Project: ETAP Page: 1

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase, LG, LL, & LLG Fault Currents

Swing V-Control Load Total

Number of Buses: 13 0 112 125

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total

Number of Branches: 14 0 0 99 0 0 113

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 2 0 0 37 0 39

System Frequency: 50.00

Unit System: Metric

Project Filename: HKN Sarsang

Output Filename: D:\Gridtect\Projects\2018\P - HKN Sarsang Block\HKN Sarsang\SC.SI2S


Project: ETAP Page: 2

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Global 20

Cable / Busway Resistance: Yes Global 20


Project: ETAP Page: 3

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 Load 0.400 0.410 1 100.00 -30.00


Bus2 Load 0.400 0.400 1 100.00 0.00
Bus3 SWNG 0.400 0.400 4 100.00 0.00
Bus4 Load 0.400 0.400 1 100.00 -30.00
Bus5 Load 0.400 0.400 1 100.00 0.00
Bus6 Load 0.400 0.420 1 100.00 -30.00
Bus7 SWNG 0.400 0.400 14 100.00 0.00
Bus8 Load 0.400 0.400 1 100.00 0.00
Bus9 Load 0.400 0.400 1 100.00 0.00
Bus10 Load 0.400 0.400 1 100.00 -30.00
Bus11 Load 0.400 0.400 1 100.00 0.00
Bus12 Load 0.400 0.410 1 100.00 -30.00
Bus13 Load 0.400 0.400 1 100.00 0.00
Bus14 Load 0.400 0.400 1 100.00 0.00
Bus15 Load 0.400 0.400 1 100.00 0.00
Bus18 Load 0.400 0.410 1 100.00 -60.00
Bus19 Load 0.400 0.400 1 100.00 0.00
Bus20 Load 0.400 0.400 1 100.00 0.00
Bus21 Load 0.400 0.410 1 100.00 -30.00
Bus22 Load 0.400 0.410 1 100.00 -30.00
Bus23 Load 0.400 0.431 1 100.00 -60.00
Bus24 Load 0.400 0.400 1 100.00 0.00
Bus25 Load 0.400 0.410 1 100.00 -30.00
Bus26 Load 0.400 0.400 1 100.00 0.00
Bus27 Load 6.600 6.600 1 100.00 0.00
Bus28 Load 0.400 0.420 1 100.00 -60.00
Bus29 Load 6.600 6.600 1 100.00 0.00
Bus30 Load 0.400 0.420 1 100.00 -60.00
Bus31 Load 0.400 0.420 1 100.00 -30.00
Bus32 Load 0.400 0.400 1 100.00 0.00
Bus33 Load 0.400 0.420 1 100.00 -30.00
Bus34 Load 0.400 0.400 1 100.00 0.00
Bus35 Load 0.400 0.420 1 100.00 -30.00
Bus36 SWNG 0.400 0.400 5 100.00 0.00
Bus37 Load 0.400 0.420 1 100.00 -60.00
Bus38 SWNG 0.400 0.400 6 100.00 0.00
Bus39 Load 0.400 0.410 1 100.00 -60.00
Bus40 SWNG 0.400 0.400 7 100.00 0.00
Bus41 Load 0.400 0.410 1 100.00 -30.00
Bus42 Load 0.400 0.410 1 100.00 -30.00
Bus43 Load 0.400 0.420 1 100.00 -30.00
Project: ETAP Page: 4

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus44 Load 0.400 0.410 1 100.00 -30.00


Bus45 Load 0.400 0.420 1 100.00 -30.00
Bus47 Load 0.400 0.420 1 100.00 -30.00
Bus48 Load 0.400 0.420 1 100.00 -30.00
Bus49 Load 0.400 0.420 1 100.00 -30.00
Bus50 Load 0.400 0.420 1 100.00 -60.00
Bus52 Load 0.400 0.431 1 100.00 -60.00
Bus53 Load 0.400 0.400 1 100.00 0.00
Bus54 Load 0.400 0.400 1 100.00 0.00
Bus56 Load 0.400 0.400 1 100.00 0.00
Bus57 Load 0.400 0.400 1 100.00 0.00
Bus59 Load 0.400 0.400 1 100.00 0.00
Bus60 Load 0.400 0.410 1 100.00 -30.00
Bus61 Load 0.400 0.431 1 100.00 -60.00
Bus62 Load 0.400 0.400 1 100.00 0.00
Bus63 Load 0.400 0.400 1 100.00 0.00
Bus64 Load 0.400 0.400 1 100.00 -30.00
Bus65 Load 0.400 0.410 1 100.00 -30.00
Bus66 Load 0.400 0.400 1 100.00 0.00
Bus67 Load 0.400 0.410 1 100.00 -30.00
Bus68 Load 0.400 0.431 1 100.00 -60.00
Bus69 Load 0.400 0.410 1 100.00 -30.00
Bus70 Load 0.400 0.431 1 100.00 -60.00
Bus71 Load 0.400 0.400 1 100.00 0.00
Bus72 Load 0.400 0.410 1 100.00 -30.00
Bus73 Load 0.400 0.410 1 100.00 -30.00
Bus75 Load 0.400 0.410 1 100.00 -30.00
Bus76 Load 0.400 0.400 1 100.00 0.00
Bus78 Load 0.400 0.410 1 100.00 -30.00
Bus79 Load 0.400 0.410 1 100.00 -30.00
Bus80 Load 0.400 0.410 1 100.00 -30.00
Bus84 SWNG 0.400 0.400 10 100.00 0.00
Bus86 Load 0.400 0.410 1 100.00 -30.00
Bus88 SWNG 0.400 0.400 8 100.00 0.00
Bus90 Load 0.400 0.410 1 100.00 -30.00
Bus91 Load 0.400 0.410 1 100.00 -30.00
Bus92 Load 0.400 0.410 1 100.00 -30.00
Bus93 Load 0.400 0.410 1 100.00 -30.00
Bus94 Load 0.400 0.410 1 100.00 -30.00
Bus95 Load 0.400 0.410 1 100.00 -60.00
Bus96 Load 0.400 0.410 1 100.00 -30.00
Bus97 Load 0.400 0.410 1 100.00 -60.00
Bus99 SWNG 0.400 0.400 13 100.00 0.00
Project: ETAP Page: 5

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus100 Load 0.400 0.400 1 100.00 0.00


Bus104 Load 0.400 0.400 1 100.00 0.00
Bus105 Load 0.400 0.400 1 100.00 0.00
Bus106 SWNG 0.400 0.400 9 100.00 0.00
Bus107 Load 0.400 0.410 1 100.00 -30.00
Bus109 Load 0.400 0.410 1 100.00 -30.00
Bus111 Load 0.400 0.410 1 100.00 -30.00
Bus114 Load 0.400 0.400 1 100.00 0.00
Bus115 Load 0.400 0.400 1 100.00 0.00
Bus116 Load 0.400 0.400 1 100.00 0.00
Bus117 Load 0.400 0.400 1 100.00 0.00
Bus131 Load 0.400 0.400 1 100.00 0.00
Bus132 Load 0.400 0.400 1 100.00 0.00
Bus133 Load 0.400 0.400 1 100.00 0.00
Bus144 Load 0.400 0.400 1 100.00 0.00
Bus151 Load 0.400 0.420 1 100.00 -30.00
Bus152 SWNG 0.400 0.400 11 100.00 0.00
Bus153 SWNG 0.400 0.400 12 100.00 0.00
Bus157 Load 0.400 0.420 1 100.00 -30.00
Bus162 Load 0.400 0.420 1 100.00 -30.00
Bus163 Load 0.400 0.431 1 100.00 -60.00
Bus165 SWNG 0.400 0.400 1 102.50 0.00
Bus166 SWNG 0.400 0.400 1 102.50 0.00
Bus167 Load 0.400 0.400 1 100.00 0.00
Bus168 Load 0.400 0.400 1 100.00 0.00
Bus169 Load 0.400 0.400 1 100.00 0.00
LSP-DB-B3 Load 0.400 0.431 1 100.00 -60.00
LSPDB-B1 Load 0.400 0.410 1 100.00 -30.00
MCC-B1 BUS A Load 0.400 0.400 1 100.00 0.00
MCC-B2 Load 0.400 0.410 1 100.00 -30.00
MCC-B3 Load 0.400 0.420 1 100.00 -30.00
P-20-PA-138A~ Load 0.400 0.400 0 100.00 0.00
P-B1-21-PA-120A~ Load 0.400 0.400 0 100.00 0.00
P-B1-63-CX-928A~ Load 0.400 0.400 0 100.00 0.00
P-B1-63-CX-928B~ Load 0.400 0.400 0 100.00 0.00
P-B1-CX-63-928C~ Load 0.400 0.400 0 100.00 0.00
P-B1-HC-21-107A~ Load 0.400 0.400 0 100.00 0.00
P-B1-HOT OIL PAC FAN A~ Load 0.400 0.400 0 100.00 0.00
P-B1-HOT OIL PAC FAN B~ Load 0.400 0.400 0 100.00 0.00
P-B3-PA-39-119A~ Load 0.420 0.420 0 100.00 0.00
Project: ETAP Page: 6

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

P-B3-PA-39-119B~ Load 0.420 0.420 0 100.00 0.00

125 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project: ETAP Page: 7

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Line/Cable/Busway Input Data

ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R1 X1 Y1 R0 X0 Y0

P-20-PA-138A 1.0NCUN3 50 120.0 0.0 1 20 0.3874361 0.079 0.0001188 0.6160233 0.20066

P-20-TX-140 1.0NCUN3 185 160.0 0.0 2 20 0.1003883 0.073 0.0001442 0.1596174 0.18542

P-28-PA-204A 1.0NCUN3 4.0 90.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-28-PA-209A 1.0NCUN3 6.0 50.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-41-PA-XXXA 1.0NCUN3 35 100.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-53-PA-442A 1.0NCUN3 4.0 120.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-62-PA-924A 1.0NCUN3 4.0 100.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B1-20-PA-117A 1.0NCUN3 25 170.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-21-PA-120A 1.0NCUN3 70 170.0 0.0 1 20 0.268225 0.075 0.0001307 0.4264777 0.1905

P-B1-28-PA-137A 1.0NCUN3 50 130.0 0.0 1 20 0.3874361 0.079 0.0001188 0.6160233 0.20066

P-B1-28-PA-145A 1.0NCUN3 6.0 140.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B1-29-PA-211A 1.0NCUN3 6.0 60.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B1-63-CX-928A 1.0NCUN3 300 90.0 0.0 1 20 0.0627427 0.071 0.0001643 0.0997609 0.18034

P-B1-63-CX-928B 1.0NCUN3 300 75.0 0.0 1 20 0.0627427 0.071 0.0001643 0.0997609 0.18034

P-B1-81-EG-926A 1.0NCUN4 10 60.0 0.0 1 20 1.827381 0.084 0.0000807 2.905535 0.21336

P-B1-82-EG-926B 1.0NCUN4 10 60.0 0.0 1 20 1.827381 0.084 0.0000807 2.905535 0.21336

P-B1-BE-25-321 1.0NCUN3 50 140.0 0.0 1 20 0.3874361 0.079 0.0001188 0.6160233 0.20066

P-B1-BX-43-511 1.0NCUN4 10 250.0 0.0 1 20 1.827381 0.084 0.0000807 2.905535 0.21336

P-B1-CX-63-928C 1.0NCUN3 400 90.0 0.0 1 20 0.0501941 0.071 0.0001687 0.0798087 0.18034

P-B1-CX-64-929 1.0NCUN3 4.0 50.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B1-EL-82-00X 1.0NCUN4 16 10.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B1-EL-82-003 1.0NCUN4 16 10.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B1-EL-82-004 1.0NCUN4 6.0 10.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B1-EL-82-005 1.0NCUN4 150 10.0 0.0 1 20 0.1247011 0.073 0.0001442 0.1982747 0.18542

P-B1-EL-83-002 1.0NCUN4 6.0 30.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B1-ET-82-00X 1.0NCUN3 240 165.0 0.0 1 20 0.0760755 0.072 0.0001565 0.12096 0.18288

P-B1-ET-82-003 1.0NCUN3 240 160.0 0.0 1 20 0.0760755 0.072 0.0001565 0.12096 0.18288

P-B1-ET-82-004 1.0NCUN3 70 140.0 0.0 1 20 0.268225 0.075 0.0001307 0.4264777 0.1905

P-B1-ET-82-005 1.0NCUN3 240 160.0 0.0 2 20 0.0760755 0.072 0.0001565 0.12096 0.18288

P-B1-HC-21-107A 1.0NCUN3 35 150.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B1-HC-21-107B 1.0NCUN3 35 150.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B1-HC-21-107C 1.0NCUN3 35 150.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B1-HE-25-310 1.0NCUN3 25 175.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-HOT OIL PAC FAN A 1.0NCUN3 25 100.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-HOT OIL PAC FAN B 1.0NCUN3 25 90.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828
Project: ETAP Page: 8

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R1 X1 Y1 R0 X0 Y0

P-B1-HOT OIL TRANSFER B 1.0NCUN3 35 100.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B1-PA-25-315A 1.0NCUN3 16 175.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B1-PX-25-306A 1.0NCUN3 4.0 175.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B1-PX-25-309A 1.0NCUN3 4.0 175.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B1-TX-20-139 1.0NCUN3 240 140.0 0.0 1 20 0.0760755 0.072 0.0001565 0.12096 0.18288

P-B1-XX-AMINE REFLUX 1.0NCUN3 25 175.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828
COND
P-B1-XX-AMINE-PACKAGE 1.0NCUN3 4.0 175.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622
HEA
P-B1-XX-ANCILLERIES 1.0NCUN4 10 175.0 0.0 1 20 1.827381 0.084 0.0000807 2.905535 0.21336

P-B1-XX-COMBUSTION 1.0NCUN3 25 100.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-XX-XX-CONTROL RO 1.0NCUN4 25 175.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-XX-XX-UPS BYPASS B 1.0NCUN4 4.0 30.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622
1
P-B1-XX-XX-XXX AMINE 1.0NCUN3 25 175.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B1-XX-XX-XXX 1.0NCUN3 4.0 175.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622
ANITFOAM
P-B1-XX-XX-XXX HEAT 1.0NCUN3 150 200.0 0.0 1 20 0.1247011 0.073 0.0001442 0.1982747 0.18542

P-B1-XX-XX-XXX HOT OIL 1.0NCUN3 10 100.0 0.0 1 20 1.827381 0.084 0.0000807 2.905535 0.21336

P-B1-XX-XX-XXX OFFICES 1.0NCUN4 35 175.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B1-XX-XX-XXX UPS B1 1.0NCUN3 4.0 30.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B1-XX-XX-XXX 1.0NCUN4 25 175.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828


WORKSHOP
P-B1-XX-XX-XXXX 1.0NCUN3 4.0 100.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EC-13-001 1.0NCUN3 4.0 80.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EC-13-002 1.0NCUN3 4.0 80.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EC-13-003 1.0NCUN3 4.0 80.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EC-13-004 1.0NCUN3 4.0 80.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EC-13-005 1.0NCUN3 16 80.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B2-EC-13-006 1.0NCUN3 4.0 80.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-EL-82-001 1.0NCUN4 95 20.0 0.0 1 20 0.193718 0.073 0.0001433 0.3080117 0.18542

P-B2-EL-82-006 1.0NCUN4 16 50.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B2-EL-82-007 1.0NCUN4 6.0 10.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B2-ER-83-001 1.0NCUN3 4.0 30.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-ET-82-001 1.0NCUN3 300 850.0 0.0 8 20 0.0627427 0.071 0.0001643 0.0997609 0.18034

P-B2-ET-82-006 1.0NCUN3 95 120.0 0.0 1 20 0.193718 0.073 0.0001433 0.3080117 0.18542

P-B2-ET-82-007 1.0NCUN3 35 90.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B2-PD-42-951A 1.0NCUN3 4.0 65.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-PD-42-953A 1.0NCUN3 4.0 65.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B2-XX- HEAT TRACE 1.0NCUN3 4.0 50.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-63-KF-001 1.0NCUN3 4.0 85.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622
Project: ETAP Page: 9

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R1 X1 Y1 R0 X0 Y0

P-B3-EL-82-001 1.0NCUN4 300 50.0 0.0 3 20 0.0627427 0.071 0.0001643 0.0997609 0.18034

P-B3-EL-82-008 1.0NCUN4 240 10.0 0.0 1 20 0.0760755 0.072 0.0001565 0.12096 0.18288

P-B3-EL-82-009 1.0NCUN4 16 50.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B3-EL-82-010 1.0NCUN4 70 10.0 0.0 1 20 0.268225 0.075 0.0001307 0.4264777 0.1905

P-B3-EL-83-006 1.0NCUN4 6.0 50.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B3-ER-83-001 1.0NCUN3 4.0 20.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-ER-83-002 1.0NCUN4 6.0 50.0 0.0 1 20 3.074391 0.089 0.0000663 4.888282 0.22606

P-B3-ET-82-001 1.0NCUN3 300 10.0 0.0 3 20 0.0627427 0.071 0.0001643 0.0997609 0.18034

P-B3-ET-82-002 1.0NCUN4 95 2520.0 0.0 1 20 0.193718 0.073 0.0001433 0.3080117 0.18542

P-B3-ET-82-008 1.0NCUN3 400 290.0 0.0 5 20 0.0501941 0.071 0.0001687 0.0798087 0.18034

P-B3-ET-82-010 1.0NCUN3 50 20.0 0.0 1 20 0.3874361 0.079 0.0001188 0.6160233 0.20066

P-B3-KA-63-001 1.0NCUN3 16 85.0 0.0 1 20 1.145054 0.08 0.0000971 1.820636 0.2032

P-B3-KF-39-902 1.0NCUN3 50 400.0 0.0 1 20 0.3874361 0.079 0.0001188 0.6160233 0.20066

P-B3-PA-21-135 1.0NCUN3 4.0 50.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-PA-39-119A 1.0NCUN3 150 400.0 0.0 2 20 0.1247011 0.073 0.0001442 0.1982747 0.18542

