You are on page 1of 19

An American National Standard

Designation: F 1704 – 99

Standard Test Methods for


Performance of Commercial Kitchen Ventilation Systems1
This standard is issued under the fixed designation F 1704; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.

1. Scope F 1521 Test Method for the Performance of Range Tops2


1.1 These test methods cover the performance evaluation of F 1605 Test Method for Performance of Double-Sided
exhaust hoods with commercial cooking appliances and asso- Griddles2
ciated replacement air configurations. The scope of these test F 1639 Test Method for Performance of Combination Ov-
methods include: ens2
1.1.1 Characterization of capture and containment perfor- F 1695 Test Method for Performance of Underfired Broil-
mance of hood, appliance(s), and replacement air system ers2
during cooking and non-cooking conditions; F 1785 Test Method for Performance of Steam Kettles2
1.1.2 Determination of appliance heat gain to space derived F 1787 Test Method for Performance of Rotisserie2
from the measurement and calculation of appliance energy F 1817 Test Method for the Performance of Conveyor
consumption, energy exhausted, and energy to food, based on Ovens2
a system energy balance; 2.2 NFPA Standard:3
1.1.3 Parametric evaluation of operational or design varia- NFPA 96 Standard for Ventilation Control and Fire Protec-
tions in appliances, hoods, or supply air. tion of Commercial Cooking Operations
1.2 These test methods are contained in the sections indi- 2.3 ASHRAE Standards:4
cated as follows: “A Field Test Method for Determining Exhaust Rates in
Sections
Grease Hoods for Commercial Kitchens,” ASHRAE
Test Method to Determine Threshold of Capture and Contain- 8 Transactions, Vol 100, Part 2, 1994
ment ASHRAE Guideline 2-1986 (RA90) Engineering Analysis
Test Method to Determine Heat Gain to Space 16
of Experimental Data
1.3 The values stated in inch-pound units are to be regarded 2.4 ANSI Standards:5
as the standard. The values given in parentheses are for ANSI/ASHRAE 51 and ANSI/AMCA 210 Laboratory
information only. Method of Testing Fans for Rating
1.4 This standard does not purport to address all of the 2.5 ICC Standards:6
safety concerns, if any, associated with its use. It is the International Mechanical Code
responsibility of the user of this standard to establish appro-
NOTE 1—The replacement air and exhaust system terms and their
priate safety and health practices and determine the applica- definitions are consistent with terminology used by the American Society
bility of regulatory limitations prior to use. of Heating, Refrigeration, and Air Conditioning Engineers, see Ref (1).7
Where there are references to cooking appliances, an attempt has been
2. Referenced Documents made to be consistent with terminology used in the test methods for
2.1 ASTM Standards: commercial cooking appliances. For each energy rate defined as follows,
F 1275 Test Method for the Performance of Griddles2 there is a corresponding energy consumption that is equal to the average
energy rate multiplied by elapsed time. Electric energy and rates are
F 1361 Test Method for the Performance of Open Deep Fat
expressed in W, kW, and kWh. Gas Energy consumption quantities and
Fryers2
F 1484 Test Method for the Performance of Steam Cookers2
F 1496 Test Method for the Performance of Convection 3
Available from National Fire Protection Association, 1 Batterymarch Park,
Ovens2 Quincy, MA 02269–9101.
4
Available from American Society of Heating, Refrigerating, and Air Condi-
tioning Engineers, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329.
1 5
These test methods are under the jurisdiction of ASTM Committee F-26 on Available from American National Standards Institute, 11 W. 42nd St., 13th
Food Service Equipment and are the direct responsibility of Subcommittee F26.06 Floor, New York, NY 10036.
6
on Productivity and Energy Protocol. Available from International Code Council, 5203 Leesburg Pike, Suite 708,
Current edition approved Oct. 10, 1999. Published January 2000. Originally Falls Church, VA 22041.
7
published as F 1704 – 96. Last previous edition F 1704 – 96. The boldface numbers in parentheses refer to the list of references at the end of
2
Annual Book of ASTM Standards, Vol 15.07. these test methods.

Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.

1
F 1704
rates are expressed in Btu, kBtu, and kBtu/h. Energy rates for natural 3.1.12 latent heat gain, n—the energy added to the test
gas-fueled appliances are based on the higher heating value of natural gas. system by the vaporization of liquids that remain in the vapor
phase prior to being exhausted, for example, by vapor emitted
3. Terminology by products of combustion and cooking processes.
3.1 Definitions of Terms Specific to This Standard: 3.1.13 makeup air handling hardware:
3.1.1 energy rate, n—the average rate at which an appliance 3.1.13.1 diffuser, n—an outlet discharging supply air in
consumes energy during a specified condition (for example, various directions and planes.
idle or cooking). 3.1.13.2 grille, n—a covering for any opening through
3.1.2 appliance/hood energy balance, n—mathematical ex- which air passes.
pression of appliance, exhaust system, and food energy rela- 3.1.13.3 register, n—a grille equipped with a damper.
tionship. 3.1.13.4 throw, n—the horizontal or vertical axial distance
[actual appliance energy consumption]
= [heat gain to space from appliance(s)] + [energy exhausted] +
an air stream travels after leaving an air outlet before maximum
[energy-to-food, if any] stream velocity is reduced to a specified terminal velocity, for
example, 100, 150, or 200 ft/min (0.51, 0.76, or 1.02 m/s).
3.1.3 cold start, n—the condition in which appliances are
3.1.14 measured energy input rate, n—the maximum or
energized with all components being at nominal room tempera-
peak rate at which an appliance consumes energy measured
ture.
during appliance preheat, that is, measured during the period of
3.1.4 cooking energy consumption rate, n—the average rate
operation when all gas burners or electric heating elements are
of energy consumed by the appliance(s) during heavy-load
set to the highest setting.
cooking specified in appliance test methods in 2.1.
3.1.4.1 Discussion—In this test method, this rate is mea- 3.1.15 radiant heat gain, n—the fraction of the space
sured for heavy-load cooking in accordance with the applicable energy gain provided by radiation.
test method. 3.1.15.1 Discussion—Radiant heat gain is not immediately
3.1.5 exhaust energy rate, n—the average rate at which converted into cooling load. Radiant energy must first be
energy is removed from the test system. absorbed by surfaces that enclose the space and objects in the
3.1.6 exhaust flow rate, n—the volumetric flow of air (plus space. As soon as these surfaces and objects become warmer
other gases and particulates) through the exhaust hood, mea- than the space air, some of their heat is transferred to the air in
sured in standard cubic feet per minute, scfm (standard litre per the space by convection. The composite heat storage capacity
second, sL/s). This also shall be expressed as scfm per linear of these surfaces and objects determines the rate at which their
foot (sL/s per linear metre) of active exhaust hood length. respective surface temperatures increase for a given radiant
3.1.7 energy-to-food rate, n—the average rate at which input and thus governs the relationship between the radiant
energy is transferred from the appliance to the food being portion of heat gain and its corresponding part of the cooling
cooked, using the cooking conditions specified in the appli- load. The thermal storage effect is critically important in
cable test methods. differentiating between instantaneous heat gain for a given
3.1.8 fan and control energy rate, n—the average rate of space and its cooling load for that moment.
energy consumed by fans, controls, or other accessories asso- 3.1.16 rated energy input rate, n—the maximum or peak
ciated with cooking appliance(s). This energy rate is measured rate at which an appliance consumes energy as rated by the
during preheat, idle, and cooking tests. manufacturer and specified on the appliance nameplate.
3.1.9 heat gain energy rate from appliance(s), n—the aver- 3.1.17 replacement air, n—air deliberately supplied into the
age rate at which energy is transferred from appliance(s) to the space (test room), and to the exhaust hood to compensate for
test space around the appliance(s), exclusive of the energy the air, vapor, and contaminants being expelled (typically
exhausted from the hood and the energy consumed by the food referred to as makeup air).
if any. 3.1.18 supply flow rate, n—the volumetric flow of air
3.1.9.1 Discussion—This gain includes conductive, convec- supplied to the exhaust hood in an airtight room, measured in
tive, and radiant components. In conditions of complete standard cubic feet per minute, scfm (standard litre per second,
capture, the predominant mechanism of heat gain consists of sL/s). This also shall be expressed as scfm per linear foot (sL/s
radiation from the appliance(s), and radiation from hood. In the per linear metre) of active exhaust hood length.
condition of hood spillage, heat is gained additionally by 3.1.19 threshold of capture and containment, n—the condi-
convection. tions of hood operation in which minimum flow rates are just
3.1.10 hood capture and containment, n—the ability of the sufficient to capture and contain the products generated by the
hood to capture and contain grease-laden cooking vapors, appliance(s). In this context, two minimum capture and con-
convective heat, and other products of cooking processes. tainment points are determined, one for appliance idle condi-
Hood capture refers to the products getting into the hood tion, and the other for heavy-load cooking condition.
reservoir from the area under the hood while containment 3.1.20 uncertainty, n—a measure of the precision errors in
refers to the products staying in the hood reservoir. specified instrumentation or the measure of the repeatability of
3.1.11 idle energy consumption rate, n—the average rate at a reported result.
which an appliance consumes energy while it is idling, holding, 3.1.21 ventilation, n—that portion of supply air that is
or ready-to-cook, at a temperature specified in the applicable outdoor air plus any recirculated air that has been treated for
test method from 2.1. the purpose of maintaining acceptable indoor air quality.

