You are on page 1of 4

EQUIPMENT LIST TOTAL 4 PAGE

(Including Cover)
FOR COOLING TOWER

Purpose
● PROJECT CODE : A80385EA

● PROJECT NAME : COCHRANE THERMOELECTRIC POWER PLANT


□ For Approval

● DOCUMENT No. : 0-WD517-EZ440-00001


■ For Construction

● TITLE : EQUIPMENT LIST


□ For Information

● PACKAGE : COOLING TOWER

● OWNER : EMPRESA ELECTRICA COCHRANE S.A.

Y.H.
1 Jul.02.2014 S.M.LEE - H.H.KIM For Construction Y.H.JUNG B.C.LEE
JEONG
Y.H.
0 May.01.2014 S.M.LEE - H.H.KIM For Construction Y.H.JUNG B.C.LEE
JEONG
Y.H.
B Apr.15.2014 S.M.LEE - H.H.KIM For Approval Y.H.JUNG B.C.LEE
JEONG
Y.H.
A Feb.06.2014 S.M.LEE - H.H.KIM For Approval Y.H.JUNG B.C.LEE
JEONG
PREPARED REVIEWED APPROVED CHECKED REVIEWED APPROVED
Rev.
DATE DESCRIPTION
No. HAMON KOREA POSCO E&C
Owner:

Contractor: Supplier

HAMON KOREA CO., LTD


DOC No. 0-WD517-EZ440-00001
Equipment List
REV. No. 1
for Cooling Tower
PAGE 2 OF 4

REVISION STATUS
REV. No. CONTENTS
A FIRST ISSUED
B SECOND ISSUED
- Revision the Equipment No. to KKS No.
- Revision the minor comments

0 FIRST ISSUED FOR CONSTRUCTION


- Addition the Equipment No.
1 SECOND ISSUED FOR CONSTRUCTION
- Revision the equipment number of Junction Box

HAMON KOREA CO., LTD


EQUIPMENT LIST
Project Name: Cochrane Thermoelectric Power Plant (266 MW x 2 Unit)
Equipment Name: COOLING TOWER
Vendor Name: HAMON KOREA
Sheet No.: 3 of 4
Duty Elec.
Size Loading
Equipment No. Description Q’ty Type Capacity Location Power
(W x L x H) (Ton)
C I S (kW)
12PAE00~90AN001 FAN & HUB 20 20 Axial 516.10m3/s 9,144mm(D) Top N/A 1.6
22PAE00~90AN001 7 Blades

12PAE00~90AE001 SPEED REDUCER 20 20 Right Reduction 650 x 1,315 x Top N/A 0.96
22PAE00~90AE001 Angle-Shaft 12.797 1,060mm

12PAE00~90AN001-M01 MOTOR 20 20 TEFC 185kW 1,000 x 1,725 Top 185kW 1.65


22PAE00~90AE001-M01 x 1,140mm

12PAE00~90AU001 DRIVE SHAFT 20 2O Floating Actual 4,000mm Top N/A 0.035


22PAE00~90AU001 S.F = 3.5 (DBSE)

12PAE00~90CY201 VIBRATION S/W 20 2O Mechanical 2-SPDT 162 x 143 x On the N/A 0.01
22PAE00~90CY201 124mm S/R

12PAE00~90CL201 OIL LEVEL S/W 20 2O REED 1-SPST 390mm(L) x Out of N/A 0.002
22PAE00~90CL201 151mm(D) Fan Stack

12PAE00~90GH001 LOCAL PANEL 20 20 STAND 1Cell/1EA 500 x 400 Out of N/A 0.07
22PAE00~90GH001 X 1,500 (H) Fan Stack

12PAE00~90GA001 JUNCTION BOX 2 2 ILS 10Cells/ 600 x 580 Out of N/A 0.05
22PAE00~90GA001 1EA X 300 Fan Stack

Note: Duty – C: Continuous, I: Intermittent, S: Stand-by


EQUIPMENT LIST
Project Name: Cochrane Thermoelectric Power Plant (266 MW x 2 Unit)
Equipment Name: COOLING TOWER
Vendor Name: HAMON KOREA
Sheet No.: 4 of 4
Duty Elec.
Size Loading
Equipment No. Description Q’ty Type Capacity Location Power
C I S (W x L x H) (Ton)
(kW)
12PBB11BB001 SCALE INHIBITOR TANK 1 1 Vertical 1,000L Ø1,080 X 1,430H Skid - 0.1

12PBB11AP001/2/3 SCALE INHIBITOR PUMP 3 2 1 Solenoid 17ℓ/hr 90W X 180L X 160H Skid 0.087 0.018
Diaphragm

12PBB11CQ001 3D TRASAR 1 1 - - 850W X 850H Skid 1 0.08

22PBB11BB001 SCALE INHIBITOR TANK 1 1 Vertical 1,000ℓ Ø1,080 X 1,430H Skid - 0.1

22PBB11AP001/2/3 SCALE INHIBITOR PUMP 3 2 1 Solenoid 17ℓ/hr 90W X 180L X 160H Skid 0.087 0.018
Diaphragm

22PBB11CQ001 3D TRASAR 1 1 - - 850W X 850H Skid 1 0.08

02PBB11BZ001 Safety Eye Washer 1 1 Self- 76ℓ/min Foundation 0.4 0.05


Standing

Barrel Pump 1 1 70ℓ/min - 0.02

Note: Duty – C: Continuous, I: Intermittent, S: Stand-by

You might also like