Professional Documents
Culture Documents
MaxPlant
CENTUM VP function blocks
Articles about the project
news Contacts
Peter
Posted on 1/26/2018
All articles of the YOKOGAWA section
Functional blocks
Input processing
Convert the input signal to the process variable PV.
Output processing
Convert the calculated value to the output variable MV.
Alarm processing
The detected process errors are reflected in the Alarm Status and displayed as messages to the operator.
http://www.maxplant.ru/article/centum_fb.php#mode 1/13
11/7/2018 CENTUM VP function blocks
Block Mode - determines the control status and the status of the outputs of the function block.
Compound Block Mode - a functional block can be simultaneously in several basic modes with different
priorities. Active is the mode with the highest priority.
The transition from one mode to another is carried out by an external command (operator or other block) or
automatically by changing the internal state of the block itself (for example, if an I / O module fails).
http://www.maxplant.ru/article/centum_fb.php#mode 3/13
11/7/2018 CENTUM VP function blocks
Pulse Count Input Block (PTC)
PAUS Pause Pulse count on pause
Palm Pre-Alarm The counter has reached the pre-alarm setting.
CTUP Count up The counter has reached the specified value
NR Normal Counts or CTUP, PALM is not active.
SO *
SIM Simulation The exit is stopped, but the output is simulated.
NR Normal Normal status
SIO *
ANCK Answer - Back Check Inhibition Feedback control blocked
SIM Simulation The exit is stopped, but the output is simulated.
NR Normal Normal status
Timer Block (TM)
PAUS Pause Pause Timer
NR Normal Timer counts and DV> DL
Palm Pre-Alarm Timer counts and 0 <DV ≤ DL
CTUP Count up Timer counts and DV = 0
RUN Run Timer counts after the Start command
STOP Stop Timer stopped by Stop command
Pulse Train Input Counter Block (CTP)
PAUS Pause Pause Counter
NR Normal Counter counts and DV> DL
Palm Pre-Alarm Counter counts and 0 <DV ≤ DL
CTUP Count up Counter counts and DV ≤ 0
RUN Run The counter counts after the Start command
STOP Stop Counter stopped by Stop command
Software Counter Block (CTS)
NR Normal Counter counts and DV> DL
Palm Pre-Alarm Counter counts and 0 <DV ≤ DL
CTUP Count up Counter counts and DV ≤ 0
RUN Run The counter counts after the Start command
STOP Stop Counter stopped by Stop command
Code Input Block (CI)
NR Normal 0 ≤ PV <PH-DL
HI High PV ≥ PH
LO Low PH-DL ≤ PV <PH
Code Output Block (CO)
NR Normal 0 ≤ PV <PH-DL
HI High PV ≥ PH
LO Low PH-DL ≤ PV <PH
Cumulative-Average Block (AVE-C)
RUN Averaging Starts Start initialization or averaging.
STOP Averaging Stops Averaging is stopped, output is held.
Accident status
The alarm status is displayed in the alarm status of the function block (ALRM).
Not all functional blocks have emergency status.
Blocking accidents
Suppression of accidents
Alarm Inhibition (AOFS) - is used to temporarily suppress alarm messages (at the same time, accidents
continue to be detected and affect the alarm status).
The operator can turn on AOFS only at once for all alarm messages of the function block, and in the program it
is possible to suppress the alarm messages individually.
Data status
Data Status
Symbol Name Description
BAD BAD value Unreliable data. A meaningless value or last normal value is saved.
QueSTionable The quality of the data is questionable: not normal and not bad. The value obtained from the outside, manually
QST
value set in the calibration mode or the last normal value is saved.
No
NCOM Data received from another station, have ceased to be updated due to a communication break.
COMmunication
Not From The data was not received from the process inputs / outputs, but from the outside, either set manually in the
NFP
Process calibration mode, or obtained by the calculated method.
CLP + CLamp high The output value is fixed at the upper limit.
CLP- CLamp low The output value is fixed at the lower limit.
CND Conditional Cascade communication with the next functional block is open.
Cal Calibration The data is set manually in an emergency.
Invalid data: value not yet set after switching to calibration mode or not yet updated after exiting calibration
Nefv Not EFfeciVe
mode.
O/s Out of service The I / O related function block is in O / S mode. Input is not updated.
MNT MaiNTenance The I / O related function block is in online maintenance mode. Input is not updated.
IOP + Input Open high Input process signal is brought to maximum due to wire breakage or other malfunction.
IOP- Input Open low The input process signal is brought to a minimum due to a wire break or hardware failure.
OOP Output OPen Open signal due to wire break or hardware failure.