2
F 1704
4. Significance and Use 5. Apparatus
4.1 Threshold of Capture and Containment—This test 5.1 Specialized apparatus requirements are listed in the
method describes flow visualization techniques that are used to Apparatus Section in each method.
determine the threshold of capture and containment (c&c) for 5.2 The general configuration and apparatus necessary to
idle and specified heavy cooking conditions. The threshold of perform this test method is shown schematically in Fig. 1 and
c&c can be used to estimate minimum flow rates for hood/ described in detail in Ref (4). Example test facilities are
appliance systems. described in Refs (5,6,7). The exhaust hood under test is
4.2 Heat Gain to Space—This test method determines the connected to an exhaust duct and fan and mounted in an
heat gain to the space from a hood/appliance system. airtight room. The exhaust fan is controlled by a variable speed
drive to provide operation over a wide range of flow rates. A
NOTE 2—To maintain a constant temperature in the conditioned space, complementary makeup air fan is controlled to balance the
this heat gain must be matched by space cooling. The space sensible exhaust rate, thereby maintaining a negligible static pressure
cooling load, in tons, then equals the heat gain in Btu/h divided by the difference between the inside and outside of the test room. The
conversion factor of 12 000 Btu/h (3.412 W) per ton of cooling. Appliance
test facility includes the following:
heat gain data can be used for sizing air conditioning systems. Details of
load calculation procedures can be found in ASHRAE, see Ref (2) and Ref 5.2.1 Airtight Room, with sealable access door(s), to contain
(3). The calculation of associated cooling loads from heat gains to the test the exhaust hood to be tested, with specified cooking appli-
space at various flow rates can be used along with other information by ance(s) to be placed under the hood. The minimum volume of
heating, ventilation, air conditioning (HVAC), and exhaust system design- the room shall be 6000 ft3. The room air leakage shall not
ers to achieve energy-conservative, integrated kitchen ventilation system exceed 20 scfm (9.4 sL/s) at 0.2 in. w.c. (49.8 Pa).
designs. 5.2.2 Exhaust and Replacement Air Fans, with variable-
4.3 Parametric Studies—This test method also can be used speed drives, to allow for operation over a wide range of
to conduct parametric studies of alternative configurations of exhaust air flow rates.
hoods, appliances, and replacement air systems. In general, 5.2.3 Control System and Sensors, to provide for automatic
these studies are conducted by holding constant all configura- or manual adjustment of replacement air flow rate, relative to
tion and operational variables except the variable of interest. exhaust flow rate, to yield a differential static pressure between
This test method, therefore, can be used to evaluate the inside and outside of the airtight room not to exceed 0.05 in.
following: w.c. (12.5 Pa).
4.3.1 The overall system performance with various appli- 5.2.4 Air Flow Measurement System Laminar Flow Ele-
ances, while holding the hood and replacement air system ment, AMCA 210 or equivalent nozzle chamber, mounted in
characteristics constant. the replacement or exhaust airstream, to measure air flow rate.
4.3.2 Entire hoods or characteristics of a single hood, such NOTE 3—Because of potential problems with measurement in the hot,
as end panels, can be varied with appliances and replacement possibly grease-laden exhaust air stream, exhaust air flow rate can be
air constant. determined by measuring the replacement air flow rate on the supply side.
This requires the design of an airtight test facility that ensures the supply
4.3.3 Replacement air characteristics, such as makeup air rate equals the exhaust rate since air leakage outside the system boundary,
location, direction, and volume, can be varied with constant that is, all components between supply and exhaust blowers making up the
appliance and hood variables. system, is negligible.

FIG. 1 Test Space Cross Section

3
F 1704
NOTE 4—Laminar flow elements have been used as an equivalent 10.1.2 Seeding Methods, such as theater fog, smoke (for
alternative to the flow nozzles in AMCA 210 (see 2.4). example, puffers, wands, candles, and so forth), neutrally
5.2.5 Data Acquisition System, to provide for automatic buoyant bubbles, or other equivalent means.
logging of test parameters. NOTE 5—The seeding process shall only introduce small amounts of
tracer material to avoid disturbances to the air flow. A seeding process
6. Reagents and Materials introduces a tracer which artificially seeds the thermal plume that is rising
6.1 Water and Test Food Products—Use water and test food between the cooking surface and the perimeter of the hood for visualiza-
tion, and thereby making it more visible. This flow path will be generated
products to determine energy-to-food as specified in the continuously throughout the determination of the threshold capture and
standards listed in Section 2. containment flow rate by suitable equipment and introduced at a trace rate
only and not at an appreciable volume.
7. Sampling 10.1.3 Illumination, such as with high-intensity, focused
7.1 Hood and Appliance(s)—Select representative produc- lighting.
tion models for performance testing.
NOTE 6—A 300-W halogen lamp with a lens and a dark backdrop in
place aids in visualizing seeded effluent.
TEST METHOD TO DETERMINE THE THRESHOLD
OF CAPTURE AND CONTAINMENT 11. Preparation of Apparatus
11.1 Install the test hood in the airtight room in accordance
8. Scope with the applicable ASTM test method, see 2.1, and as close to
8.1 This test method characterizes the capture and contain- the manufacturer’s instructions, or as determined by particular
ment performance of commercial kitchen ventilation systems. experimental conditions.
11.2 Makeup air shall be supplied to diffusers as determined
9. Summary of Test Method by the test conditions. The specific arrangement shall be noted
9.1 This test method uses flow visualization to determine in the report.
the threshold of c&c of a hood/appliance combination under NOTE 7—In general, makeup air provided to the test space shall be
idle and cooking conditions. admitted from diffusers located as far away from the hood as possible. The
principal direction of makeup air flow from these diffusers shall be away
10. Apparatus from the exhaust hood in order to minimize the effects the air flow might
have on the capture and containment process. Additionally, it is important
10.1 Flow Enhancement Visualization Systems: to adjust registers to provide a horizontally symmetric throw of supply air
10.1.1 Optical Systems, such as schlieren visualization, see from diffusers. The general arrangement of diffusers and supply air is
Fig. 2. shown in Fig. 3. Document supply air configuration and damper positions,

