You are on page 1of 9

Solar Energy 80 (2006) 795–803

www.elsevier.com/locate/solener

Performance of a multi-functional direct-expansion


solar assisted heat pump system
Y.H. Kuang, R.Z. Wang *

Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200030, PR China

Received 21 October 2004; received in revised form 14 April 2005; accepted 1 June 2005
Available online 20 July 2005

Communicated by: Associate Editor Volker Wittwer

Abstract

This paper reports on the long-term performance of a direct-expansion solar assisted heat pump (DX-SAHP) system
for domestic use, which can offer space heating in winter, air conditioning in summer and hot water during the whole
year. The system employs a bare flat-plate collector array with a surface area of 10.5 m2, a variable speed compressor, a
storage tank with a total volume of 1 m3 and radiant floor heating unit. The performance under different operation
modes is presented and analyzed in detail. For space-heating-only mode, the daily-averaged heat pump COP varied
from 2.6 to 3.3, while the system COP ranged from 2.1 to 2.7. For water-heating-only mode, the DX-SAHP system
could supply 200 l or 1000 l hot water daily, with the final temperature of about 50 °C, under various weather condi-
tions in Shanghai, China. For space-cooling-only mode, the compressor operates only at night to take advantage of a
utilityÕs off-peak electrical rates by chilling water in the thermal storage tank for the daytime air-conditioning. It shows
that, the multi-functional DX-SAHP system could guarantee a long-term operation under very different weather con-
ditions and relatively low running cost for a whole year.
Ó 2005 Elsevier Ltd. All rights reserved.

Keywords: Solar assisted; Heat pump; Direct expansion; Water heater

1. Introduction system, which is called direct-expansion solar assisted


heat pump (DX-SAHP) system. An advantage from
Solar energy systems and heat pumps are two prom- the heat pump standpoint is that the collector/evapora-
ising means of reducing the consumption of fossil energy tor can operate at a temperature higher than ambient
resources (coal, petroleum, etc.), and hopefully, the cost due to solar heating, which increases the heat pump
of delivered energy for residential use. An intelligent COP. From a solar viewpoint, the working fluid for
extension is to use refrigerant-filled solar collectors to re- the collector is a refrigerant, which undergoes a phase
place the standard air-source evaporator in a heat pump change at a relatively low temperature. This yields high-
er collector efficiency than that of a straight solar sys-
*
Corresponding author. Tel.: +86 21 629 33838; fax: +86 21 tem. Thus there are reasons for expecting higher
629 33250. performance for such systems than conventional air-
E-mail address: rzwang@sjtu.edu.cn (R.Z. Wang). to-air heat pumps or conventional solar systems.

0038-092X/$ - see front matter Ó 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.solener.2005.06.003
796 Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803

Nomenclature

COP coefficient of performance c cooling


f frequency, Hz comp compressor
H daily amount of solar irradiation on the eva evaporator
plane of the collector, MJ m2 (or f floor
kWh m2) h heating
G global solar flux density on the plane of the HR heating room
collector, W m2 i inlet
Q heat rate, W NHR no heating room
T temperature, K (or °C) o outlet
t time, s rad radiator
W power, W R room
s operating period of the system, min st storage tank
sys system
Subscripts t tilted surface
a ambience or air w water
av averaged value