P-B3-PA-39-119B 1.0NCUN3 150 400.0 0.0 2 20 0.1247011 0.073 0.0001442 0.1982747 0.18542

P-B3-PH-57-101A 1.0NCUN3 4.0 60.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-XX-OTHERS 1.0NCUN3 35 100.0 0.0 1 20 0.5246857 0.08 0.0001015 0.8342423 0.2032

P-B3-XX-OTHERS2 1.0NCUN4 4.0 10.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-XX-XX-HEAT 1.0NCUN3 95 500.0 0.0 1 20 0.193718 0.073 0.0001433 0.3080117 0.18542


TRACING
P-B3-XX-XX-LABORATORY 1.0NCUN4 25 50.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-B3-XX-XX-OFFICES 1.0NCUN4 4.0 50.0 0.0 1 20 4.603744 0.093 0.0000575 7.319953 0.23622

P-B3-XX-XX-WEIGH 1.0NCUN3 25 300.0 0.0 1 20 0.7270308 0.082 0.0000889 1.155955 0.20828

P-MCC-B1-1 1.0NCUN3 400 90.0 0.0 5 20 0.0501941 0.071 0.0001687 0.0798087 0.18034

P-MCC-B1-2 1.0NCUN3 400 80.0 0.0 5 20 0.0501941 0.071 0.0001687 0.0798087 0.18034

P-MCC-B1-3 1.0NCUN1 630 80.0 0.0 4 20 0.0329399 0.086 0.0002023 0.0523745 0.21844

P-MCC-B1-4 1.0NCUN1 630 80.0 0.0 4 20 0.0329399 0.086 0.0002023 0.0523745 0.21844

P-Oil Serve Supply 1.0NCUN3 400 260.0 0.0 4 20 0.0501941 0.071 0.0001687 0.0798087 0.18034

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: ETAP Page: 10

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

20-TX-139 0.100 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

20-TX-140 0.150 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B1-ET-82-00X 0.080 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B1-ET-82-003 0.080 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

B1-ET-82-004 0.050 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B1-ET-82-005 0.300 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B2-ET-82-001 0.150 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B2-ET-82-006 0.050 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

B2-ET-82-007 0.050 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

B3-ET-82-001 1.000 6.600 0.400 5.00 3.50 0 0 0 0 0 5.00 Dd 0.00

B3-ET-82-002 1.000 6.600 0.400 5.00 3.50 0 0 0 0 5.000 5.00 Dyn 30.00

B3-ET-82-008 0.300 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

B3-ET-82-010 0.100 0.400 0.400 4.00 1.50 0 0 0 0 2.500 4.00 Dyn 30.00

B3-XX-XX-XXX 0.050 0.400 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00

2-Winding Transformer Grounding Input Data

Grounding
Transformer Rating Conn. Primary Secondary

ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm

20-TX-139 0.100 0.400 0.400 D/Y Solid

20-TX-140 0.150 0.400 0.400 D/Y Solid

B1-ET-82-00X 0.080 0.400 0.400 D/Y Solid

B1-ET-82-003 0.080 0.400 0.400 D/Y Solid

B1-ET-82-004 0.050 0.400 0.400 D/Y Solid

B1-ET-82-005 0.300 0.400 0.400 D/Y Solid

B2-ET-82-001 0.150 0.400 0.400 D/Y Solid

B2-ET-82-006 0.050 0.400 0.400 D/Y Solid

B2-ET-82-007 0.050 0.400 0.400 D/Y Solid

B3-ET-82-001 1.000 6.600 0.400 D/D

B3-ET-82-002 1.000 6.600 0.400 D/Y Solid

B3-ET-82-008 0.300 0.400 0.400 D/Y Solid

B3-ET-82-010 0.100 0.400 0.400 D/Y Solid


Project: ETAP Page: 11

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

2-Winding Transformer Grounding Input Data

Grounding
Transformer Rating Conn. Primary Secondary

ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm

B3-XX-XX-XXX 0.050 0.400 0.400 D/Y Solid


Project: ETAP Page: 12

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

20-TX-139 2W XFMR Bus24 Bus10 2169.92 3254.88 3911.88

20-TX-140 2W XFMR Bus26 Bus12 1446.62 2169.92 2607.92

B1-ET-82-00X 2W XFMR Bus66 Bus41 2712.40 4068.60 4889.85

B1-ET-82-003 2W XFMR Bus63 Bus64 2712.40 4068.60 4889.85

B1-ET-82-004 2W XFMR Bus76 Bus60 4339.84 6509.77 7823.77

B1-ET-82-005 2W XFMR Bus62 Bus65 723.31 1084.96 1303.96

B2-ET-82-001 2W XFMR Bus71 Bus1 1446.62 2169.92 2607.92

B2-ET-82-006 2W XFMR Bus96 Bus97 4130.73 6196.09 7446.77

B2-ET-82-007 2W XFMR Bus22 Bus39 4130.73 6196.09 7446.77

B3-ET-82-001 2W XFMR Bus27 Bus2 133.18 466.11 484.77

B3-ET-82-002 2W XFMR Bus29 Bus6 133.18 466.11 484.77

B3-ET-82-008 2W XFMR Bus48 Bus30 656.06 984.09 1182.73

B3-ET-82-010 2W XFMR Bus162 Bus163 1968.18 2952.28 3548.19

B3-XX-XX-XXX 2W XFMR Bus33 Bus50 3936.37 5904.55 7096.39

P-20-PA-138A Cable MCC-B1 BUS A P-20-PA-138A~ 2905.77 592.50 2965.56 0.0000023

P-20-TX-140 Cable MCC-B1 BUS A Bus26 501.94 365.00 620.62 0.0000074

P-28-PA-204A Cable MCC-B1 BUS A Bus15 25896.06 523.13 25901.34 0.0000008

P-28-PA-209A Cable MCC-B1 BUS A Bus11 9607.47 278.13 9611.50 0.0000005

P-41-PA-XXXA Cable MCC-B1 BUS A Bus9 3279.29 500.00 3317.19 0.0000016

P-53-PA-442A Cable MCC-B1 BUS A Bus19 34528.08 697.50 34535.13 0.0000011

P-62-PA-924A Cable MCC-B1 BUS A Bus5 28773.40 581.25 28779.27 0.0000009

P-B1-20-PA-117A Cable MCC-B1 BUS A Bus54 7724.70 871.25 7773.68 0.0000024

P-B1-21-PA-120A Cable MCC-B1 BUS A P-B1-21-PA-120A~ 2849.89 796.88 2959.20 0.0000036

P-B1-28-PA-137A Cable MCC-B1 BUS A Bus34 3147.92 641.88 3212.69 0.0000025

P-B1-28-PA-145A Cable MCC-B1 BUS A Bus53 26900.92 778.75 26912.19 0.0000015

P-B1-29-PA-211A Cable MCC-B1 BUS A Bus13 11528.97 333.75 11533.80 0.0000006

P-B1-63-CX-928A Cable MCC-B1 BUS A P-B1-63-CX-928A~ 352.93 399.38 532.97 0.0000024

P-B1-63-CX-928B Cable MCC-B1 BUS A P-B1-63-CX-928B~ 294.11 332.81 444.14 0.0000020

P-B1-81-EG-926A Cable LSPDB-B1 Bus79 6522.48 299.82 6529.36 0.0000008

P-B1-82-EG-926B Cable LSPDB-B1 Bus80 6522.48 299.82 6529.36 0.0000008

P-B1-BE-25-321 Cable MCC-B1 BUS A Bus114 3390.07 691.25 3459.82 0.0000027

P-B1-BX-43-511 Cable LSPDB-B1 Bus21 27176.99 1249.26 27205.68 0.0000034

P-B1-CX-63-928C Cable MCC-B1 BUS A P-B1-CX-63-928C~ 282.34 399.38 489.10 0.0000024

P-B1-CX-64-929 Cable MCC-B1 BUS A Bus105 14386.70 290.63 14389.63 0.0000005

P-B1-EL-82-00X Cable Bus41 Bus44 681.17 47.59 682.83 0.0000002

P-B1-EL-82-003 Cable Bus64 Bus4 715.66 50.00 717.40 0.0000002


Project: ETAP Page: 13

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

P-B1-EL-82-004 Cable Bus60 Bus42 1828.91 52.94 1829.67 0.0000001

P-B1-EL-82-005 Cable Bus65 LSPDB-B1 74.18 43.43 85.96 0.0000002

P-B1-EL-83-002 Cable LSPDB-B1 Bus72 5486.72 158.83 5489.02 0.0000003

P-B1-ET-82-00X Cable MCC-B1 BUS A Bus66 784.53 742.50 1080.18 0.0000041

P-B1-ET-82-003 Cable MCC-B1 BUS A Bus63 760.76 720.00 1047.45 0.0000040

P-B1-ET-82-004 Cable MCC-B1 BUS A Bus76 2346.97 656.25 2436.99 0.0000029

P-B1-ET-82-005 Cable MCC-B1 BUS A Bus62 380.38 360.00 523.72 0.0000080

P-B1-HC-21-107A Cable MCC-B1 BUS A P-B1-HC-21-107A~ 4918.93 750.00 4975.78 0.0000024

P-B1-HC-21-107B Cable MCC-B1 BUS A Bus56 4918.93 750.00 4975.78 0.0000024

P-B1-HC-21-107C Cable MCC-B1 BUS A Bus8 4918.93 750.00 4975.78 0.0000024

P-B1-HE-25-310 Cable MCC-B1 BUS A Bus144 7951.90 896.88 8002.32 0.0000025

P-B1-HOT OIL PAC FAN A Cable MCC-B1 BUS A P-B1-HOT OIL PAC FAN A~ 4543.94 512.50 4572.75 0.0000014

P-B1-HOT OIL PAC FAN B Cable MCC-B1 BUS A P-B1-HOT OIL PAC FAN B~ 4089.55 461.25 4115.48 0.0000013

P-B1-HOT OIL TRANSFER B Cable MCC-B1 BUS A Bus14 3279.29 500.00 3317.19 0.0000016

P-B1-PA-25-315A Cable MCC-B1 BUS A Bus32 12524.03 875.00 12554.56 0.0000027

P-B1-PX-25-306A Cable MCC-B1 BUS A Bus20 50353.45 1017.19 50363.72 0.0000016

P-B1-PX-25-309A Cable MCC-B1 BUS A Bus57 50353.45 1017.19 50363.72 0.0000016

P-B1-TX-20-139 Cable MCC-B1 BUS A Bus24 665.66 630.00 916.52 0.0000035

P-B1-XX-AMINE REFLUX Cable MCC-B1 BUS A Bus104 7951.90 896.88 8002.32 0.0000025
COND
P-B1-XX-AMINE-PACKAGE Cable MCC-B1 BUS A Bus117 50353.45 1017.19 50363.72 0.0000016
HEA
P-B1-XX-ANCILLERIES Cable LSPDB-B1 Bus78 19023.89 874.48 19043.98 0.0000024

P-B1-XX-COMBUSTION Cable MCC-B1 BUS A Bus100 4543.94 512.50 4572.75 0.0000014

P-B1-XX-XX-CONTROL RO Cable LSPDB-B1 Bus73 7568.73 853.66 7616.72 0.0000026

P-B1-XX-XX-UPS BYPASS B1 Cable LSPDB-B1 Bus86 8216.08 165.97 8217.76 0.0000003

P-B1-XX-XX-XXX AMINE Cable MCC-B1 BUS A Bus133 7951.90 896.88 8002.32 0.0000025

P-B1-XX-XX-XXX ANITFOAM Cable MCC-B1 BUS A Bus132 50353.45 1017.19 50363.72 0.0000016

P-B1-XX-XX-XXX HEAT Cable MCC-B1 BUS A Bus59 1558.76 912.50 1806.21 0.0000046

P-B1-XX-XX-XXX HOT OIL Cable MCC-B1 BUS A Bus115 11421.13 525.00 11433.19 0.0000013

P-B1-XX-XX-XXX OFFICES Cable LSPDB-B1 Bus67 5462.23 832.84 5525.35 0.0000030

P-B1-XX-XX-XXX UPS B1 Cable MCC-B1 BUS A Bus131 8632.02 174.38 8633.78 0.0000003

P-B1-XX-XX-XXX WORKSHOP Cable LSPDB-B1 Bus25 7568.73 853.66 7616.72 0.0000026

P-B1-XX-XX-XXXX Cable MCC-B1 BUS A Bus116 28773.40 581.25 28779.27 0.0000009

P-B2-EC-13-001 Cable MCC-B2 Bus91 21909.55 442.59 21914.02 0.0000008

P-B2-EC-13-002 Cable MCC-B2 Bus93 21909.55 442.59 21914.02 0.0000008

P-B2-EC-13-003 Cable MCC-B2 Bus107 21909.55 442.59 21914.02 0.0000008

P-B2-EC-13-004 Cable MCC-B2 Bus109 21909.55 442.59 21914.02 0.0000008

P-B2-EC-13-005 Cable MCC-B2 Bus111 5449.40 380.73 5462.68 0.0000013

P-B2-EC-13-006 Cable MCC-B2 Bus90 21909.55 442.59 21914.02 0.0000008


Project: ETAP Page: 14

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

P-B2-EL-82-001 Cable MCC-B2 Bus1 230.48 86.85 246.30 0.0000005

P-B2-EL-82-006 Cable Bus97 Bus95 3405.87 237.95 3414.17 0.0000008

P-B2-EL-82-007 Cable Bus39 Bus18 1828.91 52.94 1829.67 0.0000001

P-B2-ER-83-001 Cable MCC-B2 Bus92 8216.08 165.97 8217.76 0.0000003

P-B2-ET-82-001 Cable MCC-B1 BUS A Bus71 416.65 471.48 629.20 0.0001788

P-B2-ET-82-006 Cable MCC-B2 Bus96 1382.88 521.12 1477.81 0.0000029

P-B2-ET-82-007 Cable MCC-B2 Bus22 2809.14 428.32 2841.61 0.0000015

P-B2-PD-42-951A Cable MCC-B2 Bus69 17801.51 359.61 17805.14 0.0000006

P-B2-PD-42-953A Cable MCC-B2 Bus75 17801.51 359.61 17805.14 0.0000006

P-B2-XX- HEAT TRACE Cable MCC-B2 Bus94 13693.47 276.62 13696.26 0.0000005

P-B3-63-KF-001 Cable MCC-B3 Bus43 22183.58 448.13 22188.10 0.0000009

P-B3-EL-82-001 Cable Bus6 MCC-B3 59.28 67.08 89.52 0.0000043

P-B3-EL-82-008 Cable Bus30 Bus28 43.13 40.82 59.38 0.0000003

P-B3-EL-82-009 Cable LSP-DB-B3 Bus70 3089.23 215.83 3096.76 0.0000009

P-B3-EL-82-010 Cable Bus163 LSP-DB-B3 144.73 40.47 150.28 0.0000002

P-B3-EL-83-006 Cable LSP-DB-B3 Bus52 8294.36 240.11 8297.84 0.0000006

P-B3-ER-83-001 Cable MCC-B3 Bus49 5219.67 105.44 5220.73 0.0000002

P-B3-ER-83-002 Cable LSP-DB-B3 Bus23 8294.36 240.11 8297.84 0.0000006

P-B3-ET-82-001 Cable MCC-B1 BUS A Bus2 13.07 14.79 19.74 0.0000008

P-B3-ET-82-002 Cable Bus29 Bus27 112.07 42.23 119.76 0.0157302

P-B3-ET-82-008 Cable MCC-B3 Bus48 165.04 233.45 285.89 0.0000432

P-B3-ET-82-010 Cable MCC-B3 Bus162 439.27 89.57 448.31 0.0000004

P-B3-KA-63-001 Cable MCC-B3 Bus157 5517.55 385.49 5531.00 0.0000015

P-B3-KF-39-902 Cable MCC-B3 Bus151 8785.40 1791.38 8966.18 0.0000084

P-B3-PA-21-135 Cable MCC-B3 Bus31 13049.16 263.61 13051.82 0.0000005

P-B3-PA-39-119A Cable MCC-B3 P-B3-PA-39-119A~ 1413.84 827.66 1638.29 0.0000203

P-B3-PA-39-119B Cable MCC-B3 P-B3-PA-39-119B~ 1413.84 827.66 1638.29 0.0000203

P-B3-PH-57-101A Cable MCC-B3 Bus45 15658.99 316.33 15662.19 0.0000006

P-B3-XX-OTHERS Cable MCC-B3 Bus33 2974.41 453.51 3008.79 0.0000018

P-B3-XX-OTHERS2 Cable Bus50 Bus37 2609.83 52.72 2610.37 0.0000001

P-B3-XX-XX-HEAT TRACING Cable MCC-B3 Bus47 5490.87 2069.16 5867.80 0.0000126

P-B3-XX-XX-LABORATORY Cable LSP-DB-B3 Bus61 1961.45 221.23 1973.88 0.0000008

P-B3-XX-XX-OFFICES Cable LSP-DB-B3 Bus68 12420.38 250.90 12422.92 0.0000005

P-B3-XX-XX-WEIGH Cable MCC-B3 Bus35 12364.47 1394.56 12442.87 0.0000047

P-MCC-B1-1 Cable Bus165 MCC-B1 BUS A 56.47 79.88 97.82 0.0000121

P-MCC-B1-2 Cable Bus166 MCC-B1 BUS A 50.19 71.00 86.95 0.0000108

P-MCC-B1-3 Cable Bus167 MCC-B1 BUS A 41.17 107.50 115.12 0.0000104

P-MCC-B1-4 Cable MCC-B1 BUS A Bus168 41.17 107.50 115.12 0.0000104

P-Oil Serve Supply Cable MCC-B1 BUS A Bus169 203.91 288.44 353.24 0.0000281
Project: ETAP Page: 15

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Synchronous Generator Input Data

% Impedance in Machine Base

Synchronous Generator Rating Xd" Grounding Excitation


ID Type MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Conn. Type Amp Type

GG-001 Steam Turbo 2.790 0.400 1500 80.00 0.774 14.70 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

GG-002 Steam Turbo 2.790 0.400 1500 80.00 0.774 14.70 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Total Connected Synchronous Generators ( = 2.00 ) : 5.580 MVA


Project: ETAP Page: 16

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Induction Machine Input Data

Pos. Seq. Imp.


