Document Title : Bill of Quantities for Air Handling Units

Offer Ref No. : ASIPL/KGP/101/17-18


Date : 04.09.2017 ; Rev : 00

ANNEXURE - II PART A (AHU -FF-01 TO AHU -FF-12)


SUPPLY INSTALLATION TOTAL (INR)
Sr.
Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

1 AIR HANDLING UNITS

1.1 GRADE B ‐ RECIRCULATION TYPE

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm)
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with
thermal break profile & internal coving.

Unit ‐ Part Unit with Double Section for below, considering 1 working & 1
standby
(Refer air flow diagram)
Mixing chamber section of minimum 600 mm length for fresh air and
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300
x300 Size)
Pre‐filter section with Pre‐filter (G4)
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame
with vibration isolation.

Bleed air cutout with low leak volume control damper in Aluminium profile
and with H13 grade (0.3µ) filter with plenum and fixing arrangment. Bleed
air filter ‐ H13 (as per exhaust CFM, consider minimum 300 x300 Size)

Unit ‐ Part Unit with Single Section for each below sections (as per flow
diagram)
Chilled water cooling Coil section with chilled water coil ( min 6 row deep)
with aluminum fins & condenste tray made out of SS 304 in 18 gauge
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and
hot water coil should be less than 200 mm.
Fine filter section with washable 3 micron (F7) filter in Aluminium
construction as per airflow diagram. Filter efficiency as per EN 779

HEPA filter section with throw‐away 0.3 micron (H13) filter in Aluminium
construction as per airflow diagram. Filter efficiency as per EN 1822.

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch.
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

SS 304 drain insulated pan, Cable entry for motor and sufficient distance
between all section.
Common Points for both units

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch.
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized
Operation)
All Cable & pipes should be Roxtec flexible sealed type.

Spring Mounted Vibration Isolator to be provided for Mounting AHUs.

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will
be provided in all the sections which are in positive stream of air to avoid
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than
500 fpm.
D.P. Switch to be provided across pre & fine filter & final filter section of
AHU.

AHU‐FF‐06 Nos 1 1256400 1256400 15000 15000 1271400


Fan Capacity (CFM) 8963 0
Supply air quantity (CFM) 7527 0
Coil air Capacity (CFM) 5645 0
Return air Capacity (CFM) 8056 0
Fresh air Capacity (CFM) 907 0
Bleed air Capacity (CFM) 1436 0
Static pressure ( MM OF WG ) 180 0
Cooling capacity ( TR ) 8.71 0
Heating Capacity (KW) 12.98 0
0
AHU‐FF‐07 Nos 1 526500 526500 10000 10000 536500
Fan Capacity (CFM) 2637 0
Supply air quantity (CFM) 2637 0
Coil air Capacity (CFM) 1978 0
Return air Capacity (CFM) 2317 0
Fresh air Capacity (CFM) 320 0
Bleed air Capacity (CFM) ‐ 0
Static pressure ( MM OF WG ) 180 0
Cooling capacity ( TR ) 2.38 0
Heating Capacity(KW) 3.43 0

Page 1 of 11
ANNEXURE - II PART A (AHU -FF-01 TO AHU -FF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

0
AHU‐FF‐08 Nos 1 504900 504900 10000 10000 514900
Fan Capacity (CFM) 1223 0
Supply air quantity (CFM) 1223 0
Coil air Capacity (CFM) 917 0
Return air Capacity (CFM) 1063 0
Fresh air Capacity (CFM) 160 0
Bleed air Capacity (CFM) ‐ 0
Static pressure ( MM OF WG ) 180 0
Cooling capacity ( TR ) 1.46 0
Heating Capacity(KW) 2.19 0
0
AHU‐FF‐09 Nos 1 760500 760500 15000 15000 775500
Fan Capacity (CFM) 5271 0
Supply air quantity (CFM) 5053 0
Coil air Capacity (CFM) 4256 0
Return air Capacity (CFM) 4733 0
Fresh air Capacity (CFM) 538 0
Bleed air Capacity (CFM) 218 0
Static pressure ( MM OF WG ) 180 0
Cooling capacity ( TR ) 10.85 0
Heating Capacity(KW) 7.83 0
0
1.2 GRADE C / D ‐ RECIRCULATION TYPE 0
0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and 0
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0
x300 Size)
Pre‐filter section with Pre‐filter ‐ Combination filter (G4 + F5) 0
Chilled water cooling Coil section with chilled water coil ( min 6 row deep)
with aluminum fins & condenste tray made out of SS 304 in 18 gauge 0
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction 0