The concept of DX-SAHP was first proposed by expected to contribute to further studies and applica-
Sporn and Ambrose (1955) in West Virginia. Studies tions of such systems in the future.
of refrigerant-filled collectors alone (Chaturvedi et al.,
1982; Aziz et al., 1999) and the resulting heat pump per-
formance with elevated evaporating temperatures (Mor- 2. System description
rison, 1994; Chaturvedi et al., 1998; Ito et al., 1999;
Hawlader et al., 2001; Chyng et al., 2003; Kuang A multi-functional domestic DX-SAHP system is
et al., 2003) have been done theoretically and experimen- shown as Fig. 1. It mainly consists of a cost-effective
tally. A review on such work has indicated that, the COP simple flat-plate collector array, a variable speed com-
values of the DX-SAHP systems range from 2 to 9, and pressor, a water-to-refrigerant heat exchanger, a radiant
the collector efficiencies vary between 40% and 98% (or floor heating sub-system, a thermal storage tank, a hot
even above 1) under very different climatic conditions. water tank with an immersed condensing coil, two fan-
Although there are some DX-SAHP water heaters coil units, a forced-air heat exchanger, a water circulat-
currently being marketed, the potential of such a tech- ing pump and piping.
nology is far from being realized. In some regions, air- The solar flat-plate collector array without any glaz-
conditioning is the dominating energy consuming service ing or back insulation was used as a heat source as well
in buildings, but there is lack of enough information as an evaporator for the refrigerant, R22. It consists 10
about the application of DX-SAHP systems for air-con- aluminum absorber plates with the total aperture area of
ditioning of buildings. 10.5 m2, which were connected in parallel–series form, as
In the present study, a multi-functional domestic shown in Fig. 2. Each aluminum plate was made by a
DX-SAHP system was designed and fabricated in special process, in which the piping network design
Shanghai Jiao Tong University, China. During the first was laid between two sheets of aluminum (1 mm thick)
half year of 2004, a series of experimental studies were and retained after the sheets was bonded by rolling them
performed on such a multi-functional DX-SAHP system together, and then the tubes were formed by overpres-
at different operating modes, which aimed to investigate surizing the network, with an inside diameter of
the long-term thermal performance of the system and to 8.0 mm and a pitch between tubes of 40 mm. The collec-
analysis its component matching rules. The effects of tors could be integrated into the structure of a house
various system parameters on the response of indoor roof or wall so as to accord with the architecture and
air temperature of the building, water temperature vari- to reduce total initial cost. The solar collector array
ation in the heat storage tank, heating or cooling capac- was mounted on the south-facing slope roof of a solar
ities and electrical power consumption of the system energy laboratory with a floor area of 38.5 m2.
were investigated. A lot of experimental data and prac- A rotary-type hermetic compressor with a rated input
tical skills including component design, system match- power of 3 HP (abbr. horsepower) (50 Hz) was used in
ing, and operation control were obtained, which are the system, with the compressor volumetric displacement
Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803 797

8 electromagnetic valve thermometer


ball valve pressure gauge
7 check valve flowmeter
1
PC
20
EV1
3 RV
EV2
19
9
EV3
EV5
15
4 5 6

13 16 EV6

2 14
EV4

17 18
12 11
10 Space-heating-only mode
Water-heating-only mode
Space-cooling-only mode

1-solar collector/evaporator, 2-air source heat exchanger, 3-reversing valve, 4-accumulator, 5-compressor, 6-oil separator,
7-condensing coil, 8-hot water tank, 9-plate heat exchanger, 10-receiver, 11-filter-drier,
12-sight glass, 13-thermostatic expansion valve, 14-electronic expansion valve, 15-filter, 16-water pump,
17-floor heating circuit, 18-fan coil, 19-heat storage tank, 20-transducer

Fig. 1. Schematic overview of the DX-SAHP system.

Fig. 2. Front view of the solar collector array.

of 47 cm3. The compressor speed variation was achieved hot water tank, and the other is a water-to-refrigerant
through a variable frequency drive (VFD), to avoid the plate heat exchanger. A forced-air heat exchanger was
mismatch between the variable load on the system and coupled to the solar collectors as a backup evaporator
the constant capacity of the compressor. In the present during times of nun or low solar insolation. The energy
set-up, a VFD capable of adjusting the frequency from rejected by the plate condenser contributed to space-
30 to 90 Hz was employed. A refrigerant receiver and heating load requirements through a radiant floor heat-
accumulator were included in the system to help in con- ing unit in winter, whereas two fan-coil units were
trolling the refrigerant distribution, while the thermal installed parallel to carry the cooling load of the build-
expansion valve with an external pressure equalizer reg- ing in summer. The storage tank is made of sheet iron
ulates refrigerant flow to the evaporators, in order to with a capacity of 1.0 m3, and was linked to the plate
maintain constant superheat at the compressor inlet. heat exchanger and the floor heating tubing in a closed
The heat pump has two condensers, one of which is loop. A detailed overview of the heat pump system is
made of a copper tube coil and immersed in a 200 l shown in Fig. 3.
798 Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803

Fig. 3. Overview of the major components of the system.

