EP_3EV53600STP - Ladder Diagram Page 1

WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:38


Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Wyeth Nutritional (China)

Function: EP_3EV53600STP

Version: 1.00
Created by: Charles Zha
Last updated date: 2009-09-01
Version:1.30
Updated by: Wilber Shou
Last updated date: 2009-10-20
Note:
Updated after Function FAT
---

0 NOP

*** Control Button Logic ***


EP_3EV53600STP Phase
control button1
EP_3EV53600STP.CTL_CB1
1 NOP

*** Functional Logic ***


EP_3EV53600STP Phase
control button2
EP_3EV53600STP.CTL_CB2
2 NOP

*** Interlock Mapping ***


Any CM in Manual Mode
any Control Module
of Evaporator 1 in EP_3EV53600STP
Manual Mode Interlock condition
EVAP1_Any_CM_Man EP_3EV53600STP.Interlock.1
3

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 2
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:39
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Any CM in Simulation Mode
any Control Module
of Evaporator 1 in EP_3EV53600STP
Simulation Mode Interlock condition
EVAP1_Any_CM_Sim EP_3EV53600STP.Interlock.2
4

Main sequence not at step 2


EP_3EV53600STP
Interlock condition
MSE_Step_002.X EP_3EV53600STP.Interlock.3
5 /

InBatch. RUNNING

PHASE START Command from InBatch


(Put Running Logic in this section)
EP_3EV53600STP Phase EP_3EV53600ESD Phase
Run status Run status
EP_3EV53600STP.STS_Run EP_3EV53600ESD.STS_Run
6 / MCR

Running Logic

7 NOP

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 3
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


*** Phase step sequence ***

Step 1
Stop steam supply
Stop condensor
EP_3EV53600STP Phase EP_3EV53600STP Phase
run step buffer FAT Force Bit run step buffer
EQU FAT_STP_Force[0] MOV
8 Equal Move
Source A EP_3EV53600STP.STS_SI Source 1
0
Source B 0 Dest EP_3EV53600STP.STS_SI
0

Step 2
Stop water supply

EP_3EV53600STP Phase Evaporator Steam


run step buffer FAT Force Bit Stopped Condensor stopped
EQU FAT_STP_Force[1] EVAP_STEAM_STOPPED EVAP_COND_STOPPED
9 Equal
Source A EP_3EV53600STP.STS_SI
0
Source B 1

EP_3EV53600STP Phase
run step buffer
MOV
Move
Source 2

Dest EP_3EV53600STP.STS_SI
0

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 4
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Step 3
Stop product pumps
EP_3EV53600STP Phase Water supply to EP_3EV53600STP Phase
run step buffer FAT Force Bit balance tank stopped run step buffer
EQU FAT_STP_Force[2] EVAP_BTD_WATER_STOPPED MOV
10 Equal Move
Source A EP_3EV53600STP.STS_SI Source 3
0
Source B 2 Dest EP_3EV53600STP.STS_SI
0

Step 4
Stop condensate pumps
EP_3EV53600STP Phase EP_3EV53600STP Phase
run step buffer FAT Force Bit Product pump stopped run step buffer
EQU FAT_STP_Force[3] EVAP_PRODUCT_PUMP_STOPPED MOV
11 Equal Move
Source A EP_3EV53600STP.STS_SI Source 4
0
Source B 3 Dest EP_3EV53600STP.STS_SI
0

Step 5
Stop vacuum pumps
EP_3EV53600STP Phase Condensate pump EP_3EV53600STP Phase
run step buffer FAT Force Bit stopped run step buffer
EQU FAT_STP_Force[4] EVAP_COND_PUMP_STOPPED MOV
12 Equal Move
Source A EP_3EV53600STP.STS_SI Source 5
0
Source B 4 Dest EP_3EV53600STP.STS_SI
0

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 5
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Step 6
Stop sealwater
EP_3EV53600STP Phase EP_3EV53600STP Phase
run step buffer FAT Force Bit Vacuum Pump Stopped run step buffer
EQU FAT_STP_Force[5] EVAP_VACUUM_PUMP_STOPPED MOV
13 Equal Move
Source A EP_3EV53600STP.STS_SI Source 6
0
Source B 5 Dest EP_3EV53600STP.STS_SI
0

