3RV1 Circuit-Breakers

SIRIUS General Data


Sirius12

Busbar accessories

■ Overview
3RV1 Circuit-Breakers

Busbar adapters
The circuit-breakers are moun- The circuit-breakers are snap- SIRIUS circuit-breakers and load feeders with busbar adapters snapped
ted directly with the aid of bus- ped onto the adapter and con- onto busbars
bar adapters on busbar nected on the line side. This nsb0056h
systems with 40 mm and 60 mm prepared unit is then plugged
centerline spacing, in order to directly onto the busbar system,
save space and to permit and is thus connected both
infeed times and costs to be mechanically and electrically at
cut. the same time.
Busbar adapters for busbar Refer to page 2/10 for busbar
systems with 40 mm centerline adapters for specific circuit-
spacing are suitable for copper breakers and accessories.
busbars with a width of 12 mm
to 15 mm, while those with 60 Further busbar adapters for
mm centerline spacing are sui- snap-mounting direct-on-line
table for widths of 12 mm to starters and reversing starters,
30 mm. The busbars can be as well as additional accesso-
4 to 5 mm or 10 mm thick. ries such as line terminals and
outgoing terminals, busbar cop-
per, etc., can be found under
„Distribution and Busbar
Systems“

Insulated 3-phase busbar systems


3-phase busbar systems pro- The circuit-breakers are supp- 3-phase busbar system, size S00
vide an easy, timesaving and lied via appropriate line-side 3RV19 15-5A
straightforward means of fee- terminals.
ding a series of adjacent 3RV1 3RV19 15-1CB
S00, S0 and S2 circuit-breakers 3-phase busbar systems are
which are snap-mounted on a safe against finger touch. They rotated
are designed for any short cir- through
standard mounting rail. 180°
cuit stress the load side of con-
The busbars are suitable for nected circuit-breakers might
between 2 and 5 circuit-brea- be subject to.
kers. However, any kind of
extension is possible by clam-

NSB01073c
ping the tags of an additional
busbar (rotated through 180°)
underneath the terminals of the 3RV19 15-5B
respective last circuit-breaker. 3-phase
busbar system, size S2
Different sized circuit-breakers 3RV19 15-6AB
3RV19 35-5A 3RV19 35-1C
cannot be clamped together
due to the different fixing 3RV19 35-1A 3-phase busbar system, with example for combining
sizes S00 and S0
dimensions. Special connec-
tors are available for connecting 3RV19 25-5AB
3-phase busbars for S0 circuit- 3RV19 15-1AB 3RV19 15-5DB
breakers to busbars for S00 cir- 3RV19 15-1CB
cuit-breakers.
NSB01075a

Busbars with larger modular


NSB01074a

spacing can be used for circuit-


breakers with laterally mounted
accessories.
3RV19 35-6A

3RV19 15-6AB

3-phase busbar system for Cage Clamp connection


3-phase busbar systems are 3-phase busbar system for Cage Clamp connection, size S00
also available for S00 circuit-
breakers with Cage Clamp con- 3RV19 15-1CA
nection.
Infeed via commonly available
terminal blocks.
NSB01076a

Siemens NS K · 2002 2/35


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Busbar accessories

■ Dimension drawings
3RV19 15-1. . 3-phase busbar
for S00 and S0 circuit-breakers, modular spacing 45 mm
for 2 circuit-breakers 3RV19 15-1AB
for 3 circuit-breakers 3RV19 15-1BB
for 4 circuit-breakers 3RV19 15-1CB
for 5 circuit-breakers 3RV19 15-1DB
13
NSB 00055b

21
64
45
83 108
128
173
218

3RV19 15-2. . 3-phase busbar


for S00 and S0 circuit-breakers, modular spacing 55 mm
for 2 circuit-breakers with accessories 3RV19 15-2AB
for 3 circuit breakers with accessories 3RV19 15-2BB
for 4 circuit breakers with accessories 3RV19 15-2CB
for 5 circuit-breakers with accessories 3RV19 15-2DB
13
NSB 00056b
21
64

