8620 Configuration
Module
Module Options
Description
1
2
3
4
LED Indicators
Miscellaneous Options
Displayed Pages
Event Log
Display Options
about:blank 17/06/2019
8620 Configuration Page 2 of 41
Logging Options
Data Logging
Configuration
Data Logging
about:blank 17/06/2019
8620 Configuration Page 3 of 41
13 -1 1 second
14 -1 1 second
15 -1 1 second
16 -1 1 second
17 -1 1 second
18 -1 1 second
19 -1 1 second
20 -1 1 second
Options
Data Log Options
about:blank 17/06/2019
8620 Configuration Page 4 of 41
Application
ECU (ECM) Options
Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s
about:blank 17/06/2019
8620 Configuration Page 5 of 41
Inputs
Oil Pressure
Input Type
Alarm Enabled
Trip 1.03Bar, 14.94 PSI, 103 kPa
Pre-Alarm Enabled
Trip 1.24Bar, 17.98 PSI, 124 kPa
Return 1.38Bar, 20.01 PSI, 138 kPa
Coolant Temperature
Coolant Temperature Alarm
Sensor Usage
Input Type
Enable No
Alarm
Trip 95 °C, 203 °F
Electrical Trip No
Trip 92 °C, 198 °F 198 °F
Pre-Alarm Yes
Trip 90 °C, 194 °F
Return 88 °C, 190 °F
Pre-Alarm No
about:blank 17/06/2019
8620 Configuration Page 6 of 41
Enable No
On 50 °C, 122 °F
Off 55 °C, 131 °F
Enable No
Off 70 °C, 158 °F
On 75 °C, 167 °F
Fan Control
Fuel Level
Fuel Control and Monitoring
Sensor Usage
Input Type
Not used
Enable No
On 25 %
Off 75 %
Fuel Monitoring
Logging Interval 8h
Dial Out On Logging No
SMS Enabled Yes
SMS interval every 1 logs
Stable Timer 0.5s
Change Indicating Filling 1%
Change Indicating Stable 1%
about:blank 17/06/2019
8620 Configuration Page 7 of 41
Fuel Alarms
Level Alarms
Enable No
Action Warning Always Latched
Running Rate 10 % / Hr
Stopped Rate 10 % / Hr
Flexible Sensor
Sensor Description
Digital Inputs
Digital Inputs A - C
Digital Input A
about:blank 17/06/2019
8620 Configuration Page 8 of 41
Arming
LCD Display
Activation Delay 0s
Digital Input B
Digital Input C
about:blank 17/06/2019
8620 Configuration Page 9 of 41
Digital Inputs D - F
Digital Input D
Digital Input E
Digital Input F
Digital Inputs G - I
Digital Input G
Digital Input H
Digital Input I
about:blank 17/06/2019
8620 Configuration Page 10 of 41
Digital Inputs J - K
Digital Input J
Digital Input K
about:blank 17/06/2019
8620 Configuration Page 11 of 41
Outputs
Digital Outputs
Relay Outputs (Supplied From Emergency Stop Input)
Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise
Source Polarity
Output C (N/C) Close Mains Output Pulse De-Energise
Output D Close Gen Output Pulse Energise
Source Polarity
Output E Open Gen Output Pulse De-Energise
Output F Open Mains Output Pulse Energise
Output G Common Electrical Trip Energise
Output H Common Alarm Energise
Output I Fail To Synchronise Energise
Output J Out Of Sync Mains Energise
Virtual LEDs
LED Configuration
Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
LED 20 Not Used Lit
about:blank 17/06/2019
8620 Configuration Page 12 of 41
Timers
Start Timers
Start Delay
Start Timers
Load/Stopping Timers
Load Timers
Stopping Timers
Module Timers
Interface Timers
Page 5m
Scroll 2s
about:blank 17/06/2019
8620 Configuration Page 13 of 41
Generator
Generator Options
Generator Options
Enable Yes
Phase Rotation L1-L2-L3
Breaker Control
Generator Voltage
Under Voltage Alarms
Alarm Yes
Action Shutdown
Trip 318V PhPh 79.7 %
Pre-Alarm Yes
Trip 339V PhPh 84.8 %
Loading Voltage
Nominal Voltage
400V PhPh
Pre-Alarm Yes
Return 439V PhPh 110.0 %
Trip 458V PhPh 114.7 %
Alarm
Trip 479V PhPh 119.9 %
