Professional Documents
Culture Documents
net/publication/224122654
CITATIONS READS
2 120
2 authors, including:
Shahram Jamali
University of Mohaghegh Ardabili
104 PUBLICATIONS 423 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Intrusion Detection and Identification of Attacks in the RPL-Based Internet of Things (IoT) View project
All content following this page was uploaded by Shahram Jamali on 19 August 2015.
S. JAMALI H. SHATERI
Iran University of Science and Technology - Iran
sjamali@iust.ac.ir
In the first step, the network topology should be defined Network topology is an important aspect in the distribution
properly for the optimisation procedure. Unlike the systems studies. References [1-4] present methods for
transmission systems, in distribution systems numbering the numbering the network components for solving the load-flow
network branches and nodes is very important. This paper problem, which can be used in any other studies. In general, a
presents a numbering method for the distribution systems. numbering strategy is required in the studies of distribution
networks.
It has been a common practice to install reclosers in the sub-
transmission substations. In this case, the feeder circuit- This paper uses the numbering method in [6], which is
breaker can be controlled by a recloser relay. In the recent somehow similar to the method presented by Goswami and
years, recloser packages are largely introduced into Basu [2]. In this method, similar to the other methods, the
distribution networks. These are composed of a circuit- numbering process starts from the source node, i.e. sub-
breaker and a recloser relay and can be installed anywhere on transmission substation. The far end node of the connected
the distribution feeder. branch to this node is numbered one. The number of each
CIRED2005
Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005
branch is the number of its far end node. After first branch, where C s , C d and Pi are similar to (1), ρ i is the fault
the connected branch to its far end is then numbered. This distribution density function along the feeder, with a
process continues and if there is a lateral on the feeder, the magnitude between 0 and 1,and kc is a coefficient defined as
branches of the lateral with fewer components are first follows:
numbered. Fig. 1 shows this numbering method for a typical
network. kc = KF Ltcn (3)
where K , cn and t are similar to (1) and FL is the annual
10 15
number of the permanent fault occurrence on the feeder.
10 15
ρ i can be computed as below:
1 2 8 9 16 18
∑p l
1 2 8 9 14 16 18
14 j j
j∈ D
3 11 17
ρi = n (4)
∑p l
4 12
4 3 11 12 17
j j
5 j =1
13
5 6
6
13
where:
p j : Relative probability of fault occurrence on the line
7
section j
7
l j : Length of the line section j
Fig. 1- Numbering method on a typical network n : Number of the nodes in the network
D : Set of nodes which are located at the downstream of the
node j
SAVING GAINED BY UTILISING A DISCONNECTOR
THE ALGORITHM
The main purpose of utilising automation equipment is to
restore the upstream loads when a fault occurs on the network,
or in other word, reducing the cost of NDE. This is done by Reclosers can be installed on the supplying point or along the
disconnecting the downstream faulted section. This cost must feeder. It has been a common practice to install reclosers in
be balanced to the equipment installation cost. For a single the sub-transmission substations or the feeder circuit breaker
disconnector, its optimal location can be found as [5]: can be controlled by recloser relay. In the recent years,
recloser packages are largely introduced in the distribution
Ci = KPi f Lli tc n − C d (1) networks, and they can be installed anywhere on a distribution
where: feeder.The installation point of the recloser affects the
Ci : Amount of savings gained by installing a disconnector procedure of finding the optimal number and location of the
K : Coefficient for converting the first year costs to the whole sectionalisers.
review period
Pi : Upstream demand of node i
f L : Annual failure rate per line length Recloser Installed at the Sub-Transmission Substation
li : Line length downstream of node i
t : Difference between repair time and switching time
cn : Outage-cost parameter of NDE When the recloser is located at the sub-transmission
C d : Cost of a disconnector (including maintenance) over the substation, sectionalisers can be installed anywhere on the
whole review period feeder.
CIRED2005
Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005
is not economical. On the other hand, for positive values of on a lateral, and then s 2 can be chosen from the downstream
C s , the use of sectionaliser is economical and the node with network of this lateral.
the highest value of C s is the optimal position for its
installation. The C( s1 ,s 2 ) value is calculated for all the nodes. s1 and s 2
corresponding to the highest value of C( s1 ,s 2 ) are the optimal
The value of C s is normally negative at twigs. Therefore the installation locations of two sectionalisers.
twigs can be omitted from optimal placement process, without
losing the global optimum. Reference [6] recommends If s1 and s 2 corresponding to the twigs or when they are very
ignoring the branches with downstream load of less than 5% close to each other, usually C( s1 ,s 2 ) is low or negative.