FIG. 2 Example of Schlieren Flow Visualization

4
F 1704

FIG. 3 Supply Air Configuration

following the manufacturer’s recommendations. runs may be necessary to obtain the required precision of the
11.3 Connect the appliance(s) to energy sources and test the reported test results (Annex A1).
instruments in accordance with the applicable test methods. 13.2 Set the initial flow rate high enough to be certain to
Included is the connection to calibrated energy test meters and capture and contain the thermal plume and contaminants
for gas equipment and the connection to a pressure regulator produced from the cooking appliance(s) under either idle or
downstream of the test meter. Electric and gas energy sources cooking conditions. If uncertain where this flow rate is, set the
are adjusted to within 2.5 % of voltages and pressures, respec- exhaust flow rate initially at the code specified rate (see 2.5)
tively, as specified by the manufacturer’s instructions or in and set the makeup at approximately the same flow rate. Keep
accordance with applicable test methods. room differential pressure within 0.05 in. w.c. by opening the
11.4 Once the equipment has been installed, draw a front laboratory door or by using automatic pressure equilibration.
and side view of the test setup. Turn off all test space recirculating systems.
13.3 Establish the idle or cooking threshold capture and
12. Calibration containment flow rate, whereby the appliance is operating to
12.1 Calibrate the instrumentation and data acquisition sys- maintain a ready to cook condition (for the idle test) or a
tem in accordance with device requirements to ensure accuracy full-load cooking condition (for the cook test) using a flow
of measurements. enhancement visualization system. While idling, the appliances
12.2 Calibrate the flow measurement systems in accordance shall cycle for at least 2 periods; while cooking, the appliance
with the manufacturer’s specifications and installed in accor- must cycle a minimum of one full-load cook cycle. The hood
dance with AMCA 210. Other flow measurement systems must must show capture and containment during the full cycle
meet or exceed AMCA 210 accuracy requirements. period over the full hood perimeter during both idle and
12.3 Calibrate humidity measuring instruments in accor- cooking conditions when using a flow enhancement visualiza-
dance with the manufacturer’s specifications annually against tion system.
NIST-traceable reference meters. Relative humidity accuracy 13.4 During the test, reduce the exhaust flow rate until the
within 60.5 % at 40 % RH and 61.25 % at 95 % RH. hood begins to spill. Any observed leak moving beyond 3 in.
12.4 Calibrate all temperature sensors in the temperature (7.6 cm) from the hood face will be construed to have escaped
Measurements Systems upon receipt to within +2°F against a from the hood, even if it may appear to be drawn back into the
NIST-traceable temperature reference over the range of ex- hood.
pected measurements. 13.5 Gradually increase the exhaust flow rate in fine incre-
ments until full capture and containment is achieved.
13. Procedure
13.6 Note the exhaust fan RPM (Nexh) and supply fan RPM
NOTE 8—The following procedures are the instructions for implement- (Nsupply).
ing the test method for determining the threshold capture and containment
flow rate for appliance(s) during idle and cooking conditions under island, 13.7 Perform Runs 2 and 3 by repeating 13.2-13.6 to ensure
wall-mounted canopy, and backshelf hoods. The procedure will establish proper capture and containment of the entire thermal plume at
two threshold capture and containment flow rates, one for appliance idling this flow rate.
and the other for heavy-load cooking, cfmidle and cfmcook, respectively. 13.8 Allow hood/appliance system to stabilize 5 min at the
13.1 Conduct the capture and containment test for idle and maximum exhaust rpm required for capture and containment,
cooking conditions a minimum of three times. Additional test noted in 13.6. After the stabilization period, take a 1-min

5
F 1704
average of the actual flow. Note whether it is a measurement of 14.4.2.8 Eapp, Btu/h—Average rate of energy consumed by
the air exhausted or the makeup air supplied to an airtight burners of gas appliances, or heating elements of electric
room. appliances, to maintain set operating temperature.
NOTE 9—The makeup air supplied is representative of the flow require-
14.4.2.9 Einput, Btu/h—Average rate of total energy (that is,
ments necessary for roof top units supplying a restaurant during typical Eapp + Ectrl) consumed by the appliance(s).
appliance idling at the capture and containment rate. 14.4.2.10 Epeak, Btu/h—Average rate of actual appliance(s)
energy input, measured during the first 10 min of the preheat
13.9 Calculate the corresponding air flow rate at standard
period.
conditions, in accordance with AMCA 210.
14.4.2.11 DPneut, in. H2O—Static pressure differential be-
tween inside and outside the test space, measured at the neutral
14. Calculation and Report
zone of the test space.
14.1 Capture and Containment Flow Rate Percent Uncer- 14.4.2.12 Pgas, in. Hg—Gas line gage pressure.
tainty: 14.4.2.13 Bp, in. Hg—Ambient barometric pressure.
14.1.1 Calculate mean of capture and containment flow 14.4.2.14 Tis, °F—Average dry bulb temperature of supply
rates in accordance with Annex A1. air into the test space.
14.1.2 Calculate standard sample deviation of capture and 14.4.2.15 Texh, °F—Average dry bulb temperature of ex-
containment flow rates in accordance with Annex A1. haust air.
14.1.3 Calculate percent uncertainty of capture and contain- 14.4.2.16 Ttree, °F—Average dry bulb temperature of
ment flow rates expressed as a percentage. makeup air supplied from the test space
14.2 Test Hood and Appliance(s)—Summarize the physical 14.4.2.17 Tspace, °F—Average dry bulb temperature of test
and operating characteristics of the exhaust hood and installed space.
appliances, reporting all manufacturers’ specifications and 14.4.2.18 Tgas, °F—Average dry bulb temperature of the gas
deviations therefrom. Include in the summary hood and appli- consumed by the appliance(s).
ance(s) nameplates specifications; hood overhangs; and hood 14.4.2.19 Tw,tree, °F—Average wet bulb temperature of test
and appliance(s) height(s) and size. Describe the specific space air, measured at the aspirated thermocouple tree(s) plane.
appliance operating condition (for example, type and amount 14.4.2.20 Ttest, minutes—Elapsed time of the test run.
of product cooked, number of burners or elements on, and 14.4.3 The following parameters are calculated at the end of
actual control settings). each test run:
14.3 Apparatus—Describe the physical characteristics of 14.4.3.1 Cp, Btu/lb°F—Specific heat of supply [makeup]
the airtight room, exhaust and makeup air systems, and air.
installed instrumentation. 14.4.3.2 Pcf, dimensionless—Pressure correction factor.
14.4 Data Acquisition:
14.4.3.3 Tcf, dimensionless—Temperature correction factor.
14.4.1 The following parameters are determined or known
14.4.3.4 scfmtree, scfm—Flow rate of makeup air supplied
prior to each test run:
from the test space at standard density air.
14.4.1.1 HV, Btu/ft3—Higher (gross) saturated heating
14.4.3.5 Msup, lb/h—Total mass flow rate of air supplied by
value of natural gas.
the system.
14.4.1.2 Cpa, specific heat of dry air, 0.24 Btu/[lba·°F].
14.4.3.6 W sup , lb v /lb a —Equivalent humidity ratio of
14.4.1.3 Cpv, specific heat of water vapor, 0.44 Btu/[lba·°F].
makeup air supplied from the hood and test space.
14.4.1.4 Ra, gas constant for dry air, 53.352 ft·lbf / [lbm·°F].
14.4.3.7 W*s,tree, lbv/lba—Humidity ratio at saturation of
14.4.2 The following parameters are monitored and re-
makeup air supplied from the test space.
corded during each test run or at the end of each test run, or
both: 14.4.3.8 Wtree, lbv/lba—Humidity ratio of makeup air sup-
14.4.2.1 cfmidle, standard cubic feet per minute, scfm- plied from the test space.
Threshold capture and containment exhaust flow rate under 14.4.3.9 RHtree, %—Relative humidity of air supplied from
idle condition. the test space.
14.4.2.2 cfmcook, standard cubic feet per minute, scfm- 14.4.3.10 ntree, (ft3/lba)—Specific volume of makeup air
Threshold capture and containment exhaust flow rate under supplied from the test space.
heavy-load cooking mode. 14.5 Report the threshold capture and containment flow rate
14.4.2.3 Nexh, exhaust fan RPM at threshold of capture and for a particular hood/appliance(s) system based on flow visu-
containment. alization techniques. The standard flow rate will be reported
14.4.2.4 Nsupply, supply fan RPM at threshold of capture and along with its associated uncertainty.
containment. 14.5.1 Note the type of measurement system. Using the flow
14.4.2.5 Vgas, cubic feet, ft3—Volume of gas consumed by rates acquired in 13.9 convert the flow rates to standard
the appliance(s) over the test period. conditions in accordance with AMCA 210. Note whether it is
14.4.2.6 cfmgas, cubic feet per minute, cfm—Average flow a measurement of the air exhausted or the makeup air supplied
rate of combustion gas consumed over the test period. to an airtight room.
14.4.2.7 Ectrl, Btu/h—Average rate of energy consumed by
controls, indicator lamps, fans, or other accessories associated 15. Precision and Bias
with cooking appliance(s). 15.1 Precision:

6
F 1704
15.1.1 Repeatability (Within Laboratory, Same Operator is heat gain to the test space. In the cooking mode, energy to
and Equipment)—For capture and containment flow rate the food also must be subtracted from appliance energy input to
percent uncertainty shall not exceed 20 %. calculate heat gain to space.
15.1.2 Reproducibility (Multiple Laboratories)—The inter- 17.1.3 Figs. 4-6 show sample curves for the theoretical view
laboratory precision of the procedures in this test method for of heat gain due to hood spillage, an overall energy balance,
measuring each reported parameter is being determined. and for heat gain versus exhaust flow rate for the general case.
15.2 Bias—No statement can be made concerning the bias
18. Apparatus
of the procedures in this test method because there are no
accepted reference values for the parameters reported. 18.1 Aspirated Temperature Tree(s), for measurement of
average temperature of makeup air from the test space crossing
TEST METHOD TO DETERMINE HEAT GAIN TO the plane of the tree (s) into the hood, see Fig. 7.
SPACE 18.2 Exhaust Duct Temperature Sensors, a grid for measure-
ment of the exhaust air temperature.
16. Scope 18.3 The standards listed in 2.1 include descriptions of the
16.1 This test method covers the determination of appliance necessary apparatus and procedures for determining cooking
heat gain to space derived from the measurement and calcula- appliance energy quantities.
tion of appliance energy consumption, energy exhausted, and
energy to food, based on a system energy balance. 19. Preparation of Apparatus
19.1 Install the test hood in the airtight room in accordance
17. Summary of Test Method with the applicable ASTM test method and as close to the
17.1 This test method is used to characterize the perfor- manufacturer’s instructions. When these instructions are not
mance of commercial kitchen ventilation systems. Such sys- available, install wall canopy hoods flush against a wall or
tems include one or more exhaust-only hoods, one or more partition. Backshelf hoods shall be installed against a wall or
cooking appliances under the hood(s), and a means of provid- partition. For wall canopy hoods, the lower front edge shall be
ing replacement (makeup) air. Ventilation system performance a minimum of 78 in. (1.98 m) above the finished floor. Connect
includes the evaluation of the rate at which heat is transferred exhaust duct(s) to hood collar(s).
to the space. 19.2 Install specified appliance(s) under the test hood in
17.1.1 The heat gain from appliance(s) hood system is accordance with the applicable test methods, or manufacturer’s
measured through energy balance measurements and calcula- instructions if no test method exists. When such information is
tions determined at specified hood exhaust flow rate(s). When not available for griddles, fryers, and open top burners, allow
heat gain is measured over a range of exhaust flow rates, the a distance between the lowest edge of hood grease filters and
curve of energy gain to the test space versus exhaust rate the cooking surface between 1 ft (31 cm) and 2 ft (61 cm). For
reflects kitchen ventilation system performance, in terms of charbroilers, allow the range from 3.5 to 4 ft (107 to 122 cm).
heat gain associated with the tested appliance(s). For wall canopy hoods, allow the minimum side and front
17.1.2 In the simplest case, under idle mode, energy ex- overhangs to be 6 in. (15.3 cm). For backshelf hoods, allow the
hausted from the test system is measured and subtracted from minimum side overhang to be 0 in. and the maximum front
the energy into the appliance(s) under the hood. The remainder setback to be 12 in. (30.6 cm). If the hood is equipped with side

FIG. 4 Theoretical View of Heat Gain—Convective/Radiant Split

7
F 1704

FIG. 5 Overall Energy Balance—Idle Condition

FIG. 6 Heat Gain Curve—Typical

panels, then the requirement of side overhang is ignored, 19.4 Replacement air may be supplied to diffusers in the test
provided that the cooking surface does not extend beyond the space. The specific arrangement shall be noted.
vertical plane of the hood sides. There shall be no obstructions 19.4.1 Makeup air provided to the test space shall be
or blockage of air flow for a minimum of 6 ft (183 cm) around introduced from diffusers outside the thermal boundary. It is
the hood perimeter. important to adjust registers to provide a horizontally symmet-
ric throw of supply air from diffusers. The general arrangement
NOTE 10—Size the exhaust hood appropriately to match the above
specified appliance(s). of supply air diffusers and energy balance quantities are shown
in Fig. 8.
19.3 Place the temperature trees 4 ft (1.2 m) to 6 ft (1.8 m)
in front of the hood or appliance(s) vertical, whichever is NOTE 11—Document supply air configuration and damper positions.
further into the test space, and maintain within the range from 19.5 Connect the appliance(s) to energy sources and test
75°F (24°C) to 78°F (26°C). At a minimum, place 2 trees in instruments in accordance with the applicable test methods.
front of the hood, with optional trees placed around the Included is the connection to calibrated energy test meters and
hood/appliance system. for gas equipment and the connection to a pressure regulator

8
F 1704

FIG. 7 Aspirated Temperature Tree Schematic and Setup

FIG. 8 Supply Air Diffusers and Energy Balance Quantities

downstream of the test meter. Electric and gas energy sources difference between the exhaust and tree measurements. Experience
are adjusted to within 2.5 % of voltages and pressures, respec- indicates four-wire RTD sensors are the most practical.
tively, as specified by the manufacturer’s instructions or in 20.3 Gas Meter, for measuring the gas consumption of an
accordance with applicable test methods. appliance, shall be a positive displacement type with a resolu-
19.6 Once the equipment has been installed, draw a front tion of at least 0.01 ft3 (0.0003 m3) and a maximum error no
and side view of the test setup. greater than 1 % of the measured value for any demand greater
than 2.2 ft3/h (0.06 m3/h).
20. Calibration 20.4 Watt-Hour Meter, for measuring the electrical energy
20.1 Calibrate the instrumentation and the data acquisition of an appliance, shall have a resolution of at least one watt hour
system in accordance with the device requirements to ensure and a maximum error no greater than 1.5 % of the measured
accuracy of measurements. value for any demand greater than 100 W.
20.2 Temperature Sensors—Calibrate all temperature sen-
sors upon receipt to within 60.1°F (0.5°C) against a NIST- 21. Procedure
traceable temperature reference over the range of expected 21.1 Determination of Appliance Heat Gain to Space—The
measurements. general procedure for each test run includes determination of
NOTE 12—The accuracy of the heat gain result is directly related to the heat gain to the test space from operating hooded appliance(s)

9
F 1704
under specified flow rates or over a range of flow rates. Energy appliance’s energy consumption. This is due to the higher cooling effects
to food is determined using the applicable test methods. of the appliance cooking sections at higher exhaust rates yielding more
Maintain the tree(s) of aspirated temperature sensors within the energy demand by the thermostats to maintain the same appliance set
operating conditions. For non-thermostatically controlled appliances, the
range from 75 to 78°F (24 to 26°C) for all test points. For appliance(s) energy consumption remains the same regardless of exhaust
testing with appliance(s) under idle condition, energy to food is flow rate, but during the preheat period, the consumption rate may drop
set equal to zero. due to thermal expansion of fuel/energy transport components. If adjust-
21.2 Bulk Air Temperature Measurement Calibration: ment is required, it must be done during the first 10 min of the appliance
21.2.1 Turn off the appliance(s) under the hood and main- preheat period.
tain them at room temperature. Turn off standing pilots of gas 21.7 Measurement with Appliance(s) Cooking:
appliances. 21.7.1 Balance supply air and exhaust air volumes to obtain
21.2.2 Balance supply air and exhaust air volumes to obtain ambient pressure |DPneut| # 0.05 in. w.c. in the test space at the
ambient pressure |DPneut| # 0.05 in. w.c. in the test space at predetermined flow rate, cfm1.
exhaust rate cfm1. Apply cooling/heating as necessary to 21.7.2 Allow an idle stabilization period until the appliance
maintain average laboratory temperature as measured with the develops a constant heating cycle (typically 2 h from a cold
temperature trees (Ttree) within the range from 75 to 78°F (24 start condition). Apply cooling/heating as necessary to main-
to 26°C). tain average laboratory temperature as measured with the
21.2.3 Allow the temperatures to stabilize for a minimum of temperature trees Ttree within the range from 75 to 78°F (24 to
15 min. 26°C) during the test.
21.2.4 The temperature difference between the aspirated 21.7.3 Operate the appliance(s) under full-capacity condi-
temperature tree(s) Ttree and the exhaust temperature Texh must tions as specified in the ASTM procedure in 2.1. Stabilize the
be within 60.2°F (0.1°C). system under heavy-load cooking conditions. Stabilization is
21.3 Heat Gain Determination at Specified Flow Rates— done by cooking the number of stabilization loads specified in
Conduct the heat gain test a minimum of three times. Addi- the ASTM test procedure and when during the cooking
tional test runs may be necessary to obtain the required process, Texh is |Texh max (load n)–Texh max (load (n–1))| of successive
precision for the reported test results (Annex A1). loads #1°F.
21.4 Heat Gain Determination for a Range of Flow Rates— 21.7.4 Confirm full recovery of the appliance(s) cooking
Conduct the heat gain test at a minimum of six different flow sections as specified in the ASTM procedure. Begin data
rates at the desired condition (cooking or idle). Additional collection before loading the first load of the actual cooking
points may be necessary to obtain the required precision for the test. Continue sampling until unloading the last load and full
reported test results (ASHRAE Guideline 2-1986). recovery of the appliance(s) cooking sections.
NOTE 13—The most practical points to test at are idle capture and NOTE 15—Place the cooked food either in a sealed and insulated
containment, cooking capture and containment, the U/L listed flow rate, container or removed outside the test system to minimize its energy from
and the IMC code flow rate. being released to the test space.
21.5 Determine the condition for the heat gain test (cooking 21.7.5 Calculate the required parameters from 22.3, and
or idle). If idling, proceed to 21.6; if cooking, proceed to 21.7. calculate results for HGcook.
21.6 Measurements with Appliance(s) Idling:
21.6.1 Balance supply air and exhaust air volumes to obtain 22. Calculation and Report
ambient pressure |DPneut| # 0.05 in. w.c. in the test space at 22.1 Test Hood and Appliance(s)—Summarize the physical
predetermined flow rate, cfm1 and operating characteristics of the exhaust hood and installed
21.6.2 Operate the appliance(s) under idle conditions as appliances, reporting all manufacturer’s specifications and
specified in the ASTM procedure. Allow stabilization until the deviations therefrom. Include in the summary hood and appli-
appliance develops a constant heating cycle (typically 2 h from ance(s) nameplates specifications; hood overhangs; and hood
a cold start condition) Apply cooling/heating as necessary to and appliance(s) height(s) and size. Describe the specific
maintain average laboratory temperature as measured with the appliance operating condition (for example, number of burners
temperature trees Ttree within the range from 75 to 78°F (24 to or elements on, and actual control settings).
26°C) during the test. 22.2 Apparatus—Describe the physical characteristics of
21.6.3 Take a sample for 2 h for thermostatically controlled the airtight room, exhaust and makeup air systems, and
appliances and 1 h for non-thermostatically controlled appli- installed instrumentation.
ances. Include in the sample the variables outlined in 22.3. 22.3 Data Acquisition:
21.6.4 Adjust the flow rate down to the next predetermined 22.3.1 The following parameters are determined or known
flow rate. Allow a stabilization period until the appliance prior to each test run:
develops a constant heating cycle (typically 30 min) at each 22.3.1.1 a, an operator used to offset latent losses from
test point. Repeat 21.6.1 and 21.6.4 for predetermined flow combustion, defined as equal to 0.096 for hooded gas appli-
rates ances, and zero for electric appliances.
21.6.5 Calculate the required parameters, and report results 22.3.1.2 HV, Btu/ft3—Higher (gross) saturated heating
for HGidle value of natural gas.
NOTE 14—For thermostatically controlled appliances, an incremental 22.3.1.3 cfm1,2,n, predetermined test flow rates.
increase in exhaust flow rate results in an incremental increase in the 22.3.1.4 Cpa, specific heat of dry air, 0.24 Btu/[lba·°F].