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and 0
hot water coil should be less than 200 mm.
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame 0
with vibration isolation.
Fine Filter Section with Fine filter ‐ F9 (50‐75% eff 0.3 micron). 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch. 0
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor

Bleed air cutout with low leak volume control damper in Aluminium profile
and with H13 grade (0.3µ) filter with plenum and fixing arrangment. Bleed 0
air filter ‐ H13 (as per exhaust CFM, consider minimum 300 x300 Size)

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized 0
Operation)
SS 304 drain insulated pan, Cable entry for motor and sufficient distance
0
between all section.
All Cable & pipes should be Roxtec flexible sealed type. 0

Spring Mounted Vibration Isolator to be provided for Mounting AHUs. 0

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will 0
be provided in all the sections which are in positive stream of air to avoid
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than
0
500 fpm.
D.P. Switch to be provided across pre & fine filter section of AHU. 0
0
AHU‐FF‐02 Nos 1 678600 678600 15000 15000 693600
Fan Capacity (CFM) 10508 0
Supply air quantity (CFM) 9291 0
Coil air Capacity (CFM) 6968 0
Return air Capacity (CFM) 9702 0
Fresh air Capacity (CFM) 806 0
Bleed air Capacity (CFM) 1217 0
Static pressure ( MM OF WG ) 150 0
Cooling capacity ( TR ) 13.38 0
Heating Capacity(KW) 19.77 0
0
AHU‐FF‐03 Nos 1 702900 702900 15000 15000 717900
Fan Capacity (CFM) 8916 0
Supply air quantity (CFM) 8488 0
Coil air Capacity (CFM) 7769 0
Return air Capacity (CFM) 8113 0
Fresh air Capacity (CFM) 803 0
Bleed air Capacity (CFM) 428 0
Static pressure ( MM OF WG ) 150 0
Cooling capacity ( TR ) 19.15 0
Heating Capacity(KW) 12.37 0
0
AHU‐FF‐04 Nos 1 324900 324900 10000 10000 334900
Fan Capacity (CFM) 2467 0

Page 2 of 11
ANNEXURE - II PART A (AHU -FF-01 TO AHU -FF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

Supply air quantity (CFM) 2270 0


Coil air Capacity (CFM) 1703 0
Return air Capacity (CFM) 2156 0
Fresh air Capacity (CFM) 311 0
Bleed air Capacity (CFM) 197 0
Static pressure ( MM OF WG ) 150 0
Cooling capacity ( TR ) 3.42 0
Heating Capacity(KW) 4.84 0
0
AHU‐FF‐05 Nos 1 362700 362700 10000 10000 372700
Fan Capacity (CFM) 3291 0
Supply air quantity (CFM) 2999 0
Coil air Capacity (CFM) 2249 0
Return air Capacity (CFM) 2823 0
Fresh air Capacity (CFM) 468 0
Bleed air Capacity (CFM) 292 0
Static pressure ( MM OF WG ) 150 0
Cooling capacity ( TR ) 3.29 0
Heating Capacity(KW) 6.86 0
0
AHU‐FF‐12 Nos 1 268200 268200 10000 10000 278200
Fan Capacity (CFM) 735 0
Supply air quantity (CFM) 670 0
Coil air Capacity (CFM) 503 0
Return air Capacity (CFM) 556 0
Fresh air Capacity (CFM) 179 0
Bleed air Capacity (CFM) 65 0
Static pressure ( MM OF WG ) 150 0
Cooling capacity ( TR ) 1.08 0
Heating Capacity(KW) 1.99 0
0
1.3 CNC ‐ RECIRCULATION TYPE 0
0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and
return air. 0

Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0
x300 Size)
Pre‐filter section with Pre‐filter ‐ Combination filter (G4) 0
Chilled water cooling Coil section with chilled water coil (min 6 row deep)
with 0
aluminum fins & condenste tray made out of SS 304 in 18 gauge
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction 0

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and 0
hot water coil should be less than 200 mm.
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame 0
with vibration isolation.
Fine Filter Section with Fine filter ‐ F7 (99% eff 3 micron). 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch. 0
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

Bleed air cutout with low leak volume control damper in Aluminium profile
and with air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0
x300 Size)

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized 0
Operation)
SS 304 drain insulated pan, Cable entry for motor and sufficient distance 0
between all section.
All Cable & pipes should be Roxtec flexible sealed type. 0

Spring Mounted Vibration Isolator to be provided for Mounting AHUs. 0

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will 0
be provided in all the sections which are in positive stream of air to avoid
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than
0
500 fpm.
D.P. Switch to be provided across pre & fine filter section of AHU. 0
0
AHU‐FF‐01 Nos 1 426600 426600 15000 15000 441600
Fan Capacity (CFM) 4109 0
Supply air quantity (CFM) 3858 0
Coil air Capacity (CFM) 2894 0
Return air Capacity (CFM) 3583 0
Fresh air Capacity (CFM) 526 0
Bleed air Capacity (CFM) 251 0
Static pressure ( MM OF WG ) 80 0
Cooling capacity ( TR ) 7.24 0
Heating Capacity(KW) 14.03 0
0
AHU‐FF‐10 Nos 1 830700 830700 15000 15000 845700
Fan Capacity (CFM) 12961 0
Supply air quantity (CFM) 12523 0
Coil air Capacity (CFM) 11667 0
Return air Capacity (CFM) 12523 0

Page 3 of 11
ANNEXURE - II PART A (AHU -FF-01 TO AHU -FF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

Fresh air Capacity (CFM) 438 0


Bleed air Capacity (CFM) 438 0
Static pressure ( MM OF WG ) 80 0
Cooling capacity ( TR ) 25.82 0
Heating Capacity(KW) 17.67 0
0
AHU‐FF‐11 Nos 1 458100 458100 15000 15000 473100
Fan Capacity (CFM) 4554 0
Supply air quantity (CFM) 4438 0
Coil air Capacity (CFM) 3423 0
Return air Capacity (CFM) 4398 0
Fresh air Capacity (CFM) 288 0
Bleed air Capacity (CFM) 116 0
Static pressure ( MM OF WG ) 80 0
Cooling capacity ( TR ) 7.85 0
Heating Capacity(KW) 11.08 0
0
1.3 SERVICE FLOOR FRESH AIR HEATING SYSTEM 0
0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and
0
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0
x300 Size)
Hot Water coil section (min 2 row deep coil), Gap between cooling coil and 0
hot water coil should be less than 200 mm.
Steam Section with Steam Spray and solenoid valves for ON/OFF control 0
action and condensate steam trap
Fan section with DIDW Fan & Motor. 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON
/ OFF outside the fan section, Blower door shall be provided with limit
0
switch.
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

Opposed blade low leakage extruded aluminum volume control dampers 0


For F.A./S.A. (Damper should be Suitable for Motorized Operation)

All filters and cooling coils should be selected for air face velocity less than
500 fpm. 0