Induction Machine Connected Bus Rating (Motor Base) Grounding

ID Type Qty ID HP/kW kVA kV Amp PF %R % X" R/X" Conn. Type Amp MW/PP

B1-20-PA-117A Motor 1 Bus3 18.50 25.69 0.400 37.09 80.00 7.42 14.92 0.50 Wye Open 0.01
62-PA-924A Motor 1 Bus5 2.20 3.44 0.400 4.96 80.00 11.11 12.42 0.89 Wye Open 0.00
B1-CX-63-928A Motor 1 Bus7 290.00 358.02 0.400 516.76 90.00 3.37 16.32 0.21 Wye Open 0.15
B1-HC-21-107C Motor 1 Bus8 30.00 41.67 0.400 60.14 80.00 6.59 15.31 0.43 Wye Open 0.02

HOT OIL TRANSFER PUMP Motor 1 Bus9 55.00 67.90 0.400 98.01 90.00 5.54 15.72 0.35 Wye Open 0.03
A
B1-28-PA-209A Motor 1 Bus11 15.00 20.83 0.400 30.07 80.00 7.79 14.74 0.53 Wye Open 0.01
B1-29-PA-211A Motor 1 Bus13 11.00 15.28 0.400 22.05 80.00 8.32 14.44 0.58 Wye Open 0.01
B1-HOT OIL TRANSFER B Motor 1 Bus14 55.00 67.90 0.400 98.01 90.00 5.54 15.72 0.35 Wye Open 0.03
B1-28-PA-204A Motor 1 Bus15 2.20 3.44 0.400 4.96 80.00 11.11 12.42 0.89 Wye Open 0.00
B1-53-PA-442A Motor 1 Bus19 4.00 4.94 0.400 7.13 90.00 10.07 13.28 0.76 Wye Open 0.00
B1-PX-25-306A Motor 1 Bus20 0.37 0.58 0.400 0.83 80.00 14.11 8.87 1.59 Wye Open 0.00
B3-PA-21-135 Motor 1 Bus31 5.00 6.17 0.400 8.91 90.00 9.69 13.56 0.71 Wye Open 0.00
B1-PA-25-315A Motor 1 Bus32 15.00 20.83 0.400 30.07 80.00 7.79 14.74 0.53 Wye Open 0.01
B1-28-PA-137A Motor 1 Bus34 45.00 62.50 0.400 90.21 80.00 5.89 15.59 0.38 Wye Open 0.02
B1-21-PA-120A Motor 1 Bus36 55.00 67.90 0.400 98.01 90.00 5.54 15.72 0.35 Wye Open 0.03
B1-HC-21-107A Motor 1 Bus38 30.00 41.67 0.400 60.14 80.00 6.59 15.31 0.43 Wye Open 0.02
B1-20-PA-138A Motor 1 Bus40 55.00 67.90 0.400 98.01 90.00 5.54 15.72 0.35 Wye Open 0.03
B3-PH-57-101A Motor 1 Bus45 7.50 10.42 0.400 15.04 80.00 8.99 14.04 0.64 Wye Open 0.00
B1-28-PA-145A Motor 1 Bus53 7.50 9.26 0.400 13.36 90.00 8.99 14.04 0.64 Wye Open 0.00
B1-HC-21-107B Motor 1 Bus56 30.00 41.67 0.400 60.14 80.00 6.59 15.31 0.43 Wye Open 0.02
B1-PX-25-309A Motor 1 Bus57 1.50 2.34 0.400 3.38 80.00 11.77 11.80 1.00 Wye Open 0.00
B2-PD-42-951A Motor 1 Bus69 0.37 0.58 0.400 0.83 80.00 14.11 8.87 1.59 Wye Open 0.00
B2-PD-42-953A Motor 1 Bus75 0.37 0.58 0.400 0.83 80.00 14.11 8.87 1.59 Wye Open 0.00
B1-CX-63-928C Motor 1 Bus84 290.00 402.78 0.400 581.36 80.00 3.37 16.32 0.21 Wye Open 0.15
B1-HOT OIL PAC FAN A Motor 1 Bus88 37.00 51.39 0.400 74.17 80.00 6.23 15.46 0.40 Wye Open 0.02
B1-CX-63-928B Motor 1 Bus99 290.00 358.02 0.400 516.76 90.00 3.37 16.32 0.21 Wye Open 0.15
B1-XX-COMBUSTION Motor 1 Bus100 30.00 41.67 0.400 60.14 80.00 6.59 15.31 0.43 Wye Open 0.02

B1-XX-AMINE REFLUX Motor 1 Bus104 18.50 25.69 0.400 37.09 80.00 7.42 14.92 0.50 Wye Open 0.01
COND
B1-CX-64-929 Motor 1 Bus105 4.00 5.56 0.400 8.02 80.00 10.07 13.28 0.76 Wye Open 0.00
B1-HOT OIL PAC FAN B Motor 1 Bus106 37.00 51.39 0.400 74.17 80.00 6.23 15.46 0.40 Wye Open 0.02
HOT OIL FILL DRAIN PUMP Motor 1 Bus116 0.60 0.94 0.400 1.35 80.00 13.42 9.88 1.36 Wye Open 0.00
B1-XX-XX-XXX ANTIFOAM Motor 1 Bus132 2.20 3.44 0.400 4.96 80.00 11.11 12.42 0.89 Wye Open 0.00
B1-HE-25-310 Motor 1 Bus144 18.50 25.69 0.400 37.09 80.00 7.42 14.92 0.50 Wye Open 0.01
B3-KF-39-902 Motor 1 Bus151 18.50 25.69 0.400 37.09 80.00 7.42 14.92 0.50 Wye Open 0.01
B3-PA-39-119A Motor 1 Bus152 112.00 138.27 0.400 199.58 90.00 4.39 16.08 0.27 Wye Open 0.06
B3-PA-39-119B Motor 1 Bus153 112.00 138.27 0.400 199.58 90.00 4.39 16.08 0.27 Wye Open 0.06
Project: ETAP Page: 17

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Induction Machine Input Data

Pos. Seq. Imp.


Induction Machine Connected Bus Rating (Motor Base) Grounding

ID Type Qty ID HP/kW kVA kV Amp PF %R % X" R/X" Conn. Type Amp MW/PP

B3-KA-63-001 Motor 1 Bus157 22.00 30.56 0.400 44.10 80.00 7.12 15.07 0.47 Wye Open 0.01

Total Connected Induction Machines ( = 37 ): 2240.9 kVA


Project: ETAP Page: 18

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

VFD Input Data

AC Rating
% Impedance
kVA kV FLA Input Output Bypass Equipment Base
ID Output Input Output Input Output % EFF % PF Hz % Imax Switch R X

VFD107A 30.00 0.400 0.400 43.30 43.30 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD117A 18.50 0.400 0.400 26.70 26.70 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_119A 112.00 0.400 0.400 161.66 161.66 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_119B 112.00 0.400 0.400 161.66 161.66 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD120A 55.00 0.400 0.400 79.39 79.39 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD138A 55.00 0.400 0.400 79.39 79.39 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_928A 290.00 0.400 0.400 418.58 418.58 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_928B 290.00 0.400 0.400 418.58 418.58 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_928C 290.00 0.400 0.400 418.58 418.58 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_FANA 37.00 0.400 0.400 53.40 53.40 100.00 100.00 60.00 150.0 No 66.67 0.00

VFD_FANB 37.00 0.400 0.400 53.40 53.40 100.00 100.00 60.00 150.0 No 66.67 0.00
Project: ETAP Page: 19

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus1


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus1 Total 0.00 4.155 0.00 100.75 101.79 4.483 4.483 1.91E+003 2.90E+003 1.45E+003 2.17E+003

MCC-B2 Bus1 0.02 0.010 0.01 100.75 101.79 0.006 0.000 1.17E+006 7.30E+005

Bus71 Bus1 76.77 4.145 87.95 103.50 89.08 4.477 4.483 * 1.91E+003 2.91E+003 1.45E+003 2.17E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.155 4.483 3.546 4.385
Peak Current (kA), Method C : 6.803 7.339 5.806 7.180
Breaking Current (kA, rms, symm) : 4.483 3.546 4.385
Steady State Current (kA, rms) : 4.125 4.483 3.546 4.385

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 20

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus2


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus2 Total 0.00 52.541 0.00 103.30 112.02 52.016 52.016 5.83E+001 2.83E+002 6.97E+001 1.80E+002

MCC-B1 BUS A Bus2 7.10 51.935 9.79 102.62 110.91 51.638 52.016 5.77E+001 2.86E+002 6.97E+001 1.80E+002

Bus27 Bus2 2.18 0.648 24.41 101.38 104.18 0.391 0.000 1.26E+004 1.97E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 52.541 52.016 38.419 57.726
Peak Current (kA), Method C : 116.974 115.806 85.534 128.518
Breaking Current (kA, rms, symm) : 52.016 38.419 57.726
Steady State Current (kA, rms) : 45.652 52.016 38.419 57.726

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 21

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus3


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus3 Total 0.00 0.255 0.00 126.32 180.01 0.098 0.098 3.40E+004 4.87E+004 3.60E+005 5.41E-005

B1-20-PA-117A Bus3 105.00 0.234 105.00 105.00 105.00 0.059 0.000 2.89E+004 5.81E+004

VFD117A Bus3 105.00 0.042 105.00 105.00 105.00 0.042 0.098 3.60E+005 5.41E-005 3.60E+005 5.41E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.255 0.098 0.165 0.199
Peak Current (kA), Method C : 0.470 0.180 0.304 0.366
Breaking Current (kA, rms, symm) : 0.098 0.165 0.199
Steady State Current (kA, rms) : 0.042 0.098 0.165 0.199

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 22

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus4


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus4 Total 0.00 2.285 0.00 101.09 104.47 2.387 2.387 4.23E+003 5.11E+003 3.85E+003 4.20E+003

Bus64 Bus4 11.36 2.285 14.22 101.59 102.31 2.387 2.387 4.23E+003 5.11E+003 3.85E+003 4.20E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.285 2.387 1.965 2.380
Peak Current (kA), Method C : 3.560 3.719 3.061 3.709
Breaking Current (kA, rms, symm) : 2.387 1.965 2.380
Steady State Current (kA, rms) : 2.279 2.387 1.965 2.380

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 23

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus5


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus5 Total 0.00 0.548 0.00 114.94 116.66 0.446 0.446 2.76E+004 1.96E+003 4.58E+004 1.62E+003

MCC-B1 BUS A Bus5 104.81 0.526 104.82 104.82 105.22 0.438 0.446 2.88E+004 8.50E+002 4.58E+004 1.62E+003

62-PA-924A Bus5 105.00 0.031 105.00 105.00 105.00 0.013 0.000 3.23E+005 3.61E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.548 0.446 0.468 0.511
Peak Current (kA), Method C : 0.790 0.643 0.674 0.737
Breaking Current (kA, rms, symm) : 0.446 0.468 0.511
Steady State Current (kA, rms) : 0.526 0.446 0.468 0.511

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 24

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus6


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus6 Total 0.00 10.904 0.00 98.61 96.75 13.171 13.171 4.28E+002 1.19E+003 1.33E+002 4.66E+002

MCC-B3 Bus6 0.42 0.615 0.28 98.66 96.88 0.409 0.000 1.22E+004 1.88E+004

Bus29 Bus6 36.34 10.306 66.04 103.76 63.74 12.766 13.171 * 4.36E+002 1.26E+003 1.33E+002 4.66E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 10.904 13.171 8.995 13.342
Peak Current (kA), Method C : 20.991 25.356 17.317 25.685
Breaking Current (kA, rms, symm) : 13.171 8.995 13.342
Steady State Current (kA, rms) : 10.168 13.171 8.995 13.342

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 25

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus7


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus7 Total 0.00 3.450 0.00 130.55 182.39 1.614 1.614 1.68E+003 4.06E+003 2.30E+004 3.45E-006

B1-CX-63-928A Bus7 105.00 3.256 105.00 105.00 105.00 1.011 0.000 9.43E+002 4.56E+003

VFD_928A Bus7 105.00 0.659 105.00 105.00 105.00 0.659 1.614 2.30E+004 3.45E-006 2.30E+004 3.45E-006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.450 1.614 2.708 3.186
Peak Current (kA), Method C : 8.074 3.777 6.338 7.457
Breaking Current (kA, rms, symm) : 1.614 2.708 3.186
Steady State Current (kA, rms) : 0.659 1.614 2.708 3.186

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 26

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus8


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus8 Total 0.00 3.222 0.00 115.99 117.97 2.558 2.558 4.49E+003 1.39E+003 7.87E+003 2.05E+003

MCC-B1 BUS A Bus8 103.10 2.991 103.25 104.05 106.27 2.466 2.558 4.96E+003 1.02E+003 7.87E+003 2.05E+003

B1-HC-21-107C Bus8 105.00 0.379 105.00 105.00 105.00 0.161 0.000 1.58E+004 3.67E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.222 2.558 2.722 2.978
Peak Current (kA), Method C : 4.661 3.701 3.938 4.307
Breaking Current (kA, rms, symm) : 2.558 2.722 2.978
Steady State Current (kA, rms) : 2.991 2.558 2.722 2.978

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 27

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus9


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus9 Total 0.00 4.801 0.00 114.13 119.48 3.835 3.835 2.98E+003 1.04E+003 5.26E+003 1.41E+003

MCC-B1 BUS A Bus9 102.07 4.441 102.38 103.58 106.84 3.661 3.835 3.32E+003 7.71E+002 5.26E+003 1.41E+003

HOT OIL Bus9 105.00 0.617 105.00 105.00 105.00 0.301 0.000 8.16E+003 2.32E+004
TRANSFER PUMP
A

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.801 3.835 4.091 4.521
Peak Current (kA), Method C : 6.982 5.577 5.950 6.575
Breaking Current (kA, rms, symm) : 3.835 4.091 4.521
Steady State Current (kA, rms) : 4.441 3.835 4.091 4.521

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 28

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus10


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus10 Total 0.00 2.998 0.00 101.73 101.13 3.220 3.220 2.88E+003 4.15E+003 2.17E+003 3.25E+003

Bus24 Bus10 81.26 2.998 92.57 105.73 91.91 3.220 3.220 * 2.88E+003 4.15E+003 2.17E+003 3.25E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.998 3.220 2.572 3.143
Peak Current (kA), Method C : 4.847 5.205 4.157 5.080
Breaking Current (kA, rms, symm) : 3.220 2.572 3.143
Steady State Current (kA, rms) : 2.989 3.220 2.572 3.143

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 29

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus11


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus11 Total 0.00 1.673 0.00 114.12 118.86 1.344 1.344 8.95E+003 1.39E+003 1.53E+004 8.49E+002

MCC-B1 BUS A Bus11 104.39 1.568 104.45 104.48 105.69 1.304 1.344 9.65E+003 5.47E+002 1.53E+004 8.49E+002

B1-28-PA-209A Bus11 105.00 0.189 105.00 105.00 105.00 0.081 0.000 3.74E+004 7.07E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.673 1.344 1.418 1.571
Peak Current (kA), Method C : 2.414 1.939 2.046 2.266
Breaking Current (kA, rms, symm) : 1.344 1.418 1.571
Steady State Current (kA, rms) : 1.568 1.344 1.418 1.571

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 30

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus12


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus12 Total 0.00 4.193 0.00 101.89 100.85 4.515 4.515 1.99E+003 2.80E+003 1.45E+003 2.17E+003

Bus26 Bus12 77.66 4.193 89.56 103.49 88.44 4.515 4.515 * 1.99E+003 2.80E+003 1.45E+003 2.17E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.193 4.515 3.581 4.419
Peak Current (kA), Method C : 6.743 7.260 5.758 7.105
Breaking Current (kA, rms, symm) : 4.515 3.581 4.419
Steady State Current (kA, rms) : 4.174 4.515 3.581 4.419

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 31

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus13


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus13 Total 0.00 1.388 0.00 114.37 118.30 1.118 1.118 1.08E+004 1.48E+003 1.84E+004 9.90E+002

MCC-B1 BUS A Bus13 104.49 1.308 104.54 104.56 105.57 1.088 1.118 1.16E+004 6.03E+002 1.84E+004 9.90E+002

B1-29-PA-211A Bus13 105.00 0.139 105.00 105.00 105.00 0.059 0.000 5.45E+004 9.45E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.388 1.118 1.178 1.300
Peak Current (kA), Method C : 2.002 1.613 1.700 1.876
Breaking Current (kA, rms, symm) : 1.118 1.178 1.300
Steady State Current (kA, rms) : 1.308 1.118 1.178 1.300

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 32

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus15


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus15 Total 0.00 0.606 0.00 114.88 116.48 0.495 0.495 2.50E+004 1.70E+003 4.12E+004 1.47E+003

MCC-B1 BUS A Bus15 104.79 0.584 104.80 104.80 105.25 0.487 0.495 2.59E+004 7.91E+002 4.12E+004 1.47E+003

B1-28-PA-204A Bus15 105.00 0.031 105.00 105.00 105.00 0.013 0.000 3.23E+005 3.61E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.606 0.495 0.518 0.566
Peak Current (kA), Method C : 0.874 0.714 0.747 0.816
Breaking Current (kA, rms, symm) : 0.495 0.518 0.566
Steady State Current (kA, rms) : 0.584 0.495 0.518 0.566

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 33

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus19


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus19 Total 0.00 0.468 0.00 114.99 118.01 0.375 0.375 3.22E+004 3.33E+003 5.49E+004 1.91E+003

