You are on page 1of 16

SSVT and SSMV product catalog

Oil-filled station service transformers


Auxiliary power from high voltage
transmission lines
ABB innovations for changing demands

ABB (www.abb.com) is a leader in power and automation ABB has been producing instrument transformers for
technologies that enables utility and industry customers to more than 60 years. Thousands of our products perform
improve their performance while lowering environmental vital functions in electric power networks around the
impact. world – day after day, all year round. Their main applications
include revenue metering, control, indication and relay
The ABB Group of companies operates in approximately protection.
100 countries and employs around 145,000 people.
All instrument transformers supplied by ABB are tailormade
to meet the needs of our customers. An instrument transformer
must be capable of withstanding very high stresses in all
climatic conditions. We design and manufacture our products
for a service life of at least 30 years. Actually, most last even
longer.

2 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
SSVT and SSMV transformers – designed for power

ABB’s family of Station Service Voltage Transformer (SSVT)


products combine the characteristics of voltage transformers
with the power rating capability of distribution transformers.
This results in fully-insulated products, up to 362 kV, with power
performance up to 333 kVA.

The SSVT and SSMV feature rugged transformer designs


incorporating high creepage insulators and high over-voltage
capability with impedance protection to limit fault currents.

Station Service Voltage Transformer (SSVT)


The SSVT is a line-to-ground connected single-phase
transformer that can be used either as an individual unit for
supplying single-phase loads, or in a three-phase bank to
support larger kVA three-phase loads.

Station Service Voltage Transformer for Medium Voltage


(SSMV)
This variation of the SSVT transforms power directly from the
high voltage transmission line and steps it down to a medium
voltage output capable of transmitting this power over
immediate distances (up to 20-30 kM).

Benefits of ABB’s advanced technology

– Reliable power for a substation or a stand-alone project.


– Minimum space for installation, low environmental impact,
flexible and compact unit.
– Power directly from a high voltage transmission line to a low
voltage in one step.
– Low initial and running cost, compared to alternate solutions Ratings and distance application for low side supply
such as power transformer tertiary winding, LV distribution
feeders or generator sets. SSVT SSMV
– Modular design for quick project configuration, design and
Nominal System Sec: 600 V Sec: 15 kV
execution. Voltage (L-L) class Distance Class Distance
– Power ratings up to 333 kVA per phase (1 MVA, 3 Ph bank),
46 kV ≤ 125 KVA 0.75kM ≤ 200 KVA 30 kM
available with isolated measuring winding option.
69 kV ≤ 167 KVA 0.75kM ≤ 200 kVA 30 kM
– Two isolated windings for flexibility.
115 kV ≤ 167 KVA 0.75kM ≤ 200 KVA 30 kM
– Medium voltage output for long distance power delivery.
138 kV ≤ 167 KVA 0.75kM ≤ 200 KVA 30 kM
– Reliable transmission voltage access for substation power
which eliminates need to bring in outside distribution voltage. 161 kV ≤ 333 KVA 0.75kM ----

– Special designs easily accommodate for different low 230kV ≤ 333 KVA 0.75kM ----
voltages and outputs. 345 kV ≤ 333 KVA 0.75kM ----
– High seismic withstand capability.
– Short lead-times due to lean manufacturing techniques.

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 3
Applications

SSVT and SSMV instrument transformers can be used in many Remote cell towers
areas for reducing initial cost, while increasing the reliability of When a cell tower needs to be placed in a remote location and
the power supply. lacks nearby electrical secondary feeders, siting the cell tower
adjacent to a high voltage transmission line is an economical
Applications for their use are wide-ranging and include: option. A tap can be taken from the transmission line to an
SSVT placed in a fenced-in area (a miniature substation) to
Switching stations energize the cell tower. Where permitted, the cell transceiver
SSVTs are mounted onto a pedestal inside the substation, can be located directly on the transmission tower.
with the primary tied to the incoming transmission line and
the output secondary control wiring connected to the station
power panel. This solution saves utilities from having to rely on
distrubution feeders outside of the substation for low voltage
control power.

Multiple units can be used for redundancy of power supply for


critical switching stations.