10
F 1704
22.3.1.5 Cpv, specific heat of water vapor, 0.44 Btu/[lba·°F] 22.3.3.9 scfmtree, scfm—Flow rate of makeup air supplied
22.3.1.6 Ra, gas constant for dry air, 53.352 ft·lbf/[lbm·°F]. from the test space at standard density air.
22.3.2 The following parameters are monitored and re- 22.3.3.10 Msup, lb/h—Total mass flow rate of air supplied
corded during each test run or at the end of each test run, or by the system.
both: 22.3.3.11 Wsup, lbv/lba—Equivalent humidity ratio of
22.3.2.1 Vgas, cubic feet, ft3—Volume of gas consumed by makeup air supplied from the hood and test space.
the appliance(s) over the test period.
22.3.3.12 W*s,tree, lbv/lba—Humidity ratio at saturation of
22.3.2.2 cfmgas, cubic feet per minute, cfm—Average flow
makeup air supplied from the test space.
rate of combustion gas consumed over the test period.
22.3.2.3 Ectrl, Btu/h—Average rate of energy consumed by 22.3.3.13 Wtree, lbv/lba—Humidity ratio of makeup air sup-
controls, indicator lamps, fans, or other accessories associated plied from the test space.
with cooking appliance(s). 22.3.3.14 RHtree, %—Relative humidity of air supplied
22.3.2.4 Eapp, Btu/h—Average rate of energy consumed by from the test space.
burners of gas appliances, or heating elements of electric 22.3.3.15 ntree, (ft3/lba)—Specific volume of makeup air
appliances, to maintain set operating temperature. supplied from the test space.
22.3.2.5 Einput, Btu/h—Average rate of total energy (that is, 22.3.4 The following are optional parameters and could be
Eapp + Ectrl) consumed by the appliance(s). calculated at the end of each test run:
22.3.2.6 Epeak, Btu/h—Average rate of actual appliance(s) 22.3.4.1 htree, Btu/lba—Specific enthalpy of makeup air
energy input, measured during the first 10 min of the preheat supplied from the test space.
period.
22.3.4.2 Htot, Btu/h—Total enthalpy of makeup air supplied
22.3.2.7 DPneut, in. H2O—Static pressure differential be-
from the system.
tween inside and outside the test space, measured at the neutral
zone of the test space. 22.3.4.3 Etree, Btu/h—Energy of makeup air supplied from
22.3.2.8 Pgas, in. Hg—Gas line gage pressure. the test space.
22.3.2.9 Bp, in. Hg—Ambient barometric pressure. 22.3.4.4 Eexh, Btu/h—Energy of exhaust air leaving the test
22.3.2.10 cfmtree, cubic feet per minute, cfm—Actual flow system.
rate of makeup air supplied from the test space. 22.3.4.5 Mexh, lb/min—Total exhaust mass flow rate.
22.3.2.11 Tis, °F—Average dry bulb temperature of supply 22.4 Calculation and Reporting of Test Results—The pre-
air into the test space. ceding quantities are calculated for each tested exhaust rate,
22.3.2.12 Texh, °F—Average dry bulb temperature of ex- then reported for the specific hood/appliance(s) combination or
haust air. exhaust flow rate, or plotted over the range of the tested
22.3.2.13 Ttree, °F—Average dry bulb temperature of exhaust rates. Average data over 2 h for thermostatically
makeup air supplied from the test space, that is crossing the controlled appliances and 1 h for non-thermostatically con-
plane of aspirated temperature tree(s). trolled appliances. Whenever necessary, refer to 22.3 for the
22.3.2.14 Tspace, °F—Average dry bulb temperature of test definition of symbols used throughout this test method. The
space. complete description of relevant equations is provided in
22.3.2.15 Tgas, °F—Average dry bulb temperature of the gas Appendix X1.
consumed by the appliance(s). 22.4.1 Energy rates can be reported for a particular hood/
22.3.2.16 Tw,tree, °F—Average wet bulb temperature of test appliance(s) system at a specific exhaust flow rate with
space air, measured at the aspirated temperature tree(s) plane. associated uncertainty.
22.3.2.17 Ttest, min—Elapsed time of the test run. 22.4.2 The data can be used to generate energy rate curves
22.3.3 The following parameters are calculated at the end of over a range of flow rates. It is useful to make two graphs for
each test run: each test run. The first graph is a plot of actual total appli-
22.3.3.1 Cp, Btu/lb·°F—Specific heat of supply [makeup] ance(s) energy consumption, energy exhausted, energy to food
air. (if any), and heat gain versus flow rate. It is the global picture
22.3.3.2 Hg1,2,n, Btu/h—Average rate of heat gained by the of energy consumed by the appliance(s) and all uses/
test space at predetermined flow rates. dispositions of this energy. The second graph is just the heat
22.3.3.3 Eexh, Btu/h—Average rate of heat removed from gain curve with an expanded scale versus flow rate. The shape
the test space out of the hood energy exhaust rate. of this curve is a description of the overall performance of the
22.3.3.4 Efood, Btu/h—Average rate of energy gained by the hood, appliance(s), and supply air combination. Theoretically,
food product over the period Ttest. there will be an inflection point corresponding to the flow rate
22.3.3.5 Efood,lat, Btu—Latent energy gained by the food for minimum capture and containment. This inflection point
product to vaporize some of its water content. exists because at flow rates above minimum capture and
22.3.3.6 Efood,sens, Btu—Sensible energy gained by the food containment, heat transfer to the space is mainly by radiation,
product to bring it from its initial temperature to its final however, it appears as a smooth curve due to the marginal
temperature. effect of spillage. At flow rates lower than this point, heat
22.3.3.7 Pcf, dimensionless—Pressure correction factor. transfer to the space is increased dramatically by convection, as
22.3.3.8 Tcf, dimensionless—Temperature correction factor. well as radiation. The modes of heat gain is shown in Fig. 9.

