Understanding Voltage Regulators

You are here: > Siemens USA > Smart Grid Solutions > Newsletters > Archive > Understanding Voltage Regulators

Understanding Voltage Regulators


April 2010

Electric Power International - Quality and Reliability: Ongoing Challenge for Distribution Systems
During initial operation, most utility and industrial electrical distribution systems present few problems with the voltage supplied to their loads. Progressive expansion, load growth and
economic considerations eventually impose voltage conditions on these systems which are less than ideal. This can cause electric equipment to operate at reduced efficiency and
overall power costs to rise. Increased industrial use of electronic equipment with its demand for voltage within rather critical limits, compounds the problem. Step-type voltage
regulators are increasingly being used to solve this problem.
Theory of Operation
A step-type voltage regulator provides essentially in-phase voltage regulation (Fig.1). Regarding its construction, it can be compared to a basic auto-transformer, with its exciting
winding connected across the line. This exciting winding in turn excites the serires winding by inducing voltage. The series winding, with no further modification, is capable of raising or
lowering the system voltage by 10%, depending on whether it is connected in additive or subtractive polarity.

To obtain regulation in finer steps, the series winding is tapped into eight 1.25% sections. The taps are connected to stationary contacts on a dial switch panel (Fig.2).
In order to tap this voltage without breaking the load current, a set of two moving fingers are mechanically ganged together and physically spaced to that they can form a bridge
between stationary contacts or be on the same stationary contact.

The moving fingers are connected to the two ends of a center-tapped preventive autotransformer that allows tap changes to be made without breaking load current. The
autotransformer also provides a step size of 0.625% by introducing a bridging position between each 1.25% tap; this gives 10% regulation in sixteen o.625% steps from the top to the
bottom of the series winding. Finally, the reversing switch, which connects the series winding in either additive or subtractive polarity, provides + or - 10% regulation in thirty-two
0.625% steps.
Continuous control of the voltage-regulator output is obtained by an automatic control system. Output voltage of the regulator is first sensed by a potential transformer (PT) or a tertiary
winding (in the case of ANSI Type B design units) which steps the voltage down to a standard utilization level of 120V That voltage is then applied to a control circuit through a tapped
sensing transformer which permits operation at any voltage between 106 and 134 V.

https://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/pages/understanding-voltage-regulators.aspx 1/5
Using microprocessor-based controls, the output of the PT is converted
4/20/2019 to either a derived
Understanding average
Voltage or a true- root-mean-square
Regulators Smart Grid Solutions(rms) value by a precision full wave rectifier. These
- Siemens
values vary directly with the ac output of the regulator and are compared to a user-defined set point (voltage level setting). If it is above the fixed reference, power is applied through a
time-delay circuit to the lower winding of the regulator tap-changing motor, and the regulator lowers its output voltage. Conversely, if the output of the circuit is low, the regulator raises
its output voltage.
Application
Because the voltage change caused by one tap change is 0.625% at 120V or 0.75 V, a bandwidth setting is required for proper operation. Possible bandwidth settings on a voltage
regulator are determined by the size of the regulator step, because a smaller one would cause excessive tap changes as the unit searches for the nominal voltage (referred to as
"hunting").
A one-step bandwidth is impractical because any small increase in the size of the step-- such as from increased excitation voltage -- also results in hunting. The smallest practical
bandwidth is therefore somewhat larger than a one- or two-step voltage band. For regulators with 0.625% steps, the bandwidth would be 1.5% or +/- 0.75 V.
Many system voltage fluctuations correct themselves. Example: When a motor starts, it draws a high current that causes the voltage to drop; however, as the motor comes up to
speed, the current decreases and the voltage increases. To prevent the regulator from "chasing" this type of fluctuation, a time delay is introduced to the control system, which allows
the regulator to "wait and see" before initiating a tap change. For flexibility, this time delay is adjustable in 10-sec increments from 10 to 180 seconds.
As a general rule, regulators are located as close as possible to the load center. The farther away from the load, the greater the voltage drop that can be introduced between the
regulator and the load. But practical considerations may require that the regulator be located some distance from the load. In this case, it is necessary to add a line-drop compensator
to the control circuit to compensate for the voltage drop. With the line-drop compensator, a regulator minimizes the effects of resistance and reactance line drops and improves voltage
at the load center. Also, average voltage at other points along the distribution line is obtained.
Note that the voltage drop is a function of load current; therefore, the regulator must be able to measure current and estimate the corresponding voltage drop. In addition to the current
transformer, a resistor and reactor are added to the regulator control compensator circuit. These two circuit elements are variable and are adjusted to supply the necessary values to
each individual application.

