Professional Documents
Culture Documents
1046(2)a CHB NON LOAD BEARING (Including Reinforcing Steel) sq.m. 28.77
1 2 3
1018(1) GLAZED FLOOR TILES sq.m. 165.60
1.20 4.50
9.00
4.50 1.20
W E
1003(1)a1 CEILING ON METAL FRAME sq.m. 125.60
1.20
D
1047(2)b STRUCTURAL STEEL FOR TRUSSES kgs. 537.38
S
4.00
C
10.40
1.20
D D D D
4.00
4.00
4.00
4.00
C C C C
10.40
10.40
10.40
10.40
4.00
4.00
4.00
4.00
B B B B
2.40
2.40
2.40
2.40
A A A A
1.20
1.20
ROOF FRAMING PLAN ROOF PLAN ROOF FRAMING PLAN REFLECTED CEILING PLAN (SECOND FLOOR)
SCALE 1:100mts SCALE 1:100mts SCALE 1:100mts SCALE 1:100mts
A A
1 1' 2 2' 3 1 2 3
9.00 9.00
4.50 4.50 4.50 4.50
W 1 W3 W2 W3 W 1
D D D C B A 1 1' 2 2' 3
D3
4.00
4.00
1.80
W2 W 1 W 1
1.80
D 1
C C
3.00
3.00
10.40
10.40
4.00
4.00
W2 W2 W 1 W 1
B B
W 1 W2 W 1 W2
B D2
B D2
2.40
2.40
A A FRONT ELEVATION
GROUND FLOOR PLAN SECOND FLOOR PLAN LEFT SIDE ELEVATION SCALE 1:100mts
SCALE 1:100mts
SCALE 1:100mts SCALE 1:100mts
0.30
0.30
0.50
1.20
1.20
2.40
2.40
2.10
2.10
2.10
2.10
1.60
0.90
0.90
SCHEDULE OF DOORS AND WINDOWS
D C B A SCALE 1:30 mts
ROD SUSPENSION HANGER WITH
ADJUSTMENT SPRING
1.80
3.00
1.175
0.30
REQUIRED DIMENSION
DEPTH OF CEILING TO
PREFORMED
WIRE CLIP
SECTION THRU "A" 0.40mm WALL
SCALE 1:100mts
ANGLE
3 2 1
25mm X 25mm WOOD SLAT
0.012 0.012 PROVIDE INSECT SCREEN
0.325 4.50mm THK. FIBER CEMENT
1.80
CEILING FURRING
FIBER CEMENT SECTION
CEILING BOARD
350mm MAX.
2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS SLAB SHALL BE CUT AS 1. UNLESS , OTHERWISE NOTED IN PLANS, CAMBER ALL BEAMS AND GIRDER AT
FOLLOWS. LEAST 6mm FOR EVERY 4.50m OF SPAN, EXCEPT CANTILEVERS FOR WHICH THE
7. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEEL,
MISCELLANEOUS IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGINEERS CAMBER SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER BUT
10
APPROVAL BEFORE FABRICATION. IN NO CASE LESS THAN 20mm FOR EVERY 3.0m OF FREE SPAN.
H
mi
L1 L2
n.
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, 2. TYPICAL BARS BENDING AND CUTTING DETAILS SHALL BE AS SHOWN IN FIG. B - 1
L1/3 L1/3 L2/3
EQUIPMENT'S AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, TOP BAR TOP BAR
ELECTRICAL AND MECHANICAL DRAWINGS.
LAP SPLICES ARE ALLOWED
9. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL ONLY IN THIS PORTION
JOINT REINF.CONF. REINF . PER SCHEDULE CONF. REINF. JOINT REINF.CONF. REINF.
STEEL MUST BE NOTED & APPROVED BY THE STRUCTURAL DESIGNER.
