _______ ______ _______ ______ ______ __
____ ______ _______ ______ _______ ______ ______ _______ ______ _______ ______ _______ ______ _______ ______ _______ ______ ______ __

ABB Statio n Service Volt ag e Transformers


Type SSMV: Addit ional Informat ion

Frequency 60 Hz 50 Hz

Operating Enviro nment 6 - 61 kV 72 kV 7 - 62 kV 7- 96 kV

Power Take-o ff Underground Overhe ad

14 Types SSVT and SSMV o il-filled station service voltage tran sformer s | ABB product bu lletin
Catalog number breakdown

Low Voltage Output

250 kV through 750 kV BIL (46 kV - 161 kV Systems)

Typical SSVT Catalog Number:


J99N328050C-XXX

J 99 N 328 050 C XXX

Transformer Type KVA Series


Ú¿½¬±®§ ¿­­·¹²»¼ Winding Code 10 Factory assigned
Factory assigned 25 Special Features
Dielectric Insulation Code (kV BIL) Highest turns ratio 50 ß­ ®»¯«·®»¼
H = 250 kV 100/125
J = 350 kV Power / Meter 160/167
K = 550 kV M = Meter windings 200
L = 650 kV N = No meter windings 250
M = 750 kV D = Dual meter windings

900 kV through 1300 kV BIL (230 kV - 345 kV Systems)

Typical SSVT Catalog Number:


N91110N100-XXX

N 91 110 N 100 XXX

Series KVA
Factory assigned Power / Meter
100
M = Meter windings
167 Special Features
N = No meter windings
200 As required
D = Dual meter windings
250
Dielectric Insulation Code (kV BIL) T = Taps power only
Winding Code 315/333
N = 900 kV or 1050 BIL
P = 1300 kV BIL Factory assigned
Highest turns
ratio

Medium Voltage Output

350 kV through 750 kV BIL (46 kV - 161 kV Systems)

Typical SSVT-MV Catalog Number:


J99NA28050C-XXX

J 99 N A 28 050 C XXX

Transformer Type Winding Code Series


Ú¿½¬±®§ ¿­­·¹²»¼ Factory assigned Factory assigned
Highest turns ratio KVA
Dielectric Insulation Code (kV BIL) 10
J = 350 kV Frequency 25 Special Features
K = 550 kV A = 60 Hz 50 ß­ ®»¯«·®»¼
L = 650 kV B = 50 Hz 100/125
M = 750 kV Power / Meter 160/167
N = No meter windings 200

ABB product b ulletin | Type s SSVT and S SMV oil-filled sta tio n se rvice v oltage transformers 15
Notes

16 Types SSVT and SSMV o il-filled station service voltage tran sformer s | ABB product bu lletin
Contact us

ABB, Inc. Note:

Docume nt Numbe r P PHVI TS SV 1110BR / August 2012


We reserve th e r ight to make technical chang es o r
High Voltage Instrument Transformers
modify the contents of this documen t with out pr ior
3101 Beaumont Centre Circle no tic e. With regard to pu rc hase o rders, the agreed
Suite 225 particulars shall prevail. ABB does not accept any
Lexington, KY 40513 respo nsibility whatsoever for po tential errors or possible
Toll free: +1 800-950-6966 lack of in fo rmation in this do cument. We reser ve all
righ ts in this do cument and in the subject matter an d
Phone: +1 859-219-6040 illustrations contain ed therein. Any reproduction – in
Fax: +1 859-223-2025 who le o r in parts –is for bidden witho ut ABB’s prio r
written co nsen t.
www.abb.com/highvoltage
May no t be available in all mar kets.

Copyrig ht ® 20 12 ABB
All rights reserved