ProjNet: Logged In User https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCo...

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954325 Civil Plans and Specs n/a CD-101 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

From the grading and site plans it appears that fencing will require removal, however limits of removal are not noted on the demolition plans;

Clarify limits of fence demolition and fence type/size, provide fence installation details and specifications.

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954333 Civil Plans and Specs n/a CD-101 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Plans should slow limits of pavement removal/saw cutting for proposed water/sewer/storm sewer piping. Plans should show how pavement will be restored following pipe
installation.

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954340 Civil Plans and Specs n/a CU-601 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Provide notes indicating the size and material of existing water main pipe and the proposed size of valve "T".

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954346 Civil Plans and Specs n/a CU-601 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Plans should indicate type of water service pipe; specifications are unclear, listing multiple pipe material options.

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954364 Civil Plans and Specs n/a CU-601 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

It appears that the fire hydrants will require bollard protection; provide a detail for bollard placement and a detail for bollard construction.

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954443 Civil Plans and Specs n/a CU-601 n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

The pump and piping layout for the Warehouse truck well is not clearly defined, provide more detail in next plan set.

Submitted By: Russell Fischer (651-290-5970). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954431 Electrical Design Directives n/a n/a n/a

4 of 29 5/12/2019, 1:07 PM
ProjNet: Logged In User https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCo...

Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)


Coordinating Discipline(s): Electrical

Drawing ED-101: Recommend to expand Key Note 1 to tell the contractor to terminate the electrical circuit as required.

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954432 Electrical Design Directives n/a n/a n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Coordinating Discipline(s): Electrical

Is the feeder from Substation to the building in Concrete Encased? It is not clear from the drawing.

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954433 Electrical Design Directives n/a n/a n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Coordinating Discipline(s): Electrical

Electrical Specifications: When editing the specifications, please ensure all measurements are in metric system.

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954434 Electrical Design Directives n/a n/a n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Coordinating Discipline(s): Electrical

I was not able to open the PDF file for electrical design analysis.

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954436 Electrical Design Directives n/a n/a n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Coordinating Discipline(s): Electrical

Drawing XE-101 has a reference to Drawing SE-503. I did not find drawing SE-503 in this submittal.

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7954437 Electrical Design Directives n/a n/a n/a
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Coordinating Discipline(s): Electrical

Drawing XE-101 is the compact substation a new one or existing one. How is the power coming to this compact substation?

Submitted By: Morteza Mostaghim ((540) 665-4031). Submitted On: Apr 24 2019

Evaluation not conducted

Id Discipline DocType Spec Sheet Detail


7985334 Paving Plans n/a Sheet C-501 Detail 1
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

the actual dimension of the rigid slabs are not clear.

5 of 29 5/12/2019, 1:07 PM