Ceiling Diffusers, Types ANK and ANKS


Types ANO and ANOS

oprema
10430 SAMOBOR
KRALJA KREŠIMIRA IV b.b.
H R V AT S KA
TEL: (**385 1) 33 62 513
FAX: (**385 1) 33 62 905
INDEX

Ceiling Diffuser, Type ANK oprema


C

D = A - 52

D - 55

ANK

35
A

Supply and return ceiling diffusers with fixed curved blades, type ANK, for
application in up to 4-m high rooms, are made of sheet steel and plastic coated Standard A C D
white, RAL 9010. Due to high induction these diffusers are very convenient for sizes [mm] [mm] [mm]
cooling of rooms with high temperature differences. Fixing with visible screws or
with a traverse (crossbeam). Volume control dampers are made of galvanised 1 244 208 192
sheet steel. At special request, volume control dampers can be made of pickled 2 300 264 248
sheet steel and lacquered black.
3 356 320 304
4 412 376 360
ANK 468 432 416
5
Ceiling diffuser with fixed curved 498
blades with no volume control
6 462 446
damper. 7 598 562 546
8 623 587 571
ANK - L
Ceiling diffuser with an opposed
blade action volume control damper,
type L. Damper blades are commonly
powered.

Installation arrangements, selection


ANK - KL diagrams and technical data at the
end of this register.
Ceiling diffuser with a volume control
damper type KL comprising two
individually adjustable flaps.

ANK - KNU

Supply ceiling diffuser ANK with a


combined flap-type damper and
equalising grid - type KNU, for
installation in dynamic air ducts.
Damper is supplied separately. Stub
duct between damper and diffuser is
supplied in the required length on
request.

Ordering Example: - Without plenum box, with a traverse - With plenum box
(crossbeam)
ANK 4 - KL - T
- Without plenum box The shape and dimensions
of the plenum box are - the
Traverse type same as for diffuser type
ANK 4 - KL (s. page 8)
KAK (see register 2/S3)
Damper type Damper type

Standard size Standard size

2/S2-02
INDEX

oprema Ceiling Diffuser Type ANK with 1, 2 or 3 Air Discharge Directions

D = A - 52

D - 55

ANK ... / 1
35
A

ANK ... / 2

Supply ceiling diffuser type ANK with 1, 2 or 3 air discharge directions,


suitable for up to 4-m high rooms. It is made of sheet steel and plastic coated
white, RAL 9010. Due to high induction these diffusers are very convenient
for cooling of rooms with high temperature differences. Fixing with visible
screws or with a traverse. Volume control dampers are made of galvanised
sheet steel. At special request, volume control dampers can be made of
pickled sheet steel and lacquered black. ANK .../1 ANK .../2 ANK .../3

2
Standard A C D Effective outlet areas (m)
ANK sizes [mm] [mm] [mm] A1 A2 A3 A4
Ceiling diffuser (no volume control 1 244 208 192 0,011 0,005 0,004 0,0027
damper), with 1, 2 or 3 air discharge 2 300 264 248 0,021 0,011 0,008 0,0046
directions. 3 366 320 304 0,033 0,015 0,011 0,0074
4 412 376 360 0,048 0,022 0,021 0,0110
5 468 432 416 0,067 0,031 0,024 0,0157
ANK - L 6 498 462 446 0,071 0,036 0,027 0,0182
Ceiling diffuser with an opposed 7 598 562 546 0,115 0,057 0,042 0,0293
blade action volume control damper, 8 623 587 571 0,127 0,060 0,044 0,0320
type L. Damper blades are commonly
powered.

ANK - KL
Selection diagrams, technical
Ceiling diffuser with a volume control
data and calculations - the same
damper type KL comprising two
as for ceiling diffuser type AND
individually adjustable flaps.
(see register 2/S1).

ANK - KNU Installation arrangements


see page 8 of this register.
Supply ceiling diffusers with
combined flap-type damper and
equalising grid type KN, for
installation in dynamic air ducts.
Damper is supplied separately. Stub
duct between damper and diffuser is
supplied in the required length on
request.

