You are on page 1of 1

TAL rating table

10 to 1000 kVA - 50 Hz / 12.5 to 1250 kVA - 60 Hz

Technical definitions

INTRODUCTION
This catalogue is a summary of ratings for the TAL low voltage range at the most common voltages around the world.
For other voltages, please consult LEROY-SOMER.

1 - RATING DEFINITION
- Continuous rating S1/40°C - IEC 60034-1 definition
Running at constant load limited to the insulation class ; permissible overload 1 h every 12 hours.
- Stand-by rating 40°C
Running at constant load without over load, for a limited duration of maximum 500h/year, with a permissible increase of the
temperature rise above class H.
- Stand-by rating 27°C
Same conditions than stand-by duty 40°C but with acceptance of a lower ambient temperature (27°C) that allows to increase the
rating and the temperature rise for the same level of temperature in the alternator.
ex: S1/40°C = 100 kW - std by/40°C = 105 kW - std by/27°C = 110 kW

2 - INSULATION CLASS AND TEMPERATURE RISE

°c Example: Insulation, class H H


165 Maximum acceptable temperature
F
145 Winding temperature at lower rating
125 K

140 B
105 K

105 K

120 Temperature rise class F


100 K
80 K

A thermal reserve ensures


a long life for the machine
40
Ambient temperature
Nominal value class B = nominal value class H x 0.8

3 - DERATING
Multiply nominal rating by derating factor from following chart.

Altitude (m) 1000 1500 2000 2500 3000 3500 4000


Derating factor 1 0.975 0.949 0.922 0.894 0.866 0.837

Ambient T °C 25 40 45 50 55 60 (*)
Class H 1.076 1 0.973 0.946 0.918 0.889
Class F 1.095 1 0.966 0.931 0.894 0.856
Class B 1.140 1 0.949 0.894 0.837 0.775
(*) External AVR if ≥ 56 °C

Lagging PF 0.6 0.7 0.8 0.9 1


Derating factor 0.86 0.93 1 1 1

Electric Power Generation 3

You might also like