Rural electrification
In developing countries where transmission systems are in place
but a wide-spread distribution infrastructure is lacking, SSVTs
can be used as a compact transformer to greatly reduce the
electrification costs for small villages or compounds. SSVTs
can either be used with its low voltage output to directly supply
needed power for in-close loads near the transmission right of
way, or simply step up the SSVT low voltage output through
distribution transformers for a local distribution network.

With the addition of SSMV, power can now be distributed


further via medium voltage distribution feeders, covering
communities even farther away from a high voltage transmission
line.

4 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
Applications (continued)

Substation auxiliary power without transformer tertiary Transmission tower lighting


SSVTs can eliminate the need for dependency on a power When high voltage transmission lines cross a large body of
transformer tertiary output to a distribution transformer to water, they are typically taller and require aviation safety hazard
provide the low voltage required for control power supply. This lighting. ABB has designed a 46 KV, 5 kVA power rating SSVT
two transformer configuration can now be handled with one with hanger brackets for pole-mounting and fusing in the
step transformation, while also enhancing the reliability of the control cabinet. These units are mounted atop a transmission
control power supply. pole adjacent to the transmission line, eliminating the need to
maintain control supply near the ground level from a distribution
In a similar way, wind and solar power projects located in far feeder.
flung regions would also benefit from the SSVT/SSMV. In the
event of zero generation, essential back up power can be
imported from the transmission line typically tasked with the Oil and gas, mining projects, construction power
export of power when the stations are generating. Many oil and gas exploration and mining projects are far
away from a distribution network and dependent on portable
generator sets for electric power. SSVTs or SSMVs can bring
cheaper electric power reliably to such remote sites. This
option requires low maintenance and running costs along with a
low cost of energy. The SSVT initually used as a power supply
for during construction of a substation project, can continue
to serve as a second control power source. Additionally, the
SSVTs and SSMVs can be relocated to another project site
quickly and easily where required.

Defense and special applications power


Small power needs can arise in an emergency situation, with
constraints on timeframe, footprint, safety, transportation
logistics and reliability. SSVT and SSMV offer a ready, easy
solution for managing these situations quickly.

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 5
Product cutaway and details

The ABB Station Service Voltage Transformer (SSVT) Components and details
incorporates an integral inner condenser bushing connected to 1 NEMA and IEC 50 mm 4-hole stainless steel 4”x4” (100 mm x
a layer wound coil (except 50 and 100 kVA 230 kV unit which is 100 mm) pad primary terminal
a disk wound design). 2 Gas cushion (dry air or dry nitrogen cushion)
3 Pressure relief valve to prevent pressure buildup
The overall structure and components of the SSMV are the 4 Shrader gas valve for cushion application / fillcap
same as the SSVT, with the addition of the surge arrestors 5 Magnetic oil level gauge
applied to the primary and low side bushings. The low side 6 Powder-coated polyester paint on mild steel dome
bushings are also upgraded to distribution class medium 7 Glazed porcelain with major-minor shed pattern for high creepage
voltage bushings. distance
8 Condenser graded inner bushing
9 Stainless and bronze corrosion-resistant hardware
4 10 Powder-coated polyester paint on mild steel cover and tank
1 11 High contrast aluminum schematic and nameplates (not shown)
2 12 Power conduit box with 12” x 20” (305 mm x 508 mm) removable
bottom plate
3 13 Aluminum 2-hole lugs for standard low voltage terminals
14 Measuring conduit box (if measuring winding is specified) with three
5 6
(3) 1-1/2” (38 mm) NPT openings (not shown)
15 Measuring low voltage ¼”-20 (6 mm) copper alloy terminals (not
shown)
16 High visibility ratio and kVA stencils
17 5 kV rated isolated H0 bushing connected to dedicated tank ground
18 ½” (13 mm) bronze drain ball valve with stainless steel pipe plug
19 Two (2) NEMA 2-hole stainless steel ground pads
7
20 Four (4) 2” (51 mm) and four (4) ¾” (19 mm) lifting holes

8
Optional accessories
- One (1) or two (2) measuring windings
- Special low voltage lugs or connectors (NEMA 4-hole, stud or cable
connectors, etc.)
9 - Special low voltage output ratings (277 VAC, 347 VAC, 480 VAC, any
voltage up to 600 VAC)
13 10
- Special medium voltage output ratings (voltages up to 15 kV class
17 output)
- Extra strike and creep insulators
- Polymer insulators in lieu of porcelain designs
14 - Corrosion-resistant stainless steel housings
15
- Secondary terminal box heaters
- Sudden pressure relay
- CTs to power secondary monitoring
19 - Oil sampling valve

12 20 For needs or features not listed, please contact the factory.

