Ifm efector AC1144 addressing/diagnostic handheld for AS-I Systems

Instructions to Address AS-I nodes and Force Outputs of AS-I Nodes* :


*(The AC1144 has many capabilities not listed below, see included Operating Instructions for more information.)

To ADDRESS AS-I nodes:


1. To turn the AC1144 on, push the Read/On button
2. AC1144 is now in “Address Mode” – ADDR
3. Address is displayed on right side (example: 07)
4. To change address, scroll up or down using + and – keys
5. To assign the new address, push the Write/Set button. The address number is displayed on the right side
6. To read the new address, push the Read/On button. The new address number is displayed on the right side

To FORCE OUTPUTS of AS-I nodes:


1. Use a Micro DC Male to Female patch cable (ifm efector P/N: E70117 or other) and screw the male plug onto the main
power/communication plug of the AS-I node.
2. Plug the female end of the E70117 into the top port of the AC1144
3. Turn AC1144 on, push the Read/On button
4. Push the Mode button eight times until DATA is displayed in the upper middle of the screen
5. Push the + button once, the right side of the display reads 01
6. Push the WRITE/SET button to force the output

Example: To force the solenoid output of the AC2306 AS-I valve sensor. Repeat the above instructions.

Notes:
1. Handheld device turns off after 1 minute of non-use
2. Use the included AC power cable to recharge the AC1144

Error Messages:
Error Code Meaning Description
F1 Overloaded handheld AC1144 not able to provide adequate power because of I/O device
current draw
F2 I/O device not found No I/O device found at the active address
F3 Error during programming Value was not stored in I/O device EEPROM
F4 Target address occupied Duplicate address of I/O device
F5 Address 0 occupied Two I/O devices are addressed 0
F6 Standard I/O device instead of Activated I/O device is not version 2.1 compatible
extended I/O device found
F7 Extended I/O device instead of Standard I/O device was replaced by AS-I version 2.1 I/O device
standard I/O device found
Ifm Efector Technical Help: 800-441-8246
Using the
AC1144

A new node
comes
An from1-
address the
31 must be
READING
ADDRESS
Connect the
AC1144
Press to the
MODE
until ADDR
Press READ.is
The address is
displayed.
WRITING
ADDRESS
Connect the
AC1144
Press to the
MODE
until ADDR
Press READ.is
Press + or –
until
Pressthe
WRITE.
The new
address is

FORCING
OUTPUTS
Connect the
AC1144
Press to the
READ.
Press MODE
until the word
Press WRITE
to force the
FORCING
OUTPUTS
Disconnect the
AS-I master
Keep the AS-I
power supply
Press READ.

The address
that is active
Repeatedly
press
Press the
MODE
until the word
Press WRITE
to force the
Using the AC1144 AS-I addressing tool page 2

READING
INPUTS
Connect the
AC1144
Press to the
READ.
Press MODE
until the
Press word
READ.
The
hexadecimal
READING
INPUTS
Disconnect the
AS-I master
Keep the AS-I
power supply
Press READ.

The address
that is active
Repeatedly
press the
Press MODE
until the
Press READ.word
The
hexadecimal
INPUT /
OUTPUT
DISPLAYED OUTPUT 4 OUTPUT 3 INPUT 2 INPUT 1
0 0 0 0 0
1 0 0 0 1
2 0 0 1 0
3 0 0 1 1
4 0 1 0 0
5 0 1 0 1
6 0 1 1 0
7 0 1 1 1
8 1 0 0 0
9 1 0 0 1
A 1 0 1 0
B 1 0 1 1
C 1 1 0 0
D 1 1 0 1
E 1 1 1 0
F 1 1 1 1