MCC-B1 BUS A Bus19 104.84 0.438 104.86 104.85 105.19 0.364 0.375 3.46E+004 9.66E+002 5.49E+004 1.91E+003

B1-53-PA-442A Bus19 105.00 0.045 105.00 105.00 105.00 0.019 0.000 2.04E+005 2.69E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.468 0.375 0.396 0.436
Peak Current (kA), Method C : 0.675 0.541 0.572 0.628
Breaking Current (kA, rms, symm) : 0.375 0.396 0.436
Steady State Current (kA, rms) : 0.438 0.375 0.396 0.436

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 34

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus20


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus20 Total 0.00 0.305 0.00 115.00 115.10 0.253 0.253 4.96E+004 1.70E+003 8.01E+004 2.73E+003

MCC-B1 BUS A Bus20 104.89 0.301 104.89 104.89 105.12 0.251 0.253 5.04E+004 1.29E+003 8.01E+004 2.73E+003

B1-PX-25-306A Bus20 105.00 0.005 105.00 105.00 105.00 0.002 0.000 2.44E+006 1.53E+006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.305 0.253 0.263 0.285
Peak Current (kA), Method C : 0.440 0.364 0.379 0.411
Breaking Current (kA, rms, symm) : 0.253 0.263 0.285
Steady State Current (kA, rms) : 0.301 0.253 0.263 0.285

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 35

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus24


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus24 Total 0.00 13.230 0.00 120.28 116.18 10.223 10.223 7.11E+002 8.98E+002 1.11E+003 1.74E+003

MCC-B1 BUS A Bus24 84.01 13.230 88.00 102.64 107.44 10.223 10.223 7.11E+002 8.98E+002 1.11E+003 1.74E+003

Bus10 Bus24 0.00 0.000 67.08 69.45 107.31 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 13.230 10.223 10.998 12.168
Peak Current (kA), Method C : 20.838 16.102 17.323 19.165
Breaking Current (kA, rms, symm) : 10.223 10.998 12.168
Steady State Current (kA, rms) : 13.054 10.223 10.998 12.168

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 36

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus25


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus25 Total 0.00 1.573 0.00 111.20 113.88 1.365 1.365 8.79E+003 2.61E+003 1.29E+004 3.36E+003

LSPDB-B1 Bus25 87.20 1.573 90.92 102.71 105.76 1.365 1.365 8.79E+003 2.61E+003 1.29E+004 3.36E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.573 1.365 1.358 1.506
Peak Current (kA), Method C : 2.269 1.970 1.960 2.172
Breaking Current (kA, rms, symm) : 1.365 1.358 1.506
Steady State Current (kA, rms) : 1.573 1.365 1.358 1.506

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 37

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus26


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus26 Total 0.00 18.109 0.00 115.74 116.52 14.518 14.518 5.47E+002 6.33E+002 8.47E+002 1.07E+003

MCC-B1 BUS A Bus26 77.86 18.109 82.08 101.34 108.92 14.518 14.518 5.47E+002 6.33E+002 8.47E+002 1.07E+003

Bus12 Bus26 0.00 0.000 68.95 68.49 110.89 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 18.109 14.518 14.850 16.507
Peak Current (kA), Method C : 28.078 22.510 23.026 25.594
Breaking Current (kA, rms, symm) : 14.518 14.850 16.507
Steady State Current (kA, rms) : 17.735 14.518 14.850 16.507

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 38

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus27


Nominal kV = 6.600
Voltage c Factor = 1.10 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus27 Total 0.00 1.280 0.00 190.53 190.53 0.000 0.000 1.93E+002 7.27E+002

Bus29 Bus27 0.57 0.042 0.00 190.53 190.53 0.000 0.000 1.24E+004 1.93E+004

Bus2 Bus27 68.72 1.240 110.00 110.00 110.00 0.000 0.000 1.91E+002 7.52E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.280 0.000 1.032 1.032
Peak Current (kA), Method C : 2.674 0.000 2.157 2.157
Breaking Current (kA, rms, symm) : 0.000 1.032 1.032
Steady State Current (kA, rms) : 1.203 0.000 1.032 1.032

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 39

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus29


Nominal kV = 6.600
Voltage c Factor = 1.10 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus29 Total 0.00 1.173 0.00 190.53 190.53 0.000 0.000 2.98E+002 7.64E+002

Bus27 Bus29 15.49 1.132 0.00 190.53 190.53 0.000 0.000 3.03E+002 7.94E+002

Bus6 Bus29 2.45 0.042 115.50 115.50 115.50 0.000 0.000 1.23E+004 1.92E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.173 0.000 0.951 0.951
Peak Current (kA), Method C : 2.211 0.000 1.792 1.792
Breaking Current (kA, rms, symm) : 0.000 0.951 0.951
Steady State Current (kA, rms) : 1.104 0.000 0.951 0.951

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 40

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus31


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus31 Total 0.00 1.048 0.00 112.31 117.70 0.867 0.867 1.30E+004 1.98E+003 2.10E+004 1.31E+003

MCC-B3 Bus31 100.64 1.010 102.03 103.42 106.14 0.853 0.867 1.35E+004 1.51E+003 2.10E+004 1.31E+003

B3-PA-21-135 Bus31 105.00 0.056 105.00 105.00 105.00 0.024 0.000 1.42E+005 1.99E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.048 0.867 0.896 0.997
Peak Current (kA), Method C : 1.512 1.251 1.292 1.439
Breaking Current (kA, rms, symm) : 0.867 0.896 0.997
Steady State Current (kA, rms) : 1.008 0.867 0.896 0.997

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 41

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus32


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus32 Total 0.00 1.314 0.00 115.29 119.22 1.038 1.038 1.13E+004 2.43E+003 2.00E+004 2.36E+003

MCC-B1 BUS A Bus32 104.45 1.201 104.50 104.62 105.53 0.995 1.038 1.26E+004 1.14E+003 2.00E+004 2.36E+003

B1-PA-25-315A Bus32 105.00 0.189 105.00 105.00 105.00 0.080 0.000 3.74E+004 7.07E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.314 1.038 1.106 1.220
Peak Current (kA), Method C : 1.896 1.498 1.596 1.762
Breaking Current (kA, rms, symm) : 1.038 1.106 1.220
Steady State Current (kA, rms) : 1.201 1.038 1.106 1.220

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 42

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus34


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus34 Total 0.00 4.924 0.00 115.51 118.51 3.915 3.915 2.87E+003 1.12E+003 5.05E+003 1.77E+003

MCC-B1 BUS A Bus34 101.58 4.564 101.91 103.57 106.82 3.743 3.915 3.19E+003 9.13E+002 5.05E+003 1.77E+003

B1-28-PA-137A Bus34 105.00 0.568 105.00 105.00 105.00 0.275 0.000 9.42E+003 2.49E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.924 3.915 4.193 4.586
Peak Current (kA), Method C : 7.155 5.689 6.094 6.664
Breaking Current (kA, rms, symm) : 3.915 4.193 4.586
Steady State Current (kA, rms) : 4.562 3.915 4.193 4.586

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 43

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus35


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus35 Total 0.00 1.048 0.00 113.87 114.18 0.885 0.885 1.28E+004 2.64E+003 1.99E+004 4.18E+003

MCC-B3 Bus35 99.62 1.048 101.05 103.32 105.94 0.885 0.885 1.28E+004 2.64E+003 1.99E+004 4.18E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.048 0.885 0.906 0.986
Peak Current (kA), Method C : 1.512 1.277 1.307 1.422
Breaking Current (kA, rms, symm) : 0.885 0.906 0.986
Steady State Current (kA, rms) : 1.046 0.885 0.906 0.986

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 44

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus36


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus36 Total 0.00 0.669 0.00 130.44 178.19 0.299 0.299 1.12E+004 1.97E+004 1.21E+005 1.82E-005

B1-21-PA-120A Bus36 105.00 0.617 105.00 105.00 105.00 0.183 0.000 8.16E+003 2.32E+004

VFD120A Bus36 105.00 0.125 105.00 105.00 105.00 0.125 0.299 1.21E+005 1.82E-005 1.21E+005 1.82E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.669 0.299 0.519 0.606
Peak Current (kA), Method C : 1.368 0.611 1.061 1.239
Breaking Current (kA, rms, symm) : 0.299 0.519 0.606
Steady State Current (kA, rms) : 0.125 0.299 0.519 0.606

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 45

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus38


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus38 Total 0.00 0.411 0.00 126.22 181.32 0.160 0.160 1.96E+004 3.13E+004 2.22E+005 3.33E-005

B1-HC-21-107A Bus38 105.00 0.379 105.00 105.00 105.00 0.097 0.000 1.58E+004 3.67E+004

VFD107A Bus38 105.00 0.068 105.00 105.00 105.00 0.068 0.160 2.22E+005 3.33E-005 2.22E+005 3.33E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.411 0.160 0.266 0.322
Peak Current (kA), Method C : 0.789 0.307 0.512 0.619
Breaking Current (kA, rms, symm) : 0.160 0.266 0.322
Steady State Current (kA, rms) : 0.068 0.160 0.266 0.322

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 46

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus40


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus40 Total 0.00 0.669 0.00 130.44 178.19 0.299 0.299 1.12E+004 1.97E+004 1.21E+005 1.82E-005

B1-20-PA-138A Bus40 105.00 0.617 105.00 105.00 105.00 0.183 0.000 8.16E+003 2.32E+004

VFD138A Bus40 105.00 0.125 105.00 105.00 105.00 0.125 0.299 1.21E+005 1.82E-005 1.21E+005 1.82E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.669 0.299 0.519 0.606
Peak Current (kA), Method C : 1.368 0.611 1.061 1.239
Breaking Current (kA, rms, symm) : 0.299 0.519 0.606
Steady State Current (kA, rms) : 0.125 0.299 0.519 0.606

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 47

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus42


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus42 Total 0.00 1.268 0.00 103.29 102.24 1.325 1.325 8.56E+003 7.49E+003 7.25E+003 6.64E+003

Bus60 Bus42 16.89 1.268 21.12 103.96 99.09 1.325 1.325 8.56E+003 7.49E+003 7.25E+003 6.64E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.268 1.325 1.094 1.306
Peak Current (kA), Method C : 1.887 1.971 1.628 1.943
Breaking Current (kA, rms, symm) : 1.325 1.094 1.306
Steady State Current (kA, rms) : 1.267 1.325 1.094 1.306

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 48

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus43


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus43 Total 0.00 0.605 0.00 113.29 115.16 0.509 0.509 2.27E+004 1.69E+003 3.55E+004 1.77E+003

MCC-B3 Bus43 102.50 0.605 103.25 104.02 105.63 0.509 0.509 2.27E+004 1.69E+003 3.55E+004 1.77E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.605 0.509 0.523 0.572
Peak Current (kA), Method C : 0.872 0.734 0.755 0.826
Breaking Current (kA, rms, symm) : 0.509 0.523 0.572
Steady State Current (kA, rms) : 0.604 0.509 0.523 0.572

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 49

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus44


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus44 Total 0.00 2.172 0.00 101.06 104.25 2.274 2.274 4.22E+003 5.13E+003 3.80E+003 4.19E+003

Bus41 Bus44 10.79 2.172 13.55 101.56 102.18 2.274 2.274 4.22E+003 5.13E+003 3.80E+003 4.19E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.172 2.274 1.867 2.264
Peak Current (kA), Method C : 3.388 3.548 2.914 3.533
Breaking Current (kA, rms, symm) : 2.274 1.867 2.264
Steady State Current (kA, rms) : 2.167 2.274 1.867 2.264

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 50

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus47


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus47 Total 0.00 2.012 0.00 116.27 112.57 1.687 1.687 5.97E+003 3.31E+003 8.96E+003 5.89E+003

MCC-B3 Bus47 90.20 2.012 93.79 102.21 105.90 1.687 1.687 5.97E+003 3.31E+003 8.96E+003 5.89E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.012 1.687 1.733 1.914
Peak Current (kA), Method C : 2.916 2.444 2.511 2.773
Breaking Current (kA, rms, symm) : 1.687 1.733 1.914
Steady State Current (kA, rms) : 1.995 1.687 1.733 1.914

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 51

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus48


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus48 Total 0.00 8.523 0.00 103.83 103.18 8.819 8.819 6.48E+002 1.48E+003 4.90E+002 1.23E+003

MCC-B3 Bus48 18.61 8.523 27.27 99.59 100.83 8.819 8.819 6.48E+002 1.48E+003 4.90E+002 1.23E+003

Bus30 Bus48 0.00 0.000 59.57 59.95 107.87 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 8.523 8.819 7.101 8.775
Peak Current (kA), Method C : 15.541 16.081 12.949 16.001
Breaking Current (kA, rms, symm) : 8.819 7.101 8.775
Steady State Current (kA, rms) : 8.028 8.819 7.101 8.775

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 52

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus49


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus49 Total 0.00 2.346 0.00 108.13 117.34 2.032 2.032 5.70E+003 1.35E+003 8.53E+003 9.04E+002

MCC-B3 Bus49 93.55 2.346 96.99 101.13 107.24 2.032 2.032 5.70E+003 1.35E+003 8.53E+003 9.04E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.346 2.032 2.024 2.305
Peak Current (kA), Method C : 3.384 2.932 2.919 3.325
Breaking Current (kA, rms, symm) : 2.032 2.024 2.305
Steady State Current (kA, rms) : 2.333 2.032 2.024 2.305

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 53

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus50


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus50 Total 0.00 1.296 0.00 104.11 94.55 1.456 1.456 7.39E+003 7.60E+003 3.94E+003 5.90E+003

Bus37 Bus50 0.00 0.000 0.00 104.11 94.55 0.000 0.000

Bus33 Bus50 70.27 1.296 91.64 105.40 80.62 1.456 1.456 * 7.39E+003 7.60E+003 3.94E+003 5.90E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.296 1.456 1.117 1.464
Peak Current (kA), Method C : 1.968 2.210 1.696 2.222
Breaking Current (kA, rms, symm) : 1.456 1.117 1.464
Steady State Current (kA, rms) : 1.287 1.456 1.117 1.464

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 54

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus52


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus52 Total 0.00 1.071 0.00 105.09 114.99 0.977 0.977 1.13E+004 4.57E+003 1.54E+004 3.66E+003

LSP-DB-B3 Bus52 71.33 1.071 77.84 101.13 105.96 0.977 0.977 1.13E+004 4.57E+003 1.54E+004 3.66E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.071 0.977 0.925 1.074
Peak Current (kA), Method C : 1.546 1.409 1.335 1.551
Breaking Current (kA, rms, symm) : 0.977 0.925 1.074
Steady State Current (kA, rms) : 1.067 0.977 0.925 1.074

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 55

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus53


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus53 Total 0.00 0.614 0.00 114.98 119.40 0.486 0.486 2.44E+004 3.73E+003 4.28E+004 2.12E+003

MCC-B1 BUS A Bus53 104.79 0.562 104.81 104.82 105.25 0.466 0.486 2.69E+004 1.05E+003 4.28E+004 2.12E+003

B1-28-PA-145A Bus53 105.00 0.084 105.00 105.00 105.00 0.035 0.000 9.71E+004 1.52E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.614 0.486 0.517 0.572
Peak Current (kA), Method C : 0.886 0.701 0.745 0.825
Breaking Current (kA, rms, symm) : 0.486 0.517 0.572
Steady State Current (kA, rms) : 0.562 0.486 0.517 0.572

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 56

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus54


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus54 Total 0.00 1.930 0.00 115.72 113.84 1.607 1.607 7.77E+003 1.14E+003 1.23E+004 2.36E+003

MCC-B1 BUS A Bus54 103.94 1.930 103.96 104.32 105.76 1.607 1.607 7.77E+003 1.14E+003 1.23E+004 2.36E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.930 1.607 1.667 1.821
Peak Current (kA), Method C : 2.784 2.318 2.405 2.626
Breaking Current (kA, rms, symm) : 1.607 1.667 1.821
Steady State Current (kA, rms) : 1.930 1.607 1.667 1.821

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 57

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus56


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus56 Total 0.00 3.222 0.00 115.99 117.97 2.558 2.558 4.49E+003 1.39E+003 7.87E+003 2.05E+003

MCC-B1 BUS A Bus56 103.10 2.991 103.25 104.05 106.27 2.466 2.558 4.96E+003 1.02E+003 7.87E+003 2.05E+003

B1-HC-21-107B Bus56 105.00 0.379 105.00 105.00 105.00 0.161 0.000 1.58E+004 3.67E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.222 2.558 2.722 2.978
Peak Current (kA), Method C : 4.661 3.701 3.938 4.307
Breaking Current (kA, rms, symm) : 2.558 2.722 2.978
Steady State Current (kA, rms) : 2.991 2.558 2.722 2.978

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 58

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus57


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus57 Total 0.00 0.316 0.00 115.21 116.99 0.256 0.256 4.78E+004 3.44E+003 8.01E+004 2.73E+003

MCC-B1 BUS A Bus57 104.89 0.301 104.90 104.90 105.13 0.250 0.256 5.04E+004 1.29E+003 8.01E+004 2.73E+003

B1-PX-25-309A Bus57 105.00 0.021 105.00 105.00 105.00 0.009 0.000 5.02E+005 5.03E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.316 0.256 0.269 0.294
Peak Current (kA), Method C : 0.456 0.369 0.388 0.425
Breaking Current (kA, rms, symm) : 0.256 0.269 0.294
Steady State Current (kA, rms) : 0.301 0.256 0.269 0.294

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 59

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus59


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus59 Total 0.00 7.609 0.00 120.75 114.36 6.001 6.001 1.60E+003 1.18E+003 2.53E+003 2.46E+003