PI / O Not
NRDY Input / output signals are blocked due to a power failure, maintenance, or other failure.
ReaDY
PI / O Power
Pfal Input / output signals are blocked due to a power failure.
FAiLure
PI / O Long
LPFL Input-output signals are blocked for a long time due to a power failure or other failure.
Power FAiLure
MINT Master INitialize Cascade communication with the previous block is in a state that requires balancing.
The next block in a cascade is in a state where the SV pushback operation should bring the CSV in accordance
SVPB SV PushBack
with the SV.
http://www.maxplant.ru/article/centum_fb.php#mode 5/13
11/7/2018 CENTUM VP function blocks
Regulators
Cal(calibration)
During maintenance or testing, the process variable (PV) or the calculated output value (CPV) can be manually
set by the operator.
BAD
BAD - a signal of poor quality.
PV overshoot
If the signal status is BAD, then its boundary value is substituted for the real signal.
http://www.maxplant.ru/article/centum_fb.php#mode 6/13
11/7/2018 CENTUM VP function blocks
Types of regulators
http://www.maxplant.ru/article/centum_fb.php#mode 7/13
11/7/2018 CENTUM VP function blocks
PI-HLD Sampling PI Controller Block Discrete PI controller.
PID- PID Controller Block with Batch
PID controller with batch switching.
BSW Switch
Two-Position ON / OFF
ONOFF Two-way control.
Controller Block
ONOFF- Enhanced Two-Position ON /
Improved on-off controller.
E OFF Controller Block
ONOFF- Three-Position ON / OFF
Three-way controller.
G Controller Block
ONOFF- Enhanced Three-Position ON /
Improved three-way controller.
GE OFF Controller Block
Time Proportioning ON / OFF
PID-TP Electric oven temperature control.
Controller
PD Controller Block with Manual
PD-MR Proportional differential controller with manual reset.
Reset
PI-
Blending PI Controller Block PI controller mixing process.
BLEND
PID-
Self-Tuning PID Controller Block Self-tuning PID controller.
STC
Manual Loader Block
Mld Manual Loader Block Manual control valve.
MLD- Manual Loader Block with Input
Manual valve control with process variable indication.
PVI Indicator
MLD- Manual Loader Block with AUTO
Manual control valve with automatic / manual switching.
SW / MAN SW
Two-Position Motor Control
MC-2 2nd position motor control for pump or gate valve.
Block
Enhanced Two-Position Motor
MC-2E Improved 2-position motor control for pump or gate valve.
Control Block
Three-Position Motor Control
MC-3 3-position motor control of the pump or valve. <
Block
Enhanced Three-Position Motor
MC-3E Improved 3-position motor control of the pump or valve.
Control Block
Signal setter block
RATIO Ratio set block Maintain a constant relationship between two variables.
PG-L13 13-Zone Program Set Block Set 13 different time settings.
BSETU-
Flow-Totalizing Batch Set Block Portioning dosing.
2
BSETU- Weight-Totalizing Batch Set
Portion weighing.
3 Block
Signal limiter block
VELLIM Velocity Limiter Block Limit the rate of increase of the signal.
Signal selector block
SS-H /
Signal selector block Compares 2 or 3 input signals and selects the minimum, average or maximum.
M/L
AS-H /
Auto Selector Block Compares 2 or 3 input signals and selects the minimum, average or maximum.
M/L
SS- Dual-Redundant Signal Selector
Selects one signal from the two reserved ones.
DUAL Block
Signal Distributor Block
Fout Cascade Signal Distributor Block Distributes the reference signal to 8 blocks.
Feedforward Signal Summing
Ffsum Sum the lead signal with the feedback signal.
Block
Non-Interference Control Output
Xcpl
Block
Split Control Signal Splitter Block Spreads a task signal into two signals with different ranges.
Alarm block
ALM-R Representative Alarm Block Controls the alarm of 16 other blocks.
Pulse Count Input Block
http://www.maxplant.ru/article/centum_fb.php#mode 8/13
11/7/2018 CENTUM VP function blocks
PTC Pulse Count Input Block Pulse counter.
Calculators
Types of calculators
Calculation Blocks
http://www.maxplant.ru/article/centum_fb.php#mode 9/13
11/7/2018 CENTUM VP function blocks
http://www.maxplant.ru/article/centum_fb.php#mode 10/13
11/7/2018 CENTUM VP function blocks
C with String I / O
Calculation Auxiliary Block.
3-Pole 3-Position Selector Switch
SW-33 3 pole 3 position switch.
Block
1-Pole 9-Position Selector Switch
SW-91 1 pole 9 position switch.
