You are on page 1of 198

0 Standards and principles 5

1 Enclosures, terminal boxes, junction boxes 15

2 Assembled housings 47

3 Lighting 61

4 Signalling 95

5 Switches, control units, sockets and plugs 105

6 Heating 133

7 Man - machine interface 143

8 Cable glands and accessories 155

9 Miscellaneous 195

EDITION 2011-10

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 1


0 Explosion safety standards and
principles
1 EN / IEC standards ........................................................................................ 5

2 Protection methods ........................................................................................ 6

3 Classification into groups and temperature classes ....................................... 8

4 Classification in zones and choice of electrical equipment (= categories) ..... 9

5 Equipment Protection Level ......................................................................... 10

6 Certification .................................................................................................. 12

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 3


0 Explosion safety standards and principles
1 EN / IEC standards

0 Explosion safety standards and principles

Introduction

During the production, handling, storage and transport of flammable products, gases are inevitably released. In combination with
air these gases form an explosive mixture. A spark, or even a hot surface, can cause an explosion, jeopardising man and material.
Therefore, explosion hazardous environments are a very specific area, for which international legislation has issued specific
construction and installation regulations.

In many industries powder and dust is raised during production.


Most of the substances in powderform contain a risk for fire or explosion, no matter if it concerns raw materials or waste products (for
example with the production of plastics, greases or farmaceuticals). 80% of all dusts occuring in industry is flammable; for a dust layer of
1 mm thickness in a sealed room this can already result in a dust explosion due to air raising clouds of dust.
All this together with the rather limited knowledge of the dangers, in contrast with gasexplosionsafety, emphasize the importance of this
theme of dustexplosionsafety

On March 1st 1996 the directive 94/9/EC was issued, better known as ATEX95.

Standards

A.o. the following standards are applicable to explosionsafe electrical equipment

Protection method EN / IEC


General requirements (Gas) 60079-0
Flameproof enclosures “d” 60079-1
Pressurized apparatus “p” 60079-2
Powder filling “q” 60079-5
Oil immersion “o” 60079-6
Increased safety “e” 60079-7
Intrinsic safety “i” 60079-11
Protection “n” 60079-15
Encapsulation “m” 60079-18
Intrinsically safe electrical systems 60079-25
Classification of hazardous areas (Gas) 60079-10
Electrical installations in hazardous areas (Gas) 60079-14
Inspection and maintenance of electrical installations in hazardous areas (Gas) 60079-17
General requirements (Dust) 61241-0
Protection “tD” 60079-31
Protection “pD” 61241-4
Protection “iD” 60079-11
Protection “mD” 60079-18
Reparation and revision 61241-19
Classification of hazardous areas (Dust) 61241-10
Electrical installations in hazardous areas (Dust) 61241-14
Inspection and maintenance of electrical installations in hazardous areas (Dust) 61241-17

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 5


0 Explosion safety standards and principles
2 Protection methods

Protection methods for gas environments:

Flameproof enclosure “d”


With this protection method any sparking parts, that may ignite an explosive atmosphere,
are placed inside a housing that is able to withstand the pressure of an internal explosion
and impede the propagation of the explosion to the surrounding atmosphere. This
requires a precise construction of the material, with flanges and threads having a well-
determined gap width and length.

Increased safety “e”


This protection method refers to equipment that does not ordinarily produce sparks and
for which special precautions must be taken during construction.
Unacceptably high temperatures must also be avoided, during both regular operation and
certain irregular situations.

Pressurized apparatus “p”


The ingress of an explosive atmosphere in a housing containing electrical equipment, is
avoided by maintaining a protective gas (air or an inert gas) at a slight overpressure to the
surrounding atmosphere. The overpressure may or may not be maintained by continuous
P
flow.

Intrinsic safety “i”

R L This protection method applies to a complete circuit. A circuit is intrinsically safe when
there are no sparks or thermal effects that may cause an explosive atmosphere to ignite
U C under particular circumstances.

Oil immersion “o”


Electrical equipment or parts of it are immersed in oil, thus avoiding ignition of the
explosive atmosphere above the oil surface or outside the housing. This protection
method is rarely applied now.

Powder filling “q”


This protection is achieved by filling a housing with a powdered material. An electric
arc or spark, originating in the housing, is thus prevented from igniting the explosive
atmosphere.

Encapsulation “m”

With this protection method all parts that may ignite an explosive atmosphere, are
encapsulated in a resin that is sufficiently resistant to ambient influences. The atmosphere
must neither be ignited by sparks, nor by heating inside the encapsulation.