3. Data acquisition and processing system are a four-way reversing valve, five electromagnetic
valves on the refrigerant pipes and an electromagnetic
The pressures, temperatures and flow rate of working valve on the water pipe at the locations shown in
fluid (water) were measured at the locations shown in Fig. 1. A control box was employed to control the oper-
Fig. 1. Also, the ambient temperature, relative humidity ating modes of the system, which provided with digital
and its velocity, the incident solar insolation, the collec- outputs to take care of compressor frequency, on–offs
tor surface temperature, indoor air and floor tempera- of valves, fans and water pump.
tures were measured. Pressures were measured with For about four months from February to June 2004,
pressure gages. Temperatures were measured with cop- experiments were carried out for the three fundamental
per–constantan thermocouples and platinum resistance operating modes to investigate the long-term perfor-
thermometers (RTDs). A solar pyranometer was mance of the multi-functional DX-SAHP system in dif-
mounted on the roof to measure the instantaneous solar ferent seasons. The following parameters have been
radiation. A turbine flow meter was used to measure the measured: electric power consumed by the compressor
water flow rate. Two digital power meters were used to and the whole system including compressor, pump, fans
measure the power consumptions of the compressor and other electric power consuming elements; tempera-
and the whole system including compressor, fans, pumps tures of both water and refrigerant at different locations
and electrical valves, respectively. All above measuring of the two loops, the absorber plate, the water in thermal
processes were monitored and controlled by a personal storage tank, indoor and outdoor air; flow rate of the
computer-based data-acquisition system. The data was water loop; insolation incident on the collector/evapora-
recorded at every 5 min interval in a data logger, which tor; pressures of refrigerant at inlets and outlets of com-
was later used for analysis. pressor, evaporator and condenser. All above
parameters were scanned and recorded each 5 min in
an automatic scan.
4. Experimental methods and procedure
4.1. Space-heating-only mode
In general, the multi-functional DX-SAHP system
can offer three fundamental operating modes, i.e. This mode serves the cold season when heating of the
space-heating-only mode, water-heating-only mode and room air is required. At this mode, the refrigerant-filled
space-cooling-only mode, and if necessary, it can also solar collector array on the roof serves as an evaporator,
produce domestic hot water at space-heating mode or while the plate heat exchanger works as a condenser.
space-cooling mode. The switching between those modes The refrigerant vapor from the compressor enters the
is by means of valve position and on–off controls. There plate heat exchanger directly, without passing through
Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803 799

the immersed condenser coil in the hot water tank. The 4.3. Space-cooling-only mode
radiant floor heating sub-system was used to dissipate
the heat to the room air, and meanwhile fan-coil units In summer, the DX-SAHP system can be switched to
do not operate at all. As a part of the control strategy, the space-cooling-only mode. By reverting the refriger-
the heat pump operate only from 9:00 to 17:00, because ant flow direction at the four-way valve, the refriger-
at low radiation levels, the collector temperature is sig- ant-filled solar collector works as a condenser or
nificantly below the ambient temperature and the system radiator, which rejects the condensing heat to the sur-
COP drops. From 17:00 to 22:00, the water circulation rounding by night radiation cooling. The water-
pump continues to operate and the water loop with- to-refrigerant plate heat exchanger produces the cooling
draws the heat from the thermal storage tank, which water by working as an evaporator. The fan-coil units
has been stored during the daytime. In the second half are used to cool the indoor air. The compressor operates
of the night, it is the stored heat of indoor floor that only from 22:00 pm to 6:00 am, when the local power
maintains the temperature level of the room air. companies offer an ‘‘off-peak’’ electric rate that is nearly
At the space-heating-only mode, there is no hot water 50% of the standard electric rate in Shanghai. During
producing function, and the system COP at any time in- the daytime, the water loop withdraws the chilled water
stant (t) is defined as from the thermal storage tank for air-conditioning, un-
Qh ðtÞ der the operation of water circulation pump.
COPh-sys ðtÞ ¼ ð1Þ At the space-cooling mode, the COP is defined as
W ðtÞ
Qc ðtÞ
where Qh(t) is the heat exchange rate in the plate con- COPc-sys ðtÞ ¼ ð5Þ
denser, and W(t) is the system input power. If W(t) is de- W ðtÞ
fined as the compressor power input, the rate from Eq. and
(1) is called heat pump COP. Rs
Q ðtÞ dt
Within an operating period of duration s, the average COPc-sys;av ¼ R0s c ð6Þ
COPh-sys is defined as 0
W ðtÞ dt
Rs
Q ðtÞ dt where Qc(t) is the heat exchanger rate in the plate
COPh-sys;av ¼ R0s h ð2Þ evaporator.
0
W ðtÞ dt