about:blank 17/06/2019
8620 Configuration Page 14 of 41
Generator Frequency
Under Frequency Alarms
Alarm Yes
Action Shutdown
Trip 40.0 Hz 80.0 %
Pre-Alarm Yes
Trip 42.0 Hz 84.0 %
Loading Frequency
Nominal Frequency
50.0 Hz 100.0 %
Pre-Alarm Yes
Return 54.0 Hz 108.0 %
Trip 55.0 Hz 110.0 %
Alarm Yes
Trip 57.0 Hz 114.0 %
Generator Current
Generator Current
Generator
Current
about:blank 17/06/2019
8620 Configuration Page 15 of 41
Enable No
Action Shutdown
Trip Level 20 %
Delay 0s
Short Circuit
Enabled Yes
Action Electrical Trip
Trip 200 % 2320.0 A
Time Multiplier 0.01
Earth Fault
Enable Yes
Action Shutdown
Trip Level 10 % 116.0 A
Time Multiplier 0.5
about:blank 17/06/2019
8620 Configuration Page 16 of 41
Generator Power
Overload Protection
Overload Protection
Pre-Alarm Yes
Trip 90 % 576 kW
Return 80 % 512 kW
Delay 5s
Alarm Yes
Action Shutdown
Trip 100 % 640 kW
Delay 5s
Load Control
Dummy Load Control
Enable No
Outputs in Scheme 1
Trip 20 % 128 kW
Trip Delay 5s
Return 50 % 320 kW
Return Delay 5s
Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 512 kW
Trip Delay 5s
Return 70 % 448 kW
Return Delay 5s
Transfer Time / Load Delay 1.0s
Reverse Power
Reverse Power Alarm
Enabled Yes
Action Electrical Trip
Trip 51 kW
Delay 2.0s
Low Load
Low Load Alarm
about:blank 17/06/2019
8620 Configuration Page 17 of 41
Enabled No
Description Low Load
Trip 30 %
Delay 1m
Generator Rating
Generator Rating
Synchronising
Synchronising
Sync
Sync Options
Options
Governor
AVR
Check Sync
Check Sync
Load Control
Load Options
about:blank 17/06/2019
8620 Configuration Page 18 of 41
Ramp
Insufficient Capacity
Action Indication
Delay 1s
AVR
Loss Of Excitation
Arming Always
Pre-Alarm Yes
Trip 25.0 % %
Return 20.0 % %
Alarm Yes
Action Shutdown
Trip 35.0 % %
Delay 1s
Action None
Delay 0s
Mains
Mains
Mains
Mains Options
Mains Options
Enable Yes
Phase Rotation L1-L2-L3
Breaker Control
about:blank 17/06/2019
8620 Configuration Page 19 of 41
Phase Offset
Phase Offset 0
Enable Yes
Trip 318V PhPh
Return 358V PhPh
Nominal Voltage
Enable Yes
Return 438V PhPh
Trip 478V PhPh
Enable Yes
Trip 45.0 Hz
Return 48.0 Hz
Enable Yes
Return 52.0 Hz
Trip 55.0 Hz
Mains Current
Mains Current Options
CT Enabled Yes
CT Primary (L1) 1200 A
CT Secondary 5 Amp
Full Load Rating 630 kW
Full KVAr Rating 473kVAr
Export Power
Enable No
about:blank 17/06/2019
8620 Configuration Page 20 of 41
Action None
Trip 0 kW
Delay 0s
about:blank 17/06/2019
8620 Configuration Page 21 of 41
Mains Decoupling
Options
R.O.C.O.F. Alarm
Enable No
Trip 0.13 Hz/s
Enable No
Trip 6.0 °
Voltage Alarms
Frequency Alarms
Under Frequency No
Trip 47.0 Hz
Delay 0s
Over Frequency No
Trip 50.5 Hz
Delay 0s
about:blank 17/06/2019
8620 Configuration Page 22 of 41
Engine
Engine Options
ECU (ECM) Options
Sensing Options
Startup Options
Overspeed Options
Overspeed Overshoot 0 %
Overshoot Delay 0s
Droop
Enable No
4.0 %
CAN Options
Engine Hours
Speed Switch
ECU Wakeup
Enable No
Periodic Wakeup Time 1h
about:blank 17/06/2019
8620 Configuration Page 23 of 41
about:blank 17/06/2019
8620 Configuration Page 24 of 41
CAN Alarms
CAN Data Fail
CAN ECU Data Fail
Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s
DM1 Signals
ECU Amber
Action Warning
Arming Always
Activation Delay 0s
ECU Red
Action Shutdown
Arming From Safety On
Activation Delay 0s
ECU Malfunction
Action Warning
Arming Always
Activation Delay 0s
ECU Protect
Action Warning
Arming From Safety On
Activation Delay 0s
Advanced
Water In Fuel
Action Warning
Arming Always
Activation Delay 0s
DPTC Filter
Enabled Yes
Action Warning
Arming From Safety On
HEST Active
about:blank 17/06/2019
8620 Configuration Page 25 of 41
Enabled Yes
Action Warning
Arming From Safety On
Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s
Cranking
Options
Crank Disconnect
Manual Crank
about:blank 17/06/2019
8620 Configuration Page 26 of 41
Speed Settings
Under Speed
Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM
Over Speed
Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Alarm
Trip 1710 RPM
Plant Battery
Voltage Alarms
about:blank 17/06/2019
8620 Configuration Page 27 of 41
Inlet Temperature
Inlet Temperature Alarms
Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F
about:blank 17/06/2019
8620 Configuration Page 28 of 41
Communications
Communications Options
Module Identification
Site Identity
Genset Identity
RS232 Port
Basic
Serial Port Configuration
Slave ID 10
Baud Rate 19200
Port Usage No Modem
Modem Settings
Alarm numbers
GSM Modem No
SMS Message centre number
SMS Recipient numbers
Advanced
Initialisation Strings
Connection Settings
SMS Control
SMS Module Control
Require PIN No
PIN prefix : 0 0 0 0
about:blank 17/06/2019
8620 Configuration Page 29 of 41
Enabled commands
Start off load (code 1) No
Start on load (code 2) No
Cancel (code 3) No
Stop mode (code 4) No
Auto mode (code 5) No
Start in Island Mode (code 6) No
RS485 Port
Basic
Slave ID 10
Baud Rate 19200
Advanced
Ethernet Port
Dynamic Host Configuration Protocol
Names
Domain Name
Host Name
Vendor Name
IP Addresses
IP address
0 . 0 . 0 . 0
Subnet Mask
255 . 255 . 255 . 0
Gateway Address
0 . 0 . 0 . 0
DNS Address
0 . 0 . 0 . 0
about:blank 17/06/2019
8620 Configuration Page 30 of 41
Modbus
about:blank 17/06/2019
8620 Configuration Page 31 of 41
Scheduler
Exercise Scheduler
Enabled No
Run Mode Off Load
Schedule Period Weekly
about:blank 17/06/2019
8620 Configuration Page 32 of 41
Maintenance Alarm
Maintenance Alarm 1
Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 2
Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 3
Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
about:blank 17/06/2019
8620 Configuration Page 33 of 41
Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options
Advanced
Advanced
Advanced
Advanced Options
Protections
Disable No
Protections Are Disabled Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled
Out Of Sync
Other Timers
Synchronisation Delay 3s
Mains Decoupling Supervision 1.0s
Interlock Override Off 0.1s
Test mode
Ramp
PLC
PLC Logic
PLC Functions 1-4
Function 1
Function 2
about:blank 17/06/2019
8620 Configuration Page 34 of 41
Function 3
Function 4
Function 6
Function 7
about:blank 17/06/2019
8620 Configuration Page 35 of 41
LCD Display
Activation Delay 0s
Function 8
Function 10
Function 11
Function 12
about:blank 17/06/2019
8620 Configuration Page 36 of 41
Function 13
Function 14
Function 15
Function 16
Function 18
about:blank 17/06/2019
8620 Configuration Page 37 of 41
Action Warning
Arming Always
LCD Display
Activation Delay 0s
Function 19
Function 20
Module Display
Displayed Pages
Configurable Gencomm
Pages
Page 166
about:blank 17/06/2019
8620 Configuration Page 38 of 41
about:blank 17/06/2019
8620 Configuration Page 39 of 41
about:blank 17/06/2019
8620 Configuration Page 40 of 41
about:blank 17/06/2019
8620 Configuration Page 41 of 41