MCC-B1 BUS A Bus59 95.22 7.609 96.49 103.10 107.01 6.001 6.001 1.60E+003 1.18E+003 2.53E+003 2.46E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.609 6.001 6.460 7.163
Peak Current (kA), Method C : 11.160 8.801 9.475 10.506
Breaking Current (kA, rms, symm) : 6.001 6.460 7.163
Steady State Current (kA, rms) : 7.571 6.001 6.460 7.163

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 60

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus61


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus61 Total 0.00 1.937 0.00 99.73 109.01 1.963 1.963 5.00E+003 4.55E+003 5.32E+003 3.62E+003

LSP-DB-B3 Bus61 30.68 1.937 37.35 99.21 104.14 1.963 1.963 5.00E+003 4.55E+003 5.32E+003 3.62E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.937 1.963 1.665 2.034
Peak Current (kA), Method C : 2.894 2.934 2.488 3.040
Breaking Current (kA, rms, symm) : 1.963 1.665 2.034
Steady State Current (kA, rms) : 1.915 1.963 1.665 2.034

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 61

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus62


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus62 Total 0.00 19.972 0.00 116.21 116.53 15.903 15.903 4.26E+002 6.28E+002 6.54E+002 1.06E+003

MCC-B1 BUS A Bus62 72.47 19.972 78.22 101.67 108.55 15.903 15.903 4.26E+002 6.28E+002 6.54E+002 1.06E+003

Bus65 Bus62 0.00 0.000 68.96 68.77 111.38 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 19.972 15.903 16.238 18.080
Peak Current (kA), Method C : 32.567 25.931 26.478 29.482
Breaking Current (kA, rms, symm) : 15.903 16.238 18.080
Steady State Current (kA, rms) : 19.429 15.903 16.238 18.080

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 62

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus63


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus63 Total 0.00 11.884 0.00 121.11 116.08 9.133 9.133 8.06E+002 9.88E+002 1.26E+003 1.97E+003

MCC-B1 BUS A Bus63 86.24 11.884 89.84 102.85 107.21 9.133 9.133 8.06E+002 9.88E+002 1.26E+003 1.97E+003

Bus64 Bus63 0.00 0.000 67.02 69.92 107.06 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 11.884 9.133 9.923 10.976
Peak Current (kA), Method C : 18.605 14.298 15.534 17.184
Breaking Current (kA, rms, symm) : 9.133 9.923 10.976
Steady State Current (kA, rms) : 11.745 9.133 9.923 10.976

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 63

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus64


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus64 Total 0.00 2.460 0.00 102.08 101.32 2.627 2.627 3.52E+003 5.06E+003 2.71E+003 4.07E+003

Bus4 Bus64 0.00 0.000 0.00 102.08 101.32 0.000 0.000

Bus63 Bus64 83.34 2.460 93.84 105.60 93.00 2.627 2.627 * 3.52E+003 5.06E+003 2.71E+003 4.07E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.460 2.627 2.114 2.569
Peak Current (kA), Method C : 3.973 4.243 3.414 4.149
Breaking Current (kA, rms, symm) : 2.627 2.114 2.569
Steady State Current (kA, rms) : 2.454 2.627 2.114 2.569

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 64

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus65


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus65 Total 0.00 6.993 0.00 99.33 100.15 7.828 7.828 1.15E+003 1.71E+003 7.23E+002 1.08E+003

LSPDB-B1 Bus65 0.00 0.000 0.00 99.33 100.15 0.000 0.000

Bus62 Bus65 64.76 6.993 81.12 104.27 82.08 7.828 7.828 * 1.15E+003 1.71E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.993 7.828 5.915 7.631
Peak Current (kA), Method C : 11.401 12.762 9.642 12.441
Breaking Current (kA, rms, symm) : 7.828 5.915 7.631
Steady State Current (kA, rms) : 6.936 7.828 5.915 7.631

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 65

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus67


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus67 Total 0.00 2.012 0.00 110.40 113.35 1.768 1.768 6.69E+003 2.59E+003 9.53E+003 3.31E+003

LSPDB-B1 Bus67 80.92 2.012 85.67 102.16 105.76 1.768 1.768 6.69E+003 2.59E+003 9.53E+003 3.31E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.012 1.768 1.735 1.935
Peak Current (kA), Method C : 2.904 2.551 2.504 2.792
Breaking Current (kA, rms, symm) : 1.768 1.735 1.935
Steady State Current (kA, rms) : 2.011 1.768 1.735 1.935

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 66

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus68


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus68 Total 0.00 0.812 0.00 107.40 115.42 0.721 0.721 1.55E+004 4.58E+003 2.19E+004 3.69E+003

LSP-DB-B3 Bus68 80.93 0.812 86.03 102.04 105.94 0.721 0.721 1.55E+004 4.58E+003 2.19E+004 3.69E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.812 0.721 0.702 0.801
Peak Current (kA), Method C : 1.171 1.040 1.012 1.155
Breaking Current (kA, rms, symm) : 0.721 0.702 0.801
Steady State Current (kA, rms) : 0.810 0.721 0.702 0.801

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 67

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus70


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus70 Total 0.00 1.716 0.00 100.35 111.49 1.690 1.690 6.12E+003 4.54E+003 7.11E+003 3.60E+003

LSP-DB-B3 Bus70 42.65 1.716 50.32 99.40 105.00 1.690 1.690 6.12E+003 4.54E+003 7.11E+003 3.60E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.716 1.690 1.477 1.788
Peak Current (kA), Method C : 2.518 2.479 2.168 2.623
Breaking Current (kA, rms, symm) : 1.690 1.477 1.788
Steady State Current (kA, rms) : 1.701 1.690 1.477 1.788

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 68

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus71


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus71 Total 0.00 17.388 0.00 118.66 116.57 13.534 13.534 4.62E+002 7.39E+002 7.11E+002 1.34E+003

MCC-B1 BUS A Bus71 75.76 17.378 81.60 102.40 107.71 13.529 13.534 4.62E+002 7.40E+002 7.11E+002 1.34E+003

Bus1 Bus71 0.20 0.011 69.03 70.27 110.90 0.004 0.000 1.17E+006 7.33E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 17.388 13.534 14.239 15.793
Peak Current (kA), Method C : 28.891 22.487 23.658 26.241
Breaking Current (kA, rms, symm) : 13.534 14.239 15.793
Steady State Current (kA, rms) : 16.986 13.534 14.239 15.793

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 69

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus72


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus72 Total 0.00 2.067 0.00 107.67 115.51 1.829 1.829 6.71E+003 1.92E+003 9.57E+003 1.60E+003

LSPDB-B1 Bus72 82.60 2.067 87.46 101.87 106.15 1.829 1.829 6.71E+003 1.92E+003 9.57E+003 1.60E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.067 1.829 1.784 2.034
Peak Current (kA), Method C : 2.982 2.638 2.573 2.934
Breaking Current (kA, rms, symm) : 1.829 1.784 2.034
Steady State Current (kA, rms) : 2.067 1.829 1.784 2.034

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 70

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus73


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus73 Total 0.00 1.573 0.00 111.20 113.88 1.365 1.365 8.79E+003 2.61E+003 1.29E+004 3.36E+003

LSPDB-B1 Bus73 87.20 1.573 90.92 102.71 105.76 1.365 1.365 8.79E+003 2.61E+003 1.29E+004 3.36E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.573 1.365 1.358 1.506
Peak Current (kA), Method C : 2.269 1.970 1.960 2.172
Breaking Current (kA, rms, symm) : 1.365 1.358 1.506
Steady State Current (kA, rms) : 1.573 1.365 1.358 1.506

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 71

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus75


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus75 Total 0.00 0.718 0.00 111.41 115.47 0.613 0.613 1.98E+004 3.38E+003 3.01E+004 3.30E+003

MCC-B2 Bus75 92.46 0.713 94.89 103.91 105.59 0.611 0.613 1.99E+004 3.35E+003 3.01E+004 3.30E+003

B2-PD-42-953A Bus75 105.00 0.005 105.00 105.00 105.00 0.002 0.000 2.32E+006 1.46E+006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.718 0.613 0.620 0.688
Peak Current (kA), Method C : 1.036 0.885 0.894 0.993
Breaking Current (kA, rms, symm) : 0.613 0.620 0.688
Steady State Current (kA, rms) : 0.713 0.613 0.620 0.688

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 72

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus78


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus78 Total 0.00 0.707 0.00 112.98 114.51 0.600 0.600 2.02E+004 2.63E+003 3.11E+004 3.42E+003

LSPDB-B1 Bus78 97.94 0.707 99.57 103.93 105.47 0.600 0.600 2.02E+004 2.63E+003 3.11E+004 3.42E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.707 0.600 0.611 0.669
Peak Current (kA), Method C : 1.019 0.865 0.882 0.965
Breaking Current (kA, rms, symm) : 0.600 0.611 0.669
Steady State Current (kA, rms) : 0.707 0.600 0.611 0.669

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 73

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus79


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus79 Total 0.00 1.800 0.00 109.00 115.13 1.578 1.578 7.75E+003 2.06E+003 1.12E+004 1.96E+003

LSPDB-B1 Bus79 85.55 1.800 89.79 102.29 106.01 1.578 1.578 7.75E+003 2.06E+003 1.12E+004 1.96E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.800 1.578 1.554 1.754
Peak Current (kA), Method C : 2.597 2.276 2.242 2.530
Breaking Current (kA, rms, symm) : 1.578 1.554 1.754
Steady State Current (kA, rms) : 1.800 1.578 1.554 1.754

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 74

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus80


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus80 Total 0.00 1.800 0.00 109.00 115.13 1.578 1.578 7.75E+003 2.06E+003 1.12E+004 1.96E+003

LSPDB-B1 Bus80 85.55 1.800 89.79 102.29 106.01 1.578 1.578 7.75E+003 2.06E+003 1.12E+004 1.96E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.800 1.578 1.554 1.754
Peak Current (kA), Method C : 2.597 2.276 2.242 2.530
Breaking Current (kA, rms, symm) : 1.578 1.554 1.754
Steady State Current (kA, rms) : 1.800 1.578 1.554 1.754

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 75

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus86


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus86 Total 0.00 1.497 0.00 109.60 115.52 1.301 1.301 9.44E+003 1.92E+003 1.39E+004 1.62E+003

LSPDB-B1 Bus86 89.57 1.497 93.11 102.71 105.95 1.301 1.301 9.44E+003 1.92E+003 1.39E+004 1.62E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.497 1.301 1.294 1.454
Peak Current (kA), Method C : 2.160 1.876 1.867 2.097
Breaking Current (kA, rms, symm) : 1.301 1.294 1.454
Steady State Current (kA, rms) : 1.498 1.301 1.294 1.454

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 76

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus91


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus91 Total 0.00 0.594 0.00 111.94 115.06 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

MCC-B2 Bus91 94.73 0.594 96.73 104.08 105.48 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.594 0.507 0.514 0.567
Peak Current (kA), Method C : 0.857 0.731 0.741 0.818
Breaking Current (kA, rms, symm) : 0.507 0.514 0.567
Steady State Current (kA, rms) : 0.594 0.507 0.514 0.567

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 77

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus93


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus93 Total 0.00 0.594 0.00 111.94 115.06 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

MCC-B2 Bus93 94.73 0.594 96.73 104.08 105.48 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.594 0.507 0.514 0.567
Peak Current (kA), Method C : 0.857 0.731 0.741 0.818
Breaking Current (kA, rms, symm) : 0.507 0.514 0.567
Steady State Current (kA, rms) : 0.594 0.507 0.514 0.567

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 78

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus95


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus95 Total 0.00 0.970 0.00 97.96 104.73 1.043 1.043 1.11E+004 9.94E+003 9.55E+003 6.80E+003

Bus97 Bus95 24.11 0.970 31.06 98.37 100.54 1.043 1.043 1.11E+004 9.94E+003 9.55E+003 6.80E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.970 1.043 0.838 1.045
Peak Current (kA), Method C : 1.447 1.556 1.250 1.560
Breaking Current (kA, rms, symm) : 1.043 0.838 1.045
Steady State Current (kA, rms) : 0.969 1.043 0.838 1.045

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 79

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus96


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus96 Total 0.00 2.903 0.00 105.50 108.54 2.793 2.793 3.52E+003 3.51E+003 4.01E+003 3.71E+003

MCC-B2 Bus96 31.23 2.903 37.27 101.64 104.77 2.793 2.793 3.52E+003 3.51E+003 4.01E+003 3.71E+003

Bus97 Bus96 0.00 0.000 62.66 60.91 105.62 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.903 2.793 2.491 2.889
Peak Current (kA), Method C : 4.388 4.222 3.765 4.367
Breaking Current (kA, rms, symm) : 2.793 2.491 2.889
Steady State Current (kA, rms) : 2.890 2.793 2.491 2.889

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 80

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus97


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus97 Total 0.00 1.167 0.00 100.14 96.22 1.342 1.342 7.65E+003 9.70E+003 4.13E+003 6.20E+003

Bus95 Bus97 0.00 0.000 0.00 100.14 96.22 0.000 0.000

Bus96 Bus97 63.28 1.167 84.43 105.32 79.74 1.342 1.342 * 7.65E+003 9.70E+003 4.13E+003 6.20E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.167 1.342 1.007 1.311
Peak Current (kA), Method C : 1.836 2.111 1.584 2.062
Breaking Current (kA, rms, symm) : 1.342 1.007 1.311
Steady State Current (kA, rms) : 1.165 1.342 1.007 1.311

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 81

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus99


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus99 Total 0.00 3.450 0.00 130.55 182.39 1.614 1.614 1.68E+003 4.06E+003 2.30E+004 3.45E-006

B1-CX-63-928B Bus99 105.00 3.256 105.00 105.00 105.00 1.011 0.000 9.43E+002 4.56E+003

VFD_928B Bus99 105.00 0.659 105.00 105.00 105.00 0.659 1.614 2.30E+004 3.45E-006 2.30E+004 3.45E-006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.450 1.614 2.708 3.186
Peak Current (kA), Method C : 8.074 3.777 6.338 7.457
Breaking Current (kA, rms, symm) : 1.614 2.708 3.186
Steady State Current (kA, rms) : 0.659 1.614 2.708 3.186

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 82

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus100


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus100 Total 0.00 3.476 0.00 114.87 118.27 2.785 2.785 4.21E+003 1.12E+003 7.27E+003 1.44E+003

MCC-B1 BUS A Bus100 103.14 3.256 103.29 103.95 106.39 2.697 2.785 4.59E+003 7.82E+002 7.27E+003 1.44E+003

B1-XX-COMBUSTIO Bus100 105.00 0.379 105.00 105.00 105.00 0.162 0.000 1.58E+004 3.67E+004
N

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.476 2.785 2.943 3.241
Peak Current (kA), Method C : 5.022 4.023 4.252 4.682
Breaking Current (kA, rms, symm) : 2.785 2.943 3.241
Steady State Current (kA, rms) : 3.256 2.785 2.943 3.241

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 83

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus104


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus104 Total 0.00 2.018 0.00 115.82 117.87 1.607 1.607 7.30E+003 1.79E+003 1.27E+004 2.42E+003

MCC-B1 BUS A Bus104 103.97 1.875 104.05 104.39 105.81 1.551 1.607 8.00E+003 1.17E+003 1.27E+004 2.42E+003

B1-XX-AMINE Bus104 105.00 0.234 105.00 105.00 105.00 0.099 0.000 2.89E+004 5.81E+004
REFLUX COND

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.018 1.607 1.707 1.867
Peak Current (kA), Method C : 2.912 2.319 2.463 2.695
Breaking Current (kA, rms, symm) : 1.607 1.707 1.867
Steady State Current (kA, rms) : 1.876 1.607 1.707 1.867

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 84

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus105


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus105 Total 0.00 1.082 0.00 114.49 116.49 0.887 0.887 1.40E+004 1.05E+003 2.29E+004 8.80E+002

MCC-B1 BUS A Bus105 104.61 1.049 104.63 104.64 105.44 0.875 0.887 1.44E+004 5.59E+002 2.29E+004 8.80E+002

B1-CX-64-929 Bus105 105.00 0.051 105.00 105.00 105.00 0.022 0.000 1.81E+005 2.39E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.082 0.887 0.927 1.014
Peak Current (kA), Method C : 1.561 1.280 1.337 1.462
Breaking Current (kA, rms, symm) : 0.887 0.927 1.014
Steady State Current (kA, rms) : 1.050 0.887 0.927 1.014

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 85

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus107


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus107 Total 0.00 0.594 0.00 111.94 115.06 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

MCC-B2 Bus107 94.73 0.594 96.73 104.08 105.48 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.594 0.507 0.514 0.567
Peak Current (kA), Method C : 0.857 0.731 0.741 0.818
Breaking Current (kA, rms, symm) : 0.507 0.514 0.567
Steady State Current (kA, rms) : 0.594 0.507 0.514 0.567

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 86

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus109


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus109 Total 0.00 0.594 0.00 111.94 115.06 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

MCC-B2 Bus109 94.73 0.594 96.73 104.08 105.48 0.507 0.507 2.40E+004 3.43E+003 3.66E+004 3.51E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.594 0.507 0.514 0.567
Peak Current (kA), Method C : 0.857 0.731 0.741 0.818
Breaking Current (kA, rms, symm) : 0.507 0.514 0.567
Steady State Current (kA, rms) : 0.594 0.507 0.514 0.567

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 87

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus111


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus111 Total 0.00 1.738 0.00 106.87 114.27 1.567 1.567 7.59E+003 3.37E+003 1.05E+004 3.36E+003

MCC-B2 Bus111 69.11 1.738 74.65 102.39 105.89 1.567 1.567 7.59E+003 3.37E+003 1.05E+004 3.36E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.738 1.567 1.499 1.718
Peak Current (kA), Method C : 2.510 2.262 2.165 2.481
Breaking Current (kA, rms, symm) : 1.567 1.499 1.718
Steady State Current (kA, rms) : 1.736 1.567 1.499 1.718

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 88

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus114


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus114 Total 0.00 4.249 0.00 116.27 113.96 3.514 3.514 3.44E+003 9.59E+002 5.44E+003 1.90E+003

