You are on page 1of 5

ABB AG RTU560

Remote Terminal Unit


Data Sheet
Communication Unit 560CMG10

Application Characteristics
• The 560CMG10 is the Communication Unit The two microprocessors are the essential
(CMU) of the remote terminal unit RTU560G. hardware parts of the board, which share
The 560CMG10 consists of a metal DIN Rail themselves in the tasks:
Housing, which includes a CPU and a Power
Supply.
• MPU: 32 Bit Main Processing Unit
• SLC: 8 Bit Serial Line Controller

The SLC works as master for the RTU560G serial


The essential tasks of the 560CMG10 are:
peripheral bus (I/O-Interface/‘Wired-OR-Bus’).
• Managing and controlling of the I/O The MPU is responsible for the other tasks. The
boards via the interface to the RTU560G
MPU handles the absolute time and date for the
serial peripheral bus (I/O-Interface/Wired- RTU. The time can be set and synchronized from
OR-Bus). the central system via the serial lines or via the
• Reading Process events from the input Ethernet LAN interface.
boards.
• Writing commands to the output boards.
• Communications with control centers and
local MMI systems via the integrated
serial line interfaces and the implemented
Ethernet 10/100BaseT LAN interface.
• Managing the time base for the RTU560G
station and synchronizing the I/O boards.
• Handling the dialogue between RTU560G
and Web-Browser via LAN interface.

Figure 1: Function block diagram 560CMG10

Doc.-No.: 1KGT 150 645 V001 1 1


ABB AG

Data Sheet Communication Unit 560CMG10 RTU560

The control unit stores configuration files power ERR (1x) red Error / Warning
fail save in a removable Compact Flash memory
card. That allows the 560CMG10 to have valid Tx (3x) green Transmit data,
configuration data after power on and 560CMG10 communication
will be available again after a short initialization. ports 1, 2, A
The serial communication interfaces Rx (3x) green Receive data,
• Communication Port ‘1’ communication
ports 1, 2, A
• Communication Port ‘2’
A (1x) green Ethernet activity
are based on a USART (universal
synchronous/asynchronous receiver/transmitter)
and designed for RS232C standard. L (1x) green Ethernet link
The serial communication interface CPA is IO-Bus (1x) green Wired-OR-Bus
designed for RS485 standard. activity
The interface ‘E’ is based for the Ethernet Power Fail (1x) red One of the
standard 10BaseT/100BaseT. output voltage
The connectors of the serial and Ethernet is fail
communication interfaces are provided as RJ45
RUN (1x) green The CMU is
jacks integrated in the board's front plate.
reachable via
The 560CMG10 serial peripheral bus (I/O- ethernet
Interface/‘Wired-OR-Bus’) is connected via 20-
Def-IP (1x) red The default IP-
pole pluggable connector.
address is
560CMG10 indicates operational and error states active
by light emitting diodes on the front plate. The
exact definition for the LED has to be taken from
the functional description of the RTU560 releases.

DC-Out 24V DC-In

-
+
Error
Power RTU560
Run

Def. IP-Addr
560CMG10
Off On

IO-Bus

CPA
Tx Rx CP1 CP2
Tx LAN
Rx
Tx Rx Tx RX Tx RX Lnk ACT
IO-Bus

Figure 2: Layout 560CMG10

2 Doc.-No.: 1KGT 150 645 V001 1


ABB AG

RTU560 Data Sheet Communication Unit 560CMG10

Technical Data
In addition to the RTU560 general technical data, DC Input
the following applies:
Voltage: 24 V DC
Tolerance Range -15 ... +20 %
Main Processing Unit MPU
Max. Current 2,8 A @ 24 V DC
Microprocessor: ELAN520 @ 133 MHz Starting Current: < 20 A, 1.5 m sec
(incorporating an Intel 586TM (Class S1)
class 32 bit processor) according IEC 60870-
4
RAM: 64 MByte
Efficiency: 88 % @ 24 V DC
Flash Memory: 128 MByte (CompactFlash)

Internal Output 1
Serial Line Controller SLC Voltage: 5,0 V DC
Controller Type: 80C251 Tolerance: ±5%
RAM: 32 kByte Current min.: 0A
Dual Ported RAM: 16 kByte Current max.: 1A
Residual Ripple ≤ 100 mVss
Serial Interfaces ‘1’ and ‘2’
Physical Interfaces: RS232C
Internal Output 2
Bit rate: ≤ 38 400 bit/s Voltage: ± 15 V DC
Signal lines RS232C: GND E2/102 Tolerance: ±5%
TxD D1/103
Current min.: 0A
RxD D2/104
RTS S2/105 Current max.: 0,5 A
CTS M2/106
Residual Ripple ≤ 200 mVss
DTR S1.2/108
DCD M5/109
Internal Output 3
Serial Interface ‘A’ Voltage: 18 V DC
Physical Interface: RS485 Tolerance: ±5%

Bit rate: ≤ 19 200 bit/s Current min.: 0A

Signal lines RS485: G Signal ground Current max.: 1A


A Receive/Transmit Residual Ripple ≤ 200 mVss
B Receive/Transmit

Ethernet LAN Interface ‘E’ DC Output


(It is not allowed for the process supply)
Physical Interface: 10BaseT/100BaseT Voltage: 24 V DC
Bit rate: 10/100 MBit/s Tolerance: -15 % … +20 %
Current min.: 0A
Current max.: 500m A
Residual Ripple ≤ 200 mVss

Doc.-No.: 1KGT 150 645 V001 1 3


ABB AG

Data Sheet Communication Unit 560CMG10 RTU560

Mechanical Layout
Metal Housing: 204 x 105 mm
Height: 55 mm
Weight: approx. 0.5 kg

Connector Types
Power Supply 2 x 3 pole pluggable
screw terminals
IO-Interface 1 x 20-pole
Wired-OR-Interface pluggable connectors
Ethernet Interface: RJ45 jack, 8 pole
Serial interfaces
1, 2 and A: RJ45 jack, 8 pole

Environmental Conditions
Temperature: -25 ... 70 °C
Relative humidity: 5 ... 95 % (non condensing)

Ordering Information
560CMG10 R0001 1KGT 017 600 R0001

4 Doc.-No.: 1KGT 150 645 V001 1


ABB AG

RTU560 Data Sheet Communication Unit 560CMG10

ABB
ABB AG
Power Technologies Division
Power Technology Systems
Kallstadter Str.1, D 68309 Mannheim
Telephone: +49 (0) 621 381-7133
Fax: +49 (0) 621 381-7622

www.abb.com

Doc.-No.: 1KGT 150 645 V001 1 5