L1/6 BOTTOM BAR L1/5 L2/5 BOTTOM BAR JOINT HOOP SPACE @ "2Sh" WHEN THERE ARE
BEAMS HAVING WIDTH OF AT LEAST ONE-HALF THE L1 L2 L3
D
COLUMN WIDTH & DEPTHS NOT LESS THAN THREE L2/3 L2/3 L3/3 L3/3
QUARTERS OF THE DEEPEST BEAM THAT FRAME 2D 2D 2D 2D 2D
INTO FOUR SIDES OF THE COLUMN. ALL OTHER
CONDITIONS USE HOOP @ "Sh" CENTER
0.96
FOLLOW. 3. IF SLABS ARE REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED
Sh
D
BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN WEB BARS
2-12mm SIDE BARS BOTTOM BARS
FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN TOP BARS
FOR COL. BAR SPLICES SEE TABLE OF MIN. LAP
COLUMN TIES AS
ALL OTHERS, INCLUDING STRIPS SHALL NOT BE MORE THAN ONE AND A HALF ( 1 21 ) SLAB THICKNESS
SUSPENDED SLABS 4000 psi ( 27.6 mpa ) 20mm 100mm SPLICE LENGTH OF COLUMN REINFORCEMENT
4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION (SPACING OF TIES ALONG THIS REGION SHALL NOT
COLUMNS 4000 psi ( 27.6 MPA ) 20mm 100mm AND SHALL NOT BE LESS THAN 0.0025 x GROSS CROSS-SECTIONAL AREA ( Ag ) OF THE SLAB BE LESS THAN 100mm)
BEAMS, SLABS 4000 psi ( 27.6 MPA ) 20mm 100mm ( SEE SCHEDULE BELOW )
TABLE "A" TABLE "B"
TENSION BARS COMPRESSION BARS
SLAB ON FILL 3000 psi ( 27.6 MPA ) 20mm 100mm EMBEDMENT LENGTHS AND LAPPED EMBEDMENT LENGTHS AND LAPPED
Sh
SPLICES IN MILLIMETERS SPLICES IN MILLIMETERS
D
BAR SIZE fc' = 20.7MPa (3000psi) fc' = 20.7MPa (4000psi) BAR SIZE fc' = 20.7MPa (3000psi) fc' = 20.7MPa (4000psi)
2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS SCHEDULE OF MINIMUM SLAB REINFORCEMENT (DEFORMED) EMBEDMENT (DEFORMED) EMBEDMENT
LAPPED EMBEDMENT LAPPED LAPPED EMBEDMENT LAPPED
SUSPENDED SLABS ------------------------------------------------------------------ 20mm
THICKNESS MINIMUM TEMPERATURE BARS
NOTE:
10mm 300 300 300 300 10mm 225 300 200 300
SLAB ON GRADE ----------------------------------------------------------------------- 40mm ALL CONCRETE REINF. DETAIL SHOULD BE
WALLS ABOVE GRADE --------------------------------------------------------------- 25mm 100mm 10mm @ 250mm EACH WAY DONE IN ACCORDANCE WITH THE LATEST 12mm 300 300 300 300 12mm 275 300 250 300
BEAM STIRRUPS AND COLUMN TIES ----------------------------------------------- 40mm
CONF. REINF.
125mm 10mm @ 225mm EACH WAY EDITION OF ACI DETAILING MANUAL. 16mm 300 400 300 400 16mm 350 400 325 400
WHERE CONCRETE IS EXPOSED TO 20mm 20mm
400 550 350 500 450 500 475 500
D
EARTH BUT POURED AGAINST FORMS -------------------------------------------- 50mm 150mm 10mm @ 185mm EACH WAY
25mm 25mm
WHERE CONCRETE IS DEPOSITED 600 800 550 750 550 625 550 625
175mm 10mm @ 150mm EACH WAY 28mm 28mm
750 1000 650 850 625 675 625 675
DIRECTLY AGAINST THE EARTH ----------------------------------------------------- 75mm
3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION. 200mm 10mm @ 140mm EACH WAY 32mm 950 1300 850 1100 32mm 700 775 700 775
RE-HANDLING OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR
WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM
HOPPER TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED 3. IF THE BEAM REINFORCING BARS END IN A WALL THE CLEAR DISTANCE FROM THE BAR TO THE
SIX ( 6 ) METERS IN AGGREGATE LENGTH. FARTHER FACE OF THE WALL NOT BE LESS THAN 25mm. EMBEDMENT LENGTH SHALL BE AS
4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS SHOWN IN A TABLE "A" FOR TENSION BARS AND TABLE "B" FOR COMPRESSION BARS UNLESS
LAP SPACE LENGTH: SPECIFIED IN PLAN. TOP BAR SHALL NOT BE SPLICED WITHIN THE COLUMN. AT LEAST TWO
UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS
5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED WITH AT ANY LEVEL NO MORE THAN ALTERNATE BARS SHOULD BE SPLICED MIN. STIRRUPS SHALL BE PROVIDED AT ALL SPLICES.
WHERE VIBRATIONS IS EXTREMELY DIFFICULT TO ACCOMPLISH.