MCC-B1 BUS A Bus114 101.85 4.249 101.98 103.57 106.57 3.514 3.514 3.44E+003 9.59E+002 5.44E+003 1.90E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.249 3.514 3.654 4.001
Peak Current (kA), Method C : 6.129 5.068 5.271 5.772
Breaking Current (kA, rms, symm) : 3.514 3.654 4.001
Steady State Current (kA, rms) : 4.247 3.514 3.654 4.001

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 89

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus115


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus115 Total 0.00 1.319 0.00 114.71 114.53 1.101 1.101 1.15E+004 7.93E+002 1.82E+004 1.48E+003

MCC-B1 BUS A Bus115 104.45 1.319 104.46 104.53 105.53 1.101 1.101 1.15E+004 7.93E+002 1.82E+004 1.48E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.319 1.101 1.140 1.236
Peak Current (kA), Method C : 1.902 1.589 1.645 1.783
Breaking Current (kA, rms, symm) : 1.101 1.140 1.236
Steady State Current (kA, rms) : 1.319 1.101 1.140 1.236

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 90

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus116


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus116 Total 0.00 0.533 0.00 114.83 115.16 0.441 0.441 2.84E+004 1.10E+003 4.58E+004 1.62E+003

MCC-B1 BUS A Bus116 104.81 0.526 104.81 104.81 105.22 0.439 0.441 2.88E+004 8.49E+002 4.58E+004 1.62E+003

HOT OIL FILL Bus116 105.00 0.009 105.00 105.00 105.00 0.004 0.000 1.43E+006 1.05E+006
DRAIN PUMP

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.533 0.441 0.459 0.498
Peak Current (kA), Method C : 0.768 0.637 0.662 0.718
Breaking Current (kA, rms, symm) : 0.441 0.459 0.498
Steady State Current (kA, rms) : 0.526 0.441 0.459 0.498

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 91

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus117


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus117 Total 0.00 0.301 0.00 114.81 114.41 0.251 0.251 5.04E+004 1.29E+003 8.01E+004 2.73E+003

MCC-B1 BUS A Bus117 104.89 0.301 104.89 104.89 105.12 0.251 0.251 5.04E+004 1.29E+003 8.01E+004 2.73E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.301 0.251 0.260 0.282
Peak Current (kA), Method C : 0.434 0.362 0.375 0.407
Breaking Current (kA, rms, symm) : 0.251 0.260 0.282
Steady State Current (kA, rms) : 0.301 0.251 0.260 0.282

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 92

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus131


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus131 Total 0.00 1.744 0.00 113.96 115.21 1.458 1.458 8.68E+003 4.43E+002 1.38E+004 5.85E+002

MCC-B1 BUS A Bus131 104.34 1.744 104.36 104.37 105.71 1.458 1.458 8.68E+003 4.43E+002 1.38E+004 5.85E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.744 1.458 1.508 1.643
Peak Current (kA), Method C : 2.516 2.103 2.176 2.370
Breaking Current (kA, rms, symm) : 1.458 1.508 1.643
Steady State Current (kA, rms) : 1.745 1.458 1.508 1.643

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 93

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus132


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus132 Total 0.00 0.323 0.00 115.27 118.10 0.258 0.258 4.67E+004 4.50E+003 8.01E+004 2.73E+003

MCC-B1 BUS A Bus132 104.89 0.301 104.90 104.90 105.13 0.250 0.258 5.04E+004 1.29E+003 8.01E+004 2.73E+003

B1-XX-XX-XXX Bus132 105.00 0.031 105.00 105.00 105.00 0.013 0.000 3.23E+005 3.61E+005
ANTIFOAM

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.323 0.258 0.273 0.300
Peak Current (kA), Method C : 0.466 0.372 0.394 0.433
Breaking Current (kA, rms, symm) : 0.258 0.273 0.300
Steady State Current (kA, rms) : 0.301 0.258 0.273 0.300

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 94

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus133


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus133 Total 0.00 1.875 0.00 115.76 113.81 1.562 1.562 8.00E+003 1.17E+003 1.27E+004 2.42E+003

MCC-B1 BUS A Bus133 103.97 1.875 103.99 104.34 105.74 1.562 1.562 8.00E+003 1.17E+003 1.27E+004 2.42E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.875 1.562 1.620 1.770
Peak Current (kA), Method C : 2.705 2.253 2.337 2.553
Breaking Current (kA, rms, symm) : 1.562 1.620 1.770
Steady State Current (kA, rms) : 1.876 1.562 1.620 1.770

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 95

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus144


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus144 Total 0.00 2.018 0.00 115.82 117.87 1.607 1.607 7.30E+003 1.79E+003 1.27E+004 2.42E+003

MCC-B1 BUS A Bus144 103.97 1.875 104.05 104.39 105.81 1.551 1.607 8.00E+003 1.17E+003 1.27E+004 2.42E+003

B1-HE-25-310 Bus144 105.00 0.234 105.00 105.00 105.00 0.099 0.000 2.89E+004 5.81E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.018 1.607 1.707 1.867
Peak Current (kA), Method C : 2.912 2.319 2.463 2.695
Breaking Current (kA, rms, symm) : 1.607 1.707 1.867
Steady State Current (kA, rms) : 1.876 1.607 1.707 1.867

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 96

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus151


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus151 Total 0.00 1.581 0.00 115.49 119.00 1.247 1.247 7.92E+003 3.58E+003 1.42E+004 5.19E+003

MCC-B3 Bus151 96.41 1.408 98.88 103.09 106.44 1.177 1.247 9.27E+003 3.06E+003 1.42E+004 5.19E+003

B3-KF-39-902 Bus151 105.00 0.234 105.00 105.00 105.00 0.099 0.000 2.62E+004 5.27E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.581 1.247 1.324 1.462
Peak Current (kA), Method C : 2.299 1.813 1.925 2.127
Breaking Current (kA, rms, symm) : 1.247 1.324 1.462
Steady State Current (kA, rms) : 1.404 1.247 1.324 1.462

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 97

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus152


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus152 Total 0.00 1.347 0.00 130.49 180.34 0.616 0.616 4.89E+003 1.01E+004 5.95E+004 8.93E-006

B3-PA-39-119A Bus152 105.00 1.257 105.00 105.00 105.00 0.382 0.000 3.18E+003 1.16E+004

VFD_119A Bus152 105.00 0.255 105.00 105.00 105.00 0.255 0.616 5.95E+004 8.93E-006 5.95E+004 8.93E-006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.347 0.616 1.052 1.233
Peak Current (kA), Method C : 2.949 1.348 2.303 2.699
Breaking Current (kA, rms, symm) : 0.616 1.052 1.233
Steady State Current (kA, rms) : 0.255 0.616 1.052 1.233

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 98

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus153


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus153 Total 0.00 1.347 0.00 130.49 180.34 0.616 0.616 4.89E+003 1.01E+004 5.95E+004 8.93E-006

B3-PA-39-119B Bus153 105.00 1.257 105.00 105.00 105.00 0.382 0.000 3.18E+003 1.16E+004

VFD_119B Bus153 105.00 0.255 105.00 105.00 105.00 0.255 0.616 5.95E+004 8.93E-006 5.95E+004 8.93E-006

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 1.347 0.616 1.052 1.233
Peak Current (kA), Method C : 2.949 1.348 2.303 2.699
Breaking Current (kA, rms, symm) : 0.616 1.052 1.233
Steady State Current (kA, rms) : 0.255 0.616 1.052 1.233

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 99

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus157


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus157 Total 0.00 2.396 0.00 109.76 120.55 1.978 1.978 5.37E+003 2.01E+003 9.00E+003 1.62E+003

MCC-B3 Bus157 93.17 2.205 96.89 101.69 107.48 1.899 1.978 6.01E+003 1.66E+003 9.00E+003 1.62E+003

B3-KA-63-001 Bus157 105.00 0.278 105.00 105.00 105.00 0.123 0.000 2.11E+004 4.47E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.396 1.978 2.021 2.317
Peak Current (kA), Method C : 3.470 2.865 2.927 3.355
Breaking Current (kA, rms, symm) : 1.978 2.021 2.317
Steady State Current (kA, rms) : 2.198 1.978 2.021 2.317

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 100

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus162


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus162 Total 0.00 8.481 0.00 95.30 109.76 8.964 8.964 9.22E+002 1.33E+003 9.26E+002 8.64E+002

MCC-B3 Bus162 29.04 8.481 37.17 95.42 104.85 8.964 8.964 9.22E+002 1.33E+003 9.26E+002 8.64E+002

Bus163 Bus162 0.00 0.000 64.96 56.40 110.30 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 8.481 8.964 7.088 9.408
Peak Current (kA), Method C : 13.759 14.543 11.499 15.264
Breaking Current (kA, rms, symm) : 8.964 7.088 9.408
Steady State Current (kA, rms) : 8.028 8.964 7.088 9.408

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 101

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus163


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus163 Total 0.00 2.531 0.00 99.83 100.18 2.803 2.803 2.89E+003 4.29E+003 1.97E+003 2.95E+003

LSP-DB-B3 Bus163 0.00 0.000 0.00 99.83 100.18 0.000 0.000

Bus162 Bus163 70.32 2.531 84.75 103.30 85.14 2.803 2.803 * 2.89E+003 4.29E+003 1.97E+003 2.95E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.531 2.803 2.167 2.713
Peak Current (kA), Method C : 4.120 4.562 3.528 4.417
Breaking Current (kA, rms, symm) : 2.803 2.167 2.713
Steady State Current (kA, rms) : 2.487 2.803 2.167 2.713

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 102

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus165


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus165 Total 0.00 55.088 0.00 105.46 105.57 61.704 61.704 4.05E+001 2.72E+002 1.40E+001 7.86E+001

MCC-B1 BUS A Bus165 17.36 25.610 18.01 103.49 107.70 22.724 9.655 1.51E+002 5.72E+002 1.83E+002 4.77E+002

GG-001 Bus165 105.00 29.770 105.00 105.00 105.00 39.169 52.254 2.68E+001 5.08E+002 1.33E+001 9.34E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 55.088 61.704 39.956 71.266
Peak Current (kA), Method C : 131.994 147.846 95.737 170.757
Breaking Current (kA, rms, symm) : 61.704 39.956 71.266
Steady State Current (kA, rms) : 15.223 61.704 39.956 71.266

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 103

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus166


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus166 Total 0.00 55.222 0.00 105.48 105.60 61.817 61.817 4.05E+001 2.71E+002 1.40E+001 7.86E+001

MCC-B1 BUS A Bus166 15.51 25.745 16.07 103.72 107.51 22.811 9.673 1.50E+002 5.69E+002 1.83E+002 4.77E+002

GG-002 Bus166 105.00 29.770 105.00 105.00 105.00 39.195 52.350 2.68E+001 5.08E+002 1.33E+001 9.34E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 55.222 61.817 40.038 71.406
Peak Current (kA), Method C : 132.276 148.073 95.905 171.042
Breaking Current (kA, rms, symm) : 61.817 40.038 71.406
Steady State Current (kA, rms) : 15.223 61.817 40.038 71.406

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 104

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus167


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus167 Total 0.00 39.314 0.00 109.68 112.63 34.767 34.767 8.65E+001 3.76E+002 1.14E+002 4.15E+002

MCC-B1 BUS A Bus167 31.35 39.314 40.94 102.90 108.27 34.767 34.767 8.65E+001 3.76E+002 1.14E+002 4.15E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 39.314 34.767 29.924 37.473
Peak Current (kA), Method C : 85.083 75.242 64.760 81.097
Breaking Current (kA, rms, symm) : 34.767 29.924 37.473
Steady State Current (kA, rms) : 35.805 34.767 29.924 37.473

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 105

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus168


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus168 Total 0.00 39.314 0.00 109.68 112.63 34.767 34.767 8.65E+001 3.76E+002 1.14E+002 4.15E+002

MCC-B1 BUS A Bus168 31.35 39.314 40.94 102.90 108.27 34.767 34.767 8.65E+001 3.76E+002 1.14E+002 4.15E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 39.314 34.767 29.924 37.473
Peak Current (kA), Method C : 85.083 75.242 64.760 81.097
Breaking Current (kA, rms, symm) : 34.767 29.924 37.473
Steady State Current (kA, rms) : 35.805 34.767 29.924 37.473

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 106

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: Bus169


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus169 Total 0.00 24.850 0.00 115.24 116.11 19.986 19.986 2.49E+002 5.57E+002 3.73E+002 8.75E+002

MCC-B1 BUS A Bus169 60.82 24.850 69.24 102.15 108.11 19.986 19.986 2.49E+002 5.57E+002 3.73E+002 8.75E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 24.850 19.986 19.829 22.498
Peak Current (kA), Method C : 45.137 36.301 36.017 40.865
Breaking Current (kA, rms, symm) : 19.986 19.829 22.498
Steady State Current (kA, rms) : 23.780 19.986 19.829 22.498

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 107

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: LSP-DB-B3


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

LSP-DB-B3 Total 0.00 2.476 0.00 99.77 101.09 2.717 2.717 3.03E+003 4.33E+003 2.20E+003 3.06E+003

Bus70 LSP-DB-B3 0.00 0.000 0.00 99.77 101.09 0.000 0.000

Bus163 LSP-DB-B3 2.99 2.476 4.00 99.70 100.57 2.717 2.717 3.03E+003 4.33E+003 2.20E+003 3.06E+003

Bus52 LSP-DB-B3 0.00 0.000 0.00 99.77 101.09 0.000 0.000

Bus23 LSP-DB-B3 0.00 0.000 0.00 99.77 101.09 0.000 0.000

Bus61 LSP-DB-B3 0.00 0.000 0.00 99.77 101.09 0.000 0.000

Bus68 LSP-DB-B3 0.00 0.000 0.00 99.77 101.09 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.476 2.717 2.121 2.647
Peak Current (kA), Method C : 3.994 4.382 3.421 4.270
Breaking Current (kA, rms, symm) : 2.717 2.121 2.647
Steady State Current (kA, rms) : 2.434 2.717 2.121 2.647

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 108

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: LSPDB-B1


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

LSPDB-B1 Total 0.00 6.739 0.00 99.87 101.15 7.409 7.409 1.22E+003 1.76E+003 8.41E+002 1.20E+003

Bus79 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus80 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus21 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus65 LSPDB-B1 4.22 6.739 5.96 99.29 100.62 7.409 7.409 1.22E+003 1.76E+003 8.41E+002 1.20E+003

Bus72 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus78 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus73 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus86 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus67 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

Bus25 LSPDB-B1 0.00 0.000 0.00 99.87 101.15 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.739 7.409 5.706 7.252
Peak Current (kA), Method C : 10.893 11.976 9.222 11.721
Breaking Current (kA, rms, symm) : 7.409 5.706 7.252
Steady State Current (kA, rms) : 6.688 7.409 5.706 7.252

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 109

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: MCC-B1 BUS A


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

MCC-B1 BUS A Total 0.00 55.725 0.00 103.54 110.76 56.899 56.899 4.54E+001 2.68E+002 4.89E+001 1.42E+002

P-20-PA-138A~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus26 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus15 MCC-B1 BUS A 5.41 0.030 3.24 103.17 112.87 0.018 0.000 3.49E+005 3.62E+005

Bus11 MCC-B1 BUS A 11.85 0.178 7.34 102.05 115.25 0.110 0.000 4.70E+004 7.10E+004

Bus9 MCC-B1 BUS A 13.26 0.577 9.64 100.33 115.57 0.420 0.000 1.14E+004 2.37E+004

Bus19 MCC-B1 BUS A 10.07 0.042 6.14 102.67 114.67 0.026 0.000 2.39E+005 2.70E+005

Bus5 MCC-B1 BUS A 5.99 0.030 3.59 103.14 113.09 0.018 0.000 3.52E+005 3.62E+005

Bus54 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

P-B1-21-PA-120A~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus34 MCC-B1 BUS A 11.83 0.532 8.58 100.86 114.95 0.386 0.000 1.26E+004 2.56E+004

Bus53 MCC-B1 BUS A 14.39 0.077 8.90 102.08 116.29 0.048 0.000 1.24E+005 1.52E+005

Bus13 MCC-B1 BUS A 10.48 0.131 6.46 102.31 114.74 0.081 0.000 6.60E+004 9.48E+004

P-B1-63-CX-928A~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

P-B1-63-CX-928B~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus114 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

P-B1-CX-63-928C~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus105 MCC-B1 BUS A 4.89 0.049 2.95 103.10 112.64 0.030 0.000 1.96E+005 2.39E+005

Bus66 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus63 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus76 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus62 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

P-B1-HC-21-107A~ MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus56 MCC-B1 BUS A 12.20 0.354 7.60 102.05 115.23 0.221 0.000 2.07E+004 3.75E+004

Bus8 MCC-B1 BUS A 12.20 0.354 7.60 102.05 115.23 0.221 0.000 2.07E+004 3.75E+004

Bus144 MCC-B1 BUS A 12.08 0.218 7.51 102.14 115.25 0.135 0.000 3.68E+004 5.90E+004

P-B1-HOT OIL PAC MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000
FAN A~
P-B1-HOT OIL PAC MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000
FAN B~
Bus14 MCC-B1 BUS A 13.26 0.577 9.64 100.33 115.57 0.420 0.000 1.14E+004 2.37E+004

Bus32 MCC-B1 BUS A 15.10 0.174 9.41 101.82 116.46 0.108 0.000 4.99E+004 7.16E+004

Bus20 MCC-B1 BUS A 1.81 0.005 1.04 103.55 111.48 0.003 0.000 2.49E+006 1.54E+006
Project: ETAP Page: 110

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

(Cont.)