Step 7
Switch concentrate to drain
EP_3EV53600STP Phase EP_3EV53600STP Phase
run step buffer FAT Force Bit Seal water stopped run step buffer
EQU FAT_STP_Force[6] EVAP_SEALWATER_STOPPED MOV
14 Equal Move
Source A EP_3EV53600STP.STS_SI Source 7
0
Source B 6 Dest EP_3EV53600STP.STS_SI
0

Step 8
Procedure ready
EP_3EV53600STP Phase Concentrate EP_3EV53600STP Phase
run step buffer FAT Force Bit to drain run step buffer
EQU FAT_STP_Force[7] EVAP_CONC_DRAIN MOV
15 Equal Move
Source A EP_3EV53600STP.STS_SI Source 8
0
Source B 7 Dest EP_3EV53600STP.STS_SI
0

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 6
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Reset Signal

Steam Supply Stop Stop condensor Stop water supply Stop product pump Stop condensate pump
EVAP_STEAM_STOP EVAP_COND_STOP EVAP_WATER_STOP EVAP_PRODUCT_PUMP_STOP EVAP_COND_PUMP_STOP
16 U U U U U

Switch concentrate
Stop Vacuum Pump Stop seal water valve to drain
EVAP_VACUUM_PUMP_STOP EVAP_SEALWATER_STOP EVAP_CONC_VALVE_DRAIN
U U U

*** Activations ***

Step 1 - Activations
EP_3EV53600STP Phase
run step buffer Steam Supply Stop
EQU EVAP_STEAM_STOP
17 Equal L
Source A EP_3EV53600STP.STS_SI
Stop condensor
0
EVAP_COND_STOP
Source B 1
L

Step 2 - Activations
EP_3EV53600STP Phase
run step buffer Stop water supply
EQU EVAP_WATER_STOP
18 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 2

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 7
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Step 3 - Activations
EP_3EV53600STP Phase
run step buffer Stop product pump
EQU EVAP_PRODUCT_PUMP_STOP
19 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 3

Step 4 - Activations
EP_3EV53600STP Phase
run step buffer Stop condensate pump
EQU EVAP_COND_PUMP_STOP
20 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 4

Step 5 - Activations
EP_3EV53600STP Phase
run step buffer Stop Vacuum Pump
EQU EVAP_VACUUM_PUMP_STOP
21 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 5

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 8
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:40
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Step 6 - Activations
EP_3EV53600STP Phase
run step buffer Stop seal water
EQU EVAP_SEALWATER_STOP
22 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 6

Step 7 - Activations
EP_3EV53600STP Phase Switch concentrate
run step buffer valve to drain
EQU EVAP_CONC_VALVE_DRAIN
23 Equal L
Source A EP_3EV53600STP.STS_SI
0
Source B 7

Master Control Reset

24 MCR

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 9
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:41
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Set Complete

EP_3EV53600STP Phase
EP_3EV53600STP Phase run logic complete
run step buffer FAT Force Bit flag
EQU FAT_STP_Force[8] EP_3EV53600STP.CTL_Complete
25 Equal
Source A EP_3EV53600STP.STS_SI
0
Source B 8

EP_3EV53600ESD Phase
run step buffer
EQU
Equal
Source A EP_3EV53600ESD.STS_SI
0
Source B 2

Emergency Shutdown

EP_3EV53600ESD Phase
run step buffer Steam Supply Stop Stop condensor Stop water supply Stop product pump
EQU EVAP_STEAM_STOP EVAP_COND_STOP EVAP_WATER_STOP EVAP_PRODUCT_PUMP_STOP
26 Equal U U U U
Source A EP_3EV53600ESD.STS_SI
0
Source B 2

Switch concentrate
Stop condensate pump Stop Vacuum Pump Stop seal water valve to drain
EVAP_COND_PUMP_STOP EVAP_VACUUM_PUMP_STOP EVAP_SEALWATER_STOP EVAP_CONC_VALVE_DRAIN
U U U U

RSLogix 5000
EP_3EV53600STP - Ladder Diagram Page 10
WNC_PLC04:MainTask:U_3EV53600 10/23/2009 08:58:41
Total number of rungs in routine: 28 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091021_1113.ACD

Stop Evaporator Phase


Set Complete

EP_3EV53600STP Phase EP_3EV53600STP Phase


Done status Reset command
EP_3EV53600STP.STS_Done EP_3EV53600STP.CTL_Reset
27 L

(End)

RSLogix 5000