Technical Report
2A-150-JD-801
Investigation of the situation when the both
instrument air compressors (NG-01) operates
simultaneously
Document No:
2014-MMAC-TR-031/IAS
TABLE OF CONTENTS
1. Equipment Description
Tag Number : 2A-150-JD-801
Functional Unit : 2A-150-KC-001A/B
Area : NG-01
Equipment Description : Siemens PLC S7-200
Serial number :
2. Historical Data
The simultaneously occurrence in the local panel of the instrumental air
compressors of the following indication:
- Compressor A – “Main” local indication (ULKC 01A-5M);
- Compressor B – “Main” local indication (ULKC 01B-5M);
3. Work Description
On 28th April 2014, the responsible for the ECS and the Instrumentation team
start the investigation on this subject.
2. The reset one by one of the both PLCs, by STOP command from the local
CPU button.
3. Start one by one of the both PLCs, by RUN command from the local CPU
button
5. Conclusions
The redundant communication between the PLC S7-200 (A & B), it is based on
the PPI port and it hasn’t a specialized card for the synchronization. For this
reason, any disruption in the communication or commands can affect the data
communication between PLCs.
The causes of this event can be understood with the following pictures:
Any changing in the PLC-B OK status, due un-properly commands, can inhibit
the synchronization of the PLC-A with PLC-B.
Moreover, at this situation is added the internal clock for cross-over of the
compressor by time can generate a cross reference loop that will keep the active
PLC in between sequence.
The alternative changing (Set/Reset) of the M7.4, generated by the PLC cycles,
will get the alternative activation of the MAIN lamps for both compressors.
6. Recommendations
The main recommendation is to respect the requests from the Instrumental air
compressor Operation Manual (see attachment).
Regarding the best practice PLC S7-200 functionality:
1. For the prevention of any CPU’s cumulative errors, shall be included in the
Preventive Maintenance procedure, a special activity for the saving of the
alarms on the field portable workstation (PG) and for the testing of the
To prevent any other combination it is more safety to use a single switch button
(with different internal contacts) for Auto A + B and Manual A + B or a common
software connection in the PLC for both signals. In this manner, the both air
compressors will be only in MAN or AUTO mode.
3. To avoid a long functionality of the compressors in other operation mode
than AUTO, this situation can be software added in one of the existed DO-
Remote contact signalization:
- General Alarm (K10);
- Status (K11);
- PLC error (K16);
4. The un-synchronization phenomenon can appear frequently due external
or internal causes and the redundant PLC can’t make the switchover in
time. For this reason the PLC network can be upgraded to MPI or Profibus
connection and the synchronization can be made more accuracy.
7. References