Fault at bus: MCC-B1 BUS A


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus57 MCC-B1 BUS A 7.07 0.020 4.23 103.17 113.54 0.012 0.000 5.53E+005 5.04E+005

Bus24 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus104 MCC-B1 BUS A 12.08 0.218 7.51 102.14 115.25 0.135 0.000 3.68E+004 5.90E+004

Bus117 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus100 MCC-B1 BUS A 11.31 0.357 7.04 102.05 114.93 0.222 0.000 2.04E+004 3.73E+004

Bus133 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus132 MCC-B1 BUS A 10.16 0.029 6.15 102.88 114.73 0.018 0.000 3.74E+005 3.62E+005

Bus59 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus115 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus131 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus116 MCC-B1 BUS A 1.68 0.008 0.97 103.51 111.43 0.005 0.000 1.46E+006 1.05E+006

Bus71 MCC-B1 BUS A 0.05 0.011 0.03 103.54 110.77 0.006 0.000 1.17E+006 7.33E+005

Bus2 MCC-B1 BUS A 0.09 0.648 0.06 103.54 110.78 0.405 0.000 1.26E+004 1.97E+004

Bus165 MCC-B1 BUS A 17.29 25.509 25.60 101.89 108.36 26.474 27.291 8.32E+001 5.88E+002 1.03E+002 2.96E+002

Bus166 MCC-B1 BUS A 15.62 25.930 23.96 102.09 108.17 27.494 29.609 7.70E+001 5.79E+002 9.31E+001 2.74E+002

Bus167 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus168 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

Bus169 MCC-B1 BUS A 0.00 0.000 0.00 103.54 110.76 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 55.725 56.899 40.377 63.863
Peak Current (kA), Method C : 129.237 131.959 93.642 148.108
Breaking Current (kA, rms, symm) : 56.899 40.377 63.863
Steady State Current (kA, rms) : 15.266 56.899 40.377 63.863

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 111

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: MCC-B2


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

MCC-B2 Total 0.00 3.928 0.00 101.17 103.52 4.143 4.143 2.14E+003 2.99E+003 1.81E+003 2.39E+003

Bus91 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus93 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus107 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus109 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus111 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus90 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus1 MCC-B2 7.02 3.918 9.20 100.64 102.40 4.138 4.143 2.14E+003 3.00E+003 1.81E+003 2.39E+003

Bus92 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus96 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus22 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

Bus69 MCC-B2 0.68 0.005 0.36 101.24 103.79 0.003 0.000 2.34E+006 1.46E+006

Bus75 MCC-B2 0.68 0.005 0.36 101.24 103.79 0.003 0.000 2.34E+006 1.46E+006

Bus94 MCC-B2 0.00 0.000 0.00 101.17 103.52 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 3.928 4.143 3.355 4.104
Peak Current (kA), Method C : 6.309 6.654 5.389 6.592
Breaking Current (kA, rms, symm) : 4.143 3.355 4.104
Steady State Current (kA, rms) : 3.901 4.143 3.355 4.104

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 112

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Fault at bus: MCC-B3


Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

MCC-B3 Total 0.00 10.305 0.00 99.25 99.09 11.876 11.876 4.83E+002 1.24E+003 2.27E+002 6.37E+002

Bus43 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus6 MCC-B3 6.63 9.701 10.97 98.17 98.06 11.487 11.876 4.95E+002 1.33E+003 2.27E+002 6.37E+002

Bus49 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus48 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus162 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus157 MCC-B3 11.08 0.262 7.03 98.20 103.35 0.166 0.000 2.67E+004 4.51E+004

Bus151 MCC-B3 14.54 0.212 9.28 98.53 104.77 0.135 0.000 3.50E+004 5.45E+004

Bus31 MCC-B3 5.42 0.054 3.37 98.93 101.26 0.034 0.000 1.55E+005 2.00E+005

P-B3-PA-39-119A~ MCC-B3 0.00 0.000 0.00 94.53 94.37 0.000 0.000

P-B3-PA-39-119B~ MCC-B3 0.00 0.000 0.00 94.53 94.37 0.000 0.000

Bus45 MCC-B3 10.65 0.089 6.70 98.53 103.35 0.056 0.000 9.39E+004 1.23E+005

Bus33 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus47 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

Bus35 MCC-B3 0.00 0.000 0.00 99.25 99.09 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 10.305 11.876 8.513 11.745
Peak Current (kA), Method C : 19.444 22.409 16.064 22.163
Breaking Current (kA, rms, symm) : 11.876 8.513 11.745
Steady State Current (kA, rms) : 9.581 11.876 8.513 11.745

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 113

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus1 0.400 4.155 6.803 4.125 4.483 7.339 4.483 4.483 3.546 5.806 3.546 3.546 4.385 7.180 4.385 4.385
Bus2 0.400 52.541 116.974 45.652 52.016 115.806 52.016 52.016 38.419 85.534 38.419 38.419 57.726 128.518 57.726 57.726
Bus3 0.400 0.255 0.470 0.042 0.098 0.180 0.098 0.098 0.165 0.304 0.165 0.165 0.199 0.366 0.199 0.199
Bus4 0.400 2.285 3.560 2.279 2.387 3.719 2.387 2.387 1.965 3.061 1.965 1.965 2.380 3.709 2.380 2.380
Bus5 0.400 0.548 0.790 0.526 0.446 0.643 0.446 0.446 0.468 0.674 0.468 0.468 0.511 0.737 0.511 0.511
Bus6 0.400 10.904 20.991 10.168 13.171 25.356 13.171 13.171 8.995 17.317 8.995 8.995 13.342 25.685 13.342 13.342
Bus7 0.400 3.450 8.074 0.659 1.614 3.777 1.614 1.614 2.708 6.338 2.708 2.708 3.186 7.457 3.186 3.186
Bus8 0.400 3.222 4.661 2.991 2.558 3.701 2.558 2.558 2.722 3.938 2.722 2.722 2.978 4.307 2.978 2.978
Bus9 0.400 4.801 6.982 4.441 3.835 5.577 3.835 3.835 4.091 5.950 4.091 4.091 4.521 6.575 4.521 4.521
Bus10 0.400 2.998 4.847 2.989 3.220 5.205 3.220 3.220 2.572 4.157 2.572 2.572 3.143 5.080 3.143 3.143
Bus11 0.400 1.673 2.414 1.568 1.344 1.939 1.344 1.344 1.418 2.046 1.418 1.418 1.571 2.266 1.571 1.571
Bus12 0.400 4.193 6.743 4.174 4.515 7.260 4.515 4.515 3.581 5.758 3.581 3.581 4.419 7.105 4.419 4.419
Bus13 0.400 1.388 2.002 1.308 1.118 1.613 1.118 1.118 1.178 1.700 1.178 1.178 1.300 1.876 1.300 1.300
Bus15 0.400 0.606 0.874 0.584 0.495 0.714 0.495 0.495 0.518 0.747 0.518 0.518 0.566 0.816 0.566 0.566
Bus19 0.400 0.468 0.675 0.438 0.375 0.541 0.375 0.375 0.396 0.572 0.396 0.396 0.436 0.628 0.436 0.436
Bus20 0.400 0.305 0.440 0.301 0.253 0.364 0.253 0.253 0.263 0.379 0.263 0.263 0.285 0.411 0.285 0.285
Bus24 0.400 13.230 20.838 13.054 10.223 16.102 10.223 10.223 10.998 17.323 10.998 10.998 12.168 19.165 12.168 12.168
Bus25 0.400 1.573 2.269 1.573 1.365 1.970 1.365 1.365 1.358 1.960 1.358 1.358 1.506 2.172 1.506 1.506
Bus26 0.400 18.109 28.078 17.735 14.518 22.510 14.518 14.518 14.850 23.026 14.850 14.850 16.507 25.594 16.507 16.507
Bus27 6.600 1.280 2.674 1.203 0.000 0.000 0.000 0.000 1.032 2.157 1.032 1.032 1.032 2.157 1.032 1.032
Bus29 6.600 1.173 2.211 1.104 0.000 0.000 0.000 0.000 0.951 1.792 0.951 0.951 0.951 1.792 0.951 0.951
Bus31 0.400 1.048 1.512 1.008 0.867 1.251 0.867 0.867 0.896 1.292 0.896 0.896 0.997 1.439 0.997 0.997
Bus32 0.400 1.314 1.896 1.201 1.038 1.498 1.038 1.038 1.106 1.596 1.106 1.106 1.220 1.762 1.220 1.220
Bus34 0.400 4.924 7.155 4.562 3.915 5.689 3.915 3.915 4.193 6.094 4.193 4.193 4.586 6.664 4.586 4.586
Bus35 0.400 1.048 1.512 1.046 0.885 1.277 0.885 0.885 0.906 1.307 0.906 0.906 0.986 1.422 0.986 0.986
Bus36 0.400 0.669 1.368 0.125 0.299 0.611 0.299 0.299 0.519 1.061 0.519 0.519 0.606 1.239 0.606 0.606
Bus38 0.400 0.411 0.789 0.068 0.160 0.307 0.160 0.160 0.266 0.512 0.266 0.266 0.322 0.619 0.322 0.322
Bus40 0.400 0.669 1.368 0.125 0.299 0.611 0.299 0.299 0.519 1.061 0.519 0.519 0.606 1.239 0.606 0.606
Bus42 0.400 1.268 1.887 1.267 1.325 1.971 1.325 1.325 1.094 1.628 1.094 1.094 1.306 1.943 1.306 1.306
Bus43 0.400 0.605 0.872 0.604 0.509 0.734 0.509 0.509 0.523 0.755 0.523 0.523 0.572 0.826 0.572 0.572
Bus44 0.400 2.172 3.388 2.167 2.274 3.548 2.274 2.274 1.867 2.914 1.867 1.867 2.264 3.533 2.264 2.264
Bus47 0.400 2.012 2.916 1.995 1.687 2.444 1.687 1.687 1.733 2.511 1.733 1.733 1.914 2.773 1.914 1.914
Bus48 0.400 8.523 15.541 8.028 8.819 16.081 8.819 8.819 7.101 12.949 7.101 7.101 8.775 16.001 8.775 8.775
Bus49 0.400 2.346 3.384 2.333 2.032 2.932 2.032 2.032 2.024 2.919 2.024 2.024 2.305 3.325 2.305 2.305
Bus50 0.400 1.296 1.968 1.287 1.456 2.210 1.456 1.456 1.117 1.696 1.117 1.117 1.464 2.222 1.464 1.464
Bus52 0.400 1.071 1.546 1.067 0.977 1.409 0.977 0.977 0.925 1.335 0.925 0.925 1.074 1.551 1.074 1.074
Bus53 0.400 0.614 0.886 0.562 0.486 0.701 0.486 0.486 0.517 0.745 0.517 0.517 0.572 0.825 0.572 0.572
Project: ETAP Page: 114

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus54 0.400 1.930 2.784 1.930 1.607 2.318 1.607 1.607 1.667 2.405 1.667 1.667 1.821 2.626 1.821 1.821
Bus56 0.400 3.222 4.661 2.991 2.558 3.701 2.558 2.558 2.722 3.938 2.722 2.722 2.978 4.307 2.978 2.978
Bus57 0.400 0.316 0.456 0.301 0.256 0.369 0.256 0.256 0.269 0.388 0.269 0.269 0.294 0.425 0.294 0.294
Bus59 0.400 7.609 11.160 7.571 6.001 8.801 6.001 6.001 6.460 9.475 6.460 6.460 7.163 10.506 7.163 7.163
Bus61 0.400 1.937 2.894 1.915 1.963 2.934 1.963 1.963 1.665 2.488 1.665 1.665 2.034 3.040 2.034 2.034
Bus62 0.400 19.972 32.567 19.429 15.903 25.931 15.903 15.903 16.238 26.478 16.238 16.238 18.080 29.482 18.080 18.080
Bus63 0.400 11.884 18.605 11.745 9.133 14.298 9.133 9.133 9.923 15.534 9.923 9.923 10.976 17.184 10.976 10.976
Bus64 0.400 2.460 3.973 2.454 2.627 4.243 2.627 2.627 2.114 3.414 2.114 2.114 2.569 4.149 2.569 2.569
Bus65 0.400 6.993 11.401 6.936 7.828 12.762 7.828 7.828 5.915 9.642 5.915 5.915 7.631 12.441 7.631 7.631
Bus67 0.400 2.012 2.904 2.011 1.768 2.551 1.768 1.768 1.735 2.504 1.735 1.735 1.935 2.792 1.935 1.935
Bus68 0.400 0.812 1.171 0.810 0.721 1.040 0.721 0.721 0.702 1.012 0.702 0.702 0.801 1.155 0.801 0.801
Bus70 0.400 1.716 2.518 1.701 1.690 2.479 1.690 1.690 1.477 2.168 1.477 1.477 1.788 2.623 1.788 1.788
Bus71 0.400 17.388 28.891 16.986 13.534 22.487 13.534 13.534 14.239 23.658 14.239 14.239 15.793 26.241 15.793 15.793
Bus72 0.400 2.067 2.982 2.067 1.829 2.638 1.829 1.829 1.784 2.573 1.784 1.784 2.034 2.934 2.034 2.034
Bus73 0.400 1.573 2.269 1.573 1.365 1.970 1.365 1.365 1.358 1.960 1.358 1.358 1.506 2.172 1.506 1.506
Bus75 0.400 0.718 1.036 0.713 0.613 0.885 0.613 0.613 0.620 0.894 0.620 0.620 0.688 0.993 0.688 0.688
Bus78 0.400 0.707 1.019 0.707 0.600 0.865 0.600 0.600 0.611 0.882 0.611 0.611 0.669 0.965 0.669 0.669
Bus79 0.400 1.800 2.597 1.800 1.578 2.276 1.578 1.578 1.554 2.242 1.554 1.554 1.754 2.530 1.754 1.754
Bus80 0.400 1.800 2.597 1.800 1.578 2.276 1.578 1.578 1.554 2.242 1.554 1.554 1.754 2.530 1.754 1.754
Bus86 0.400 1.497 2.160 1.498 1.301 1.876 1.301 1.301 1.294 1.867 1.294 1.294 1.454 2.097 1.454 1.454
Bus91 0.400 0.594 0.857 0.594 0.507 0.731 0.507 0.507 0.514 0.741 0.514 0.514 0.567 0.818 0.567 0.567
Bus93 0.400 0.594 0.857 0.594 0.507 0.731 0.507 0.507 0.514 0.741 0.514 0.514 0.567 0.818 0.567 0.567
Bus95 0.400 0.970 1.447 0.969 1.043 1.556 1.043 1.043 0.838 1.250 0.838 0.838 1.045 1.560 1.045 1.045
Bus96 0.400 2.903 4.388 2.890 2.793 4.222 2.793 2.793 2.491 3.765 2.491 2.491 2.889 4.367 2.889 2.889
Bus97 0.400 1.167 1.836 1.165 1.342 2.111 1.342 1.342 1.007 1.584 1.007 1.007 1.311 2.062 1.311 1.311
Bus99 0.400 3.450 8.074 0.659 1.614 3.777 1.614 1.614 2.708 6.338 2.708 2.708 3.186 7.457 3.186 3.186
Bus100 0.400 3.476 5.022 3.256 2.785 4.023 2.785 2.785 2.943 4.252 2.943 2.943 3.241 4.682 3.241 3.241
Bus104 0.400 2.018 2.912 1.876 1.607 2.319 1.607 1.607 1.707 2.463 1.707 1.707 1.867 2.695 1.867 1.867
Bus105 0.400 1.082 1.561 1.050 0.887 1.280 0.887 0.887 0.927 1.337 0.927 0.927 1.014 1.462 1.014 1.014
Bus107 0.400 0.594 0.857 0.594 0.507 0.731 0.507 0.507 0.514 0.741 0.514 0.514 0.567 0.818 0.567 0.567
Bus109 0.400 0.594 0.857 0.594 0.507 0.731 0.507 0.507 0.514 0.741 0.514 0.514 0.567 0.818 0.567 0.567
Bus111 0.400 1.738 2.510 1.736 1.567 2.262 1.567 1.567 1.499 2.165 1.499 1.499 1.718 2.481 1.718 1.718
Bus114 0.400 4.249 6.129 4.247 3.514 5.068 3.514 3.514 3.654 5.271 3.654 3.654 4.001 5.772 4.001 4.001
Bus115 0.400 1.319 1.902 1.319 1.101 1.589 1.101 1.101 1.140 1.645 1.140 1.140 1.236 1.783 1.236 1.236
Bus116 0.400 0.533 0.768 0.526 0.441 0.637 0.441 0.441 0.459 0.662 0.459 0.459 0.498 0.718 0.498 0.498
Bus117 0.400 0.301 0.434 0.301 0.251 0.362 0.251 0.251 0.260 0.375 0.260 0.260 0.282 0.407 0.282 0.282
Bus131 0.400 1.744 2.516 1.745 1.458 2.103 1.458 1.458 1.508 2.176 1.508 1.508 1.643 2.370 1.643 1.643
Bus132 0.400 0.323 0.466 0.301 0.258 0.372 0.258 0.258 0.273 0.394 0.273 0.273 0.300 0.433 0.300 0.300
Bus133 0.400 1.875 2.705 1.876 1.562 2.253 1.562 1.562 1.620 2.337 1.620 1.620 1.770 2.553 1.770 1.770
Bus144 0.400 2.018 2.912 1.876 1.607 2.319 1.607 1.607 1.707 2.463 1.707 1.707 1.867 2.695 1.867 1.867
Project: ETAP Page: 115

