ELECTRICAL LOAD SCHEDULE

Date Revision Status Description Prepared by Checked by Approved by


E
DOCUMENT NO. :
ABSORBED MOTOR LOAD FACTOR EFFICIENCY POWER FACTOR
EQUIPMENT LOAD RATING =A/B at load at load factor C kW = A/D
factor C
Description
Continuous

Essential
A B C D E

Normal
Equipment

Duty

Vital
No.
kW kW In decimals In decimals Cos φ kW kVAr

NORMAL LOAD BUS - A


MCC-001 MCC 001 X - - - - - 120.37 72.43
General X 12.91 9.68

Max. of normal running plant load: x= 100


133 kW, 82 kVAr, √(kW² + kVAr²) = 157 kVA TOTAL 133 82
(Est. x %E + y %F) y= 50

Peak load: z= 10

(Est. x %E + y %F + z%G)
133 kW, 82 kVAr, √(kW² + kVAr²) = 157 kVA
kVA=√(kW²+kVAr²) 157
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.

TRANSFORMER/MAIN GENERATOR RECOMMENDATIONS

SUMMARY KW KVAR KVA

Normal running load 133 82 157


250KVA GENATOR IS RECOMMENDED FOR THE MAIN OPE
TWO BOOSTER PUMPS.
Running Load With 20% for Future expansion
160 99 188
( Contigency)
20% allowance since the generator can not be
operated beyond 80% of their capacity at peak 192 118 225 OPERATING PHILOSOPHY
load
kVAr = kW*tan j

Intermittent Stand-by
Remarks

kW kVAr kW kVAr

0.00 0.00 0.00 0.00


0.00 0.00 0.00 0.00

0 0 0 0

kVAr

0 0

ATIONS

FOR THE MAIN OPERATION OF THE


R PUMPS.

HILOSOPHY
EQUIPMENT ABSORBED MOTOR LOAD FACTOR EFFICIENCY POWER FACTOR
LOAD RATING =A/B at load at load factor C kW = A/D*C

Operating Voltage
factor C

Essential

Normal
Equipment Continuous Intermittent

Duty

Vital
Description A
E
No. B C D
kW kW In decimals In decimals Cos φ kW kVAr kW

PBA-0201 BOOSTER PUMP C X 380 63.46 75.00 0.85 0.96 0.86 56.17 33.33
PBA-0202 BOOSTER PUMP C X 380 63.46 75.00 0.85 0.96 0.86 56.17 33.33
P-005 GENERATOR HOUSE C X 240 1.24 0.80 0.80 0.80 1.93 1.15
P-007 BOOSTER PUMP HOUSE C X 240 0.80 0.80 0.80 0.80 1.25 0.76
P-006 24VDC UNITERRUPTIBLE POWER SUPPLY UPS C X 240 1.00 0.80 0.80 0.80 1.00 1.56
P-007 CONTROL SWITCH DB C X 415 1.24 0.80 0.80 0.80 1.93 1.15
P-008 GENERAL SERVICE DB C X 415 1.24 0.80 0.80 0.80 1.93 1.15

Max. of normal running plant load: x= 100


120 kW, 72 kVAr, TOTAL 120 72 0
(Est. x %E + y %F) y= 50

140.48
√(kW² + kVAr²) = KVA

Peak load: 120 kW, 72 kVAr, z= 10

√(kW² + kVAr²) = 140 KVA


kVA=√(kW²+kVAr²) 140 0
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.