55
108

93
148
203
258

3RV19 15-3. . 3-phase busbar


for S00 and S0 circuit-breakers, modular spacing 63 mm
for 2 circuit breakers with accessories 3RV19 15-3A
for 4 circuit breakers with accessories 3RV19 15-3C
NSB 01092b
13
21
64

63
101
108

227

3RV19 35-1. . 3-phase busbar


for S2 circuit-breaker, modular spacing 55 mm
for 2 circuit-breakers 3RV19 35-1A
for 3 circuit-breakers 3RV19 35-1A
for 4 circuit-breakers 3RV19 35-1C
15
31

96

55
NSB00057b

111
166

165
221

2/36 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS General Data
Sirius12

Busbar accessories

■ Dimension drawings
3RV19 35-3. . 3-phase busbar
for S2 circuit-breaker, modular spacing 75 mm
for 2 circuit breakers with accessories 3RV19 35-3A
for 3 circuit breakers with accessories 3RV19 35-3B
for 4 circuit breakers with accessories 3RV19 35-3C
15

31

96
75

NSB00058b
121

166
196
271

3RV19 15-5. 3-phase line-side terminals 3RV19 25-5AB 3-phase line-side terminal
3RV19 15-5A 3RV19 15-5B
connection from above, connection from below, connection from above,
size S00 sizes S00 and S0 size S0
a) 3RV1. 1 19 mm
44 24
3RV1. 2 23 mm
NSB00059a

44
14 14 54
92

NSB01093a
73

25
NSB00060b

71
14 14 a

114
44 31

3RV19 35-5A 3-phase line-side terminal 3RV19 15-5DB Connector


for circuit-breaker size S2 For connecting a 3-phase busbar for
circuit-breakers of the size S0
(left) to size S00 (right)
112 13
55
NSB 00062c
NSB00061b

21
34

64
91

108

42,5
81
161

3RV19 15-1.. 3-phase busbar for Cage Clamp


3RV19 15-1BA, 3RV19 15-1CA for Cage Clamp
173
128
45 79
11

87
133
NSB01094a

Siemens NS K · 2002 2/37


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Rotary operating mechanisms

■ Overview
Door-coupling rotary operating mechanisms
Circuit-breakers with a rotary When the cubicle door is closed, unintentional access. This lock reclosing with up to 3 padlocks.
operating mechanism can be the operating mechanism is can be defeated by the mainte- Once again, inadvertent ope-
mounted in a cubicle and ope- coupled. When the circuit-brea- nance staff. In OFF position, the ning of the door is impossible.
rated externally by means of a ker is switched on, the coupling rotary operating mechanism can
door-coupling rotary operating is locked, thus preventing be secured against
mechanism.
3RV19 26-0K Door coupling rotary mechanism 3RV19 26-2B Door coupling rotary mechanism, heavy duty

NSB01078

NSB01079
Remote-controlled motorized operating mechanisms
3RV1 circuit-breakers are In "AUTOMATIC" position, the the circuit-breaker after 1 se- Reset function
manually operated switching circuit-breaker is switched via cond at the latest. On voltage
devices. They automatically trip electrical commands. The mini- failure during the switching ope- The RESET button on the motori-
in case of an overload or short mum period of switching com- ration it is ensured that the cir- zed operating mechanism
circuit. Intentional, remote-con- mands must be 100 ms. The cuit-breaker remains in On or Off resets a possibly installed
trolled tripping is possible by motor-driven remote-controlled position. signalling switch 3RV19 21-1M.
means of a shunt release or an mechanism closes
undervoltage release. Reclo-
sing is only possible directly at
the circuit-breaker.
The remote-controlled motori-
zed operating mechanism al-
lows the circuit-breakers to be
opened and closed by electri-
cal commands. This enables a
load or an installation to be iso-
lated from the power system or
reconnected to it from an ope-
rator panel.
If the circuit-breaker is tripped
as a result of overload or short-
circuit, it will be in tripped posi-
tion. For reclosing the motor-
driven remote-controlled moto-
rized operating mechanism
must first be set manually or
electrically to 0 position (electri-
cally via OFF command). Then
it can be reclosed.
The remote-controlled motori-
zed operating mechanism is
NSB00007

available for circuit-breakers of


size S2 (In max. = 50 A) and size
S3 (In max. = 100 A) that are de-
signed for control voltages of
AC 230 V or DC 24 V. The cir-
cuit-breaker is fitted into the re-
mote-controlled motorized ope-
rating mechanism as shown in
the block diagram.
In "MANUAL" position, the cir-
cuit-breaker in the motor-driven
remote-controlled mechanism
can still be switched locally.