0
Service AHU 01 ‐ GF ‐ SUPPLY Nos 1 727200 727200 10000 10000 737200
Fan Capacity (CFM) 4000 0
Supply air quantity (CFM) 4000 0
Fresh air Capacity (CFM) 4000 0
Static pressure ( MM OF WG ) 50 0
Heating Capacity(KW) 60 0
0
Service AHU 02 ‐ GF ‐ SUPPLY Nos 1 621900 621900 10000 10000 631900
Fan Capacity (CFM) 2300 0
Supply air quantity (CFM) 2300 0
Fresh air Capacity (CFM) 2300 0
Static pressure ( MM OF WG ) 50 0
Heating Capacity(KW) 35 0
0
Service AHU 03 ‐ FF ‐ SUPPLY Nos 1 832500 832500 15000 15000 847500
Fan Capacity (CFM) 6400 0
Supply air quantity (CFM) 6400 0
Fresh air Capacity (CFM) 6400 0
Static pressure ( MM OF WG ) 50 0
Heating Capacity(KW) 100 0
0
Service AHU 04 ‐ FF ‐ SUPPLY Nos 1 866700 866700 15000 15000 881700
Fan Capacity (CFM) 8000 0
Supply air quantity (CFM) 8000 0
Fresh air Capacity (CFM) 8000 0
Static pressure ( MM OF WG ) 50 0
Heating Capacity(KW) 115 0
0
Service AHU 01 ‐ GF ‐ EXHAUST Nos 1 186300 186300 15000 15000 201300
Fan Capacity (CFM) 4300 0
Exhaust air quantity (CFM) 4300 0
Static pressure ( MM OF WG ) 30 0
0
Service AHU 02 ‐ GF ‐ EXHAUST Nos 1 144000 144000 10000 10000 154000
Fan Capacity (CFM) 2300 0
Exhaust air quantity (CFM) 2300 0
Static pressure ( MM OF WG ) 30 0
0
Service AHU 03 ‐ FF ‐ EXHAUST Nos 1 223200 223200 15000 15000 238200
Fan Capacity (CFM) 6400 0
Exhaust air quantity (CFM) 6400 0
Static pressure ( MM OF WG ) 30 0
0
Service AHU 04 ‐ FF ‐ EXHAUST Nos 1 270000 270000 15000 15000 285000
Fan Capacity (CFM) 8200 0
Exhaust air quantity (CFM) 8200 0
Static pressure ( MM OF WG ) 30 0
0
TOTAL 10972800 260000 11232800

Page 4 of 11
Client : KGP BIOPHARMA LTD - MINSK

Location : Minsk, Belarus


Document Title : Bill of Quantities for Air Handling Units

Offer Ref No. : ASIPL/KGP/101/17-18


Date : 04.09.2017 ; Rev : 00

ANNEXURE - II PART B (AHU -SF-01 TO AHU -TF-12)


SUPPLY INSTALLATION TOTAL (INR)
Sr.
Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

1 AIR HANDLING UNITS

1.1 GRADE B ‐ RECIRCULATION TYPE

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm)
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300
x300 Size)
Pre‐filter section with Pre‐filter ‐ Combination filter (G4 + F5)
Chilled water cooling Coil section with chilled water coil ( min 6 row deep)
with aluminum fins & condenste tray made out of SS 304 in 18 gauge
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and
hot water coil should be less than 200 mm.
Electrical Heater section with thyristor control for BMS
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame
with vibration isolation.
Fine Filter Section with Fine filter ‐ F9 (50‐75% eff 0.3 micron).

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch.
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor

Bleed air cutout with low leak volume control damper in Aluminium profile
and with H13 grade (0.3µ) filter with plenum and fixing arrangment. Bleed
air filter ‐ H13 (as per exhaust CFM, consider minimum 300 x300 Size)

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized
Operation)
SS 304 drain insulated pan, Cable entry for motor and sufficient distance
between all section.
All Cable & pipes should be Roxtec flexible sealed type.

Spring Mounted Vibration Isolator to be provided for Mounting AHUs.

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will
be provided in all the sections which are in positive stream of air to avoid
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than
500 fpm.
D.P. Switch to be provided across pre & fine filter section of AHU.

