Air Cooled Screw Chiller Performance

Datasheet
Net Cooling Nominal Power
Unit Tag Qty Model No Refrigerant Type
Capacity (kW) Volts-Ph-Hz
CH-1 1 YVAA0490KMV40BAVDXX 1407 380-3-60.0 R134a

PIN:
YVAA0490KM V40BAVDXXX XAXLXXXX60 44XOTXXS19 4X1SXXA3BT XVXXXXXXXX XXXSXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°C) 12.22 Fluid Volume (L) 492.0 COP.R (kW/kW) 2.146
LWT (°C) 6.67 Min. Flow Rate (L/s) 0.0000 NPLV.IP (kW/kW) 5.067
Design Flow Rate (L/s) 60.40 Max. Flow Rate (L/s) 0.0000
Total Press. Drop (kPa) 140 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°C) 46.1 Rigging Wt. (kg) 10844
Fouling Factor (m²K/kW) 0.0176 Altitude (m) 0.000 Operating Wt. (kg) 11337
VSD Screw - Semi
Number Passes 3 Compressor Type Refrigerant Charge (kg) 358
Hermetic

Electrical Data
Circuit 1 2 3 4
Compressor kW 313.2 312.2
Compressor RLA 502 500
Fan QTY/FLA (each) 10 / 3 10 / 3

Multi Point
Min. Circuit Ampacity 664 655
Min. Fuse / CB Rating (A) 800 800
Max. Fuse / CB Rating (A) 1000 1000
Unit Short Circuit Withstand (STD) 30 kA [kA]
Wires Per Phase 3 3
Wire Range (Lug Size) #2 - 600 kcmil #2 - 600 kcmil
Operating Condition Electrical Data
Control kVA 3 Compressor kW 625.5
Total kW 655.7

Notes:

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor
Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and
AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org. Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

Min DSD (Factory Purpose/Use only): 80 psig


Use Copper Conductors only
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option
selected. Calculated value is available by request.

Minimum and maximum evaporator flow information are for full load ratings with Water.
Actuated suction service valves ARE selected
Exclusion of actuated suction service valves will require incorporation of additional freeze protection including use of glycol, pump control or draining the
evaporator.

Part Load Rating Data


Load % Ambient (°C) Capacity (kW) Total kW Unit Efficiency
100 46.1 1407 655.7 2.146

MLP Effective Date:11/1/2018 SHUBAILY MALL


Generated on 2019-01-21 E.2.0.12246.0-D.67.0032(REV. v8_09.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.05a Page_1_of_2
Air Cooled Screw Chiller Performance
Datasheet
75 26.7 1055 249.3 4.233
50 18.3 703.4 125.7 5.598
25 12.8 351.7 56.34 6.242

Sound Power Levels (In Accordance with AHRI 370)


Ambient 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Load % LWA
(°C) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB)
100 46.1 99 99 100 103 102 97 95 88 106
75 26.7 98 98 99 100 97 91 88 84 101
50 18.3 93 93 94 100 92 85 84 83 99
25 12.8 90 89 90 96 88 81 80 80 95

Note: Unit is equipped with Low Sound Fans with Variable Speed Control.

Performance at AHRI Conditions


Evaporator Data Condenser Data Performance Data
EWT (°C) 12.22 Ambient Temp. (°C) 35.0 COP.R (kW/kW) 3.049
LWT (°C) 6.67 Altitude (m) 0.000 IPLV.IP (kW/kW) 5.076
Net Cooling Capacity
Flow Rate (L/s) 60.40 1407
(kW)
Pressure Drop (kPa) 140
Fluid Water
Fouling Factor (m²K/kW) 0.0176
Fluid Volume (L) 492.0

Note: Unit rated at design condition capacity.

MLP Effective Date:11/1/2018 SHUBAILY MALL


Generated on 2019-01-21 E.2.0.12246.0-D.67.0032(REV. v8_09.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.05a Page_2_of_2