16
18

6 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
Product ratings

SSVT product rating matrix

10 25 50 100/125 160/167 200 250 315/333


Type System MSV kV BIL Style kVA(1) kVA(1) kVA(1) kVA(1) kVA(1) kVA(1) kVA(1) kVA(1)

Power windings    
SSVT-250 48 kV 250 kV Measuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)

Power windings     
SSVT-350 72 kV 350 kV Measuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)

Power windings     
SSVT-550 123 kV 550 kV Measuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2 (3) Cl 0.2(3)

Power windings   
SSVT-650 145 kV 650 kV Measuring windings(2) Cl 0.2 (3) Cl 0.2(3)

Power windings   (6) (6) (6) (6)


SSVT-650 170 kV 650 kV Measuring windings(2) Cl 0.2 (3) Cl 0.2(3)

Power windings   (6) (6) (6) (6)


SSVT-750 170 kV 750 kV Measuring windings(2) Cl 0.2(3) Cl 0.2(3)

Power windings     
SSVT-900 245 kV 900 kV Measuring windings(2) Cl 0.5(4)

Power windings     
SSVT-1050 245 kV 1050 kV Measuring windings(2) Cl 0.5(4)

Power windings  
SSVT-1300 362 kV 1300 kV

1. kVA ratings shown are based on a 30° C average ambient condition and a 65° C rise. 4. Two measuring windings are standard with accuracy class 0.5% at 400 VA or 0.3%
2. Measuring windings, where available, may be quantity of one or two windings, except at 400 VA (ZZ).
as noted. 5. One or two measuring windings are available with accuracy class 0.5% at 400 VA or
3. Accuracy of 0.2% at 400 VA or 0.15% at 400 VA (ZZ). 0.3% at 400 VA (ZZ).
6. These ratings are built with housings for SSVT-900 or above.

SSMV product rating matrix

100 125 167 200


Type System MSV kV BIL Style(2) Frequency kVA(1) kVA(1) kVA(1) kVA(1)

60 Hz    
SSMV-350 72 kV 350 kV Power windings 50 Hz    

60 Hz    
SSMV-550 123 kV 550 kV Power windings 50 Hz    

60 Hz    
SSMV650 145 kV 650 kV Power windings 50 Hz    

60 Hz    
SSMV-650 170 kV 650 kV Power windings 50 Hz    

1. kVA ratings shown are based on a 30° C average ambient condition and a 65° C rise.
2. Measurement windings not available on medium voltage output SSMV designs.

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 7
Power and measurement windings

SSVT (high and low voltage) winding options


The standard Station Service Voltage Transformer (power only) These extra windings supply rated accuracy and burden
has two (2) isolated secondary power windings that can be support only when the power winding is loaded at 10% or less
either series or parallel connected for different voltage output. of its power rating, otherwise these measuring windings will
Also, one (1) or two (2) additional tapped measuring windings become less accurate as the power winding is loaded above
can be supplied for measurement and control application 10% of rating.
with some isolation from the power coils to minimize voltage
fluctuations.

Power winding options Measurement winding options

High voltage winding High voltage winding


Line

Line
Internal shields Internal shields

Low voltage windings


Low voltage windings Measuring Single
30A
Series / Parallel
or
Power 1 Power 2 Measuring Dual

or

or
Y or Delta Auxiliary
Power Series / Parallel

SSMV (medium voltage) winding rating design SSMV (medium voltage) output bushing arrangement
This design has been developed to aid siting the product
anywhere there is a transmission line to allow connection. The
design will facilitate power tap off of transmission lines for
mining sites, rural electrification projects or remote loads of any
description.

A distribution class surge arrester is supplied on the side of the tank


wall for direct protection of the low side winding. Take off options
can be overhead directly from the medium voltage bushings (with
protective box cover removed) or sub-surface via conduit entrance
at the bottom of the box.

Unit provided for medium voltage power output cannot be provided


with measurement windings.

8 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
SSVT connection and nameplate

Power conduit box Measuring conduit box

Power conduit box internal view Measuring conduit box internal view
(750 kV BIL rating and lower) (750 kV BIL rating and lower)

Typical nameplate layout


The supplied nameplates are laser-etched aluminum and
contain product technical details, as well as winding
schematics. A power winding nameplate is affixed near the
power conduit box and, where applicable, a separate nameplate
for measuring windings is provided near the measuring
terminals. The example shown is for illustration purposes;
actual nameplates will reflect the specification for each site
application.

ABB KUHLMAN
TYPE SSVT-650-100 VOLTAGE TRANSFORMER
CRYSTAL SPRINGS
MISSISSIPPI
CATALOG NO.
SERIAL L99N656100C
NUMBER: P/N: 2257993001
NSV: PRIMARY RATED THERMAL % OIL VOL:
CONNECTION RATIO RATING IMPEDANCE
138 KV VOLTS SEC VOLTS 85 GAL
BIL: 123 X1-X2 II X3-X4 656 100 KVA 9.0% TOT. WT.
650 KV 80500
123/246 X1-X4 328 100 KVA 9.0% 3075 LB
60 HZ 65°C RISE MAX. TOTAL 100 KVA

H1 H0
123 V 123/246 V
PARALLEL CONNECTION SERIES CONNECTION
STATIC
SHIELD
X1 X3 X1 X3
TANK
X2 X4 X2 X4
Conduit box internal view X1 X2 X3 X4

(900 kV BIL rating and higher) SUBTRACTIVE POLARITY


SEE KUHLMAN INSTRUCTION MANUAL BEFORE ENERGIZING.
HERMETICALLY SEALED: DO NOT TILT OVER 25° FROM VERTICAL.
FILLED WITH NON-PCB MINERAL OIL WHEN MANUFACTURED (LESS THAN 1 PPM)
YEAR COOLING-ONAN MADE IN U.S.A.

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 9
SSVT dielectric ratings

SSVT (low voltage output only)


In general, the SSVT is produced according to IEEE C57.13 The unit can be configured for IEC dielectric ratings as well as
relative to the dielectric ratings and for 60 hertz performance. for 50 hertz systems.
The information shown below reflects the IEEE specification.

Rating Product voltage levels

SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300

NSV 46 kV 69 kV 115 kV 138 kV 161 kV 161 kV 230 kV 230 kV 345 kV

MSV 48 kV 72 kV 123 kV 145 kV 170 kV 170 kV 245 kV 245 kV 362 kV

BIL 250 kV 350 kV 550 kV 650 kV 650 kV 750 kV 900 kV 1050 kV 1300 kV

MCOV (power only) 115% 115% 115% 115% 115% 115% 110% 115% 115%

MCOV (power + measure) 140% 140% 140% 140% 140% 140% 110% N/A N/A

MMOV (power only) 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min

MMOV (power + measure) 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 120% - 1 min N/A N/A

PF Withstand
- Dry 95 kV - 1 min 140 kV - 1 min 230 kV - 1 min 275 kV - 1 min 275 kV - 1 min 325 kV - 1 min 395 kV - 1 min 460 kV - 1 min 575 kV - 1 min
- Wet 95 kV - 10 sec 140 kV - 10 sec 230 kV - 10 sec 275 kV - 10 sec 275 kV - 10 sec 315 kV - 10 sec 350 kV - 10 sec 445 kV - 10 sec 575 kV - 10 sec

PD free @ 37 kV 54 kV 93 kV 109 kV 124 kV 124 kV 186 kV 186 kV 300 kV

H0 bushing 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV

H0 bushing BIL 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV

HV bushing

Creep** in. (mm) 37 (940) 52 (1321) 130 (3302) 147 (3734) 147 (3734) 199 (5055) 267 (6782) 351 (8915) 391 (9931)

Strike** in. (mm) 17 (432) 23 (584) 42 (1067) 49 (1245) 49 (1245) 54 (1372) 72 (1829) 79 (2007) 98 (2489)

**Extra creep and strike insulators available, contact factory.


*MCOV based on square root of nominal system voltages (NSV/√3).

10 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
SSMV dielectric ratings

SSMV (MV secondary)

Rating Product voltage levels


SSMV-350 SSMV-550 SSMV-650

Frequency 60 Hz / 50 Hz 60 Hz / 50 Hz 60 Hz / 50 Hz

Thermal rating range 100-200 kVA 100-200 kVA 100-200 kVA

NSV 69 kV 115 kV 138 kV

MSV 72 kV 123 kV 145 kV

BIL 350 kV 550 kV 650 kV

MCOV (power only) 115% 115% 115%

MMOV (power only) 125% - 1 min 125% - 1 min 125% - 1 min

Power frequency withstand


- Dry 140 kV - 1 min 230 kV - 1 min 275 kV - 1 min
- Wet 140 kV - 10 sec 230 kV - 10 sec 275 kV - 10 sec

PD free @ 54 kV 93 kV 109 kV

H0 bushing 25 kV 25 kV 25 kV

H0 bushing BIL 125 kV 125 kV 125 kV

7200 V @ 60 Hz 7200 V @ 60 Hz 7200 V @ 60 Hz


Secondary voltage
6600 V @ 50 Hz 6600 V @ 50 Hz 6600 V @ 50 Hz

X0 - X12 bushing class 25 kV 25 kV 25 kV

X0 - X1 bushing BIL 125 kV 125 kV 125 kV

HV bushing

Creep** in. (mm) 52 (1321) 130 (3302) 147 (3734)

Strike** in. (mm) 23 (584) 42 (1067) 48 (1219)

Arrester ratings SSMV-350 SSMV-550 SSMV-650

HV arrester 60 kV 102 kV 120 kV

MV arrester 10 kV 10 kV 10 kV

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 11
SSVT dimensions and weights

SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300

MSV / BIL kV 48 / 250 72 / 350 123 / 550 145 / 650 170 / 650 170 / 750 245 / 900 245 / 1050 345 / 1300

A - Height in. (mm) 66.39 (1686) 75.00 (1905) 94.05 (2389) 101.73 (2584) 101.73 (2584) 124.29 (3157) 175.20 (4450) 177.56 (4510) 207.48 (5270)

B - Width in. (mm) 30.50 (775) 30.50 (775) 30.50 (775) 31.00 (787) 31.00 (787) 34.25 (870) 70.08 (1780) 70.08 (1780) 70.08 (1780)

C - Depth in. (mm) 44.82 (1138) 44.82 (1138) 44.82 (1138) 48.97 (1244) 48.97 (1244) 53.96 (1371) 68.30 (1735) 66.00 (1676) 75.00 (1905)

D - Highest Gnd Part


34.37 (873) 34.37 (873) 34.37 (873) 35.19 (894) 35.19 (894) 39.81 (1011) 61.42 (1560) 66.07 (1678) 69.53 (1766)
in. (mm)

E - Insulator Length
13.88 (353) 22.21 (582) 40.65 (1032) 47.64 (1210) 47.64 (1210) 58.38 (1483) 75.79 (1925) 74.80 (1900) 98.80 (2510)
in. (mm)

F - Lowest live part


52.51 (1334) 62.25 (1581) 81.82 (2078) 89.50 (2273) 89.50 (2273) 89.70 (2278) 137.21 (3485) 140.87 (3578) 168.30 (4275)
in. (mm)

G - Conduit box
11.50 (292) 11.50 (292) 11.50 (292) 12.25 (311) 12.25 (311) 16.63 (422) 31.10 (790) 31.10 (790) 27.96 (710)
height in. (mm)

H - Mtg Holes front-


30.38 (772) 30.38 (772) 30.38 (772) 34.75 (883) 34.75 (883) 40.88 (1038) 48.00 (1219) 48.00 (1219) 48.00 (1219)
back in. (mm)

I - Mtg Holes left- 57.00 (1448) 57.00 (1448) 57.00 (1448)


28.75 (730)) 28.75 (730) 28.75 (730) 28.87 (733) 28.87 (733) 32.25 (819)
right in. (mm) 66.00 (1676) 66.00 (1676) 66.00 (1676)

Shipping Volume 60x46x75 60x46x83 60x46x102 60x46x102 60x46x102 60x46x102 66x70x142 66x70x145 196.5x80x125
(l x w x h) in. (mm) (1524x1168x1905) (1524x1168x2108) (1524x1168x2591) (1524x1168x2591) (1524x1168x2591) (1524x1168x2591) (1676x1778x3595) (1676x1778x3683) (4991x2032x3175)

Unit Weight lb. (kg) 2255 (1009) 2470 (1120) 2550 (1156) 2960 (1343) 2960 (1343) 3500 (1588) 9500 (4318) 9910 (4505) 11084 (5038)

Shipping Weight lb. (kg) 2325 (1055) 2570 (1166) 2650 (1202) 3060 (1388) 3060 (1388) 3600 (1633) 11480 (5281) 11500 (5227) 14291 (6496)

Oil Volume gal. (liter) 69 (261) 75 (284) 80 (303) 105 (397) 105 (397) 120 (453) 541 (2048) 550 (2082) 550 (2082)

Information shown herein is for informational purposes and is subject to change without notice.
For construction purposes, contact factory for updated information.

H1 3.00
H1
(76)
N LIQUID

LO LEVEL

1.75
(44)
.62 x 1.25
(15.9 x 31.8) H
1.75 MOUNTING MTG
3.50
0.56 (44) (89) SLOT HOLES
A (14) (4) PLCS Front
OVERALL (4) HOLES to Back
HEIGHT C
50 mm hole spacing available OVERALL
DEPTH
E NEMA 4-Hole 6.00 x 20.00
INSULATOR Primary Terminal KNOCKOUT
F FOR CONDUIT
SURFACE LOWEST
ENTRY &
LIVE PART
7.25 x 21.75
HEIGHT
REMOVABLE
2.00 PLATE AL I
(51) 1/2-13 NC MTG HOLES
(2) HOLES (NOT SHOWN)
NON-DRILLED Left to Right

1.75
VIEW FROM BOTTOM
D 3.50
(89) (44)
HIGHEST MOUNTING DIAGRAM
DANGER

GROUND
High voltage.
Can cause
severe injury, death
or damage transformer.

PART
HEIGHT
NEMA 2-Hole
Ground Pad
G
XXX/XXX:1
CONDUIT XX KVA
BOX
For SSVTs with 900 kV BIL and higher ratings, a
FILLED AT THE
TIME OF
MANUFACTURE
WITH NON-PCB

HEIGHT
(LESS THAN 1 PPM)
DIELECTRIC FLUID
1250360001

single conduit box contains both the power windings


B as well as the measuring windings (when supplied)
WIDTH and has a fixed 3” conduit opening for power outlet.

12 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
SSMV dimensions and weights

SSMV-350 SSMV-550 SSMV-650

MSV / BIL kV 72 / 350 123 / 550 145 / 650

A - Height in. (mm) 89 (2262) 108.52 (2756) 116.33 (2955)

B - Width in. (mm) 33.75 (857) 33.75 (857) 34.25 (870)

C - Depth in. (mm) 66.18 (1681) 66.21 (1681) 70.56 (1792)

D - Highest Gnd Part


41.83 (1062) 42.91 (1090) 43.71 (1110)
in. (mm)

E - Insulator Length
22.91 (582) 40.65 (1033) 47.64 (1210)
in. (mm)

F - Lowest live part


64.93 (1649) 83.74 (2127) 91.55 (2325)
in. (mm)

G - Conduit box height


11.50 (292) 11.50 (292) 12.25 (311)
in. (mm)

H - Mtg Holes front- back


36.40 (925) 36.40 (925) 40.77 (1038)
in. (mm)

I - Mtg Holes left- right


32.13 (816) 32.13 (816) 32.25 (819)
in. (mm)

Crate 1 Crate 2 Crate 1 Crate 2 Crate 1 Crate 2


Shipping Volume (l x w x h)
80x48x72 24x24x26 80x48x92 24x24x26 85x50x98 24x24x26
in. (mm)
(2032x1219x1829) (610x610x660) (2032x1219x2337) (610x610x660) (2159x1270x2489) (610x610x660)

Unit Weight lb. (kg) 3513 (1593) 3593 (1629) 4343 (1970)

Shipping Weight lb. (kg) 3620 (1642) 3700 (1678) 4450 (2023)

Oil Volume gal. (liter) 150 (568) 155 (587) 180 (681)

Information shown herein is for informational purposes and is subject to


change without notice. For construction purposes, contact factory for
updated information.

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 13
Catalog number breakdown

SSVT - Low Voltage Output

250 kV through 750 kV BIL (46 kV - 161 kV Systems)

Typical SSVT Catalog Number:


J99N328050C-XXX

J 99 N 328 050 C XXX

Transformer Type KVA Series


Factory assigned Winding Code 10 Factory assigned
Factory assigned 25 Special Features
Dielectric Insulation Code (kV BIL) Highest turns ratio 50 As required
H = 250 kV 100/125
J = 350 kV Power / Meter 160/167
K = 550 kV M = Meter windings 200
L = 650 kV N = No meter windings 250
M = 750 kV D = Dual meter windings

900 kV through 1300 kV BIL (230 kV - 345 kV Systems)

Typical SSVT Catalog Number:


N91110N100-XXX

N 91 110 N 100 XXX

Series KVA
Factory assigned Power / Meter
100
M = Meter windings
167 Special Features
N = No meter windings
200 As required
D = Dual meter windings
250
Dielectric Insulation Code (kV BIL)
Winding Code 315/333
N = 900 kV or 1050 BIL
P = 1300 kV BIL Factory assigned
Highest turns
ratio

SSMV - Medium Voltage Output

350 kV through 750 kV BIL (46 kV - 161 kV Systems)

Typical SSMV Catalog Number:


J99VA28050C-XXX

J 99 V A 28 050 C XXX

Transformer Type Winding Code Series


Factory assigned Factory assigned Factory assigned
Highest turns ratio KVA
Dielectric Insulation Code (kV BIL) 10
J = 350 kV Frequency 25 Special Features
K = 550 kV A = 60 Hz 50 As required
L = 650 kV B = 50 Hz 100/125
M = 750 kV Power / Meter 160/167
N = No meter windings 200

14 | Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog
Inquiry information sheet

Copy form as needed.

ABB Station Service Voltage Transformers quote requests: HVIT@us.abb.com


Type SSVT/SSMV: Single Phase, Single Bushing

Customer / Project

Size / Load Rating kVA 10, 25, 50, 100, 167 or higher

Primary Voltage Volt Line-to-Neutral average, actual, not nominal

MMOV Volt  30 seconds or  60 seconds maximum over voltage, L-N

MCOV Volt Continuous maximum over voltage, L-N

Primary Protection kV BIL 250 - 1300 kV

SEC. Power Voltages V nominal 110/220, 120/240, 240/480, 277, 347, other (600 V class)

or Limits NLV high / FLV low (V or ratio)

Ratios: PRI. L-N:SEC :1 for each Secondary Power Voltage at no load

Load Power Factor % at maximum power loading

Measuring Outputs None Single with tap Dual with tap Special

High accuracy is standard

Elev > 3000 ft. Temp. > 40˚ C Temp < 40˚ C 24 hr. avg.
Operating Environment

STANDARD FEATURES SPECIAL FEATURES

Primary Bushing ANSI 70 Gray Brown Increased / Reduced BIL rated

H-spade terminal standard

Type of Secondary Terminals 2-hole g spade 4-hole h spade


2-hole lug

Tank Material Mild steel 304L SST or Other:

Dome Material Mild steel 304L SST or Other:

Finish Coating ANSI 70 Gray polyester powder Other:

Tank Ground Pads 1 on side 1 in T.B. Other:

Cable Connector Option Y/N Size Range

Primary Terminal MCM

Tank Ground MCM

Other options available - Oil sampling device - Export crating


- 1 or 2 CTs in terminal box - Temperature gauge
- Heater in terminal box - Mounting riser stand

Comments: ___________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________

ABB Station Service Voltage Transformers


Type SSMV: Additional information included beyond that shown above

Frequency 60 Hz 50 Hz

Output Voltage Rating 2.4 kV 4.2 kV 6.6 kV 7.2 kV 8.4 kV

Power Take-off Underground Overhead

Types SSVT and SSMV oil-filled station service voltage transformers | ABB product catalog | 15
Contact us

ABB, Inc. Note:

Document Number: PPHVITSSV1014BR / January 2015


We reserve the right to make technical changes or modify the contents of this document
High Voltage Instrument Transformers without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
3101 Beaumont Centre Circle ABB does not accept any responsibility whatsoever for potential errors or possible lack
of information in this document. We reserve all rights in this document and in the subject
Suite 225 matter and illustrations contained therein. Any reproduction–in whole or in parts–is
Lexington, KY 40513 forbidden without ABB’s prior written consent.

Phone: +1 859-219-6040 Copyright 2014 ABB.


Fax: +1 859-223-2025 All rights reserved.

www.abb.com/highvoltage

You might also like