1.1.1 AHU ‐SF ‐02 Nos 1 550000 550000 15000 15000 565000
Fan Capacity (CFM) 5137 0 0
Supply air quantity (CFM) 5058 0 0
Coil air Capacity (CFM) 4247 0 0
Return air Capacity (CFM) 4569 0 0
Fresh air Capacity (CFM) 568 0 0
Bleed air Capacity (CFM) 80 0 0
Static pressure ( MM OF WG ) 180 0 0
Cooling capacity ( TR ) 8.95 0 0
Heating Capacity(KW) 12 0 0
0 0

Page 5 of 11
ANNEXURE - II PART B (AHU -SF-01 TO AHU -TF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

1.2 GRADE D ‐ RECIRCULATION TYPE 0 0


0 0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and
0 0
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0 0
x300 Size)
Pre‐filter section with Pre‐filter ‐ Combination filter (G4 + F5) 0 0
Chilled water cooling Coil section with chilled water coil ( min 6 row deep)
with aluminum fins & condenste tray made out of SS 304 in 18 gauge 0 0
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction 0 0

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and
0 0
hot water coil should be less than 200 mm.
Electrical Heater section with thyristor control for BMS 0 0
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame 0 0
with vibration isolation.
Fine Filter Section with Fine filter ‐ F9 (50‐75% eff 0.3 micron). 0 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch. 0 0
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor

Bleed air cutout with low leak volume control damper in Aluminium profile
and with H13 grade (0.3µ) filter with plenum and fixing arrangment. Bleed 0 0
air filter ‐ H13 (as per exhaust CFM, consider minimum 300 x300 Size)

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized 0 0
Operation)
SS 304 drain insulated pan, Cable entry for motor and sufficient distance
0 0
between all section.
All Cable & pipes should be Roxtec flexible sealed type. 0 0

Spring Mounted Vibration Isolator to be provided for Mounting AHUs. 0 0

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will
be provided in all the sections which are in positive stream of air to avoid 0 0
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than 0 0
500 fpm.
D.P. Switch to be provided across pre & fine filter section of AHU. 0 0 0
0 0 0
1.2.1 AHU‐FF‐01 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1912 0 0 0
Supply air quantity (CFM) 1818 0 0 0
Coil air Capacity (CFM) 1912 0 0 0
Return air Capacity (CFM) 1582 0 0 0
Fresh air Capacity (CFM) 330 0 0 0
Bleed air Capacity (CFM) 95 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 3.82 0 0 0
Heating Capacity(KW) 8.2 0 0 0
0 0 0
1.2.2 AHU‐FF‐02 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1905 0 0 0
Supply air quantity (CFM) 1812 0 0 0
Coil air Capacity (CFM) 1905 0 0 0
Return air Capacity (CFM) 1577 0 0 0
Fresh air Capacity (CFM) 328 0 0 0
Bleed air Capacity (CFM) 93 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 3.8 0 0 0
Heating Capacity(KW) 8.1 0 0 0
0 0 0
1.2.3 AHU‐SF‐01 Nos 1 455000 455000 15000 15000 470000
Fan Capacity (CFM) 5098 0 0 0
Supply air quantity (CFM) 4853 0 0 0
Coil air Capacity (CFM) 4006 0 0 0
Return air Capacity (CFM) 4712 0 0 0
Fresh air Capacity (CFM) 386 0 0 0
Bleed air Capacity (CFM) 245 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 8.5 0 0 0
Heating Capacity(KW) 25.6 0 0 0
0 0 0
1.2.4 AHU‐SF‐03 Nos 1 655000 655000 15000 15000 670000
Fan Capacity (CFM) 8725 0 0 0
Supply air quantity (CFM) 8579 0 0 0
Coil air Capacity (CFM) 8725 0 0 0
Return air Capacity (CFM) 5719 0 0 0
Fresh air Capacity (CFM) 3006 0 0 0
Bleed air Capacity (CFM) 145 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 20.51 0 0 0
Heating Capacity(KW) 26.61 0 0 0

Page 6 of 11
ANNEXURE - II PART B (AHU -SF-01 TO AHU -TF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

