You are on page 1of 2

DECLARATION OF PERFORMANCE

number 0007/B/CPR/2013

NHXH-J, NHXH-O ; FE180 PH90 E90 0,6/1 kV


1. Code of product type: .........................................................................................................................................

(1 ÷ 5) x (1,5 ÷ 300) mm2


(6 ÷ 12) x (1,5 ÷ 10) mm2
(13 ÷ 48) x (1,5 ÷ 4) mm2
2. Type number: ..........................................................................................................................

Cables are intended to use for power supply of firesafety equipment, for usage in wet and dry rooms
with water fire extingiushing systems.
3. Application: ............................................................................................................................

Celina Bitner Cable Factory BITNER, 30-009 KRAKOV, Friedleina St 3/3


Production: Cable Factory BITNER, 32-353 TRZYCIĄŻ 165
4. Name and address of producer: .............................................................................................................................

1
5. System of assessment and verification of constancy of performance of the product :........................................

6. Notified factory production control certification body:


- CISQ/IMQ-CSQ performed initial inspection and certification of factory’s quality management
system and stated its conformity with requirements of ISO 9001:2008
- CNBOP-PIB performed initial inspection of production department and FPC. Surveillance,
assessment & approval of FPC is on-going.

7. Declared performance properties:

Essential Harmonised technical


Performance
characteristic specification
Flame retardancy of cable for verticala flame
cable is flame retardant PN-EN 60332-1-2
propagation
Flame retardancy of cable bunch for verticala cable bunch is flame retardant –
PN-EN 60332-3-22
flame propagation categoria A

Densitity of emissioned smoke light transmission not less than 70 % PN-EN 61034-2

pH > 4,3;
Gases emission during burning of materilas
conductivity PN-EN 50267-2-2
which cable is made of
C< 10µS/mm

Circuit integrity during fire application FE180 PN-IEC 60331-21

Usability of cable in cable system (cable system


cable system integrity – E90 DIN 4102-12
integrity) in coditions of fire (842 °C, 90 min)

continuation on page 2
0007/B/CPR/2013
page 2

Fire resistance of cable PH90 PN-EN 50200

Water resistance of cable during fire PH120 PN-EN 50200:2006 annex E

8. The performance of the product identified in points 1 and 2 is in conformity with the declared performance in
point 7.

This declaration o f performance is issued under the sole responsibility of the manufacturer identified in
point 4.

Trzyciąż 01.07.2013
..................................................... .................................................................
Place and date of issue name, title and signature