11
F 1704

FIG. 9 Theoretical View of Heat Gain—Convective/Radiant Split

22.4.3 For gas appliances, the energy consumption rate Eapp from kWh to Btu/h using the formula given in 22.4.4. For
(gas), corrected to standard atmospheric pressure of 29.921 in. electric appliances, Ectrl is set to zero if it is measured as part
Hg and standard temperature of 60°F is calculated using Eq 1 of Eapp.
as follows: 22.4.6 The specific heat of makeup air, Cp, is determined
Eapp ~Btu/h! 5 60 3 cfmgas 3 HV 3 Tcf 3 Pcf (1) using Eq 3:
where: Cp ~Btu/lba·°F! 5 Cpa 1 WsupCpv (3)
HV = higher heating value of gas,
where:
= total energy content of gas, Btu/ft3, measured at
Cpa = specific heat of dry air, 0.24 Btu/(lba·°F),
standard conditions of 60°F and 29.921 in. Hg, Cpv = specific heat of water vapor, 0.44 Btu/(lba·°F), and
cfmgas = ft3 of gas consumed/min, Wsup = humidity ratio of supply (makeup) air, lbv/lba.
= volume of gas consumed ~ft3!
The humidity ratio Wsup is the equivalent ratio of the mixed
test time ~min!
airstream of makeup air supplied from the hood and test space
Tcf = temperature correction factor, and is dependent on temperature and pressure. For a typical
= absolute standard temperature ~°R! HVAC calculation, a value of Wsup = 0.01 lbv/lba is often used
absolute gas temperature ~°R! and when substituted into the above equation, a value of Cp =
0.244 Btu/(lba·°F) is obtained. The use of this value results in
= 520/[Tgas + 460], a maximum error of 62 % in enthalpy calculation. If desired,
Tgas = gas temperature, °F, Appendix X1 outlines a comprehensive procedure for comput-
Pcf = pressure correction factor to 29.921 in. Hg,
= absolute gas pressure ~in. Hg! ing the actual humidity ratio.
standard gas pressure ~in. Hg! 22.4.7 Energy exhaust rate, Eexh, under idle and cooking
conditions is computed using Eq 4:
= [Bp + Pgas]/[29.921], Eexh 5 msup 3 Cp@Texh – Ttree# 1 aEapp (4)
Bp = ambient barometric pressure, in. Hg, and
Pgas = gas line gage pressure, in. Hg. where:
22.4.4 For electric appliances, the energy consumption rate a = 0 for electric appliances, and 0.096 for hooded
Eapp (elec), measured by a kWh meter or its equivalent and gas appliances,
converted from kWh to Btu/h using Eq 2: msup = mass flow rate of total makeup air, lba/h,
kWh ~measured! 3 3413 ~Btu/kWh! 3 60 ~min/h! = 60 3 0.075 lba/ft3 3 (scfmtree),
Eapp ~Btu/h! 5 test time ~min! scfmtree = ft3/min of makeup air from test space cfmtree
(2) corrected to standard density air,
Texh = average dry bulb temperature of exhaust air, °F,
22.4.5 Controls energy, Ectrl, is measured by meter measure- Ttree = average dry bulb temperature of makeup air
ment of electric energy consumed by controls, fans, or other supplied from the test space, °F, and
accessories of cooking appliances. This energy is converted

12
F 1704

Cp = specific heat of makeup air as determined from corresponds to the range of capture and containment. The
22.4.6, Btu/lba°F. threshold for capture and containment is found through flow
Appendix X1 provides a comprehensive procedure for visualization.
correcting the air flow rate cfmtree to standard density air. 22.4.15.1 Global Energy Balance Curves—Using Table 1,
NOTE 16—Under cooking conditions, the energy used to vaporize water for idle tests, plot the total energy consumed by the appli-
from food Efood,lat is also part of the energy exhausted, but Efood is treated ance(s) Eapp + Ectrl, and HGidle all in units of kBtu/h against
as a separate energy term to ease its representation graphically on the their corresponding flow rate in units of scfm/linear ft. Once all
overall performance chart and because of its significance in calculating test points are plotted, the region bounded between the appli-
other performance variables in ASTM test methods. ance energy curve and the heat gain curve is energy exhausted,
22.4.8 Heat gain from appliance(s) under hood in idle mode, Eexh. For cooking tests, however, graphing is done the same
HGidle is given in Eq 5: way as for idle tests except for one additional added energy
HGidle 5 @Eapp 1 Ectrl#– Eexh (5) quantity. This energy is the difference between appliance total
energy consumption and energy-to-food. This also is plotted
22.4.9 Energy to food, Efood, for cooking tests, some of the
against the flow rate. The resultant region bounded between
appliance(s) energy is used to vaporize water in food, Efood,lat
(Btu), and some additional energy is used to add sensible heat appliance total energy consumption and the stated difference is
to the food, Efood,sens (Btu). These quantities and perhaps other energy-to-food, and the resultant region bounded between the
components are measured and calculated in accordance with stated difference and heat gain curve is energy exhausted. A
Appliance Performance Test Methods, and converted to energy generic global (overall) energy balance chart for idle condition
rate using Eq 6 as follows: is shown in Fig. 10.
Efood,lat 1 Efood,sens
22.4.15.2 Heat Gain Curve—Using Table 1, for idle or
Efood ~Btu/h! 5 test time ~min! 3 60 ~min/h! (6) cooking tests, plot the heat gain HGidle in units of kBtu/h
against their corresponding flow rate in scfm/linear ft. A
22.4.10 Heat gain from appliances under hood in cooking
generic heat gain curve for idle condition is shown in Fig. 11.
mode, HGcook is given by Eq 7:
HGcook 5 @Eapp 1 Ectrl#– Eexh – Efood (7) NOTE 17—A minimum of six data points are required to generate a
curve. The curve must fit the functional: Ehg = A + B 3 e – (C 3 cfm/linft)
22.4.11 Normalize the flow rate to the length of the hood Where, A, B, and C are constants. Actual test results must be shown on the
used during testing, and enter it in Table 1. chart along with a 95 % confidence band. In accordance with ASTM
scfm/linear ft 5 scfm/length of hood~ft! (8) requirements, test results that need to be fitted with a curve must be
validated before they can be published. Validation is done by meeting
22.4.12 As calculations of energy quantities are performed, uncertainty requirements stated in Section 13 for the results of each test
values are entered in Table 1. point. The curves must comply with the requirements of 8.2 of ASHRAE
22.4.13 Repeat the preceding calculations for all tested flow Guideline 2-1986 (RA90). Only those curves that are validated can be
rates. Table 1 will be used for the reporting of test results. published as complying with ASTM requirements.
22.4.14 Report energy rates for a particular hood/
appliance(s) system at a specific exhaust flow rate in accor- 23. Precision and Bias
dance with Table 1, Note 1. 23.1 Precision:
22.4.15 Graphing the Energy Rate Results—As indicated in
23.1.1 Repeatability (Within Laboratory, Same Operator
22.4.2, the energy quantities are plotted against the flow rate.
and Equipment):
Two curves are generated, one that shows the global energy
balance curve, and the other shows the heat gain curve only on 23.1.1.1 For exhaust energy rate Eexh, the percent uncer-
an expanded scale. The shape of the later curve indicates the tainty has been determined to be no greater than 610 %.
overall energy performance of the hood/appliance/replacement 23.1.1.2 For energy-to-food rate results Efood, based on
air system. The magnitude of the energy gain curve can be used ASTM test methods, the percent uncertainty in each result,
to estimate the cooling load. Typically, under stable laboratory based on at least three test runs, has been determined to be no
conditions, there is smooth rise in the heat gain curve. This greater than 615 %.

TABLE 1 Sample Table of Results

NOTE 1—In accordance with ASTM requirements, test results must be validated before they can be published. Validation of results for each test point
is done by meeting uncertainty requirements stated in Section 23 and detailed in Annex A1. To determine the uncertainty at each test point, results must
be based on the average of at least three tests to obtain the required uncertainty. Only those test points that are validated can be published as complying
with ASTM requirements. Results that are not validated in accordance with the preceding procedure must be identified as not meeting ASTM requirements
if published in the same context as other points that do claim to meet the ASTM requirements.
Idle or Cooking Test Qexh, scfm/linear ft Eapp+ Ectrl, kBtu/h Efood, kBtu/h Eexh, kBtu/h HGidle, kBtu/h
cfm1 if applicable
cfm2 if applicable
cfm3 if applicable
cfm4 if applicable
cfmn if applicable

13
F 1704

FIG. 10 Overall Energy Balance—Idle Condition

FIG. 11 Heat Gain Curve with Confidence Limits—Typical

23.1.1.3 For appliance(s) energy consumption rate Eapp, the 23.2 Bias—No statement can be made concerning the bias
percent uncertainty has been determined to be no greater than of the procedures in this test method because there are no
610 %. accepted reference values for the parameters reported.
23.1.1.4 Accordingly, the percent uncertainty in heat gain is
impacted by input uncertainties and shall be reported.
23.1.2 Reproducibility (Multiple Laboratories)—The inter-
laboratory precision of the procedures in this test method for
measuring each reported parameter is being determined.

