You are on page 1of 3

Single Time Range Timer

DIN Size W48×H48mm Solid State ON Delay Timer


(A)

▣Features Counter

lDIN Size W48×H48mm


lSimple function type
(B)
lEconomical price Timer
lEasy time setting
l15 time ranges available
lPower supply (C)
Temp.
U ATE : 110/220VAC 50/60Hz controlle
U ATE1, ATE2 : 110VAC, 220VAC 50/60Hz,
12VDC, 24VDC(Option)
(D)
Please read "Caution for your safety" in operation Power
! manual before using. controlle

▣Ordering information
(E)
ATE 10 S s sec(1, 3, 6, 10, 30, 60)
Panel
meter
m min(3, 6, 10, 30, 60)
h hour(3, 6, 12, 24)
(F)
Tacho/
Number Max. range Speed/
Pulse
Time-limit (1c), Instantaneous SPST(1a) meter

1 Time-limit DPDT(2c)
2 Time-limit SPDT(1c), Instantaneous SPDT(1c) (G)
Display
ATE ON Delay Timer unit

▣Specifications (H)
Sensor
ATE- s ATE1- s ATE2- s controlle
Model m m m
h h h
Function Power ON Delay (I)
Proximit
Control time setting range sec(1, 3, 6, 10, 30, 60), min(3, 6, 10, 30, 60), hour(3, 6, 12 ,24) sensor
Power supply 110/220VAC 50/60Hz 110VAC, 220VAC 50/60Hz, 12VDC, 24VDC(Option)
Allowable voltage range 90 ~ 110% of rated voltage
(J)
Power consumption Approx. 10VA(240VAC 60Hz), Approx. 2W(24VDC, 12VDC) Photo
Return time Max. 200ms electric
sensor
Time limit SPDT(1c), Time limit SPDT(1c),
Control Contact ty pe Time limit DPDT(2c)
output Instantaneous SPST(1a) Instantaneous SPDT(1c)
Contact capacity 250VAC 3A resistive load (K)
Relay Mechanical Min.10,000,000 times Pressur
sensor
life cycle Electrical Min. 100,000 times(250VAC 3A resistive load)
Repeat error Max. ±0.3%
Setting error Max. ±5% ±0.05sec (L)
Voltage error Max. ±0.5% Rotary
encoder
Temperature error Max. ±2%
Insulation resistance 100MΩ(at 500VDC)
(M)
Dielectric strength 2000VAC 50/60Hz for 1 minute 5-Phase
stepping
Noise strength ±2kV the square wave noise(pulse width:1㎲) by the noise simulator mot or &
Dr iver &
Mechanical 0.75mm amplitude at frequency of 10 ~ 55Hz in each of X, Y, Z directions for 1 hours Controlle
Vibration
Malfunction 0.5mm amplitude at frequency of 10 ~`55Hz in each of X, Y, Z directions for 10 minutes
Mechanical 300m/s²(Approx. 30G) in X, Y, Z directions 3 times
Shock
Malfunction 100m/s²(Approx. 10G) in X, Y, Z directions 3 times
Ambient temperature -10 ~ 55℃(at non-freezing status)
Storage temperature -25 ~ 65℃(at non-freezing status)
Ambient humidity 35 ~ 85%RH
Weight Approx. 75g

B-52
ATE Series
▣Front panel identification ▣Time setting range

Max. setting time Setting range


1sec 0~1sec
3sec 0~3sec
Power ON
OUT indicator
indicator 6sec 0~6sec
10sec 0~10sec
30sec 0~30sec
60sec 0~60sec
M IN 3min 0~3min
6min 0~6min
ATE-3M
10min 0~10min
30min 0~30min
Timer unit
(sec, min, hour) 60min 0~60min
3hour 0~3hour
6hour 0~6hour
12hour 0~12hour
24hour 0~24hour

▣Operation mode
t : Setting time, Rt : Return time

Model Time chart


t Rt t

Power 2-7

Instantaneous NO 1-3
ATE Time limit NC 8-5

Time limit NO 8-6

UP LED

t Rt t
Power 2-7

1-4
Time limit NC (8-5)
ATE1
Time limit NO 1-3
(8-6)

UP LED

t Rt t
Power 2-7

Instantaneous NC 1-4

ATE2 Instantaneous NO 1-3

Time limit NC 8-5

Time limit NO 8-6

UP LED

B-53
Single Time Range Timer

▣Connections
(A)
lATE Series(Time limit 1c, Instantaneous 1a) lATE1 Series(Time limit 2c) Counter

4 5 4 5

3 6 CONTACT: 3 6
CONTACT: CONTACT:
250VAC 3A (B)
250VAC 3A 250VAC 3A
RE SIS TIVE LOAD Timer
2 7 RESISTIVE LOAD 2 7 RE SIS TIVE LOAD

1 8 1 8
(Instan- (Time limit 1c) (Time limit 1c) (Time limit 1c)
taneous (C)
1a) 110VAC 50/60Hz - Temp.
! +
~ lATE2 Series(Time limit 1c, ~ controlle

220VAC 50/60Hz Instantaneous 1c) SOURCE


!
~
4 5
(D)
Power
3 6 controlle
CONTACT:
250VAC 3A
2 7 RESISTIVE LOA D
(E)
1 8
(Time limit 1c) Panel
(Instantaneous
meter
1a) - +
! ~
SOURCE (F)
Tacho/
Speed/
▣Dimensions Pulse
lBracket(Option) 92 lPanel cut-out meter
48
Min. 53
13 64 15
(G)
Display
unit
45 +-0.6
0

M IN
Min. 65 45 +0.6
-0
(H)
ATE-3 M Sensor
controlle
P GB48 85

※P GB48 is optional. (I)


Proximit
sensor

41
(J)
Photo
electri c
Socket sensor
Unit:mm
Panel PG-08

▣Proper usage (K)


Pressur
sensor
◎Environment
Please avoid the following places: Plea se install MP c ondensor(0.1~1㎌) or Oil
lA place where this product may be damaged by condensor between power teminals when over (L)
strong impact or vibration. Impulse noise voltage occurs. Rotary
encoder
lA place where corrosive gas or flammable gas and 2)When testing dielectric voltage and insulation
water,oil, dust exist. resistance of the control panel with this unit
(M)
lA place where magnetic and electrical noise occur. installed. 5-Phase
stepping
lA place where high temperature and humidity are lPlease isolate this unit from the circuit of control motor &
Driver &
beyond rated specification. panel. Controlle

lA place where there are strong alkalis and acids. lPlease make all terminals of this unit shor-
circuited.
lA place where there are direct rays of sun.
(It prevents the damage of inner circuit.)
◎Noise
1)We test 2kV, Pulse width 1㎲ against Impulse voltage
between power terminals and 1kV, Pulse width 1㎲
at noise simulator against external noise voltage.

B-54