0 0 0
1.2.5 AHU‐TF‐01 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 2076 0 0 0
Supply air quantity (CFM) 1748 0 0 0
Coil air Capacity (CFM) 1384 0 0 0
Return air Capacity (CFM) 1901 0 0 0
Fresh air Capacity (CFM) 175 0 0 0
Bleed air Capacity (CFM) 328 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 4 0 0 0
Heating Capacity(KW) 9 0 0 0
0 0 0
1.2.6 AHU‐TF‐02 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1310 0 0 0
Supply air quantity (CFM) 1052 0 0 0
Coil air Capacity (CFM) 1310 0 0 0
Return air Capacity (CFM) 1205 0 0 0
Fresh air Capacity (CFM) 105 0 0 0
Bleed air Capacity (CFM) 258 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 2.76 0 0 0
Heating Capacity(KW) 6.95 0 0 0
0 0 0
1.2.7 AHU‐TF‐03 Nos 1 455000 455000 15000 15000 470000
Fan Capacity (CFM) 7934 0 0 0
Supply air quantity (CFM) 7781 0 0 0
Coil air Capacity (CFM) 5190 0 0 0
Return air Capacity (CFM) 4792 0 0 0
Fresh air Capacity (CFM) 3142 0 0 0
Bleed air Capacity (CFM) 152 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 16 0 0 0
Heating Capacity(KW) 41.2 0 0 0
0 0 0
1.2.8 AHU‐TF‐04 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1474 0 0 0
Supply air quantity (CFM) 1244 0 0 0
Coil air Capacity (CFM) 1474 0 0 0
Return air Capacity (CFM) 1396 0 0 0
Fresh air Capacity (CFM) 78 0 0 0
Bleed air Capacity (CFM) 231 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 3 0 0 0
Heating Capacity(KW) 4 0 0 0
0 0 0
1.2.9 AHU‐TF‐05 Nos 1 275000 275000 10000 10000 285000
Fan Capacity (CFM) 1968 0 0 0
Supply air quantity (CFM) 1769 0 0 0
Coil air Capacity (CFM) 1968 0 0 0
Return air Capacity (CFM) 1910 0 0 0
Fresh air Capacity (CFM) 58 0 0 0
Bleed air Capacity (CFM) 199 0 0 0
Static pressure ( MM OF WG ) 150 0 0 0
Cooling capacity ( TR ) 4 0 0 0
Heating Capacity(KW) 5.5 0 0 0
0 0 0
1.2.10 AHU‐TF‐06 Nos 1 275000 275000 10000 10000 285000
Fan Capacity (CFM) 2228 0 0 0
Supply air quantity (CFM) 2084 0 0 0
Coil air Capacity (CFM) 2228 0 0 0
Return air Capacity (CFM) 2172 0 0 0
Fresh air Capacity (CFM) 56 0 0 0
Bleed air Capacity (CFM) 145 0 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 4.4 0 0
Heating Capacity(KW) 5.7 0 0
0 0
1.2.11 AHU‐TF‐07 Nos 1 455000 455000 15000 15000 470000
Fan Capacity (CFM) 5256 0 0
Supply air quantity (CFM) 4878 0 0
Coil air Capacity (CFM) 5226 0 0
Return air Capacity (CFM) 5101 0 0
Fresh air Capacity (CFM) 125 0 0
Bleed air Capacity (CFM) 348 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 10.3 0 0
Heating Capacity(KW) 9.5 0 0
0 0
1.2.12 AHU‐TF‐08 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1851 0 0 0
Supply air quantity (CFM) 1469 0 0
Coil air Capacity (CFM) 1851 0 0
Return air Capacity (CFM) 1752 0 0
Fresh air Capacity (CFM) 2125 0 0
Bleed air Capacity (CFM) 99 0 0
Static pressure ( MM OF WG ) 382 0 0
Cooling capacity ( TR ) 3.7 0 0
Heating Capacity(KW) 4.5 0 0
0 0
1.2.13 AHU‐TF‐09 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 2025 0 0
Supply air quantity (CFM) 1828 0 0
Coil air Capacity (CFM) 2025 0 0
Return air Capacity (CFM) 1911 0 0
Fresh air Capacity (CFM) 114 0 0
Bleed air Capacity (CFM) 396 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 4.1 0 0
Heating Capacity(KW) 6.1 0 0

Page 7 of 11
ANNEXURE - II PART B (AHU -SF-01 TO AHU -TF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