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus151 0.400 1.581 2.299 1.404 1.247 1.813 1.247 1.247 1.324 1.925 1.324 1.324 1.462 2.127 1.462 1.462
Bus152 0.400 1.347 2.949 0.255 0.616 1.348 0.616 0.616 1.052 2.303 1.052 1.052 1.233 2.699 1.233 1.233
Bus153 0.400 1.347 2.949 0.255 0.616 1.348 0.616 0.616 1.052 2.303 1.052 1.052 1.233 2.699 1.233 1.233
Bus157 0.400 2.396 3.470 2.198 1.978 2.865 1.978 1.978 2.021 2.927 2.021 2.021 2.317 3.355 2.317 2.317
Bus162 0.400 8.481 13.759 8.028 8.964 14.543 8.964 8.964 7.088 11.499 7.088 7.088 9.408 15.264 9.408 9.408
Bus163 0.400 2.531 4.120 2.487 2.803 4.562 2.803 2.803 2.167 3.528 2.167 2.167 2.713 4.417 2.713 2.713
Bus165 0.400 55.088 131.994 15.223 61.704 147.846 61.704 61.704 39.956 95.737 39.956 39.956 71.266 170.757 71.266 71.266
Bus166 0.400 55.222 132.276 15.223 61.817 148.073 61.817 61.817 40.038 95.905 40.038 40.038 71.406 171.042 71.406 71.406
Bus167 0.400 39.314 85.083 35.805 34.767 75.242 34.767 34.767 29.924 64.760 29.924 29.924 37.473 81.097 37.473 37.473
Bus168 0.400 39.314 85.083 35.805 34.767 75.242 34.767 34.767 29.924 64.760 29.924 29.924 37.473 81.097 37.473 37.473
Bus169 0.400 24.850 45.137 23.780 19.986 36.301 19.986 19.986 19.829 36.017 19.829 19.829 22.498 40.865 22.498 22.498
LSP-DB-B3 0.400 2.476 3.994 2.434 2.717 4.382 2.717 2.717 2.121 3.421 2.121 2.121 2.647 4.270 2.647 2.647
LSPDB-B1 0.400 6.739 10.893 6.688 7.409 11.976 7.409 7.409 5.706 9.222 5.706 5.706 7.252 11.721 7.252 7.252
MCC-B1 BUS A 0.400 55.725 129.237 15.266 56.899 131.959 56.899 56.899 40.377 93.642 40.377 40.377 63.863 148.108 63.863 63.863
MCC-B2 0.400 3.928 6.309 3.901 4.143 6.654 4.143 4.143 3.355 5.389 3.355 3.355 4.104 6.592 4.104 4.104
MCC-B3 0.400 10.305 19.444 9.581 11.876 22.409 11.876 11.876 8.513 16.064 8.513 8.513 11.745 22.163 11.745 11.745

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 116

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus1 0.400 0.03206 0.04876 0.05836 0.03240 0.05059 0.06008 0.02432 0.03648 0.04384 0.00000 0.00000 0.00000

Bus2 0.400 0.00093 0.00452 0.00462 0.00128 0.00619 0.00632 0.00112 0.00288 0.00309 0.00000 0.00000 0.00000

Bus3 0.400 0.54422 0.77901 0.95028 0.81165 1.37867 1.59985 5.76594 0.00000 5.76594 0.00000 0.00000 0.00000

Bus4 0.400 0.06775 0.08171 0.10614 0.06810 0.08337 0.10765 0.06160 0.06713 0.09111 0.00000 0.00000 0.00000

Bus5 0.400 0.44167 0.03136 0.44278 0.45455 0.02866 0.45545 0.73278 0.02590 0.73324 0.00000 0.00000 0.00000

Bus6 0.400 0.00756 0.02092 0.02224 0.00780 0.02318 0.02446 0.00235 0.00822 0.00855 0.00000 0.00000 0.00000

Bus7 0.400 0.02686 0.06495 0.07029 0.03274 0.07822 0.08479 0.36783 0.00000 0.36783 0.00000 0.00000 0.00000

Bus8 0.400 0.07191 0.02218 0.07525 0.07581 0.02233 0.07903 0.12592 0.03276 0.13011 0.00000 0.00000 0.00000

Bus9 0.400 0.04767 0.01668 0.05051 0.04902 0.01781 0.05215 0.08421 0.02260 0.08719 0.00000 0.00000 0.00000

Bus10 0.400 0.04610 0.06645 0.08087 0.04645 0.06811 0.08244 0.03472 0.05208 0.06259 0.00000 0.00000 0.00000

Bus11 0.400 0.14321 0.02219 0.14492 0.14999 0.01984 0.15130 0.24520 0.01358 0.24557 0.00000 0.00000 0.00000

Bus12 0.400 0.03352 0.04712 0.05782 0.03389 0.04887 0.05947 0.02432 0.03648 0.04384 0.00000 0.00000 0.00000

Bus13 0.400 0.17307 0.02370 0.17469 0.18053 0.02121 0.18177 0.29408 0.01584 0.29451 0.00000 0.00000 0.00000

Bus15 0.400 0.39928 0.02715 0.40021 0.40981 0.02520 0.41059 0.65958 0.02354 0.66000 0.00000 0.00000 0.00000

Bus19 0.400 0.51581 0.05324 0.51855 0.53960 0.04511 0.54148 0.87918 0.03062 0.87971 0.00000 0.00000 0.00000

Bus20 0.400 0.79419 0.02724 0.79466 0.80292 0.02870 0.80343 1.28178 0.04361 1.28252 0.00000 0.00000 0.00000

Bus24 0.400 0.01138 0.01437 0.01833 0.01173 0.01603 0.01987 0.01772 0.02788 0.03303 0.00000 0.00000 0.00000

Bus25 0.400 0.14779 0.04388 0.15417 0.14816 0.04562 0.15503 0.21643 0.05654 0.22370 0.00000 0.00000 0.00000

Bus26 0.400 0.00876 0.01013 0.01339 0.00911 0.01179 0.01490 0.01355 0.01711 0.02183 0.00000 0.00000 0.00000

Bus27 6.600 0.83862 3.16578 3.27498 0.91729 3.64511 3.75876 0.00000 0.00000 0.00000

Bus29 6.600 1.29751 3.32913 3.57304 1.38251 3.81949 4.06200 0.00000 0.00000 0.00000

Bus31 0.400 0.22877 0.03488 0.23141 0.23473 0.03516 0.23735 0.37001 0.02304 0.37073 0.00000 0.00000 0.00000

Bus32 0.400 0.18045 0.03882 0.18457 0.19211 0.03513 0.19530 0.31939 0.03784 0.32163 0.00000 0.00000 0.00000

Bus34 0.400 0.04589 0.01786 0.04925 0.04717 0.01916 0.05092 0.08087 0.02836 0.08570 0.00000 0.00000 0.00000

Bus35 0.400 0.22662 0.04654 0.23135 0.22688 0.04887 0.23208 0.35080 0.07371 0.35846 0.00000 0.00000 0.00000

Bus36 0.400 0.17867 0.31508 0.36221 0.21184 0.39333 0.44675 1.93945 0.00000 1.93945 0.00000 0.00000 0.00000

Bus38 0.400 0.31342 0.50045 0.59050 0.47850 0.86353 0.98724 3.55566 0.00000 3.55566 0.00000 0.00000 0.00000

Bus40 0.400 0.17867 0.31508 0.36221 0.21184 0.39333 0.44675 1.93945 0.00000 1.93945 0.00000 0.00000 0.00000

Bus42 0.400 0.14391 0.12586 0.19118 0.14428 0.12761 0.19262 0.12184 0.11169 0.16528 0.00000 0.00000 0.00000

Bus43 0.400 0.39983 0.02984 0.40094 0.40008 0.03218 0.40138 0.62621 0.03131 0.62699 0.00000 0.00000 0.00000

Bus44 0.400 0.07100 0.08618 0.11166 0.07137 0.08793 0.11325 0.06380 0.07043 0.09503 0.00000 0.00000 0.00000

Bus47 0.400 0.10537 0.05844 0.12049 0.10563 0.06077 0.12186 0.15802 0.10394 0.18914 0.00000 0.00000 0.00000

Bus48 0.400 0.01142 0.02606 0.02845 0.01168 0.02839 0.03070 0.00864 0.02169 0.02335 0.00000 0.00000 0.00000

Bus49 0.400 0.10059 0.02380 0.10336 0.10084 0.02613 0.10417 0.15041 0.01595 0.15125 0.00000 0.00000 0.00000
Project: ETAP Page: 117

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus50 0.400 0.13042 0.13409 0.18706 0.13067 0.13643 0.18891 0.06944 0.10416 0.12518 0.00000 0.00000 0.00000

Bus52 0.400 0.20996 0.08462 0.22637 0.21023 0.08707 0.22755 0.28516 0.06792 0.29313 0.00000 0.00000 0.00000

Bus53 0.400 0.39038 0.05964 0.39491 0.41514 0.05019 0.41816 0.68514 0.03392 0.68598 0.00000 0.00000 0.00000

Bus54 0.400 0.12432 0.01823 0.12565 0.12467 0.01989 0.12625 0.19730 0.03768 0.20086 0.00000 0.00000 0.00000

Bus56 0.400 0.07191 0.02218 0.07525 0.07581 0.02233 0.07903 0.12592 0.03276 0.13011 0.00000 0.00000 0.00000

Bus57 0.400 0.76444 0.05512 0.76643 0.79212 0.04962 0.79367 1.28178 0.04361 1.28252 0.00000 0.00000 0.00000

Bus59 0.400 0.02567 0.01889 0.03187 0.02602 0.02055 0.03316 0.04044 0.03936 0.05643 0.00000 0.00000 0.00000

Bus61 0.400 0.09259 0.08427 0.12520 0.09286 0.08672 0.12706 0.09854 0.06703 0.11918 0.00000 0.00000 0.00000

Bus62 0.400 0.00681 0.01005 0.01214 0.00716 0.01171 0.01373 0.01046 0.01691 0.01988 0.00000 0.00000 0.00000

Bus63 0.400 0.01290 0.01581 0.02040 0.01325 0.01747 0.02193 0.02014 0.03154 0.03742 0.00000 0.00000 0.00000

Bus64 0.400 0.05630 0.08091 0.09857 0.05665 0.08257 0.10014 0.04340 0.06510 0.07824 0.00000 0.00000 0.00000

Bus65 0.400 0.01932 0.02880 0.03468 0.01969 0.03054 0.03634 0.01216 0.01824 0.02192 0.00000 0.00000 0.00000

Bus67 0.400 0.11238 0.04353 0.12052 0.11275 0.04527 0.12150 0.16013 0.05565 0.16953 0.00000 0.00000 0.00000

Bus68 0.400 0.28643 0.08482 0.29873 0.28670 0.08727 0.29969 0.40674 0.06843 0.41246 0.00000 0.00000 0.00000

Bus70 0.400 0.11350 0.08417 0.14130 0.11376 0.08662 0.14299 0.13177 0.06678 0.14773 0.00000 0.00000 0.00000

Bus71 0.400 0.00739 0.01183 0.01395 0.00774 0.01349 0.01556 0.01138 0.02144 0.02427 0.00000 0.00000 0.00000

Bus72 0.400 0.11279 0.03220 0.11730 0.11316 0.03394 0.11815 0.16079 0.02687 0.16302 0.00000 0.00000 0.00000

Bus73 0.400 0.14779 0.04388 0.15417 0.14816 0.04562 0.15503 0.21643 0.05654 0.22370 0.00000 0.00000 0.00000

Bus75 0.400 0.33276 0.05689 0.33759 0.33457 0.05905 0.33974 0.50627 0.05554 0.50931 0.00000 0.00000 0.00000

Bus78 0.400 0.34035 0.04423 0.34322 0.34072 0.04597 0.34381 0.52261 0.05743 0.52576 0.00000 0.00000 0.00000

Bus79 0.400 0.13021 0.03457 0.13472 0.13058 0.03631 0.13553 0.18847 0.03289 0.19132 0.00000 0.00000 0.00000

Bus80 0.400 0.13021 0.03457 0.13472 0.13058 0.03631 0.13553 0.18847 0.03289 0.19132 0.00000 0.00000 0.00000

Bus86 0.400 0.15867 0.03232 0.16193 0.15905 0.03406 0.16265 0.23374 0.02718 0.23532 0.00000 0.00000 0.00000

Bus91 0.400 0.40422 0.05765 0.40831 0.40456 0.05949 0.40892 0.61607 0.05908 0.61890 0.00000 0.00000 0.00000

Bus93 0.400 0.40422 0.05765 0.40831 0.40456 0.05949 0.40892 0.61607 0.05908 0.61890 0.00000 0.00000 0.00000

Bus95 0.400 0.18586 0.16713 0.24995 0.18620 0.16897 0.25144 0.16047 0.11432 0.19702 0.00000 0.00000 0.00000

Bus96 0.400 0.05917 0.05897 0.08354 0.05951 0.06081 0.08508 0.06744 0.06244 0.09190 0.00000 0.00000 0.00000

Bus97 0.400 0.12860 0.16313 0.20772 0.12895 0.16497 0.20938 0.06944 0.10416 0.12518 0.00000 0.00000 0.00000

Bus99 0.400 0.02686 0.06495 0.07029 0.03274 0.07822 0.08479 0.36783 0.00000 0.36783 0.00000 0.00000 0.00000

Bus100 0.400 0.06740 0.01796 0.06976 0.07067 0.01809 0.07295 0.11638 0.02310 0.11865 0.00000 0.00000 0.00000

Bus104 0.400 0.11674 0.02858 0.12018 0.12287 0.02764 0.12594 0.20308 0.03873 0.20673 0.00000 0.00000 0.00000

Bus105 0.400 0.22346 0.01674 0.22409 0.22848 0.01617 0.22905 0.36678 0.01409 0.36705 0.00000 0.00000 0.00000

Bus107 0.400 0.40422 0.05765 0.40831 0.40456 0.05949 0.40892 0.61607 0.05908 0.61890 0.00000 0.00000 0.00000

Bus109 0.400 0.40422 0.05765 0.40831 0.40456 0.05949 0.40892 0.61607 0.05908 0.61890 0.00000 0.00000 0.00000

Bus111 0.400 0.12752 0.05661 0.13953 0.12787 0.05845 0.14060 0.17613 0.05644 0.18495 0.00000 0.00000 0.00000

Bus114 0.400 0.05497 0.01535 0.05707 0.05532 0.01701 0.05788 0.08703 0.03037 0.09217 0.00000 0.00000 0.00000

Bus115 0.400 0.18346 0.01269 0.18390 0.18382 0.01435 0.18438 0.29134 0.02361 0.29229 0.00000 0.00000 0.00000
Project: ETAP Page: 118

Location: 19.0.1C Date: 05-30-2019

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: HKN Sarsang Config.: Normal

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus116 0.400 0.45487 0.01756 0.45521 0.45944 0.01874 0.45982 0.73278 0.02590 0.73324 0.00000 0.00000 0.00000

Bus117 0.400 0.80638 0.02057 0.80664 0.80673 0.02223 0.80704 1.28178 0.04361 1.28252 0.00000 0.00000 0.00000

Bus131 0.400 0.13884 0.00708 0.13902 0.13919 0.00874 0.13947 0.22038 0.00936 0.22058 0.00000 0.00000 0.00000

Bus132 0.400 0.74765 0.07205 0.75111 0.78541 0.06252 0.78790 1.28178 0.04361 1.28252 0.00000 0.00000 0.00000

Bus133 0.400 0.12796 0.01864 0.12931 0.12831 0.02030 0.12991 0.20308 0.03873 0.20673 0.00000 0.00000 0.00000

Bus144 0.400 0.11674 0.02858 0.12018 0.12287 0.02764 0.12594 0.20308 0.03873 0.20673 0.00000 0.00000 0.00000

Bus151 0.400 0.13979 0.06314 0.15339 0.15057 0.06480 0.16392 0.25042 0.09149 0.26661 0.00000 0.00000 0.00000

Bus152 0.400 0.07831 0.16209 0.18002 0.09394 0.19803 0.21918 0.95241 0.00000 0.95241 0.00000 0.00000 0.00000

Bus153 0.400 0.07831 0.16209 0.18002 0.09394 0.19803 0.21918 0.95241 0.00000 0.95241 0.00000 0.00000 0.00000

Bus157 0.400 0.09478 0.03546 0.10120 0.10017 0.03644 0.10659 0.15877 0.02850 0.16130 0.00000 0.00000 0.00000

Bus162 0.400 0.01626 0.02352 0.02859 0.01652 0.02585 0.03068 0.01633 0.01524 0.02234 0.00000 0.00000 0.00000

Bus163 0.400 0.05356 0.07942 0.09580 0.05383 0.08187 0.09798 0.03648 0.05471 0.06576 0.00000 0.00000 0.00000

Bus165 0.400 0.00065 0.00435 0.00440 0.00105 0.00602 0.00611 0.00022 0.00126 0.00128 0.00000 0.00000 0.00000

Bus166 0.400 0.00065 0.00434 0.00439 0.00105 0.00601 0.00610 0.00022 0.00126 0.00128 0.00000 0.00000 0.00000

Bus167 0.400 0.00138 0.00601 0.00617 0.00174 0.00767 0.00787 0.00183 0.00665 0.00689 0.00000 0.00000 0.00000

Bus168 0.400 0.00138 0.00601 0.00617 0.00174 0.00767 0.00787 0.00183 0.00665 0.00689 0.00000 0.00000 0.00000

Bus169 0.400 0.00399 0.00891 0.00976 0.00434 0.01057 0.01143 0.00597 0.01400 0.01522 0.00000 0.00000 0.00000

LSP-DB-B3 0.400 0.05624 0.08017 0.09793 0.05651 0.08262 0.10010 0.04074 0.05662 0.06975 0.00000 0.00000 0.00000

LSPDB-B1 0.400 0.02056 0.02953 0.03598 0.02093 0.03127 0.03763 0.01414 0.02009 0.02457 0.00000 0.00000 0.00000

MCC-B1 BUS A 0.400 0.00073 0.00429 0.00435 0.00108 0.00595 0.00605 0.00078 0.00228 0.00241 0.00000 0.00000 0.00000

MCC-B2 0.400 0.03592 0.05021 0.06174 0.03627 0.05205 0.06344 0.03048 0.04018 0.05044 0.00000 0.00000 0.00000

MCC-B3 0.400 0.00851 0.02194 0.02353 0.00877 0.02427 0.02581 0.00401 0.01123 0.01192 0.00000 0.00000 0.00000