You are on page 1of 6

2014 Annual IEEE India Conference (INDICON)

Voltage Collapse Mitigation by using SVC and


Phase-Plane Trajectory Analysis
Champa Nandi Dr. Ajoy Kumar Chakraborty
Department of Electrical Engineering Department of Electrical Engineering
Tripura University (A Central University) NIT, Agartala
Suryamaninagar, India Agartala, India
champanandi@yahoo.com akcalll@yahoo.co.in
c.nandi.2014@ieee.org

Abstract—This paper deals with modeling and simulation of In this paper Phase-Plane Trajectory is calculated from the
SVC in IEEE 14 bus System with Induction Motor load for computer simulation waveform data. Vertical axis has been
avoiding voltage collapse. Voltage collapse can be simply chosen as amplitude just likes as time-series display and
described by insufficient reactive power support to the load bus. horizontal axis is redefined so that first derivative of vertical
Three Phases to ground fault is applied in predominant axis is used rather than using time.
Induction motor load bus for voltage collapse analysis. Due to
fault, chaotic behavior is present in power system network during The symbolic differentiation of functions is a topic that is
fault time interval. The effect of Post Fault Clearing Time introduced in all elementary calculus courses. The first
[PFCT] of the system after facing the fault, to prevent permanent derivative is the rate of change of Y (amplitude) with X (time)
voltage collapse has been analyzed with and without SVC. A that is dy/dx, which is interpreted as the slope of the tangent to
simple method is used for analyzing the phase-plane trajectory. the amplitude at each point. Assuming that the x-interval
The Phase-Plane trajectory is calculated from the computer between adjacent points is constant, the simplest algorithm for
simulation waveform data. Chaotic behavior has been observed computing first derivative is
in computer simulations for an IEEE 14 bus power system
network including SVC. Yj' = Y (j+1) – Y (j) = Y (j+1) -Y (j) (1)
X (j+1)-X (j) ΔX
Keywords— SVC, Voltage Collapse, Post fault clearing time,
Phase-Plane Trajectory
Xj' = X (j+1) +X (j) (2)
2
I. INTRODUCTION (For 1<j<n-1)
The Voltage collapse is characterized by an initial slow
progressive decline in the voltage magnitude of the power Where Xj' and Yj' are the X and Y values of the jth point of
system buses and a final rapid decline in the voltage the derivative, n=number of points in the amplitude, and △X
magnitude. The main symptoms of voltage collapse are – low is the difference between the X values of adjacent data points.
voltage profiles, heavy reactive power flows, inadequate A commonly used variation of this algorithm computed the
reactive power support, and heavily loaded systems. Voltage average slope between three adjacent points:
Instability and the problem of voltage collapse can cause the
major blackout in the power system. There are many
conventional controllers such as transformer tap changers, Yj' = Y (j+1) – Y (j -1) (3)
phase shifters which are used for improving Voltage Stability. 2Δ X
But, these controllers are not fast in response and have so many
limitations. To avoid these drawbacks, FACTS devices are Xj' = Xj, (for 2<j<n-1) (4)
proposed, to get fast response and also used to study the
Voltage Stability in the power system [1, 3, and 6]. This is called central difference methods; its advantage is
that it does not involve a shift in the x-axis position of the
There are several definitions of voltage collapse [7]. One
derivative.
definition developed by CIGRE is that a power system
undergoes voltage collapse if the post-disturbance equilibrium In this paper, voltage collapse is designed by three phase to
voltages are below acceptable limits, voltage collapse may be ground fault which is electrically closed to the motor. Chaotic
total (blackout) or partial [7, 8]. Definition according to IEEE phase trajectory are observed in IEEE 14 bus power system
is that Voltage Collapse is the process by which voltage network at bus 6. The final section of this paper concentrates
instability leads to loss of voltage in a significant part of the on applying phase portraits for a sample power system to the
system [7, 9].Chaotic phenomena are one type of oscillation IEEE 14 bus network including SVC. The concepts of voltage
existing in unhealthy power systems. Study on chaotic collapse Model are firstly defined in section II. In section III
phenomena is one important part of power system stability and IV, SVC control scheme and method of Phase Plane
studies. Trajectory are described. Finally, simulation results are shown