4.2. Water-heating-only mode 5. Experimental results and analysis

This mode is used for hot water production only. At 5.1. Space-heating-only mode
this mode, the four-way valve is positioned as before and
the refrigerant-filled solar collector also serves as an The DX-SAHP system was tested under various
evaporator. The immersed condenser coil dissipates heat weather conditions at space-heating mode from 13 to
to the bath (tank) of water. The water-to-refrigerant 17 February 2004, with the daily-averaged outdoor air
plate heat exchanger and the water loop are not included temperatures (Ta,av) ranging from 7.9 to 12.1 °C and
in this operation through bypassing the refrigerant flow, the insolation incident on the collector varying from
and meanwhile the water pump on the loop is power-off. 10.4 to 42.8 kWh/day. The experimental data listed in
The compressor is shut down once the water tempera- Table 1, which reveal that the daily-averaged indoor
ture in the tank exceeds the load temperature (50 °C). air temperatures (Ta-HR,av) varied from 16.7 to 19.1 °C,
When the DX-SAHP system continues to operate, the and the values of heat pump COP (COPh-hp,av) and sys-
working temperature of the water-bath condenser rises tem COP (COPh-sys,av) were 2.6–3.3 and 2.1–2.7, respec-
and the system efficiency declines accordingly. tively. In order to investigate the space-heating
At this mode, the system COP varies sensitively with capability of the DX-SAHP system evidently, tempera-
the change in water bath temperature. The COP for tures of indoor air and floor in an adjoining room had
water-heating mode is defined as also been tested and recorded during the testing period,
Qw ðtÞ which has a floor area of 18.5 m2 without any heating
COPw-sys ðtÞ ¼ ð3Þ equipment. In the present study, the data from a typical
W ðtÞ
sunny day in winter has been chosen for analysis.
and Fig. 4 shows the variations of the meteorological data
Rs
Q ðtÞ dt (Ta, Gt), indoor air and floor temperatures (Ta-HR,
COPw-sys;av ¼ R0s w ð4Þ Ta-NHR, Tf-HR, Tf-NHR) in both the heating room (HR)
0
W ðtÞ dt
and the non-heating room (NHR) with time of day on
where Qw(t) is the heat exchanger rate at the water stor- February 10, 2004. It is seen that, in the non-heating
age tank. room, Ta-NHR and Tf-NHR were always below 15 °C
800 Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803

Table 1
Performance of DX-SAHP at space-heating-only mode in winter
Weather pattern Ht Ta,av fcomp Ta-NHR,av Ta-HR,av Qh,av COPh-hp,av COPh-sys,av
(kWh m2) (°C) (Hz) (°C) (°C) (kW)
Clear day (04-02-13) 3.25 12.1 40 13.2 17.7 5.8 3.0 2.3
Clear day (04-02-14) 3.58 7.9 50 13.1 16.7 6.2 2.7 2.2
Clear day (04-02-15) 4.08 9.0 60 13.0 17.8 7.6 2.8 2.5
Clear day (04-02-16) 3.86 11.4 Variable speed 13.6 19.1 6.6 3.3 2.7
Cloudy (04-02-17) 1.00 10.1 50 13.3 17.7 6.0 2.6 2.1

30 10 6
Tf-HR , Ta-HR 800 Feb. 14, 2004 Qh
Ta-NHR, Tf-NHR space-heating-only mode W comp
25 5
Ta , Gt 8 fcomp = 50 Hz COPh-hp
600

Solar radiation, W/m


Temperature,°C

20
4
6

Power, kW
400
15
3

COP
10 200 4
2

2
5 0
Feb. 14, 2004 2
1
space-heating-only mode
0
11:30 14:00 16:30 19:00 21:30 0:00 2:30 5:00 7:30
0 0
Time, hh:mm
10:05 11:15 12:25 13:35 14:45 15:55
Time, hh:mm
Fig. 4. Comparisons between indoor floor and air temperatures
of heating room (HR) and those of non-heating room (NHR) Fig. 5. Variations of heating power, compressor power input
under the same climatic conditions. and heat pump COP with time of day.

during the whole day, with a very little fluctuation. In the radiation drops off, while the floor temperature keeps
heating room, the floor and air got heated up with the in- increasing, and hence, the Qh decreases continuously.
crease in solar radiation in the morning. Later, as the so- In order to overcome the mismatch between the variable
lar radiation decreased after the noon, Ta-HR and Ta-NHR load on the collector and the constant capacity of the
reached their peak values respectively at around compressor in DX-SAHP systems, a variable speed com-
17:00 pm. After the compressor switched off, Ta-HR and pressor and an electronic expansion valve in the system
Ta-NHR began to decrease till the heat pump system re- is recommended to be included.
started in the next morning. It is interesting to note that, Fig. 6 reveals the effect of compressor capacity mod-
the variation trends of Gt, Ta, Tf-HR and Ta-HR are simi- ulation on the system performance. At the beginning,
lar, but their peak values appeared lingeringly one by the compressor operating frequency was kept at 40 Hz,
one, which is due to the delay of heat transfer processes. and it was raised to a higher level of 50 Hz after
Fig. 5 shows the variations of heating power (Qh), 11:00 am, and after 15:00 pm it was reduced to the lower
compressor power input (Wcomp) and heat pump effi- level of 40 Hz again. This three-step capacity modula-
ciency (COPh-hp) with time of day on February 10, tion enabled a relative stable and higher COPh-hp.
2004. At a given speed, the electrical power consumed
by the compressor was stable, but Qh and COPh-hp in- 5.2. Water-heating-only mode
creased rapidly initially after the system started to oper-
ate, and then decreased gradually until the system The experimental data listed in Table 2 are taken at
switched off. This is mainly because that, for a compres- water-heating-only mode. In this case, the total volume
sor of a given capacity, the COPh-hp mainly depends on of hot water is about 200 l, with the final temperature
the difference in temperature between evaporating and chosen to be 50 °C. It can be seen that, the daily opera-
condensing processes. With the rapid increase in solar tion time (s) is less 1 h on a typical sunny day in spring,
radiation in the morning, leading to a rapid increase in and the DX-SAHP operated longer on a cloudy day,
evaporating temperature, a relatively smaller increase about 2 h. It is important to note that, the operation
in floor temperature causes a reduction in compressor time s depends much on the compressor capacity. The
work and a higher COPh-hp. After the noon, the solar larger compressor capacity enables a bigger mass flow
Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803 801

10 6 40 1200
Feb. 16, 2004 Qh June 30-31, 2004
space-heating-only mode
W comp 5 1000
32

Solar irradiation, W / m 2
8 COPh-hp

Temperature,°C
4 800
Power, kW

6 24

600

COPh
3
f:
16
4 40 Hz (9:00 -11:00) 400
50 Hz (11:00-15:00) 2
Ta
40 Hz (15:00-17:00) 8
2 Gt 200
1

0 0
0 0 1:28 3:58 6:28 8:58 11:28 13:58
10:20 11:40 13:00 14:20 15:40 17:00
Time, hh:mm
Time, hh:mm
Fig. 7. Variations of solar radiation intensity and outdoor air
Fig. 6. Effect of compressor capacity modulation on the system
temperature with time.
performance.

rate of refrigeration, which leads to a higher compressor A- Start cold thermal storage
work and a larger heating power, thereby resulting in a B- End cold thermal storage
Ta
35
shorter s and a lower COPw-sys,av. As indicated in Table C- Start cold consumption
2, for a fixed compressor capacity, the system perfor- A C
Ta-R
Temperature,°C

mance is governed strongly by the change of solar radi- 28

ation and ambient air temperature. For example, the


COPw-sys,av is much improved with the increase in solar Tw-st
21
radiation and ambient temperature. In order to main-
tain the COPw-sys,av in a reasonable range, it is suggested
14 C
to keep the compressor working frequency below 45 Hz. June 30-31, 2004 B
space-cooling-only mode
5.3. Space-cooling-only mode 7 fcomp = 30Hz

1:28 3:58 6:28 8:58 11:28 13:58


At the mode, refrigerant flow direction is reverted by Time, hh:mm
the four-way valve, and the refrigerant-filled solar col-
lector works as a condenser, which rejects heat to the Fig. 8. Variations of outdoor air temperature, indoor air
night sky by radiation cooling. Meanwhile, the plate temperature and water temperature in the tank with time.
heat exchanger works as an evaporator to produce the
chilled water for air-conditioning.
Fig. 7 shows the typical meteorological data of June ated at a constant frequency of 30 Hz at about
30–31, 2004, which had averaged outdoor temperature 23:00 pm, when the initial temperature in the tank was
of 26.7 °C during the operation period of the compressor about 28.7 °C (point ‘‘A’’). At about 8:30 am, the com-
(23:00–8:30). As shown in this figure, the temperature pressor switched off and the water temperature in the en-
reached the maximum of 36.3 °C at around solar noon. ergy storage tank reduced to 15.9 °C (point ‘‘B’’). Hence,
In Fig. 8, the outdoor temperature (Ta), indoor tem- the total net cold energy stored in the tank was only
perature (Ta-R) and water temperature in the energy about 14.9 kWh during that period (point ‘‘A’’ to
storage tank (Tw-st) are plotted with time of day in the ‘‘B’’), while the total cooling output of the DX-SAHP
experiment study. To begin with, the compressor oper- was about 49.5 kWh, which indicates that the system

Table 2
Performance of DX-SAHP at water-heating-only mode in spring
Rs Rs
Weather pattern fcomp (Hz) s (min) Gt,av Ta,av Tw,i Tw,o 0 Qw ðkWhÞ 0 W comp ðkWhÞ COPw-sys,av
(W m2) (°C) (°C) (°C)
Cloudy (04-04-10) 30 120 136 15.0 14.9 48.3 7.79 3.73 2.1
Partly cloudy (04-04-19) 30 60 563 27.9 18.3 47.8 6.88 1.97 3.5
Clear day (04-04-20) 35 45 675 32.7 19.5 46.1 6.19 1.90 3.3
Clear day (04-04-21) 40 35 697 31.0 19.3 45.0 6.01 1.78 3.5
Clear day (04-04-24) 45 50 682 19.6 20.7 48.1 6.65 2.67 2.5
802 Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803

90 ments for its design and manufacture. Moreover, it is


June 30-31, 2004
space-cooling-only mode
needed to do further research on spectrum-selective
75 fcomp = 30 Hz coating for such a collector.
Trad,i
In the DX-SAHP system, the energy storage tank is
used to store hot water for space heating in winter,
Temperature,°C

60
but it is also used to store chilled water for air-condition-
45 ing in summer. Both the volume and insulation of the
energy storage tank will influence the whole system per-
30 Trad,o formance significantly. So the selection and design of the
Teva,o energy storage tank should consider synthetically the
15 first-loaded cost and annual operation cost of the whole
Teva,i DX-SAHP system.
0 For the DX-SAHP system, the match between differ-
0:28 1:58 3:28 4:58 6:28 7:58
ent components is critical for its good performance,
Time, hh:mm
especially the match between compressor capacity and
Fig. 9. Variations of inlet/outlet refrigerant temperatures of solar collector area. It is recommended to apply certain
radiator and evaporator with time. proper strategies for system operation control. That is,
inclusion of a variable speed compressor and an elec-
tronic expansion valve with a controller in the system
has a poor cold storage efficiency of about 30%. The would positively improve the annual system thermal per-
COPc-hp,av was about 2.9 for this nighttime operation. formance of the DX-SAHP system. Although our objec-
This problem can be overcome by optimizing the struc- tion is to conduct experiments to prove the prospective
ture of the whole system, shortening the length of piping advantage of DX-SAHP system, only some primary re-
between components, strengthening the insulation of en- sults are presented in this paper, which shows the system
ergy storage tank and chilled water loop. It can also be performance was not so good as expected. It is because,
seen that, at about 15:00 pm, the water temperature in at the time of writing, the system has not been operated
the tank was above the indoor air temperature, which in an automatic control means to adapt well to the large
implies the cold energy stored during the nighttime fluctuation of solar radiation, which affected the system
was unable to meet the whole daily cooling load. Thus, performance greatly. The experiments are still being car-
it is necessary to employ a back-up condenser when the ried out to fully realize the system match in various cli-
compressor has to work in daytime. mate conditions.
Fig. 9 shows the variations of the inlet/outlet refriger- Several previous studies have employed chlorofluoro-
ant temperatures of the radiator/condenser (Trad,i, carbons (CFCs) as the collector fluid, such as R11,
Trad,o) and the inlet/outlet refrigerant temperatures of R114, R12 and R22. However, the discovery concerning
the water-source evaporator (Teva,i, Teva,o) with time as harmful effects of CFCs on the stratospheric ozone layer
shown in the figure, during the most of operation time, has led to international agreements and legislative ac-
the experimental values of Trad,i, Trad,o and Teva,i kept tions banning the future use of fully halogenated CFCs,
about 65 °C, 28 °C and 5 °C respectively, while Teva,o de- while R22, a widely used hydrogenated CFC (HCFC)
creased gradually as the operation time continued. It indi- with an ODP of 0.055, is slated for phase out by the year
cates that the bare collector/evaporator works well as a 2040 in all countries. Thus several new refrigerants such
radiator/condenser at space-cooling mode, but its func- as R134a, a non-azeotropic mixture of R22 and R142b,
tion is limited by the meteorological parameters, such as and a mixture of R123 and R134a have been proposed
outdoor temperature, wind speed and cloud cover in the to substitute CFCs for the DX-SAHP applications (Aziz
night sky. It is suggested to take some methods to enhance et al., 1999; Chyng et al., 2003). So it is very necessary to
the heat transfer on the surface of the radiator. redesign the system components and recognize the influ-
ence of such new refrigerants on system performance by
theoretical and experimental methods in further studies.
6. Discussions