0 0
1.2.14 AHU‐TF‐10 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1974 0 0
Supply air quantity (CFM) 1835 0 0
Coil air Capacity (CFM) 1974 0 0
Return air Capacity (CFM) 1929 0 0
Fresh air Capacity (CFM) 45 0 0
Bleed air Capacity (CFM) 139 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 4 0 0
Heating Capacity(KW) 4 0 0
0 0
1.2.15 AHU‐TF‐11 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 1991 0 0
Supply air quantity (CFM) 1975 0 0
Coil air Capacity (CFM) 1991 0 0
Return air Capacity (CFM) 916 0 0
Fresh air Capacity (CFM) 1075 0 0
Bleed air Capacity (CFM) 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 5.7 0 0
Heating Capacity(KW) 9.2 0 0
0 0
1.2.16 AHU‐TF‐12 Nos 1 250000 250000 10000 10000 260000
Fan Capacity (CFM) 2160 0 0
Supply air quantity (CFM) 1394 0 0
Coil air Capacity (CFM) 2160 0 0
Return air Capacity (CFM) 1276 0 0
Fresh air Capacity (CFM) 884 0 0
Bleed air Capacity (CFM) 766 0 0
Static pressure ( MM OF WG ) 150 0 0
Cooling capacity ( TR ) 4.85 0 0
Heating Capacity(KW) 4.4 0 0
0 0
0 0
1.3 CNC ‐ RECIRCULATION TYPE 0 0
0 0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and 0 0
return air.
Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0 0
x300 Size)
Pre‐filter section with Pre‐filter ‐ Combination filter (G4) 0 0
Chilled water cooling Coil section with chilled water coil (min 6 row deep)
with
aluminum fins & condenste tray made out of SS 304 in 18 gauge 0 0
sandwidtch type, PUF as a core insulation.

Bypass Damper above cooling coil in Aluminium extruded construction 0 0

Hot Water coil section (min 2 row deep coil), Gap between cooling coil and 0 0
hot water coil should be less than 200 mm.
Electrical Heater section with thyristor control for BMS 0 0
Fan section with Backward curve Plug type Fan complete with motor and
drive package, both Motor and fan are mounted on common base frame 0 0
with vibration isolation.
Fine Filter Section with Fine filter ‐ F7 (99% eff 3 micron). 0 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON / OFF outside the fan section, Blower door shall be provided with
limit switch. 0 0
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

Bleed air cutout with low leak volume control damper in Aluminium profile
and with air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0 0
x300 Size)

Opposed blade low leakage extruded aluminum volume control dampers


For F.A./S.A./R.A./B.A. (Damper should be Suitable for Motorized 0 0
Operation)
SS 304 drain insulated pan, Cable entry for motor and sufficient distance
between all section. 0 0

All Cable & pipes should be Roxtec flexible sealed type. 0 0

Spring Mounted Vibration Isolator to be provided for Mounting AHUs. 0 0

All access door should have minimum clear opening of 500mm for filter
access and others. Inside openable doors (Double door arrangement) will
0 0
be provided in all the sections which are in positive stream of air to avoid
any type of leakage from the doors.

All filters and cooling coils should be selected for air face velocity less than
0 0
500 fpm.
D.P. Switch to be provided across pre & fine filter section of AHU. 0 0
0 0
0 0
1.3.3 AHU‐SF‐04 Nos 1 775000 775000 15000 15000 790000
Fan Capacity (CFM) 12065 0 0
Supply air quantity (CFM) 11978 0 0
Coil air Capacity (CFM) 12065 0 0
Return air Capacity (CFM) 8869 0 0
Fresh air Capacity (CFM) 1199 0 0
Bleed air Capacity (CFM) 88 0 0
Static pressure ( MM OF WG ) 80 0 0
Cooling capacity ( TR ) 27 0 0
Heating Capacity(KW) 35 0 0

Page 8 of 11
ANNEXURE - II PART B (AHU -SF-01 TO AHU -TF-12)
SUPPLY INSTALLATION TOTAL (INR)
Sr. Description Capacity Unit Qty REMARKS, IF ANY
No. UNIT RATE AMOUNT UNIT RATE AMOUNT S+I