Figure 2
2. To obtain regulation in smaller steps, the series winding is tapped into eight 1.25% sections; these taps are connected to stationary contacts on a dial switch panel
Current from the current transformer flows through a portion of the resistance and reactance elements of the compensator and a voltage drop is introduced into the control circuit. This
voltage adds or subtracts from the voltage in the voltage regulating relay and causes the regulator control to raise or lower the regulator output voltage.
By properly applying the resistance and reactance elements, the voltage rise or drop in the regulator control circuit will be proportional to the drop in the line caused by the load
currents and the resistance and reactance in the lines. Thus, the regulator maintains a constant voltage at the selected load center and also reduces the voltage swing at the end of
the line.
The calculation of correct compensator setting is based upon the size and spacing of conductors and the distance to the load center. When these values are known, they can be
substituted into formulae supplied by the manufacturer to determine the proper compensator settings.
The industry standard for the range of regulation is + or - 10%. This range has proved to be adequate to correct the majority of voltage variations in electrical systems. Further changes
can be made to the system if better regulation is required -- such as stringing heavier conductor to reduce load current, which reduces the voltage changes throughout the system.
Sizing
In selecting the correct regulator for an application, confusion can sometimes arise regarding the kVA rating required because regulators are rated in terms of kVA of regulation, not
system kVA. Regulator kVA is a function of the current and voltage measured at the regulator and the percent regulation it delivers. Thus, single-phase kVA is equal to the product of
the voltage applied across the exciting winding, rated line current, and percent regulation, divided by 1000:

where E= volts applied to the regulator and I= line amperes.


For example, a 100-A primary bus is connected to a 13,800 Y/7960-V circuit. For this system, the regulator is connected line-to-ground and three 7960 volt regulators would be
required. According to the equation, the regulator kVA would be 79.6.
For a similar circuit connected to a 13 800-V delta, the regulator is connected line-to-line and three 13 800-V units could be used resulting in a regulator kVA of 138.
From the example, note that for the same transformer kVA, a different regulator kVA is required for a wye-connected system than for a delta-connected system. Two regulators rather
than three, may be used for delta-connected systems. Connected in open-delta, they will deliver individual phase regulation on two phases while the voltage on the third phase will be
the average of the others.
The kVA of a 3-phase regulator is equal to the square foot of three times the product of the line-to-line voltage, the line current, and the percent regulation, divided by 1000. Using the
same circuit described previously:

This calculation of the 3-phase regulator kVA also provides a check for single-phase kVA calculations. The combined kVA of three single-phase regulators connected in grounded wye
will always be equal to the 3-phase regulator kVA for the system. Two regulators connected in open-delta to a 3-phase system, on the other hand, will always have a combined kVA
greater than the comparable 3-phase regulator kVA.

04/01/2010
https://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/pages/understanding-voltage-regulators.aspx 2/5
4/20/2019 Understanding Voltage Regulators - Smart Grid Solutions - Siemens
>
Share this Page: > > > >

Archived Topics from Previous Newsletters

Power Transformer Topics


> Alternative Liquid Application in Power Transformers - Natural Ester Fluids
> Bullet Resistant Power Transformers
> Collecting Transformer Dielectric Fluid Samples...
> Dissolved Gas Analysis
> Field Drying of Transformer Insulation
> Insulating Oil
> Legacy Transformer
> Oil Filled and Air Core Shunt Reactors
> Pressure Relief Devices for Transformers
> Processing Transformer Insulation
> Reading a Transformer Nameplate
> SITRAM® DRY
> Transformer Bushing Replacement
> Transformer Condition Ranking
> Transformer Conservator Tanks
> Transformer Contingency Planning
> Transformer Dew Point Measurements
> Transformer Dew Point Measurements Part 2
> Transformer Gaskets
> Transformer Monitoring and Diagnostics
> Transformer Receiving Inspection
> Welding on an Oil-filled Transformer
> Winding Temperature Simulation System