14
F 1704
ANNEX

(Mandatory Information)

A1. UNCERTAINTY IN REPORTED TEST RESULTS

NOTE A1.1—The procedure described as follows is based on the TABLE A1.1 Uncertainty Factors
method for determining the confidence interval for the average of several Number of Test Runs, n Uncertainty Factor, Cn
test results discussed in ASHRAE Guideline 2-1986 (RA90) (see 2.3). It
3 2.48
only should be applied to test results that have been obtained within the 4 1.59
tolerances specified in this test method. 5 1.24
6 1.05
A1.1 For the heat gain procedure, results are reported for 7 0.92
8 0.84
the heat gain under idle condition HGidle, or cooking condition 9 0.77
HGcook, or both. The heat gain curve must include a minimum 10 0.72
of two test flow rates, namely cfm1 and cfm4 as defined in 22.4,
each reported as an average of at least three test runs. In
addition, the uncertainty in each of the following variables is
calculated: appliance energy consumption rate Eapp, energy A1.4.1.1 Step 1—Using the results of the first three test
exhausted Eexh, and heat gain HGidle or HGcook, or both. If the runs, calculate the average and standard deviation of each
calculated uncertainty in one of the stated variables exceeds its variable.
maximum allowable uncertainty, additional test runs at the
NOTE A1.3—The following formulas may be used to calculate the
same condition are required until the uncertainty in each average and sample standard deviation. It is recommended, however, that
variable falls within its maximum allowable range. a calculator with statistical function be used. If one is used, be sure to use
A1.1.1 The uncertainty for each variable is calculated after the sample standard deviation function. Using the population standard
the test run has been repeated three times. Then, it is checked deviation function will result in an error in the uncertainty.
against the maximum allowable uncertainty specified for the The average of the variable based on three test runs is
variable. If uncertainty in one variable exceeds its maximum calculated as follows:
allowable uncertainty, the test run is repeated and the uncer-
Xa3 5 ~1/3!3 ~X1 1 X2 1 X3! (A1.1)
tainty based on four runs is calculated and verified again. This
process is continued until the uncertainty of each variable falls where:
within its maximum allowable range. Xa3 = average of results of the three test runs, and
NOTE A1.2—Verification tests that are spread over a long time span X1, X2, X3 = results of the variable from Test Runs 1
(several months) help evaluate environmental impacts like seasonal through 3.
climatic changes. A1.4.1.2 The sample standard deviation of the variable
based on the three test runs is given as follows:
A1.2 The uncertainty in a reported result helps to evaluate
S3 ~1/=2! 3 =~A3 2 B3! (A1.2)
its precision. If, for example, the HGidle is 20 kBtu/h, the
uncertainty specified for this variable in this test method must where:
be not larger than 620 % or 64 kBtu/h. This means that the S3 = standard deviation of the variable based on three test
true HGidle is within the interval between 16 and 24 kBtu/h. runs,
This interval is determined at the 95 % confidence level, which A3 = (X1)2 + (X2)2+ (X3)2, and
means that there is only a 1 in 20 chance that the true HGidle B3 = (1/3) 3 (X1 + X2+ X3)2.
could be outside of this interval. A1.4.2 Step 2—Calculate the absolute uncertainty in each
variable. From Table A1.1, look up the uncertainty factor for
A1.3 Calculating the uncertainty not only guarantees the three test runs, then multiply the standard deviation computed
maximum uncertainty in the reported result but also is used to in Step 1 by that factor:
determine how many test runs are needed to satisfy this U 3 5 C3 3 S 3 (A1.3)
requirement. The uncertainty is calculated by multiplying the
5 2.48 3 S3
standard deviation of three or more test runs by a factor from
Table A1.1, which depends on the number of test runs used to where:
compute the average. The percent uncertainty is the ratio of the U3 = absolute uncertainty in the average value of the
uncertainty to the average expressed as a percent. variable based on three test runs, and
C3 = uncertainty factor for three test runs from Table A1.1.
A1.4 Procedure:
A1.4.1 The following procedure is provided for calculating A1.4.3 Step 3—Calculate the percent uncertainty in each
uncertainty. It shall be carried out for the variables stated in variable using the average of the three test runs obtained from
A1.1. The uncertainty in the variables must be determined for Step 1 and the absolute uncertainty from Step 2:
at least two test flow rates. % U3 5 ~U3/Xa3! 3 100 % (A1.4)

15
F 1704

where: A1.4.9 Step 9—If the percent uncertainty in each variable


% U3 = percent uncertainty in the average value of the stated in Section 12 is within the maximum allowable uncer-
variable based on three test runs. tainty specified for the variable, then report the average of each
A1.4.4 Step 4—If the percent uncertainty in each variable variable obtained from Step 1 along with its uncertainty from
stated in Section 13 is within the maximum allowable uncer- Step 2 in the following format:
tainty specified for the variable, then report the average of each Xa4 6 U4 (A1.10)
variable obtained from Step 1 along with its uncertainty from
Step 2 in the following format: If the percent uncertainty in any one of the variables exceeds
its maximum allowable uncertainty, then proceed to Step 10.
Xa3 6 U3 (A1.5)
A1.4.10 Step 10—Run a fifth test for the test flow rate at
If the percent uncertainty in any one of the variables exceeds which one of the variables calculated uncertainty exceeded its
the maximum allowable uncertainty specified for that variable, maximum allowable uncertainty. Then the calculation proce-
then proceed to Step 5. dure is repeated over again for five test runs. The general
A1.4.5 Step 5—Run a fourth test for the test exhaust flow formulas for calculating the average, standard deviation, abso-
rate at which one of the variables calculated uncertainty lute uncertainty, and percent uncertainty are listed as follows.
exceeded its maximum allowable uncertainty. These formulas shall be applied for each variable. The average
A1.4.6 Step 6—Compute the average and the standard of the variable based on “n” test runs is calculated as follows:
deviation of each variable based on the four test runs as
follows:
Xan 5 ~1/n! 3 (iXi for i 5 1 to n (A1.11)
Xa4 5 ~1/4! 3 ~X1 1 X2 1 X3 1 X4! (A1.6)
5 ~1/n!3 ~X1 1 X2 1 X3 1 X4 1 . . . 1 Xn!
where:
Xa4 = average of results of the four test runs, where:
and Xan = average of results of n test
X1, X2, X3, X4 = results of the variable from Test Runs 1 runs, and
through 4. X1, X2, X3, X4, . . . , Xn = results of the variable from
A1.4.6.1 The sample standard deviation of the variable Test Runs 1 through n.
based on four test runs is given as follows: A1.4.10.1 The sample standard deviation of the variable
based on n test runs is given as follows:
S4 ~1/=3! 3 =~A4 2 B4! (A1.7)
Sn ~1/=~n – 1!! 3 =~An – Bn! (A1.12)
where:
S4 = standard deviation of the variable based on four test where:
runs, Sn = standard deviation of the variable based on n test
A4 = (X1)2+ (X2)2+ (X3)2+ (X4)2, and runs,
B4 = (1/4) 3 (X1+ X2+ X3+ X4)2. An = (X1)2+ (X2)2+ (X3)2+ (X4)2+ . . . + (Xn)2, and
A1.4.7 Step 7—Calculate the absolute uncertainty in each Bn = (1/n) 3 (X1+ X2+ X3 + X4+ . . . + Xn)2.
variable. From Table A1.1, look up the uncertainty factor for A1.4.10.2 The uncertainty in n test runs is given as follows:
four test runs, then multiply the standard deviation computed in
Step 1 by that factor: U n 5 Cn 3 S n (A1.13)
U4 5 C4 3 S4 (A1.8)
where:
5 1.59 3 S4
Un = absolute uncertainty in the average value of the
where: variable based on n test runs, and
U4 = absolute uncertainty in the average value of the Cn = uncertainty factor for n test runs from Table A1.1.
variable based on four test runs, and A1.4.10.3 The percent uncertainty in each variable is cal-
C4 = uncertainty factor for four test runs from Table A1.1. culated as follows:
% Un 5 ~Un/Xan! 3 100 % (A1.14)
A1.4.8 Step 8—Calculate the percent uncertainty in each
variable using the average of the four test runs obtained from where:
Step 1 and the absolute uncertainty from Step 2: % Un = percent uncertainty in the average value of the
variable based on n test runs.
% U4 5 ~U4/Xa4! 3 100 % (A1.9)
A1.4.10.4 Upon satisfying the uncertainty requirement for
where: each variable based on n test runs, the average value of each
% U4 = percent uncertainty in the average value of the variable is reported in the following format:
variable based on four test runs. Xan 6 Un (A1.15)