2/38 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS General Data
Sirius12

Rotary operating mechanisms

■ Circuit diagrams
Typical circuits
3RV1 circuit-breaker with 3RV19 36/3RV19 46 remote-controlled
motorized operating mechanism
US
~ ~
- +

1
O 2
M
3
4
5

L I T
v

NSB00024a

■ Dimensional drawings
3RV19 26-0. Door coupling rotary mechanism
3RV19 26-0B
3RV19 26-0C
short shaft4), for circuit-breaker sizes S0, S2, S3
66
45 19 15
1 ... 4 1) Lockable in 0 position, with shack-
le diameter max. 8 mm
34,5 1)
2) Mounting with screw cap
3) Supplied with a shaft length of
330 mm; adaptable by shortening
of the shaft.
NSB 01089b

4) Supplied with a shaft length of


5 130 mm; adaptable by shortening
2) of the shaft.
max. 327
33 17 5) Grounding terminal 35 mm2 and
min. 55
bracket for 330 mm shaft.

3
4)
24,3

22,5
NSB01107

max. 130
min. 45

3RV19 26-0K
3RV19 26-0L
long shaft (with bracket)3), for circuit-breaker sizes S0, S2, S3
66
16 45 19 15
1 ... 4
34,5
1)
NSB 01090b

5
2)
max. 327
5) 33 17
min. 55

3
3)
24,3

22,5
NSB01108

max. 330
min. 45

Siemens NS K · 2002 2/39


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Rotary operating mechanisms

■ Dimension drawings
3RV19 . 6-2. Door coupling rotary mechanism for heavy duty
3RV19 26-2., 3RV19 36-2., 3R19 46-2.
for sizes S0, S2 and S3
Drilling template, door Drilling template, base
G J
NSB01091a

65
75

B
A

40
6

max. 341
D E F 62 14 H C
min. 42

Type Size Dimensions

A B C d E f g h j
3RV19 26-2 S0 125 111 50 77 112 50 27 9 42
3RV19 36-2 S2 170 144 60 87 162 50 27 10 47
3RV19 46-2 S3 194 180 60 100 187 48 25 10 53

max. 330
min. 11 mm without shaft
min. 31

Remote-controlled motorized
operating mechanisms
3RV19. 6-3AP0
for sizes S2 and S3
5 112
NSB00044

a) 3RV19 36-3AP0 211 mm


3RV19 46-3AP0 236 mm
SI EMENS

RESET I>
I

0
182
224

MANUAL
AUTOMATIC REVISION

87 a)
148

2/40 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS General Data
Sirius12

Mounting accessories

■ Overview
Solder pin connections Terminals for "Combination Motor Controller Type E" to UL 508
Solder pin connections are The 3RV10 circuit-breaker for The terminal block 3RT19 46- 3RV19 28-1H
available for the main contacts motor protection is approved 4GA07 must be used for size

NSB01379a
and for the transverse auxiliary according to UL 508 as "Combi- S3. The standard box terminal is
switch of S00 circuit-breakers. nation Motor Controller Type E". to be replaced by this terminal
block.
The prepared connecting parts As of 16. 07. 2001, UL 508
are clamped into the upper demands at line-side of the According to CSA, these termi-
and lower screw terminals of device used for this purpose an nal blocks can be omitted when
the circuit-breakers, allowing increased clearance and cree- the device is used as "Combina-
the latter to be soldered to a page distance (1" or 2"). tion Motor Controller Type E".
printed-circuit board.
Here, the terminal block 3RV19
28-1H must be used for size S0.
3RV19 18-5 The block is simply screwed to 3RT19 46-4GA07
the basic unit.