Ordering Example: - Without plenum box, with a traverse - With plenum box
- Without plenum box
ANK 4 / 2 – L – T
The shape and dimensions of
ANK 4 / 2 – L the plenum box are - the same
Traverse type as for diffuser type KAK (see
(s. page 8) register 2/S3)
Damper type
Damper type
Number of discharge directions
Number of discharge directions
Standard size
Standard size
2/S2-03
INDEX

Ceiling Diffuser Type ANO oprema


øC

D = A - 52

øD - 55

35
øA

Supply and return ceiling diffuser type ANO, suitable for up to 4-m high
rooms. It is made of sheet steel, plastic coated white, RAL 9010. Due to Standard ØA ØC ØD
high induction these diffusers are very convenient for cooling of rooms size [mm] [mm] [mm]
with high temperature differences. Fixing with visible screws or with a
traverse. Volume control dampers are made of galvanised or black- 1 244 208 192
lacquered sheet steel. At special request, volume control dampers can be 2 300 264 248
made of pickled sheet steel and lacquered black. 3 356 320 304
4 412 376 360
5 468 432 416
6 542 506 472
ANO 7 598 562 528
8 654 618 584
Ceiling diffuser with no volume
control damper.

Installation arrangements, selection


ANO - KL diagrams and technical data at the
end of this register.
Ceiling diffuser with a volume control
damper type KL comprising two
individually adjustable flaps. The shape and dimensions of the
plenum box (PK) see page 7 of
this register.

ANO-KNU

Supply ceiling diffuser with combined - With plenum box


flap-type damper and equalising grid, ANO 4 - L - PK - V / Ø - T - Z
type KNU, for installation in dynamic
air ducts. Damper is supplied Additional mark for
separately. Stub duct between sound-adsorbing material
damper and diffuser is supplied in the
Diffuser to plenum
required length on request. box fixing type:
- by a central screw: T
- by visible perimeter screws: V

Plenum box connection diameter


Ordering Example: Air connection
- horizontal:H
- vertical:V
- Without plenum box - Without plenum box, with a traverse
Plenum box
ANO 4 – KL ANO 4 – KL – T (with volume control damper)

Traverse type Additional mark for volume


Damper type control damper (if requested)
(s. page 8)
Control dampers of type KL and KNU are
Standard size Damper type not installed in diffuser version with PK

Standard size Standard size of diffuser

2/S2-04
INDEX

oprema Ceiling Diffuser Type ANKS

D - 55

ANKS 30

D = A - 52

Supply and return air, cone-shaped, ceiling diffuser type ANKS, suitable
for very high rooms (installed up to 4 m above floor). Made of sheet steel,
plastic coated white, RAL 9010. Due to high induction these diffusers are Standard A C D h
very convenient for cooling of rooms with high temperature differences. size [mm] [mm] [mm] [mm]
Fixing with visible screws or with a traverse. Volume control dampers are 244
1 208 192 40
made of galvanised sheet steel. At special request, volume control
dampers can be made of pickled sheet steel and lacquered black. 2 300 264 248 50
3 356 320 304 50
4 412 376 360 80
5 468 432 416 80
ANKS 6 498 462 446 120
Ceiling diffuser with no volume 7 598 562 546 120
control damper. 8 623 587 571 120

ANKS-L

Ceiling diffuser type ANKS with an


opposed blade action volume control
damper, type L. Damper blades are Installation arrangements, selection diagrams
commonly powered. and technical data at the end of this register.

ANKS-KL
Ceiling diffuser type ANKS with a
volume control damper type KL
comprising two individually
adjustable flaps.

ANKS-KNU

Supply ceiling diffuser type ANKS


with combined flap-type damper and
equalising grid type KNU, for
installation in dynamic air ducts.
Damper KNU is supplied separately.
Stub duct between damper and
diffuser is supplied in the required
length on request.

Ordering Example:

- Without plenum box - Without plenum box, with a traverse - With plenum box

ANKS 4 – KL ANKS 4 – KL – T The shape and dimensions of the


plenum box are same as for diffuser
Damper type Traverse type type KAK (see register 2/S3)
(s. page 8)
Standard size
Damper type

Standard size
2/S2-05
INDEX

Ceiling Diffuser Type ANOS oprema


ø C
D - 55

ANOS 30
h

ø D = A - 52

ø A

Standard ø A øC øD h
Supply and return air, cone-shaped, ceiling diffuser type ANOS, suitable size [mm] [mm] [mm] [mm]
for very high rooms (installed up to 4 m above floor). Made of sheet steel, 1 244 208 192 30
plastic coated white, RAL 9010. Due to high induction these diffusers are 2 300 264 248 43
very convenient for cooling of rooms with high temperature differences. 3 356 320 304 56
Fixing with visible screws or with a traverse. Volume control dampers are 4 412 376 360 70
made of galvanised sheet steel. At special request, volume control 5 468 432 416 84
dampers can be made of pickled sheet steel and lacquered black. 6 542 506 472 98
7 598 562 528 112
8 654 618 584 126

ANOS

Ceiling diffuser with no volume Installation arrangements, selection


control damper. diagrams and technical data at the end of
this register.