978-1-4799-5364-6/14/$31.00 ©2014 IEEE


to demonstrate the effectiveness of this simple method in neighboring shunt reactor. If the second (parallel resonance)
voltage stability study. mode has a lower frequency (say below 20 Hz), a high pass
filter in addition to the notch filter has been suggested. The
II. MODELLING OF VOLTAGE COLLAPSE rectified signal is filtered. The DC side filters include both a
This paper makes the assumption that voltage dip is caused low pass filter (to remove the ripple content) and notch filters
by a three phase fault which is electrically closed to the tuned to the fundamental and second harmonic components.
Induction motor. The worst case scenario is that of a three The auxiliary signals mentioned in Fig. 2 are outputs from the
phase fault which occurs electrically closed to the motor. It is Susceptance (or reactive power) Regulator and Supplementary
this scenario which is examined in this paper for voltage Modulation Controller. The Susceptance Regulator is aimed at
collapse case study. A three phase to ground fault is applied at regulating the output of SVC in steady state such that the full
bus 6 (Bus 6 is already a predominant Induction motor load dynamic range is available during transient disturbances. The
bus) in IEEE 14 bus system. output of Susceptance Regulator modifies the voltage
The following table briefly summarizes the causes of reference Vref in steady state. However its operation is
disturbances which may cause voltage instability. deliberately made slow such that it does not affect the voltage
regulator function during transients
The block diagram of the controller in this case is shown in
TABLE 1 SUMMERY OF VOLTAGE COLLAPSE MODELING Fig. 2. The proportional gain (KP) may be set zero unless a
Disturbance Duration of Model
Disturbance
faster response is required. The transfer function Hm(s)
3-Phase to Ground Fault applied at represents a low pass filter as given below:
predominant Induction motor load (2-2.75 ) Sec dynamic First order LP filter:
bus 6 1
H m (s) = (5)
III. SVC CONTROL SCHEME (1 + sTm )
.
Second order LP filter:
1
H m (s) =
1 + 2 s ζ T m + ( sT m ) 2 (6)
T is the period of the supply voltage. Td arises due to the
discrete nature of the firing pulse. Tb represents the average
delay in getting BSVC from the instant of delivering the order.
The current signal ISVC is used to provide a positive slope for
the control characteristic of SVC. However the current signal
contains harmonics and there are measurement problems
particularly when ISVC is close to zero (the normal operating
point). A solution to this problem is to take the signal from Bref
SVC instead of ISVC. Here the voltage regulator is typically a
PI controller as shown in Fig. 3. Simulations of the SVC in
IEEE 14 bus system were carried out by using Power System
Fig. 1. SVC Controller Scheme Computer Aided Design (PSCAD/EMTDC) software.
The block diagram of basic SVC Controller incorporating
voltage regulator is shown in Fig. 1. [5]. This shows that both
voltage (VSVC) and current (ISVC) signals. The AC filter is
basically a notch filter to eliminate the signal component of
frequency corresponding to the parallel resonance in the
system viewed from the SVC bus. The line capacitance (in
parallel with SVC capacitance) can result in parallel resonance
with the line inductance. The SVC voltage regulator has a
tendency to destabilize this resonant mode of oscillation and
the notch filter is aimed at overcoming this problem. As a
matter of fact, any parallel resonance mode (of frequency
below second harmonic) can have adverse interaction with
SVC voltage regulator. If series capacitors are used along with Fig. 2. Block Diagram of SVC Voltage Control
SVC, then they can cause parallel resonance with a
trajectory result. The flowchart of the programming for the
Trajectory design is as below.

