Panel serial No.

: CI-2017-W46-4-0026

VERIFICATION OF " Talus/ T200 "


Project BUMI SUKSESINDO
Drawing no. A515576-14-002-1-30

Panel Name INCOMING PLN / INCOMING GENGSET Manufacturer

Instruments T200 S Type GENSET Ref. No.


T200 SN - Designation in panel T200S

VD23
VOLTAGE /Phase V1 V2 V3 Status Network configuration √ 50 Hz
Inject Voltage (V) 30 30 30 60 Hz
OK
Measure value (V) 100 100 100

I. LED indicator on Talus II. Push button and selector switch on Talus
Current transformer ratio
Description Status Description Status
Ratio : 1/500 A
Power Card OK Open Close OK
COM Card OK Test Reset OK Current transformer conf.
Control Card OK Selector Switch OK
I1, I3, I0
Enter OK
ATS button OK I1, I2, I3

III. Setting
Control and Automation n 1
o

Control type CI2 DDEF Test (DOUT 2) Pararel mode allowed in automatic mode
Return position waiting time 15000 8 Bits Measurement as in T200 serie 2 Pararel mode allowed by manual control
No complementary filtered time 10000 Manual control allowed when ATS is in operation
Operating time (Except PM6) 2200 ATS locking in case of fault detection
Automation (kontak breaking genset)

Automation type Automation type GENSET


Permutation wating time ms Permutation wating time 1000 ms
Time before returning on normal way s Time before returning on normal way 5 s
Type : SW1 -> SW2 - Genset connect to : SW2
SW2 -> SW1 - Genset SW close control : After genset inputs terminal block
SW1 <-> SW2 - After genset start control order
Auto SW1 - Genset voltage presence wired : DI4 of digital input terminal block
Auto SW2 - MV Cubicle connector
Mode of opearation : SW -> SWG -
SW <-> SWG
Auto SW √

Measurement and FPI configuration n 1


o

1. Overcurrent Off X On
SETTINGS INJECT
Status
Current Threshold (A) Delay (ms) ...x Is Value (A)
40 - 1 40.1 OK

2. Earth fault X Off On

SETTINGS INJECT
Status
Current Threshold (A) Delay (ms) ...x Is Value (A)

Tested by : ROFIK Signature : Comments :

Date of test : 10/23/2017

CS-FQC MV-027 Rev A