10mm AT 250mm O.C EACH WAY TO CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME DISTANCE BETWEEN TWO ADJACENT BARS SPLICES SHALL BE 600mm.
5. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED & SHALL NOT BE LESS THAN 3.65 METER APART
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. 4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25mm BAR SEPARATORS
SPACED AT 1.0m ON CENTER IN NO CASE SHALL THERE BE LESS THAN TWO
6. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN ( 7 ) CONSECUTIVE DAYS 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB ( TWO ADJACENT DISCONTINUOUS
( 2 ) SEPARATORS BETWEEN TWO LAYERS OF BARS.
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, FOG SPRAYING, CURING EDGES ) AS SHOWN BELOW.
COMPOUNDS OR OTHER APPROVED METHODS. 5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES BE AS
7. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED WITH 10mm STEEL
7. STRIPPING OF FORMS AND SHORES : CHAIR OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS SHOWN IN FIG. B - 2 UNLESS SPECIFIED ELSEWHERE.
FOUNDATION -------------------------------------------------------------------------- 24 hrs.
SUSPENDED SLAB EXCEPT WHEN ----------------------------------------------- 8 days A
ADDITIONAL LOADS ARE IMPOSED
WALLS --------------------------------------------------------------------------------- 24 days 12 x 1000 LONG @
MID-DEPTH OF SLAB b
BEAMS --------------------------------------------------------------------------------- 24 days DOWN INTO EDGE BEAM. EXTENDED
4- 12@ 1800 LONG TOP BARS BEND @ EACH CORNER LAP SPLICE LENGTH:
COLUMNS ----------------------------------------------------------------------------- 24 days
BARS MINIMUM OF 1200 ( 4'-0" ) INTO BARS. 1- 12 TOP & AT ANY LEVEL NO MORE THAN
t
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE
BOTTOM BARS ALTERNATE BARS SHOULD BE MAIN REINFORCEMENT
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST ( 4 ) DAYS PRIOR TO THE SPLICED. MIN. DISTANCE BET. see note
4- 12 BOTTOM BARS WEB BARS
t or 1/4D
WITHIN CENTER
POURING FOR APPROVAL.
400
ht
1- 12 EA. TWO ADJACENT BARS SPLICES see note
HALF OF "H"
t
9. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS AND SHORING UNTIL TOP & BOTTOM SHALL BE 600mm. SLEEVES FOR UTILITY
THE CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH
D
PIPES MAX 1/5D
0 L/4
0 SLAB
6 38mm TOP BARS @ SUPPORT (CONT.) 0.025m SEPARATOR
OPENING see note PROVIDE 3-10 EXTRA STIRR.
CLEAR
REQ'D. BOTT. BARS @ SUPPORT EACH SIDE OF SLEEVES
JT. REINF.
400
1- 12 EA.
0
( 2000 psf ). CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRITING, THE ACTUAL TOP & BOTTOM
D
6
SOIL CONDITION UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE
DEPOSITING CONCRETE. INTO TWO WAY SLAB EXTEND 6. WHEN A BEAM CROSSES A GIRDER, REST BEAM ON TOP OF GIRDER BARS, BEAM
BARS UP TO BEAM SUPPORT REINFORCING BAR SHALL BE SYMMETRICAL ABOUT CENTER LINE WHENEVER POSSIBLE.
2. FOOTINGS SHALL REST AT LEAST 15800mm BELOW NATURAL GRADE LINE UNLESS OMIT TRIMMER BARS WHERE
6
OTHERWISE INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL. OPENING IS FRAMED BY BEAM BOTTOM BARS AT 7. GENERALLY NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING
0
SPLICE
0
MID SPAN STRESSES OCCUR, SPLICES WHERE NO PERMITTED SHALL BE INDICATED IN THE TABLE "A"
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75mm CLEAR AND "B" WELDED SPLICES SHALL BE DEVELOP IN TENSION AT LEAST 125% OF THE
FOR CONCRETE DEPOSITED THE GROUND AND 50mm FOR CONCRETE SPECIFIED YIELD STRENGTH OF THE BAR. NOT MORE THAN 50% OF THE BARS AT ANY ONE
DEPOSITED AGAINST A FORMWORK. SECTION IS ALLOWED TO BE SPLICED THEREIN.