0 0
0 0
1.4 SERVICE FLOOR FRESH AIR HEATING SYSTEM 0 0
0 0

Supply, Installation, Testing and Commissioning of Horizontal Double/


Single deccar, Double Skin Air Handling Unit, made out of modular panel of
thickness 43 +/‐ 2 mm thick, Panel outer skin in 24 G GI Sheet (120 gsm) 0 0
and inner skin in 24 G GI (120 gsm), CFC free PUF as core insulation with
density 38 +/‐ 2 kg/sq mtr, complete with thermal break profile, with
following section:

AHU frame work shall be Anodized Aluminum Section minimum 2 mm


thick with 0 0
thermal break profile & internal coving.
Mixing chamber section of minimum 600 mm length for fresh air and
return air. 0 0

Fresh air cutout with low leak volume control damper in Aluminium profile
with Fresh air filter ‐ G4 (As per fresh air CFM, considered minimum 300 0 0
x300 Size)
Hot Water coil section (min 2 row deep coil), Gap between cooling coil and
0 0
hot water coil should be less than 200 mm.
Steam Section with Steam Spray and solenoid valves for ON/OFF control
0 0
action and condensate steam trap
Electrical Heater section with thyristor control for BMS 0 0
Fan section with DIDW Fan & Motor. 0 0

Indutrial grade heavy duty marine light in fan section, Switch for marine
light ON
/ OFF outside the fan section, Blower door shall be provided with limit 0 0
switch.
Factory Internal wiring for marine light and limit switch to be provided.
Gland for motor cable entry shall be provided.

Opposed blade low leakage extruded aluminum volume control dampers 0 0


For F.A./S.A. (Damper should be Suitable for Motorized Operation)

All filters and cooling coils should be selected for air face velocity less than 0 0
500 fpm.
1.4.1 Service AHU TFA‐01 ‐ SUPPLY Nos 1 1200000 1200000 20000 20000 1220000
Fan Capacity (CFM) 15000 0 0
Supply air quantity (CFM) 15000 0 0
Fresh air Capacity (CFM) 15000 0 0
Static pressure ( MM OF WG ) 65 0 0
Heating Capacity(KW) 350 0 0
0 0
1.4.2 Service AHU TFA‐02 ‐ SUPPLY Nos 1 655000 655000 15000 15000 670000
Fan Capacity (CFM) 5000 0 0
Supply air quantity (CFM) 5000 0 0
Fresh air Capacity (CFM) 5000 0 0
Static pressure ( MM OF WG ) 65 0 0
Heating Capacity(KW) 120 0 0
0 0
0 0
1.4.3 Service area Exhaust Unit EAU‐01 Nos 1 800000 800000 15000 15000 815000
Fan Capacity (CFM) 10000 0 0
Exhaust air quantity (CFM) 8000 0 0
Static pressure ( MM OF WG ) 65 0 0
0 0
1.4.4 Service area Exhaust Unit EAU‐02 Nos 1 250000 250000 7500 7500 257500
Fan Capacity (CFM) 3000 0 0
Exhaust air quantity (CFM) 3000 0 0
Static pressure ( MM OF WG ) 65 0 0

2 Dehumidifiers (Optional) Nos. 4 1450000 50000


(For Granulation ‐ II, Compression, Coating & Blister Packing Area)

TOTAL 9300000 267500 9567500

Page 9 of 11
Client : KGP BIOPHARMA LTD - MINSK

Location : Minsk, Belarus


Document Title : Bill of Quantities for Clean Room
Equipments & Floorings
Offer Ref No. : ASIPL/KGP/101/17-18

Date : 04.09.2017 ; Rev : 00

COST PART A COST PART B


Sr. No
SUPPLY INSTALLATION SUPPLY
1 10972800 260000 9300000
TOTAL COST FOR PART A & B (C)
COST PART B TOTAL FOR A & B = C
INSTALLATION SUPPLY INSTALLATION
267500 20272800 527500
20272800 527500