of the total load. According to the (5), C s depends on the Therefore, in this case twigs can also be omitted from the
upstream load as well as the probability fault occurrence on calculations. The defined VSLS set at previous section can be
the downstream network. If the downstream load is low and used. Here another set is required for current type
the downstream fault occurrence is high, the gained saving sectionalisers. This set is defined as a set of nodes, which are
would increase. When the downstream load is only located on the laterals, and the mentioned criterion is higher
considered, the branches with the high fault rate might be than a specified value, e.g. 0.04. This set is defined as Current
omitted. Therefore, the omission criterion should be Sectionaliser Location Set (CSLS).
composed of the upstream load and the down stream fault
rate. Here, it is suggested that their product is considered as In installation of two sectionalisers, if they are voltage type,
the omission criterion. In order to determine the criterion, it is s1 and s 2 are chosen from the VSLS set. In the case of
useful to apply the per-unit values of the downstream loads, in current type sectionalisers s1 is chosen from CSLS, and s 2 is
the base of the total load. When this criterion is less than 0.05, selected from VSLS set, corresponding to the downstream
the node can be omitted from the placement procedure. network of the lateral of s 2 .
Therefore, a set defined as Voltage Sectionaliser Location Set
(VSLS); consisting of the nodes with the criterion of higher When the maximum value of C( s1 ,s 2 ) is computed, it should
than 0.05. In this case, VSLS can be used for both voltage and be compared with highest value of C s which was calculated
current type sectionalisers. at the previous stage. If C s is higher than C( s1 ,s 2 ) , the
optimal number of sectionalisers is equal to one and its
location is at node or line section s . In this case, cost of
Savings gained by utilising two sectionalisers. If the gained installing the second sectionaliser is more than the gained
saving is positive in the case of one sectionaliser, it cab be saving. On the other hand, if C( s1 ,s 2 ) is higher, the installation
concluded that the application of the sectionaliser is of two sectionalisers is more economical. However, the cases
economical for the network. However, the higher saving of using more sectionalisers should still be considered at this
would be gained by utilising more sectionalisers. Therefore, point, in search for the optimal number.
the case of using two sectionalisers should be considered. In
this case, (5) should be modified as:
Savings gained by utilising multiple sectionalisers. When n
C( s1 ,s 2 ) = kc ( Ps1 ρ s1 + Ps2 ρ s 2 ) − 2 C S
(6) sectionalisers are installed in a distribution network, (5) can
In (5) s1 and s 2 are the installation location of the be modified as below:
sectionalisers, and s1 < s 2 .
n
C( s1 , , s n ) = kc ∑ ( Psi ρ si ) − n C S (7)
The values of s1 and s 2 depend on the type of sectionalisers. i =1
There is no limit for the voltage type sectionalisers, whereas where:
current type sectionalisers cannot be placed in series with s1 , , s n : Installation locations of n sectionalisers in order,
each other. In other words, current type sectionalisers need an i.e. s1 < < sn
extra consideration in choosing s1 and s 2 . Psi : Upstream load of node si
ρ si : Fault occurrence probability at the section related to
In the case of voltage sectionalisers, s1 and s 2 can take a the sectionaliser installed at the node si
value between 1 and n. In this case, C( s1 ,s 2 ) , kc , Ps1 , Ps 2 ,
ρ s2 and C S are similar to (5), but the value for ρ s1 differs. In this case similar to the installation of two sectionalisers, the
Here, ρ s1 is the probability of fault occurrence in the network values that variables s1 , s 2 , … , s n can take, depending on
section protected by the sectionaliser installed at the s1 , and the sectionalisers type. In the case of the voltage type
it is not necessarily equal to the probability of fault sectionalisers, the evaluation of ρ si is important, whereas for
occurrence downstream node s1 . the current type sectionalisers the values which variables s1 ,
s 2 , … , s n can take, is a question.
For current type sectionalisers, C( s1 ,s 2 ) , kc , Ps1 , Ps 2 , ρ s1 ,
ρ s2 and C S are similar to (5), but there are some limits on In the case of current type sectionalisers, similar to the case of
choosing s1 and s 2 . Here, ρ s1 is always equal to the fault using two sectionalisers, the reference sets of the variables are
occurrence density function at node s1 . At first, s1 is selected different. Locations s1 , s 2 , … , sn −1 should only be selected
CIRED2005
Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005
When the sub-transmission circuit breaker does not have the The proposed algorithm has been tested on the test network of
reclosing feature or the recloser relay is not installed, the [6]. This network topology is normally used in Iranian
recloser packages can be utilised. These are composed of a distribution networks. The network data, including line
recloser relay and a associated circuit breaker. In this case, the parameters, line sections length, fault occurrence relative
recloser can be installed anywhere along the feeder. probability and peak loads are presented in [6]. The other
parameters are similar to [6]. The cost of non-distributed
energy, cn , is equal to $ 2 × 10 −4 ,where $ is an arbitrary
Savings gained by installing recloser on the feeder. In currency unit. The value of kc is therefore equal to 0.125.
order to compute the gained saving, (5) can be modified as The cost of a sectionaliser is taken to be $15, and the cost of a
follow: recloser is $25.
CIRED2005
Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005
TABLE I- Optimal locations and gained saving of voltage sectionalisers The installation location of the recloser would be a question,
Number of Gained i.e. where should it be installed, in the sub-transmission
Optimal installation locations of sectionalisers
sectionalisers saving
substation or along the feeder. This question can not be
1 119 109.41
2 51 119 176.32 answered only by considering NDE. Some other factors
3 14 51 119 202.22 should be considered, such as power quality indexes, the
4 14 35 51 119 216.88 imposed stress to the network equipment especially to the
5 14 35 51 100 162 228.84
6 14 35 51 100 135 162 233.32
power transformer, and the characteristic of the supplied loads
7 14 35 51 100 120 135 162 232.55 via the recloser against the reclosing shuts. Therefore,
8 14 35 52 64 100 120 135 162 224.26 deciding about where the recloser should be installed can not
be done only by considering non-distributed energy.
Table II shows the optimal positions and gained savings of
installation of 1 to 8 current type sectionalisers. Here, the
optimum number of sectionalisers is 7 with a gained saving of CONCLUSION
$224.54.
TABLE II- Optimal locations and gained saving of current sectionalisers This paper presents a method for optimum use and location of
Number of Gained a recloser and sectionalisers on a distribution feeder. This is
Optimal installation locations of sectionalisers
sectionalisers saving
1 119 109.41
done by balancing the non-distributed energy cost against the
2 51 119 176.32 installation costs of the recloser and sectionalisers. A suitable
3 14 51 119 202.22 numbering methodology, which well defines the network
4 14 35 51 119 216.88 topology, is used. Different routines have been developed for
5 14 35 51 101 119 218.86
6 14 35 51 120 135 162 222.57
voltage type and current type sectionalisers considering
7 14 35 51 101 120 135 162 224.54 installation location of the recloser. The proposed algorithm
8 14 35 52 64 101 120 135 162 216.25 has been tested on a typical Iranian feeder and the results are
presented.
In the case of utilising a recloser package on the feeder, the
optimal locations and the gained savings are presented for one
recloser and 0 to 7 sectionalisers. Table III presents the REFERENCES
results. Here, the highest saving of $209.24 is gained by
installing one recloser and 6 sectionalisers.
[1] D. Shirmohammadi, H.W. Hong, A. Semlyen, G.X. Luo,
TABLE III- Optimal locations and gained saving of a recloser and 1988, "A Compensation-Based Power Flow Method for
voltage sectionalisers Weakly Meshed Distribution and Transmission
Number of Optimal installation locations of Gained Networks", PWS, vol. 3, no. 2, 753-762.
RIL
sectionalisers sectionalisers saving
0 119 099.41
1 50 119 117.17 [2] S.K. Goswami, S.K. Basu, 1991, "Direct Solution of
2 34 51 119 161.79 Distribution Systems”, IEE Proceedings C, vol. 138, no.
3 13 14 51 119 181.66 1, 78-88.
4 13 14 35 51 119 194.52
5 13 14 35 51 100 162 204.75
6 13 14 35 51 100 135 162 209.24 [3] M. Baran, F.F. Wu, 1989, "Optimal Sizing of Capacitors
7 13 14 35 51 100 120 135 162 208.46 Placed on a Radial Distribution System", PWD, vol. 4,
RIL: Recloser installation Location no. 1, 735-743.
Table IV shows the optimal positions and gained savings of [4] J. Nanda, M.S. Srinivas, M. Sharma, S.S. Dey, L.L. Lai,
installation of a recloser and up to 7 current type 2000, "New Findings on Radial Distribution System
sectionalisers. Here, the optimum number of sectionalisers is Load Flow Algorithms", Proceedings IEEE PES Winter
6 with a saving of $201.46. Meeting, vol. 2, 1157-1161.
TABLE III- Optimal locations and gained saving of a recloser and [5] E. lakervi, E. J. Holmes, 1995, Electricity Distribution
current sectionalisers Network Design, Peter Peregrinus Ltd., London, UK.
Number of Optimal installation locations of Gained
RIL
sectionalisers sectionalisers saving
[6] S. Jamali, H. Shateri, 2004, “Optimal Application and
0 119 099.41
1 50 119 117.17 Site Location of Sectionlisers in Overhead Distribution
2 34 51 119 161.79 Networks”, Proceedings 8th International Conference
3 13 14 51 119 181.66 on Developments in Power System Protection, vol. 2,
4 13 14 35 51 119 194.52
5 13 14 35 51 120 131 196.14
615-619.
6 13 14 35 51 120 135 162 201.46
7 13 14 35 52 64 120 135 162 193.35
CIRED2005
Session No 3