(DOWEL)
1. UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCKS COMPRESSIVE STRENGTH AT 28 DAYS fc' = 20.70 MPa ( 3,000 psi)
VERIFY ARCHITECTURAL
400
SHALL BE REINFORCED AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW BLOCKS AND B REINFORCING BARS
CERAMIC BLOCK REINFORCEMENT a) FOR BARS 16mm AND GREATER fy = 275 MPa (40,000 psi)
2. PROVIDE 150mm X 300mm STIFFENER COLUMN REINFORCED WITH 4 -12mm WITH 6mm TIES AT b) FOR BARS LESS THAN 16mm fy = 230 MPa (33,000 psi)
150mm ON CENTER WHERE CONCRETE HOLLOW BLOCK TERMINATES AND AT EVERY 3.00m C STRUCTURAL STEEL, ASTM - A36
LENGTH OF CONCRETE HOLLOW BLOCK WALLS UNLESS NOTED IN STRUCTURAL PLANS. FOR TRUSSES, BRACINGS, AND STRUTS fy = 248MPa (36,000 psi)
D PURLINS
COLD FORMED LIGHT CAGE SHAPES fy = 248MPa (36,000 psi)
REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT E MASONRY UNIT (CHB)
(DOWEL)
SCHEDULE OF CONCRETE HOLLOW BLOCK AND CERAMIC BLOCK REINFORCEMENT FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE PROVIDED, NON - LOADING BEARING CHB WALLS fm' = 3.45 MPa (500psi)
400
AND FOR EXPOSED FACES FORMED WALLS WHERE THE MINIMUM SHALL BE 50mm CLEAR. F WELDS - USED E - 60xx ELECTRODE
2. CARRY VERTICAL BARS AT LEAST 60mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN G STRUCTURAL BOLTS, ASTM - A307
NECESSARY STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL ENDS a) Ft = 96.60 MPa (14,000 psi) b) Fv = 69MPa(10,000 psi)
VERTICAL AND HORIZONTAL BARS SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL TO 30
AND WIRED SECURELY WITH 16 G.I. WIRE PROVIDED THAT SPLICES IN ADJACENT BARS ARE
STAGGERED AT LEAST 1.50M OC
3. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER SHALL 1 WHERE A CONSTRUCTION JOINT IS TO BE MADE, THE SURFACE OF CONCRETE SHALL BE
BE REINFORCED AROUND WITH 2 - 20mm BARS FOR 225mm, 200mm, 175mm, 150mm, USE 2 - 16mm CLEANED AND ALL LAITANCE AND STANDING WATER REMOVED. SHEAR KEY SHALL BE
. FOR 125mm AND 100mm WALLS, USE 2 - 12mm BARS. ALL WALLS SPANNING SHALL HAVE PROVIDED AT THE JOINT.
VERTICAL REINFORCEMENT BENT TO A U - FORM LIKE STIRRUPS AND SPACED ACCORDING TO THE
SCHEDULE UNLESS OTHERWISE NOTED ( SEE FIG. 1 )
550
30 BAR DIA. 30 BAR DIA.
t/3
LINTELS IN BLOCK WALLS 40
500
(min.) (min.)
CLEAR TOTAL MIN. HEIGHT
50
VARIES
t/3
SPAN LENGTH fc' OF
t
("L") (L + 0.40m) (MPa) LINTEL
D/3 D/3
BOTTOM TOP STIRRUPS
(mm)
D/3
D
600 (MIN.)
t/3
1.20m 1.60m 200 1- 10 1- 10 6mm @ 200mm
1.50m 1.90m 14.0 200 1- 10 1- 10 6mm @ 200mm 500 550
1.80m 2.20m 200 1- 12 1- 10 6mm @ 200mm
250
2.10m 2.50m 250 1- 12 1- 10 6mm @ 200mm
2.40m 2.90m 17.0 250 1- 12 1- 10 6mm @ 200mm
2.70m 3.10m 250 1- 16 1- 12 10mm @ 200mm
3.00m 3.40m
20.0
300 1 - 16 1- 12 10mm @ 200mm 400
3.30m 3.70m 300 1 - 16 1- 12 10mm @ 200mm
3.60m 4.00m 300 1 - 20 1- 12 10mm @ 200mm
1. USE E70xx ELECTRODES FOR ALL MEMBERS WELDED.
2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS OTHERWISE SHOWN
OR DETAILED IN THE DRAWINGS.
300
(TYP.)
1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE SHALL
DOWEL
COMPLY WITH ALL THE PERTINENT PROVISION OF AISC SPECIFICATION OR DESIGN, FABRICATION
400
DOWEL
2. ALL STRUCTURAL STEEL SHAPES SHALL CONFORM TO ASTM A36 STRUCTURAL STEEL UNLESS 38mm CLEAR
OTHERWISE INDICATED.