A multi-functional domestic DX-SAHP system has 7. Conclusions


been investigated experimentally in the present study.
At space-heating or water-heating mode, the refriger- In the present study, a DX-SAHP system was de-
ant-filled collector works as an evaporator, while at signed and fabricated, which consists of a refrigerant-
space-cooling mode, it works as a condenser. It is ex- filled collector array, a variable speed compressor and
pected that the collector would have high heat gain/ a radiant floor heating unit. It can offer multi-fold func-
rejection efficiency, which may impose higher require- tions for residential uses, i.e. space heating in winter,
Y.H. Kuang, R.Z. Wang / Solar Energy 80 (2006) 795–803 803

air-conditioning in summer and hot water supply in References


whole year. During the first half year of 2004, a series
of experimental studies were carried out on the DX- Aziz, W., Chaturvedi, S.K., Kheireddine, A., 1999. Thermody-
SAHP system. Experimental results show that the sys- namic analysis of two-component, two-phase flow in solar
tem operating in space-heating-only mode can provide collectors with application to a direct-expansion solar-
assisted heat pump. Energy 24, 247–259.
comfortable space heating in winter, with the daily-aver-
Chaturvedi, S.K., Chiang, Y.F., Roberts, A.S., 1982. Analysis
aged heat pump COP varying from 2.6 to 3.3 and the
of two-phase flow solar collectors with application to heat
system COP ranging from 2.1 to 2.7. For water-heat- pumps. Journal of Solar Energy Engineering, Transaction
ing-only mode, the DX-SAHP system can supply 200 l of the ASME 104, 358–365.
hot water with the final temperature of about 50 °C daily Chaturvedi, S.K., Chen, D.T., Kheireddine, A., 1998. Thermal
under various weather conditions. For space-cooling- performance of a variable capacity direct expansion solar-
only mode, the compressor operates only at night to assisted heat pump. Energy Conversion and Management
take advantage of a utilityÕs off-peak electrical rates by 39, 181–191.
chilling water in the thermal storage tank for the day- Chyng, J.P., Lee, C.P., Huang, B.J., 2003. Performance analysis
time air-conditioning. It is important to note that, the of a solar-assisted heat pump water heater. Solar Energy 74,
33–44.
multi-functional DX-SAHP system could guarantee a
Hawlader, M.N.A., Chou, S.K., Ullah, M.Z., 2001. The
long-term operation under very different weather condi-
performance of a solar assisted heat pump water heating
tions and relatively low running cost during the whole system. Applied Thermal Engineering 21, 1049–1065.
year, but its advantages should be proved fully by much Ito, S., Miura, N., Wang, K., 1999. Performance of a heat
more experimental and theoretical studies in the future. pump using direct expansion solar collectors. Solar Energy
65, 189–196.
Acknowledgements Kuang, Y.H., Sumathy, K., Wang, R.Z., 2003. Study on a
direct-expansion solar-assisted heat pump water heating
system. International Journal of Energy Research 27, 531–
This work was supported by the National Key Fun-
548.
damental Research Program under the contract no. Morrison, G.L., 1994. Simulation of packaged solar heat-pump
G2000026309 and also Shanghai Commission of Science water heaters. Solar Energy 53, 249–257.
& Technology under the contract of 03dz12012. The Sporn, P., Ambrose, E.R., 1955. The heat pump and solar
authors thanks the helps from Prof. J.Y. Wu, senior energy. In: Proceedings of the World Symposium on
engineer Mr. Y.X. Xu, and also Mr. Y.K. Sun. Applied Solar Energy, Phoenix, Ariz, November 1–5.

You might also like