NSB01380a
Basic units of size S2 are
already compliant with new
clearance and creepage
distance requirements.
NSB01077

■ Dimension drawings
3RV19 18-5. solder pin connection
3RV19 18-5A
3RV19 18-5B
13,4 13,1
12
45 5 59 5

2
9

8,4

14,4 14,4
103

97,4

8,4
NSB00041

49
14,4 14,4

Terminals for "Combination Motor Controller Type E" to UL 508


3RV19 28-1H 3RT19 46-4GA07
45 74 70
10
27
72

84
121

168

NSB 01228

NSB 01229

Siemens NS K · 2002 2/41


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Enclosures and front plates

■ Overview
Enclosures
For installing individual circuit- Corresponding premoulded ca- With S00 circuit-breakers, the The handle can be unlatched
breakers of the sizes S00 ble entries are also available at switch rocker is operated via again either by turning it or by
(In max. = 12 A), S0 (In max. = the rear side. There is a knock- the actuator diaphragm of the using a special key.
25 A) and S2 (In max. = 50 A), out for indicator lights, which enclosure. A locking device, ca-
moulded-plastic enclosures for are available as accessories, on pable of holding up to three The circuit-breaker can subse-
wall or flush mounting are top of the enclosure. padlocks, can be fitted onto the quently be switched on again.
available in various dimensi- actuator diaphragm. These The moulded-plastic enclosu-
ons. The enclosures for wall- The narrow enclosure can padlocks prevent the circuit-
accomodate a circuit-breaker res of S0 and S2 circuit-brea-
mounting are designed for breaker from closing during kers with a rotary operating
degree of protection IP 55. without accessories, with trans- maintenance work, for example.
verse and lateral auxiliary mechanism are also fitted with
The flush mounting enclosures a rotary operating mechanism.
also conform with degree of switch, while wide enclosures A mushroom-shaped EMER-
protection IP 55 at the front (the and enclosures for S2 circuit- GENCY STOP handle can be fit- The enclosures are available
flush-mounted section com- breakers also provide space for ted in place of the locking with black rotary operating
plies with IP 20). a laterally mounted auxiliary device. If it is actuated abruptly, mechanisms or with EMER-
release. The installation of a cir- the circuit-breaker opens and GENCY STOP rotary operating
All enclosures are equipped cuit-breaker with signalling the mushroom-shaped handle mechanisms with a red/yellow
with N and PE terminals. switch is not intended. latches. handle.
Respectively at the top and bot-
tom, the device is equipped All rotary operating mecha-
with 2 knock-out cable entries nisms can be locked in the
for cable glands. OFF position with up to three
padlocks.
Enclosure for wall mounting Enclosure for flush mounting

Cubicle wall
NSB01080

NSB01081

Gasket

Front plates
Circuit-breakers are frequently diaphragm for size S00 circuit The front plates for size S00 are A retaining frame for size S0
required to be actuated in any breakers, or rotary operating equipped with a retaining circuit-breakers is available for
enclosure. Front plates equip- mechanism for S0 to S3 circuit frame, into which the circuit- front plate sizes S0 to S3.
ped with an actuating breakers are available for this breakers can be snapped.
purpose.
Front plate for size S00 Accessories for enclosures and front plates

3RV19 13-7D 3RV19 13-7F


NSB 01082a

3RV19 13-6B 3RV19 13-7E


NSB01083

2/42 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS General Data
Sirius12

Enclosures and front plates

■ Dimension drawings
3RV19 . 3-1. . . . Moulded-plastic enclosure for wall mounting
for circuit-breakers of size S00
3RV19 13-1. . . . a) 3RV19 13-1CA00 85 mm
3RV19 13-1DA00 105 mm.
45 19 b) With 3RV19 13-7D: 146.5 mm
55 105 With 3RV19 13-7E: 166.5 mm,
3)
11 13 c) Dimensions refer to mounting plane.
4) 7) c) With 3RV19 13-7D: 64 mm
NSB 00035c

With 3RV19 13-7E: 84 mm.


d) Dimension refers to mounting plane
4,5

6)
5) 3) M25 knock-out.
4) M20 knock-out
145 - 148

for rear cable entry.


5) With safety lock.
6) Max. shackle diameter of the
8) padlock is 8 mm.
77,5

7) Indicator light 3RV19 03-5.


8) 3RV19 13-6B locking device
9) 9) 3RV19 13-7. EMERGENCY STOP mushroom
button
b) 99 b)
b) 100,5 d) 190
a) 88 b) 143

for circuit-breakers of size S0 for circuit-breakers of size S2


3RV19 23-1. . . . 3RV19 33-1. . . .
45 19 32 29 25

1) 1) 2)
4)
2)
4)

7
4,5

3)
145 - 148

3)
155

235
250
NSB 00036c

18
a) 126
NSB 00037c

18
150 181
a) 3RV19 23-1CA00 85 mm
3RV19 23-1DA00 105 mm. 1) Knock-outs for M32 (left) and M40 (right).
1) M25 knock-out. 2) M32 knock-outs for rear-side cable entry.
2 M20 knock-out for rear cable entry. 3) Opening for padlock with shackle diameter max. 8 mm.
3) Opening for padlock with shackle diameter max. 8 mm. 4) Indicator light 3RV19 03-5.
4) Indicator light 3RV19 03-5.

Siemens NS K · 2002 2/43


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Enclosures and front plates

■ Dimension drawings
3RV19 23-1. . . . Cast aluminum enclosure for wall mounting
for circuit-breaker size S0
3RV19 23-1DA01
3RV19 23-1GA01

2) 2) 1) 1) 3RV19 03-5. Indicator light


2) M25 knockouts for screwed cable glands

I
ON
160
170

O
OFF
O

105 116
135

2)

M 25
52

NSB 01088a

M 25

Moulded-plastic enclosure for flush mounting 3RV19. 3-2 . . . .


for circuit-breaker size S0
for circuit-breaker size S00 3RV19 23-2DA00
3RV19 13-2DA00 3RV19 23-2GA00
3) 2) max. 7 1) 3) 2) max. 6 1)
R

R
3

3
157
175

157
175
155

155
35

35
NSB 00038a

NSB 00040a
87,5

87,5

105 95 12 87 105 95 12 87
1) 3RV19 03-5. Indicator light
2) M25 knock-out
3) M20 knock-out

Moulded-plastic front plate 3RV19 13-4C Moulded-plastic front plate 3RV19 23-4.
for circuit-breaker size S00 for circuit-breaker sizes S0, S2, S3
3RV19 13-4C 3RV19 23-4B
40 3RV19 23-4E
12 3RV19 23-4G (only for size S0)
NSB 00039a 1) ø7 4,5
12 18 40
NSB 00042a 1) ø 3,5 7,4
53
53
107

95
35

53

53
36
36

39

107
45

92
35

37,5
36

36
45

85 56,5 10 62
70
85 56,5 10 62
1) 3RV19 03-5. Indicator light 70

2/44 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS for Distance Protection
Sirius12

3RV16 voltage transformer circuit-breakers


up to 3 A

■ Notes:
Conversion of voltage transformer circuit-breakers 3VU13 to 3RV1
The current version of 3VU13 Available replacement types will
voltage transformer circuit-brea- be the voltage transformer cir- Previous type Replacement type
kers will not be available any- cuit-breakers 3RV1. 3VU13 11-6HR00 ➔ 3RV16 11-1CG14
more in the near future. 3VU13 21-6HR00 ➔ 3RV16 11-1CG14 + 3RV19 01-1A
3VU13 11-6JR00 ➔ 3RV16 11-1DG14

■ Selection and ordering data


with auxiliary switch
Rated 1 aux. sw. Short-circuit DT Screw connection Weight
current Thermal Instantaneous integrated breaking approx.
overload overcurent in the switch, capacity
release release transverse at
AC 110 V
In I> Icu DT Order No. Price
A A A kA PG 101 1 unit kg
Size S00
1.4 1.4 6 1 CO 2 B 3RV16 11-1AG14 0.21
2.5 2.5 10.5 1 CO 2 B 3RV16 11-1CG14
3 3 20 1 CO 2 B 3RV16 11-1DG14

Nsb0625g

Laterally mountable auxiliary switches for other signalling purposes


3RV19 01-1A lateral auxiliary switch1) 1 NO + 1 NC } 3RV19 01-1A 0.03

nsb0015g

General data
3RV16 voltage transformer circuit-breakers
up to 3 A

■ Technical data
General technical data
Type 3RV16 11-1AG14 3RV16 11-1CG14 3RV16 11-1DG14
Rated current A 1.6 3 3
Permissible ambient temperature
Storage/transport °C -50 ... +80
Operation °C -20 ... +60 (up to 70 °C possible with current reduction)
Rated operational voltage Ue V 110
Rated frequency Hz 16 2/3 ... 60
Rated insulation voltage Ui V 230
Short-circuit breaking capacity at AC 110 V, short-circuit proof up to kA 2
Current setting of the thermal overload release A 1.4 2.5 3
Operating value of the instantaneous surge trip A 6 ± 20 % 10.5 ± 20 % 20 ± 20 %
Tripping time of the instantaneous surge trip ms approx. 6 ms at 12 approx. 6 ms at 20 approx. 6 ms at 40
Internal resistance
in cold state Ohm > 0.25 ± 6.5 %
in heated state Ohm > 0.30 ± 6.5 %
Shock resistance acc. to IEC 68, Part 2-27 g 15
Degree of protection to IEC 60 529 IP 20
Shock protection to DIN VDE 0106 Part 100 safe against finger touch
Service life
mechanical operating 10 000
electrical cycles 10 000
Permissible mounting position any

1) For further lateral auxiliary switches see Page 2/8.

Siemens NS K · 2002 2/45


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
3RV16 voltage transformer circuit-breakers
up to 3 A

■ Technical data
Conductor cross-sections, main circuit, 1 or 2 conductors
Type 3RV16 11-1AG14 3RV16 11-1CG14 3RV16 11-1DG14
Terminal type Screw connection
Terminal screw Pozidriv size 2
solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5); (max. 4)
finely stranded with end sleeve mm2 2 × (0.5 ... 1,5); 2 × (0.75 ... 2.5)
stranded mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5); (max. 4)
Auxiliary switch for blocking the distance protection
with defined time-dependent assignment for blocking distance protection 1 changeover contact, solid-state compatible
(usable as 1 NO or 1 NC)

Rated operational voltage Ue Alternating voltage AC V 3 ... 60


Rated operational current Ie/AC-14 mA 1 ... 300

Rated operational voltage Ue Direct voltage L/R 200 ms DC V 3 ... 60


Rated operational current Ie/DC-13 mA 1 ... 300

Short-circuit protection for auxiliary circuit


– Fusible link, gL/gG A 10
– Miniature circuit breaker, C characteristic A 6 (prospective short-circuit current < 0,4 kA)
Auxiliary switch for other signalling functions
For technical data see Page 2/21.

■ Application ■ Design
The voltage transformer circuit- The voltage transformer circuit- To prevent this fault response, The laterally mountable auxilia-
breaker protects the secon- breaker widely corresponds special auxiliary contacts with a ry switches of the SIRIUS range
dary side of voltage transfor- with the circuit-breaker 3RV1, time-dependent assignment to can be used for signalling
mers used to connect protec- SIRIUS, size S00. Two special the circuit-breaker’s main con- functions. They cannot be used
tive devices with voltage-de- characteristics are taken into tacts (see Technical data) must for blocking the distance pro-
pendent starting. The switch is account for safe prevention of be provided. The distance pro- tection device.
used for distance protection faulty triggering of the distance tection is blocked with the help
with low-impedance starting. protection device. of these auxiliary contacts, and Impedance across the main
thus prevents faulty triggering. contacts
Special auxiliary contacts relia-
bly prevent low-impedance Auxiliary switch for blocking
An auxiliary switch for blocking There is only minor current flow
starting from triggering di- the distance protection the distance protection device across the main contacts of
stance protection if only one er- The main contacts of the circuit is available, equipped with 1 the voltage transformer circuit-
ror has occurred in the conver- breaker open if the voltage changeover contact fitted per- breaker. To ensure reliable
ter line. transformer circuit-breaker is manently in the voltage trans- functioning of the distance
tripped or switched off. The di- former circuit-breaker. This protection, main contact resi-
The voltage transformer circuit- changeover contact can be
breaker can also be used to stance protection would falsely stance must be minimal and
interpret low impedance as an used as 1 NO (11-14) or 1 NC nearly constant throughout the
safely disconnect the distance (11-12) contact. Due to the high
error, which results in imme- service life of the circuit-brea-
protection device from the diate power cut-out within only contact stability of these auxi- ker.
voltage transformer. In this a few milliseconds. liary contacts at the lowest pos-
case the special auxiliary con- sible rated operational currents This is realized with suitable
tacts also prevent erratic trigge- Ie/AC-15 ≥ 0.5 mA at 230 V, it is contacts and contact materials
ring of the distance protection. also suitable for modern solid- for the 3RV16 voltage transfor-
state distance protection mer circuit-breaker.
Additional fuses are not requi- devices.
red. A "Fuse Failure Monitor"
(FFM) is also not required. Timing diagram of auxiliary switches for blocking distance protection

Mounting ON OFF Tripping due to short-circuit

The circuit breakers are snap- Main contacts 0 1 1 0 1 0


mounted on a 35-mm mounting
rail to DIN EN 50 022. Push-in 1 NO 11-14 +10 -10 5
lugs are available for screw 1 NC 11-12
NSB01098a

connection of the circuit-brea- +10 -10 5


kers (see Accessories for (1 changeover contact)
SIRIUS circuit-breakers 3RV1). 0 t (ms) 0 t (ms) 0 t (ms)

2/46 Siemens NS K · 2002


3RV1 Circuit-Breakers
SIRIUS General Data
Sirius12

3RV16 voltage transformer circuit-breakers


up to 3 A

■ Characteristics ■ Circuit diagrams


The specified tripping charac- The characteristic curves below Internal connections
teristics of the thermal overload are schematic representations.
release (a) correspond to the Precise characteristic curves Distance protection
mean value of the leakage are available from "Technical and starting
bandwidth in cold state; at ope- Assistance" (E-mail: nst.techni- starting
1 3 5
rating temperature these times cal-assistance@siemens.de). 11
are reduced to approx. 25 % of
the specified values. 14 12

NSB01105b
I I I

v
2 4 6

of the voltage transformer unit


NSB 01352b

1000 Typical circuit diagram


s a)
100
+
12 14
10
1 2 3

b) 11
0,1

Distance protection
0,01

BI
(binary Protective switch of
1 2 4 6 10 20 40 60 A100 input) voltage transformer is
open (active without

NSB01106a
voltage)

Note:
When using the NC contact to connect the voltage transformer circuit-brea-
ker, the binary input of the distance protection device (Siemens 7 SA xxx)
should be set to "active without voltage". This type of connection is used for
$ 1.4 A/6 A additional monitoring of correct wiring.
% 2.5 A/10,5 A
& 3 A/20 A
a) Thermal overload release
b) Instantaneous electromagnetic surge trip

■ Dimension drawings
3RV16 11-1 . G14 voltage transformer circuit-breaker

2) 1) 11) 5) 3) 4)
1)Lateral auxiliary switch
25
3)Auxiliary release
4)Transverse auxiliary switch
5)Push-in lugs for screw mounting
5 6)Only for low-voltage release
12

with leading auxiliary switch


45

7) Drilling template
8) 35 mm standard mounting rail acc. to EN 50 022
105
45
90

11) Lockable in 0 position


7)
with shackle diameter 5 mm
3,5

8)

9 45 18
NSB 00026c

18 5 62
70
6) 76

Siemens NS K · 2002 2/47


3RV1 Circuit-Breakers
General Data SIRIUS

Sirius12
Notes

2/48 Siemens NS K · 2002