Block
DSW-
Selector Switch Block for 16 Data 16 settings selector
16
DSW-
Selector Switch Block for 16 Data 16 string set selector
16C
DSET Data Set Block Buffer for storing engineering value entered by the operator.
DSET- Data Set Block with Input
Buffer for storing and displaying engineering values entered by the operator.
PVI Indicator
BDSET-
1-Batch Data Set Block Batch job 16 digital settings
1L
BDSET-
1-Batch String Set Block Batch job 16 string settings
1C
BDSET-
2-Batch Data Set Block Batch job of two sets of 16 digital settings
2L
BDSET-
2-Batch String Set Block Batch job of two sets of 16 string settings
2C
BDA-L Batch Data Acquisition Block Batch collection of 16 digital settings
BDA-C Batch String Acquisition Block Batch collection of 16 string settings
ADL Station Interconnection Block Data transfer between two function blocks at different FCS control stations.
Sequential control
http://www.maxplant.ru/article/centum_fb.php#mode 11/13
11/7/2018 CENTUM VP function blocks
Logic chart block
LC64 Logic chart block Logic circuit: 32 inputs, 32 outputs, 64 logic elements.
External Connection Logic Chart
LC64-E Logic diagram with external connections.
Block
Sequential Function Chart - Sequential Function Chart
_SFCSW 3-Position Switch SFC Block
_SFCPB Pushbutton sfc block
_SFCAS Analog SFC Block
Switch Instrument Block - control units of various actuators
SI-1 Switch Instrument Block with 1 input.
SI-2 Switch Instrument Block with 2 inputs.
SO-1 Switch Instrument Block with 1 output.
SO-2 Switch Instrument Block with 2 outputs.
SIO-11 Switch Instrument Block with 1 input and 1 output.
SIO-12 Switch Instrument Block with 1 input and 2 outputs.
SIO-21 Switch Instrument Block with 2 inputs and 1 output.
SIO-22 Switch Instrument Block with 2 inputs and 2 outputs.
SIO-12P Switch Instrument Block with 1 input and 2 pulse outputs
SIO-22P Switch Instrument Block with 2 inputs and 2 pulse outputs.
SI-1E Enhanced Switch Instrument Block with 1 input.
SI-2E Enhanced Switch Instrument Block with 2 inputs.
SO-1E Enhanced Switch Instrument Block with 1 output.
SO-2E Enhanced Switch Instrument Block with 2 outputs.
SIO-11E Enhanced Switch Instrument Block with 1 input and 1 output.
SIO-12E Enhanced Switch Instrument Block with 1 input and 2 outputs.
SIO-21E Enhanced Switch Instrument Block with 2 inputs and 1 output.
SIO-22E Enhanced Switch Instrument Block with 2 inputs and 2 outputs.
SIO-
Enhanced Switch Instrument Block with 1 input and 2 pulse outputs
12PE
SIO-
Enhanced Switch Instrument Block with 2 inputs and 2 pulse outputs.
22PE
Sequence Auxiliary Block
Tm Timer block Measure time in seconds or minutes.
CTS Software Counter Block Event counter
CTP Pulse Train Input Counter Block Pulse counter.
CI Code Input Block Indication of an integer number, binary or BCD code of which is read from the inputs.
Conversion of an integer specified by the operator into a binary format with output to the
CO Code Output Block
outputs.
Rl Relational Expression Block
RS Resource Scheduler Block Controls uniform loading of limited production resources.
Valve Monitoring Block
VLVM Valve Monitoring Block Monitors the correct operation of the valve.
http://www.maxplant.ru/article/centum_fb.php#mode 12/13
11/7/2018 CENTUM VP function blocks
INDST3 Triple-Pointer Manual Station Indication of the process variable PV and control of the task SV and the output value MV.
Block
Sequence Faceplate Blocks
BSI Batch Status Indicator Block Indication phase sequence.
Extended 5-push-button
PBS5C Control of five buttons with indication.
switch block
Extended 10-Push-Button
PBS10C Control of ten buttons with indication.
Switch Block
Hybrid Faceplate Blocks
Extended Hybrid Manual It has the functionality of Triple-Pointer Manual Station Block (INDST3) and Extended 5-Push-
HAS3C
Station Block Button Switch Block (PBS5C).
System blocks
System Function Blocks
Model Title Purpose
FCS_CPU CPU Load Information Block CPU load monitoring.
FCS_COM Communication Load Information Block Network boot monitoring.
FCS_IOC I / O Load Information Block Monitoring of loading of communication with entrances exits.
FCS_SBL SEBOL Related Information Block SEBOL monitoring.
Yandex.Direct
3D models
lessons. Al
To learn more
http://www.maxplant.ru/article/centum_fb.php#mode 13/13