250
3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS CONNECTED.
4. UNLESS OTHERWISE SPECIFIED ALL WELDING RODS SHALL CONFORM AWS E60 ELECTRODES.
5. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A 307 BOLTS.
400
A. ALL EMBEDDED PIPES FOR UTILITIES, ETC. THAT PASS THRU BEAMS SHALL NOT EXCEED 100mm IN
OR 1 / 3 BEAM DEPTH WHICHEVER IS LESS, UNLESS OTHERWISE APPROVED IN WRITING BY THE
STRUCTURAL ENGINEER
B. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY. NOTES OF STIRRUPS:
C. NO PIPES SHALL BE EMBEDDED IN COLUMNS.
1 ALL REINFORCEMENT SHALL BE BENT COLD UNLESS
300 OTHERWISE PERMITTED BY THE STRUCTURAL
DOWEL
(TYP) ENGINEER.
400
DOWEL
250
A. DEAD LOAD STRUCTURAL ENGINEER.
400 CONCRETE - 23.56 KN / m3 3 TIES AND CLOSE STIRRUPS MUST BE
DOWEL STEEL - 76.93 KN / M3 db
150mm THK. CHB WALL - 2.73 kPA
db
1.25 L
100mm THK. CHB WALL - 2.11 kPA
D + 2db
L
D
B. LIVE LOAD
ROOF - 1.00 kPA 4db or 65mm
D
db
BASIC WIND VELOCITY, V = 250 KPH
200(mm) 200(mm) P = qh [(GCpf) - (GCpi)] (DESIGN WIND PRESSURE)
WHERE: qh = VELOCITY PRESSURE, kPA
db
GCpf = EXTERNAL PRESSURE COEFFICIENT
VERIFY DEPRESSION
12db
L
NOTE:
(min.) (min.) PURSUANT TO SECTION 4 OF ANNEX "A" OF THE D. SEISMIC LOAD ( NSCP 2010 )
D = FOR BEAM
t = FOR SLAB
3 - 10mm
BASEBARS
DETAIL OF STEEL TRUSS 0.15m THK. WALL
SCALE 1:25mts 10mm RSB VERT. FOOTING
BARS @ 0.60m OC
NEOPRENE
0.05 0.25
0.05 0.25
7.40 RCB-1
1.80
6
2.3 4.90
0.58
1.08
0.05 0.25
0.05 0.25
L/4
1.24
10mm BENTBARS @
0.20m OC, BOTHWAYS
STEEL TRUSS DIAGRAM
L/2
SCALE 1:50mts
L
RCB-1
RCB-1
10mm BASE BAR
SPACED @ 0.20mm O.C.
L 0.50 1.50 0.50
L/4 L/4 7 - 16mm DOWEL, 10mm TEMP.BARS @
0.20 0.20 1.00m EXTENDED 0.20m OC, BOTHWAYS
1-16mm SPOT DETAILS "B"
4-16mm 4-16mm SCALE 1:20mts
12mm CUTBARS @
2-16mm 2-16mm 0.10m OC, BOTHWAYS
L/4
1-16mm
@ SUPPORT @ MIDSPAN
L/5 L/5
RCB-1
ELECTRICAL LEGEND:
CIRCUIT HOMERUN
LIGHT OUTLET
AIRCONDITION CONV.OUTLET
WALL LAMP
KILOWATTHOUR METER
CIRCUIT BREAKER
8" PINLIGTH
RISER DIAGRAM
SCALE NTS
1 2 3
9.00
1 2 3
4.50 4.50 9.00
4.50 4.50
D
D
TYPICAL SCHEDULE OF LOAD
4.00
AMPERE PER
4.00
C
C
10.40
10.40
4.00
4.00
USE:
B AMP. MOLDED CIRCUIT BREAKER, 2-WIRE 250 VOLTS
B WITH 4 BRANCH CIRCUIT.
2.40
2.40
A
A
0.50
0.075
0.30 0.10
PLUMBING LEGEND : 0.50
0.10 0.30 0.10
0.10
0.50
0.675
0.30
0.50
0.10
0.10
PLAN SECTION
1 1' 2 2' 3
1 2 3
9.00 9.00
4.50 4.50 4.50 4.50
D D
4.00
4.00
C C
10.40
10.40
4.00
4.00
B B
2.40
2.40
A A
ISOMETRIC DRAWING
N T S