ANOS-KL

Ceiling diffuser type ANOS with a The shape and dimensions of the
volume control damper type KL plenum box (PK) see page 7 of this
comprising two individually register.
adjustable flaps.

ANOS-KNU

- With plenum box


Supply ceiling diffuser type ANOS
with combined flap-type damper and ANOS 4 - L - PK - V / ø - T - Z
equalising grid type KNU, for
installation in dynamic air ducts. Additional mark for
Damper KNU is supplied separately. sound-adsorbing material
Stub duct between damper and Diffuser to plenum box
diffuser is supplied in the required fixing type:
length on request. - by a central screw: T
- by visible perimeter screws: V

Plenum box connection diameter


Ordering Example: Air connection
- horizontal:H
- vertical:V
- Without plenum box - Without plenum box, with a traverse
Plenum box
(with volume control damper)
ANOS 4 – KL ANOS 4 – KL – T
Additional mark for volume
Damper type Traverse type control damper (if requested)
(s. page 8) Control dampers of type KL and KNU
Standard size Damper type are not installed in diffuser version with PK

Standard size Standard size of diffuser

2/S2-06
INDEX

oprema Plenum Boxes for Ceiling Diffusers


Type ANO and ANOS

øD+22
ød Vertical air
connection Horizontal air
connection

ød

Hh
Hv
øD+22

110
D dimension given on page 6

Plenum box (PK) is attached to the diffuser types ANO and ANOS in order to make a ceiling diffuser set with optimum airflow
characteristics. The plenum box, normally made of galvanised sheet steel, contains a volume control damper. Ceiling diffusers
can be attached to the plenum box by a central screw to a traverse, or by visible screws along the perimeter. Sound absorption is
supplied on request. It is recommended that the shaded dimensions of plenum boxes are selected from the table.

Standard D Hv Hh Vmin Vmax


size (mm) (mm) (mm) (m3/h) (m3/h)
78 200 220 31 98
1 98 200 240 68 217
123 200 265 96 306
98 200 240 57 181
2 123 200 265 107 342
158 200 300 177 565
123 200 265 93 296
3 158 200 300 176 564
198 200 340 289 925
158 200 300 137 439
4 198 200 340 277 886
248 225 390 429 1372
198 200 340 193 617
5 248 225 390 435 1390
313 260 455 603 1930
198 200 340 262 839
6 248 225 390 435 1390
353 280 490 819 2621
248 225 390 344 1100
7 313 260 455 692 2215
398 300 540 1074 3438
248 225 390 414 1325
8 353 280 495 880 2817
448 325 590 1294 4140

2/S2-07
INDEX

Installation Arrangements of Ceiling Diffusers


Type ANK, ANO, ANKS, and ANOS oprema
D+12 D+22

D
D

Direct installation of ceiling diffusers to the Installation of ceiling diffusers of type ANK and ANKS by
duct by visible screws. using an installation subframe and visible screws.

D+21
D+12 T3
T1 D+17

130 130

30

D A

Installation of ceiling diffusers of type ANK, Installation of ceiling diffusers of type ANK and ANKS, size
ANKS, ANO, and ANOS in brick wall or in 6, 7, and 8, in the standard plates false ceiling by using a T3
wooden ceiling by using a T1-type traverse. -type traverse and special installation subframe.

By installation of ceiling diffusers type ANK and ANKS with


a volume control damper of type L, the duct cross section
MxN M x N should be selected from the table:
T2
Standard M×N
size [mm]
1 165×140
130 2 165×196
3 245×252
4 325×308
5 325×364
6 405×394
D
7 485×494
8 525×519

T2 D-50

130

Installation of ceiling diffusers of type ANO and


ANOS with a volume control damper of type KL in a Installation of a ceiling diffuser to a stub duct with a
stub duct by using a T2-type traverse. volume control damper of type KNU installed to the duct.

Note:
In order to achieve better airflow characteristics of ceiling diffusers, it is recommended to install them with
plenum boxes (see page 7).

