Start Up Sequence:
2. Press HS-108 “Start Pretreatment” button (soft). Send output signal to open XV-3105. XV-3105
enabled when the following are cleared:
3. When the difference between PIT-3102 and PIT-3103 is less than 50 psi, send output signal to
open SDV-3104. Once SDV-3104 opens, it only closes with a Pretreatment Shutdown.
4. Two (2) minutes after signaling SDV-3104 to open, send signals to close XV-3105 and to indicate
Pretreatment Running (on HMI).
6. Press HS-110 “Start Membrane” button (soft). Send output signal to open XV-4006. XV-4006
enabled when the following are cleared:
7. When PIT-4001 reaches 100 psig, send output signal to open SDV-4005. Once SDV-4005
opens, it only closes with a Pretreatment or Membrane Shutdown and when PIT-4001
reaches 30 psig.
8. When the difference between PIT-4002 and PIT-4001 is less than 50 psi, send output signals to
open SDV-4001 and SDV-4003. Once SDV-4001 and SDV-4003 are signaled to open, they
only close with a Pretreatment or Membrane Shutdown.
8. Two (2) minutes after signaling SDV-4001 to open, send signals to close XV-4006 and to indicate
Membrane MB01 Running (on HMI).
1
Shutdown Sequence (upon any Pretreatment Shutdown):
2. At the same time, send output signals to close XV-3105 and XV-4006.
4. When PIT-4001 reaches 30 psig, send output signals to close SDV-4005 and XV-4004.
4. When PIT-4001 reaches 30 psig, send output signals to close SDV-4005 and XV-4004.
2
Control Loops:
TIC-3301
Type: PID
Input (Measured Variable): TIT-3301 – 4/20mA – 0/200 F
Output: TY-3301 – 4/20 mA
Set Point: 140 F
Action: Increasing Input – Increasing Output
PIC-3102
Type: PID
Input (Measured Variable): PIT-3102 – 4/20mA – 0/1250 psig
Output: PY-3102 – 4/20 mA
Set Point: 895 psig
Action: Increasing Input – Increasing Output
PIC-4002
Type: PID
Input (Measured Variable): PIT-4002 – 4/20mA – 0/1250 psig
Output: PY-4002 – 4/20 mA
Set Point: 880 psig
Action: Increasing Input – Increasing Output
PIC-5001
Type: PID
Input (Measured Variable): PIT-5001 – 4/20mA – 0/1250 psig
Output: PY-5001 – 4/20 mA
Set Point: 870 psig
Action: Increasing Input – Increasing Output
PIC-5002
Type: PID
Input (Measured Variable): PIT-5002 – 4/20mA – 0/1250 psig
Output: PY-5002 – 4/20 mA
Set Point: 866 psig
Action: Increasing Input – Increasing Output
3
Alarms: