Li Cui1, Liu Zhenxing1, Zhang Botao 2
1. Engineering Research Center of Metallurgical Automation and Measurement Technology of Ministry of
Education, Wuhan University of Science and Technology, Wuhan,430081,China
E-mail: 15107118237@163.com
2. Institute of Science and Technology, Wuhan University of Science and Technology, Wuhan,430081,China
E-mail: 215850053@qq.com
Abstract: In the control of inverter power system, with reference to the dq transform in three-phase inverter control
system, a control method of single-phase power inverter system based on lead signal and dq transform is proposed. In
this method, the Įȕ frame is constructed by the physical “Real Circuit” and the second “Imaginary Orthogonal Circuit”,
which is constituted by the 90 degree lead signal, thus the control scheme based on dq transform is realized. Simulation
model based on dq transform is constructed in the simulink of MATLAB, the effectiveness and viability of the method is
verified by the simulation and experiment results.
Key Words: lead signal; three-phase inverter; dq transform; single-phase power inverter; Imaginary Orthogonal Circuit
978-1-4799-7016-2/15/$31.00 2015
c IEEE 3481
steady state error, which can improve the dynamic property ªXd º ªcosZt sin Zt º ª XD º
of the system. The dq transform needs two orthogonal « » « »« » (3)
quantities, but the single-phase only has one phase quantity.
«¬ X q »¼ ¬« sin Zt cosZt ¼» ¬« X E ¼»
It is necessary to create another quantity in quadrature with
the real one to perform the dq transform in a single-phase ª XD º ª cosZt sin Zt º ª X d º
system. « » « »« » (4)
¬« X E ¼» «¬ sin Zt cosZt »¼ «¬ X q »¼
In order to apply the dq transform to the single-phase
inverter power system, the concept about the orthogonal Through the equation (3) transform, the component in the
virtual is presented in[4]. The orthogonal virtual quantity dq frame can be obtained as:
has the same frequency and amplitude as the output ªXd º ª Aº
voltage and current signal, the only difference is that the « » « » (5)
phase of the two quantities differs 90 degree. Though the ¬« X q ¼» ¬0¼
virtual orthogonal circuit is not exist actually, it can be As it is shown in equation (5), the ac signal becomes dc
constructed from the real circuit. signal after the coordinate transform, then send the error
The method of virtual orthogonal quantity constructed between dq dc quantity and the reference quantity to the PI
from the real signal based on the lead signal is proposed in controller. Thus , the PI controller can track the output
this paper, the two quantities constitute the Įȕ static frame. signal with no steady state error so that it is can control the
Where Į quantity is from the real circuit , and the ȕ quantity system accurately, the double closed loop control block
is obtained from the access of the data. The switch diagram based on lead signal transform is shown in Figure
frequency is selected as fs=4nf , where f is the fundamental 4.
frequency of the output signal and n is an integer, BETA
data is obtained from lead queue consisting of n memory
calls to store a quarter cycle real circuit variables. How to
obtain the BETA data is shown in Figure 2.
Fig 4. Double closed loop control block diagram
50
u/v
-50
-100
0.1 0.105 0.11 0.115 0.12 0.125
t/s
Fig3. DQ frame rotating Fig 5. Plot of output voltage under stable operation
As it is shown in Figure 3, the real circuit variable XĮ is As it shown in Figure 5, the output voltage wave is 400Hz
assumed as: cosine wave under the stable operation, which is in step
with the acquired output wave.
XD A cos Zt (1)
1
Where A is the per-unit amplitude of the sine wave, f is the
0.8
fundamental frequency of the sine wave. Xȕ is advanced XĮ
0.6
Ud/V
Uq/V
error, but it also has good property of the output.
0.4
0.2
5 EXPERIMENT VALIDATION
0
-0.2
0.1 0.11 0.12 0.13 0.14
t/s
0.15 0.16 0.17 0.18 In order to further prove the validity of the proposed
method, Using TMS320F28335 DSP as main control chip,
Fig 7. Plot of Uq under stable operation
a single phase full bridge inverter prototype is made. The
As shown in Figure 6 and Figure 7, the per-unit voltage of
input voltage Vdc=110V, which is obtained from the ac
Ud after dq transform is little changed at 1V, and the Uq is
voltage rectified. The filter inductance L=0.18mH, the filter
little changed at 0V, which is consistent with the equation
capacitance C=20ȝF. The experiments under the normal
(5) described.
condition and the load plus condition are conducted, the
100
output voltage waveform are obtained as shown in Figure
50 12 and Figure 13.
u/v
-50
-100
0.13 0.14 0.15 0.16
t/s
Fig 8. Plot of voltage after plus the load
1
0.8
0.6
Ud/V
0.4
0.2
0 Fig.12 Plot of output voltage under stable operation
-0.2
0.12 0.13 0.14 0.15 0.16 0.17 0.18
t/s
Fig 9. Plot of Ud after plus the load
1
0.8
0.6
Uq/V
0.4
0.2
0
-0.2
0.12 0.13 0.14
t/s 0.15 0.16 0.17 0.18
Fig 10. Plot of Uq after plus the load
As it shown in Figure 8 to Figure 10, the output voltage and
the dq components existed short time undulate, but they
restore quickly. This results verify the reliability of the
proposed control scheme. Figure 11 shows the THD of the
output voltage wave after plus the load on the system.
Fig.13 Plot of voltage after plus the load