16
F 1704
APPENDIX

(Nonmandatory Information)

X1. ADDITIONAL EQUATIONS

X1.1 Throughout Appendix X1, equations are developed Dh = change of enthalpy required to vaporize or condense
for exhaust-only systems (that is, hoods without integral 1 lb of water, Btu/lbv, and
supply). The schematic relationship of the test system energy Cp = specific heat of makeup air, Btu/lb°F.
quantities is shown in Fig. 8. Terms not defined in Appendix
X1 are defined in 22.3. X1.8 The humidity ratio of makeup air is the humidity ratio
of the mixed airstream of makeup air supplied from the hood
X1.2 To describe the protocol mathematically, consider the and test space. This is given by the following:
energy balance of the test system shown in Fig. 1. Conserva- Wsup 5 Wtree (X1.7)
tion of energy (first law of thermodynamics) states that the total
amount of energy in a closed system remains constant. This can X1.9 Substituting Eq X1.7 into Eq X1.6 to obtain the
be written as follows: following:
( Ein – ( Eout 5 constant (X1.1) HGidle 5 Eapp – msup@Cp ~Texh – Ttree! 1 Dh~Wexh – Wsup!#
(X1.8)
where:
( = summation symbol. X1.10 Generally, cooking appliances utilize electric energy
(other than the energy used for heating elements on electric
X1.3 Referring to Fig. X1.1, neglecting losses, and consid- appliances) to power controls or other accessories associated
ering idle condition, the sum of energy in includes energy from with them. Using Ectrl to represent this energy, Eq X1.8
the appliances Eapp and energy of air supplied from the test becomes the following:
space at the tree Etree. The sum of energy out is simply the HGidle 5 @Eapp 1 Ectrl#– msup@Cp ~Texh – Ttree! (X1.9)
energy exhausted Eexh. Thus, Eq X1.1 becomes:
1 Dh~Wexh – Wsup!#
~Eapp 1 Etree! – Eexh 5 HGidle (X1.2)
where the constant term is now replaced by heat gain, X1.11 For electric appliances, Ectrl is set to zero if it is
HGidle. measured as part of Eapp. Eq X1.9 is the general equation that
governs heat gain by the test space from the appliance(s). In
X1.4 Introducing the specific enthalpy h, and mass flow practice, the energy consumed by gas appliances Eapp is
rate m. Since E = mh, upon substitution, Eq X1.2 becomes: calculated based on the higher (gross) heating value of natural
gas that includes latent energy loss, due to water evaporation
Eapp 1 mtreehtree – mexhhexh 5 HGidle (X1.3) during combustion. These latent losses amount to an average of
where: 9.6 % of the gross energy. Under full-capture mode, these
mtree = makeup air mass flow rate supplied from the test losses are part of energy exhausted. Thus, under idle condition,
space, and msupDh (Wexh− Wsup) is equal to 0.096 Eapp for gas appliances,
mexh = total exhaust mass flow rate. and is equal to zero for electric appliances.

X1.5 Applying the law of conservation of mass, X1.12 Introducing the operator, a, define:
a 5 0 for electric appliance~s!, and (X1.10)
msup 5 mtree (X1.4)

where: 0.096 for hooded gas appliances.


msup = total makeup air mass flow rate supplied by the X1.12.1 Considering the preceding discussion and applying
system. Eq X1.10 to Eq X1.9 to obtain the following:
HGidle 5 @Eapp 1 Ectrl# – msupCp@Texh – Ttree# – aEapp (X1.11)
X1.6 Upon substituting Eq X1.4, Eq X1.3 simplifies to the
5 Einput – Eexh
following:
HGidle 5 Eapp – msup@hexh – htree# (X1.5) where:
Einput = Eapp+ Ectrl, and
X1.7 The expression inside the brackets of Eq X1.5 could Eexh = msup Cp [Texh− Ttree] + aEapp
be broken down into its sensible and latent heat components.
Doing so, Eq X1.5 becomes the following: X1.13 If cooking tests are performed, some of the energy
consumed by the appliance(s) is gained by the food. The
HGidle 5 Eapp – msup@Cp ~Texh– Ttree! (X1.6) primary components of heat gained by the food are sensible
1 Dh~Wexh – Wtree!# gain Efood,sens, and latent gain Efood,lat which is part of the
energy exhausted. These and other components of food energy
where:
are calculated in accordance with the standards listed in

17
F 1704
Section 2, and must be subtracted from the right side of Eq ~1093 2 0.566 Tw,tree! W*s,ih 2 0.240 ~Ttree 2 Tw,tree!
Wtree~lbv/lba! 5 1093 1 0.444Ttree 2 Tw,tree
X1.11. To minimize food energy from being released to the test
space and be counted as part of the heat gain from the (X1.15)
appliance, the cooked food is unloaded from the appliance and The following procedures are used to correct makeup air
immediately placed either in a sealed and insulated container or volumes to standard density air for use in Eq X1.13:
removed outside the test space. Using Efood to represent total
X1.16 Correcting Makeup Air Volumes to Standard Density
energy to food, Eq X1.11 becomes the following:
Air, scfmtree:
HGcook5 @Eapp 1 Ectrl# 2 msupCp@Texh 2 Ttree# (X1.12)
X1.16.1 Compute the specific volume of air supplied from
2 aEapp 2 Efood the test space ntree (ft3/lba) as follows:
5 Einput 2 Eexh 2 Efood ntree 5 ~Ra ~Ttree 1 459.67!/Bp! ~1 1 1.6078 Wtree! (X1.16)
where: where:
Efood = Efood,lat + Efood,sens Ra = gas constant for dry air, 53.352 ft·lbf/(lbm·°F).
where: X1.16.2 Correct air volumes to standard density air as
follows:
X1.14 The humidity ratio of the total makeup air, Wsup is
scfmtree 5 cfmtree ~13.33/ntree! (X1.17)
dependent upon the humidity ratios of air supplied from test
space, Wtree. The humidity ratio of the mixed airstream is where:
calculated using the following equation: cfmtree = actual ft3/min of air supplied from the test space.
Wsup ~lbv/lba! 5 Wtree (X1.13)
X1.17 Using Eq X1.13, compute the equivalent humidity
The following procedures are used to compute humidity ratio Wsup. The following procedures are used to compute the
ratio of makeup air for use in Eq X1.13: specific and total enthalpy of makeup air.
X1.18 Specific Enthalpy of Makeup Air, htree:
X1.15 Computing the Humidity Ratio of Makeup Air From
the Test Space Wtree: X1.18.1 The specific enthalpy of makeup air supplied from
the test space is computed as follows:
X1.15.1 From the steam table, look up the saturation pres-
sure, Psat (in. Hg), at the measured wet-bulb temperature htree 5 0.24Ttree 1 Wtree ~1061 1 0.444Ttree! (X1.18)
Tw,tree, °F. X1.18.2 The total enthalpy of makeup air supplied by the
X1.15.2 Compute the humidity ratio at saturation, W*s,tree system is given as follows:
as follows: Htot 5 mtreehtree (X1.19)
W*s,tree 5 0.62198 ~Psat/~Bp – Psat! (X1.14) where:
X1.15.3 Compute the humidity ratio Wtree as follows: mtree 5 0.0753 60 3 scfmtree (X1.20)

REFERENCES

(1) ASHRAE, Terminology of Heating, Ventilation, Air-Conditioning and (5) Soling, S.P., and Knapp, J., “Laboratory design of energy efficient
Refrigeration, ASHRAE, 1991. exhaust hoods,” ASHRAE Transactions 91, 1985, (1).
(2) Chapter 28, Non-Residential Cooling and Heating Load Calculations, (6) Gordon, E.B., Horton, D.J., and Parvin, F.A., “Development and
1997 Fundamentals Handbook, American Society of Heating, Refrig- Application of a Standard Test Method for the Performance of Exhaust
eration, and Air Conditioning Engineers, Atlanta, GA. Hoods with Commercial Cooking Appliances, ASHRAE Transactions
(3) Cooling and Heating Load Calculation Manual, American Society of
100, 1994, (2).
Heating, Ventilation, and Air-Conditioning Engineers, Inc., Atlanta,
GA, 1992. (7) Smith, V.A., Swierczyna, R.T., and Claar, C.N., “Application and
(4) Gordon, E.B., Horton, D.J., and Parvin, F.A., “Description of a Enhancement of the standard test method for the performance of
Commercial Kitchen Ventilation (CKV) Laboratory Facility,” commercial kitchen ventilation systems,” ASHRAE Transactions 101,
ASHRAE Transactions, 101, 1995, (1). 1995, (2).

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.

18
F 1704

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).

19

You might also like