2/S2-08
INDEX

oprema
1 Selection Diagram for Ceiling Diffusers, Type ANK 3 Induction Diagram

Eff
Core velocity vL (m/s) 2 2

ec
tiv
0.2 5
0.3 0.4 0.5 0.7 1

e
Induction i

jet
1

ve
3

lo
cit
5

y ve
4
6

f
(m
8 5

/s)
2 10 6
40 30 20
7
8
3 9
10
Throw L (m)

0.2 0.3 0.4 0.5 0.75 1


Core velocity vL (m/s)
4

5
2 Table of Effective
6 4 b0.2 -diagram
Outlet Areas Aef (m²)
Core velocity vL (m/s)
7
1 0.75 0.5 0.4 0.3 0.2
8 0.5
Standard Aef
9 2
10 0.4
size [m ]
1 0.0104
0.3 2 0.0185

b0.2 (m)
. 3 0.0295
Supply air volume flow rate V (m3/h) 4 0.0440
0.2
5 0.0628
0
0

6 0.0728
20
10

15

30

0
40

1 0.1 7 0.1175
8 0.1280
0
50

0
1 2 3 4 5 6 7 8 9 10
Throw L (m)
2
0
80

5 Vertical Air-stream Velocity


Between Two Ceiling Diffusers
00
10

Example:
0.8
3 0.7

Vertical air-stream velocity vh (m/s)


Co Given: ANK- KNU
re
00
Standard size

0.6 ve
loc
Throw: L = 3.5 m
15

ity Air supply volume: V = 2100 m³/h


0.5 vL (
4 m/ Core velocity: vL = 0.75 m/s
00

s)
Distance from the ceiling: h=1m
20

0.4

1
5 0.3 0.7
5 Solution:
00

6
30

0.5 Diag.1: Size 5; vef = 9 m/s


Diag.3: Induction i = 11
10 0.2
0.4
9 Diag.4: b0.2= 0.5 m
7 Diag.5: Velocity at distance h = 1 m :
8 0.3 vh= 0.44 m/s
8 7 Diag.6.2: Pressure drop Dptot = 75 Pa
2.5 3 4 5 6 Diag.6.3: Sound power level 47 dB(A)
1 1.5 2 0.2
(Damper 100% open)
0.1
Effective jet velocity vef (m/s) 0.5 0.7 1.0 1.5 2.0
Distance from the ceiling h (m)

2/S2-09
INDEX

Technical Data: Ceiling Diffuser Type ANK oprema


6 Pressure Drop and Sound Power Level

6.1 Pressure Drop for ANK-KL 6.2 Pressure Drop for ANK-KNU

100 100

90 90

25 %

%
80 80

50

0
10
%
70 70

25

Pressure drop Dptot (Pa)


Pressure drop Dptot (Pa)

n
op e
60 60

50

%
en

%
0
op

10
50 50

ting
40 40

ing

se t
ett

er
rs
30 30

mp
e
mp

Da
20 20

Da
10 10

0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10

Effective jet velocity vef (m/s) Effective jet velocity vef (m/s)

6.3 Sound Power Level 6.4. Correction Values for Diagram 6.3

Standard size 1 2 3 4 5 6 7 8

%
Occupied zone %
50 0
10 %

% 25

% %
0
10

50 50
en
Correction dB(A) -3 -3 -2 -1 0 0 4 5

op
25
Nomenclature:

%
Sound power level dB (A)]
40

g
ttin
se
V (m³/h) Supply air volume flow rate

er
mp
30
vef (m/s) Effective jet/outlet velocity

Da
In Sound power level diagram:
Aef (m²) Effective outlet area - black lines: for ANK-KL
- orange lines: for ANK-KNU
20
L (m) Throw
vL (m/s) Maximum core velocity at distance L 0 1 2 3 4 5 6 7 8 9 10
(avg. velocity ~ 0.3 vL ) Effective jet velocity vef (m/s)
Total air volume in motion
i Induction = ----------------------------------
Supply air volume

D tZ (K) Temperature difference between supply air temperature Note:


tZ and room temperature tP Pressure drop and acoustic data for ceiling diffusers of type ANK and ANK-L
are given in the register 2/S3 (see KAK and KAK-L)
D tL (K) Maximum temperature difference between the core
temperature tL and room temperature tP
b0,2 (m) Distance from the ceiling to the point where the velocity
is still 0.2 m/s
vh (m/s) Vertical air-stream velocity between two ceiling
diffusers, at distance h from the ceiling
h (m) Distance from the ceiling (the level of air supply) to the
occupied zone

2/S2-10
INDEX

oprema
1 Selection Diagram for Ceiling Diffusers, Type ANO 3 Induction Diagram
3 2
1
4
5
6