NOTES: b) Absorbed loads: c) Consumed loads:


a) Load classification: - for pumps, shaft load on duty point. C - ''Continuous"; all loads that may
"Vital", "Essential" and - for lighting, during dark hours. continuously be required for normal operation
' Normal Load '' operation including lighting
kVAr = kW*tan j

Intermittent Stand-by Remarks


FLA 1.25*FLA BREAKER
RATING
kVAr kW kVAr

121.33 151.66 200.00


121.33 151.66 200.00
3.73 4.66 6.00
1.39 1.74 4.00
3.01 3.76 5.00
3.73 4.66 6.00
3.73 4.66 6.00

0 0 0
209 261 400 0.85686
power factor for the MCC

0 0
ABSORBED EQUIPMENT LOAD FACTOR EFFICIENCY POWER FACTOR
EQUIPMENT LOAD RATING =A/B at load at load factor C
factor C

Operating Voltage
Load Duty

Essential

Normal
Equipment

Vital
Description A B C D E
No.
kW kW In decimals In decimals Cos φ

LIGHTING (SWITCHGEAR ROOM) C X 240 0.60 NA 1.00 1.00 0.80


13A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 0.30 NA 0.80 1.00 0.80
15A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 1.50 NA 0.80 1.00 0.80
30A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 3.00 NA 0.80 1.00 0.80
LIGHTING (GENERATOR HOUSE) C X 240 1.12 NA 0.80 1.00 0.80
13A SOCKET OUTLET (GENERATOR HOUSE) C X 240 0.30 NA 0.80 1.00 0.80
30A SOCKET OUTLET (GENERATOR HOUSE) C X 240 3.00 NA 0.80 1.00 0.80
1.25KW UPS(LOCATED IN SWITCH GEAR ROOM) -UPS 004 C X 240 1.26 NA 0.80 0.80 0.80
LIGHTING (BOOSTER PUMP HOUSE) C X 240 0.80 NA 0.80 1.00 0.80
LIGHTING (BOOSTER PUMP HOUSE) C X 240 0.40 NA 1.00 1.00 0.80
13A SOCKET OUTLET (BOOSTER PUMP HOUSE) C X 240 0.30 NA 0.80 1.00 0.80
30A SOCKET OUTLET (BOOSTER PUMP HOUSE) C X 240 3.00 NA 0.80 1.00 0.80

Max. of normal running plant load: x= 100


13 kW, 10 kVAr, √(kW² + kVAr²) = 16 kVA TOTAL
(Est. x %E + y %F) y= 50

Peak load: z= 10
13 kW, 10 kVAr, √(kW² + kVAr²) = 16 kVA
(Est. x %E + y %F + z%G)
kVA=√(kW²+kVAr²)
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.

NOTES: b) Absorbed loads: c) Consumed loads: S-''Stand - by"; loads required in


a) Load classification: - for pumps, shaft load on duty point. C - ''Continuous"; all loads that may emergencies only, such as Spare
"Vital", "Essential" and - for instrumentation, computers, communication, & air continuously be required for normal operation pumps or those of not normally
' Normal Load '' condit'g, the required load during full operation of plant. operation including lighting and workshops running electrically driven units &
- for lighting, during dark hours. I - ''Intermittent and spares"; the loads required for electrical stand - by (rarely operate
- for workshops, the average total load in normal full intermediate pumping, storage, loading, etc normal conditions (e.g.spare produ
operation. products standby pumps)
kW = A/D*C kVAr = kW*tan j

Continuous Intermittent Stand-by Remarks


FLA 1.25*FLA BREAKER
RATING
kW kVAr kW kVAr kW kVAr

0.60 0.45 3.13 3.91 4.00


0.24 0.18 1.56 1.95 2.00
1.20 0.90 7.81 9.77 10.00
2.40 1.80 15.63 19.53 20.00
0.90 0.67 5.83 7.29 4.00
0.24 0.18 1.56 1.95 2.00
2.40 1.80 15.63 19.53 20.00
1.26 0.94 6.54 8.17 40.00
0.64 0.48 4.17 5.21 6.00
0.40 0.30 2.08 2.60 4.00
0.24 0.18 1.56 1.95 2.00
2.40 1.80 15.63 19.53 20.00

13 10 0 0 0 0
22 28 25

22 28
16 0 0

Stand - by"; loads required in


ergencies only, such as Spare
mps or those of not normally
nning electrically driven units &
ctrical stand - by (rarely operate under
rmal conditions (e.g.spare products pumps)
oducts standby pumps)