SAUDI ARAMCO INSPECTION CHECKLIST
Through-The-Wall and Window-Mounted Air Conditioners
SAIC-K-4032 30-Apr-13 HVAC
(Room Air Conditioners) Installation
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Around each Air Conditioner Unit and its attachment to the window or
SAES-K-001
A1 wall, shall be properly sealed as per manufacturer's Installation
Para 5.2.1
Manual
Units shall be adequately supported in accordance with Issued for Air
system equipment and duct work shall be installed according to the SAES-K-001
A2
Construction Drawings and Specifications, and Manufacturer's Para 5.2.1
Installation Manual.

Units shall be grounded in accordance with Issued for Construction SAES-K-001


A3
Drawings Para 5.2.1

Unit is mounted as shown (Inside flush mounting, outside flush


mounting, balance mounting, etc) and/or Specified in the Issued for SAES-K-001
A4
Construction Drawings and Specifications, and Manufacturer's Para 5.2.1
Installation Manual.

Window track, sash, and sill shall be in good condition for installing SAES-K-001
A5
the window mounted type units Para 5.2.1
Wall opening for through the wall units shall be in accordance with
SAES-K-001
A6 the manufacturer's requirements/recommendations and or IFC
Para 5.2.1
Drawings.

All HVAC Equipment shall be properly grounded in accordance with SAES-K-001


A7
NFPA 70, national Electrical Code. Para 5.1.8

Condensate drain from air cooling coils shall be collected and


drained to an approved location. Drain pans and coils shall be
SAES-K-001
A8 arranged to allow thorough drainage and access for cleaning. Where
Para 5.3.4.2 3.0
temperature can drop below freezing, heat tracing and insulation of
drains shall be installed. (UMC Section 1105 1106.10)
REMARKS:

REFERENCE DOCUMENTS:
SAES-K-001 -- Heating, Ventilating and Air Conditioning 05 July, 2009 Design and Installation of Heating, Ventilating and Air
Conditioning Systems 5 December 2012
UMC -- Uniform Mechanical Code 2009 Edition

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

Page 1 of 2
QC Supervisor Proponent and Others
Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 2

You might also like