START

Read System Data i.e. X Data, Y Data,


X=Voltage
Y=Time

Fig. 3. Voltage Regulator for SVC Read n;


Number of points in the amplitude

E 0.8

Max D Find
Vpu DX(j)=x(j)-x(j-1)
0.03 D &
N
DY(j)=(y(j+1)-y(j-1))/(2*DX(j))
- D * N/D N/D Qsvc
Isvc N
+
for j=2:n-1
F
Vpu 300.0 D

Find
DY(1)=DY(2);
DY(n)=DY(n-1)
Alpha Order

Btcr N Btcrn * AORD


N/D 0.0174533 Plot for trajectory
Bl D
BL Bl tdblk
P
BSVS BSVS BTCR CapOn + KB
D -+ TCR/TSC CSW STOP
B S V S (o rd )

I CS
F Nc QTCR(Ord) - NC

Vref Kp Ti
- Fig. 5. Flowchart for Phase Plane Trajectory design
CAPS_ON Cap Count D + CapOff CAPS_ON
F
Bl
Fig. 4. PSCAD/EMTDC software simulation representation of SVC
control scheme V. RESULTS AND OBSERVATION

A. Voltage Collapse case

IV. METHOD OF PHASE PLANE TRAJECTORY


Phase trajectory provides a powerful qualitative aid for
investigating system behavior. In this paper, Phase Plane
Trajectory has been generated by plotting voltage magnitude
as a Horizontal axis(X axis) and the first derivative as the
Vertical axis(Y axis). Fixed delay is used for taking the
Vertical axis data for each epoch. This is a very simple
method for designing the phase-plane trajectory from dynamic
wave form data. The state of the system at any moment can be
represented by a point of coordinates (x, y). Dynamic voltage
waveform data has been collected from PSCAD software
simulation result (from voltage collapse case). Matlab
software Programming is used for observing the phase plane Fig. 6. Voltage characteristics graph during voltage collapse case
B. Post Fault Clearing Time D. TSC ON/OFF time switching

Fig. 7. Critical fault clearing Time graph


Fig. 8. TSC ON /OFF Switching Time
C. Voltage level in BUS6 with and without SVC
From Figure 8 It is observed that during faulty condition
TABLE 2 Voltage Level
SL Time(sec) Voltage level Voltage level when Reactive Power requirement is extremely necessary,
NO without SVC(P.U) With SVC immediately switch on the capacitor bank (TSC
SVC(P.U) operation). After fault at 2.025 Sec one TSC has come for the
1. 0.0 0.0 0.0 operating mode but due to more capacitive reactive Power
2. .5 1.05 1.00
requirement another one TSC has switched on again for
3. 1.0 1.04 1.02
4. 1.5 1.03 1.00 compensate the system. During fault (2sec to 2.75 sec) full
5. 2.0 1.03 1.00 range support of TSC has come for the operation.
6. 2.1 0.89 1.01
7. 2.2 0.85 1.02
8. 2.3 0.82 1.02 E. Induction Motor Speed Condition
9. 2.4 0.78 1.01
10. 2.5 0.78 1.01
11. 2.6 0.76 1.01
12. 2.7 0.76 1.01
13. 2.75 0.76 1.01
14. 2.8 0.84 0.99
15. 2.9 0.83 1.00
16. 3.0 0.83 0.99
17. 3.5 0.82 1.00
18. 4.0 0.82 1.00
19 4.5 0.812 1.00
20 5 0.807 1.00

From Figure 6, Figure 7 and Table 2, it is clear that during


fault condition (2 Sec -2.75 Sec) uncompensated system
voltage levels gradually decreased and also observe that
voltage level enters in voltage instability zone even if the fault Fig. 9. Induction Motor Speed Characteristics
is cleared. But due to presence of SVC voltage level remains
healthy reason even during faulty condition. But during In this incident, an unwanted voltage drop led to motor
transient condition SVC case also shows some chaotic stalling in case of uncompensated system. But due to
behavior in system. Post fault Recovery is important to ensure presence of SVC during faulty condition motor got proper
stable operating voltage for the Induction Motor predominant reactive power support so there is no voltage dip due to
load buses. The post fault clearing time for the system to proper reactive power compensation by SVC. So motor
regain voltage at stable state due to Presence of SVC is can run smoothly in healthy condition.
70msec.Within 4.2 cycles voltage levels again reach at stable
zone. But uncompensated system voltage level gradually F. Reactive Power Demand and Compensation
decreases even after 20 cycles of fault removal Voltage level
reaches 0.82 P.U. (stable voltage level range 0.95 P.U. – 1.05 During voltage dip SVC instantly supplied the Reactive
P.U). Power .Induction Motor stalling condition nicely avoided by
Computer simulation result shows voltage level gradually proper reactive power compensation by SVC. Figure 10 shows
decreases. Voltage level enters in voltage collapse condition as different reactive power characteristics.
post-disturbance equilibrium voltages are below acceptable
limits in case of uncompensated system.
Fig. 10. Reactive Power Graphs

G. Phase-Plane trajectory for uncompensated system

Fig. 11. Phase Plane Trajectory for uncompensated system

H. Phase-Plane Trajectory for compensated (SVC) System

Fig. 12. Phase Plane Trajectory for compensated system


From Fig. 11 and Fig 12 it is clear that Phase Plane Trajectory provide a deeper insight into the dynamical mechanism of
for uncompensated system goes voltage collapse condition as voltage collapse phenomenon and effect of SVC on voltage
it enters in unstable zone. Voltage should be 1 P.U. (stable dip condition.
voltage level range 0.95 P.U. – 1.05 P.U).So singular point is
(1, 0). As equilibrium point for first derivative of voltage is REFERENCES
zero. From fig 11. It is shown that Trajectory enters in stable
zone but during fault and post fault condition trajectory enters [1] T. Van Cutsem, Proc. IEEE, “Voltage instability: phenomena,
in unstable zone. It is also clear that the behavior of trajectory countermeasures, and analysis methods,”vol. 88, pp. 208–227, Feb.
2000.. (references)
will be remain unstable zone even after post fault condition as
[2] Byung Ha Lee and Kwang Y. Lee, Senior Member, “ A Study on
direction of trajectory towards unstable Zone. But In Fig 12. Voltage Collapse Mechanism in Electric Power
Trajectory enters in Stable Zone even fault and post fault [3] M. H. J. Bollen, Understanding Power Quality Problems – Voltage Sags
condition it remain in stable zone and trajectory enters in and Interruptions,Wiley-IEEE Press September 24, 1999
singular point .Singular point is in stable focus. [4] G.K. Stefopoulos and A.P. Meliopoulos, “Induction Motor Load
Dynamics: Impact on Voltage Recovery Phenomena,” Proceedings of
VI. CONCLUSION the 2005/2006 IEEE Transmission and Distribution Conference and
Exposition, pp.752 – 759, May 21-24, 2006.
This paper presents a comparative model to describe a [5] Narain G. Hingorani, High Power Electronics and Flexible AC
voltage collapse condition with and without SVC. It has Transmission System, IEEE Power Engineering Review, July 1988.
demonstrated that the dynamic mechanism of the voltage [6] R.Mohan Mathur,Rajiv K. Varma, “Thyristor-Based Facts Controllers
collapse phenomenon using an IEEE 14 bus system model for Electrical Transmission Systems”, Wiley Interscience-IEEE
Press,ISBN 0-471-20643-1,pp-82,123,145,154.
which includes an Induction motor with fault. Especially in
this paper, the mechanism of voltage collapse phenomenon [7] Stefan Johansson & Fredrik,” Voltage collapse in power systems”
Licentiate thesis Licentiate thesis Chalmers University of Technology
has analyzed from the physical point of view. The results of 1995.
simulations on the IEEE 14 bus test system have clearly [8] CIGRÉ Task Force 38-02-10, “Modelling of Voltage collapse Including
shown that how SVC devices increased the bus voltage level Dynamic Phenomena”, 1993.
during fault condition, improve Post fault clearing Time and [9] IEEE Committee Report, Voltage Stability of Power Systems:
avoid unwanted motor stalling with proper reactive power Concepts,Analytical Tools, and Industry Experience,
IEEE/PES90TH0358-2-PWR,1990M. Young, The Technical Writer’s
compensation. A simple method is used for deigning the Phase Handbook. Mill Valley, CA: University Science, 1989.
Plane Trajectory analysis. It is believed that this paper may

You might also like