Eff
Core velocity vL (m/s)
2

ec
tiv
0.2 5
0.3 0.4 0.5 0.7 1 8

e
Induction i
1

je t
10

ve
3

lo
cit
y ve
15 4

f
(m
5

/s)
20
2 6
25
7
30 8
3 9
10
Throw L (m)

0.2 0.3 0.4 0.5 0.75 1


Core velocity vL (m/s)
4

5
6 4 b0.2 -diagram 2 Table of Effective
Outlet Areas Aef (m²)
7 Core velocity vL (m/s)
8 1 0.75 0.5 0.4 0.3 0.2
0.5
9 Standard Aef
2
10 size [m ]
0.4

1 0.0085
0.3 2 0.0157
.

b0.2 (m)
Supply air volume flow rate V (m3/h) 3 0.0257
4 0.0381
0.2
5 0.0536
0
0

0
20
10

15

30

6 0.0730
0

1
40

0.1 7 0.0955
8 0.1150
0
50

0
1 2 3 4 5 6 7 8 9 10
0
60

Throw L (m)
2
0
80

5 Vertical Air-stream Velocity


00

between Two Ceiling Diffusers


10

Example:
3 0.8 Given: ANO- KNU
0.7 Co
re
00
Standard size

ve Throw: L = 2.0 m
0.6 loc
15

ity Air supply flow rate: V = 500 m³/h

Vertical air-stream velocity vh (m/s)


vL (
4 0.5 m/ Core velocity: vL = 0.3 m/s
s)
00

Distance from the ceiling: h = 0.6 m


20

0.4
5

1
0.7 Solution:
0.3
5
00

6 Diag.1: Size 3; vef = 5 m/s


30

0.5 Diag.3: Induction i = 12


0.2 Diag.4: b0.2= 0.15 m
7
00

0.4 Diag.5: Velocity at distance h = 0.6 m


40

: vh= 0.27 m/s


8 0.3
1 1.5 2 2.5 3 4 5 6 7 8 9 10 Diag.6.2: Pressure drop Dptot = 23 Pa
Diag.6.3: Sound power level 30 dB(A)
0.2 (Damper 100% open)
0.1
Effective jet velocity vef (m/s) 0.5 0.7 1.0 1.5 2.0
Tab.6.4: Correction: 30 - 1 = 29 dB(A)

Distance from the ceiling h (m)

2/S2-11
INDEX

Technical Data: Ceiling Diffuser Type ANO oprema


6 Pressure Drop and Sound Power Level

6.1 Pressure Drop for ANO-KL 6.2 Pressure Drop for ANO-KNU

100 100

90 90

25 %

%
80 80

50

0
10
%
70 70

25

pen
Pressure drop ptot (Pa)
Pressure drop ptot (Pa)
60 60

50

%o
en

0
op

10
50 50

ting
%

se t
ing
40 40

ett

er
rs

mp
30 30

e
mp

Da
20 20

Da
10 10

0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
Effective jet velocity vef (m/s) Effective jet velocity vef (m/s)

6.3 Sound Power Level 6.4 Correction Values for Diagram 6.3

Standard 1 2 3 4 5 6 7 8

%
Occupied zone % size
50 0
10 %

% 25

% %
0

en
10 Correction

50 50
-2 -2 -1 0 2 3 4 5

op
dB(A)

25
%
Nomenclature:

Sound power level dB (A)]


40

i ng
V (m³/h) Supply air volume flow rate

ett
rs
vef (m/s) Effective jet/outlet velocity

e
mp
30
Aef (m²) Effective outlet area

Da
In Sound power level diagram:
L (m) Throw - black lines: for ANO-KL
- orange lines: for ANO-KNU
20
vL (m/s) Maximum core velocity at distance L
(avg. velocity ~ 0.3 vL ) 0 1 2 3 4 5 6 7 8 9 10
Effective jet velocity vef (m/s)
Total air volume in motion
i Induction = -----------------------------------
Supply air volume

DtZ (K) Temperature difference between supply air


temperature tZ and room temperature tP

DtL (K) Maximum temperature difference between the core


temperature tL and room temperature tP
b0,2 (m) Distance from the ceiling to the point where the
velocity is still 0.2 m/s

vh (m/s) Vertical air-stream velocity between two ceiling


diffusers, at distance h from the ceiling

h (m) Distance from the ceiling (the level of air supply) to


the occupied zone

2/S2-12