Load Tap Changer Topics


> Ferranti Packard On Load Tap Changer Upgrades
> TLF and TLS Tap Changer Upgrades

Low-Voltage Topics
> Low-Voltage Circuit Breaker Preventative Maintenance
> Low-Voltage Replacement Circuit Breaker Solutions
> Static Micro-ohm Resistance Readings

Medium-Voltage Topics
> 3AF 3AH Operators Maintenance
> Air Magnetic Breakers
> Allis Chalmers AIS Switchgear
> Allis Chalmers D and F Switchgear
> Anatomy of a Short Circuit
> Arc Flash Hazard Analysis
> Arc Flash Hazard Labels
> Arc Furnace Switching Applications
> Capacitor Trip Devices
> Circuit Breakers or Contactors
> Circuit Breaker Standards
> Closed Door Racking Systems
> GMI Breakers Go to College
> Ground Sensor Current Transformer Cable Routing
> Heat Generation Estimation for Historic Switchgear
> Interrupter Switch Technology Comparison
> Medium-Voltage Breaker Replacement
> Medium-Voltage GCB Replacement
> Medium-Voltage Power Systems
> Outdoor Switchgear
> SARRACS
> SDV Free Standing Vacuum Breakers
> Siemens Closed Door Racking Solutions
> Survey Air Magnetic Breakers
> Tech Topics
> TVA Sequioa Replaces ITE HK Breakers
> Type SP SF6 Power Circuit Breakers
> Vacuum Loss

High-Voltage Topics
> 3AT Maintenance
https://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/pages/understanding-voltage-regulators.aspx 3/5
> AC BZO oil circuit breaker
4/20/2019 Understanding Voltage Regulators - Smart Grid Solutions - Siemens
> BZO 63kA Uprate
> BZO Maintenance
> Controlled Switching with the Siemens Phase Synchronizing Device (PSD)
> Digital Radiography
> Essentials of SF6 Monitoring
> Hydraulic System Maintenance on Siemens Legacy Circuit Breakers
> kA Rated Circuit Breakers and Switchgear
> Maintenance and Adjustment Tips on BZO 242-3 Contact Rod
> Power Factor Testing of High Voltage SF6 Breakers
> Replacement Current Transformers on SP--SPS--SPS2--SF6 Power Circuit Breakers
> SF6 Breaker Maintenance
> SF6 Gas in Medium-Voltage Switchgear
> TCP HV SF6 Power Circuit Breaker

Voltage Regulator Topics


> Insulating Oil in Siemens Voltage Regulators
> Understanding Voltage Regulators
> Voltage Regulator Control Panel MJ4A
> Voltage Regulators Drive Springs

Protective Relay Topics


> Detecting Fast Power Swing Frequencies
> New Protection Method for Automated Distribution Feeders
> SIPROTEC-7SJ62
> Stator Ground Fault Protection
> Substation Simulator

Asset Management Topics


> Allis Chalmers/Load Tap Changer (LTC) Training Programs
> ARMA Services
> Cabinet Heaters
> Electrical Equipment Lifespan
> Kenett Power Unit
> Labor Resource Planning
> Maintenance Planning: NERC Reliability Standard PRC 005-6 Compliance
> Maintenance Training
> Power Circuit Breaker Training
> Refurbishment and Upgrade Solution for TD Equipment
> Transformer Condition Ranking
> Transformer Contingency Planning
> Voltage Regulator Training

About Our Authors


> Aasim Atiq
> Andre Smit
> Doug Edwards
> Jeff Phelan
> Jerrod Overcash
> Jim McIver
> Juan Acosta
> Keith Flowers
> Larry Kirchner
> Michael Miller
> Paloma Mendoza
> Rodney Fickler
> Stephen Bosak
> Ted Olsen
> Todd Rittenhouse
> Tom Melle
> Yuri Rossini
> IEEE PES Switchgear Committee Appointments

Contact us
> Customer Support
> tdguardian.ptd@siemens.com

https://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/pages/understanding-voltage-regulators.aspx 4/5
4/20/2019
Did this information help you? yes no Understanding Voltage Regulators - Smart Grid Solutions - Siemens

© 1996-2019

https://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/pages/understanding-voltage-regulators.aspx 5/5

You might also like