Protection “n”

These mode of protection can be achieved in 5 different ways :


- non sparking apparatus (A)
- housing “restricted breathing” (R)
- apparatus with limited energy (L)
- housing with simplified overpressure (P or Z)
- sparking apparatus where the contacts are properly protected, differently as in “restricted breathing”,
apparatus with limited energy and simplified overpressure (C)

6 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
0 Explosion safety standards and principles
2 Protection methods

Protection methods for dust environments:

Protection by enclosure “tD”


This method is based on the maximum surface temperature of the enclosure and the
limited ingress of explosive dust by using dustproof and dust-preventing enclosures.

Intrinsic safety “iD”

R L The dust protection method “iD” is deduced from the gas protection method “i”.
Additional prescriptions are to be followed.
U C

Pressurized apparatus “pD”


The ingress of an explosion-hazardous dust atmosphere in a housing containing electrical
equipment, is avoided by maintaining a protective gas (air or an inert gas) at a slight
overpressure to the surrounding atmosphere. Prepurging is in this case forbidden since
P
the deposited dust will cause an explosive atmosphere when it is raised in a dust cloud.

Encapsulation “mD”

The dust protection method “mD” is deduced from the gas protection method “m”.
Additional prescriptions are to be followed.

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 7


0 Explosion safety standards and principles
3 Classification into groups and temperature classes

Not all explosion-proof equipment can be constructed in accordance with the maximum demands, i.e. applied in all explosive
atmospheres.
At first instance the European standards distinguish two equipment groups:
Group I: electrical equipment for mines that are susceptible to firedamp
Group II: electrical equipment for all other potentially explosion-hazardous spaces
Equipment of group II is subdivided into explosion groups and temperature classes.

Grouping of electrical apparatus

Depending on the ignition and sparking characteristics of an explosive mixture, gases and vapours are divided into explosion groups.
Categorisation criteria are the gap dimensions, the minimum ignition energy respectively, that have been determined empirically for
the various gases. Electrical equipment is marked to indicate for which group (A , B or C) it is designed. Group IIC has the most severe
characteristics and can also be used for gases in subdivisions A and B.

Location Group Examples of gases


Mines susceptible to firedamp I Methane
IIA Propane, Octane, Acetone, Ammonia
Other locations IIB Ethylene, Carbon monoxide
IIC Hydrogen, Carbon disulphide

Temperature classes

The ignition temperature depends on the nature and characteristics of the gases present. Explosionproof equipment must not have an
external temperature that could become a source of self-ignition for the surrounding atmosphere. The electrical equipment of group II is
therefore subdivided into the following temperature classes, depending on the maximum surface temperature:

Temperature class Maximum surface temperature


T1 450°C
T2 300°C
T3 200°C
T4 135°C
T5 100°C
T6 85°C

The maximum surface temperature of an electrical device must be constantly lower than the ignition temperature for the gas or vapour
mixture in which it is used.

Classification of certain gases

The table below provides the explosion group and temperature class for a number of gases and vapours.
Name of the substance Ignition temperature Temperature class Explosion group
Acetylene 305 T2 IIC
Ammonia 630 T1 IIA
Butane 365 T2 IIA
Ethane 515 T1 IIA
Ethanol 425 T2 IIA
Ethylene 425 T2 IIB
Carbon monoxide 605 T1 IIB
Methane 595 T1 I
Octane 210 T3 IIA
Propane 470 T1 IIA
Hydrogen 560 T1 IIC
Carbon disulphide 102 T5 IIC

The above-mentioned classification is only for information purposes. Variations are always possible, so that verification through an
official body is recommended.

8 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
0 Explosion safety standards and principles
4 Classification in zones and choice of electrical equipment (= categories)

Classification in zones (for gasexplosions)

Any area or environment where a gas explosion hazard may occur, is categorised in zones (0, 1 or 2), depending on the risk related with
the possible presence of an explosive mixture in that area.

Zone Description Example

Includes areas where an explosion hazardous gasatmosphere - inside of a vessel


0
is continuously present - inside of reactor chambers

- near filling holes


Includes areas where an explosion hazardous gasatmosphere
1 - near zone 0
is occasionally present
- near pumps and valves

Includes areas where an explosion hazardous gasatmosphere - near zone 0 or 1


2
is rarely and for a short time present - near flange connections with flat seals

It is obvious that the zones should be kept as limited as possible and the use of electrical equipment shall be avoided where possible.
There is a similar division for dustexplosions (zone 20, 21 and 22).

Choice of electrical equipment

The apparatus is fitted with an additional marking (= category) that informs the user in which zone the apparatus can be installed.

Apparatus destined for mines who can contain minegas:

Category according to 94/9/EC Level of protection Number of incidents


M1
Very high 2
Remains functional with an explosive atmosphere
M2
High 1
De-energized in the event of an explosive atmosphere

Apparatus destined for explosion-hazardous areas other than mines:

Zone according to 1999/92/EC Nature of Explosive atmosphere Category of equipment Level of protection Number of incidents
atmosphere according to 94/9/EC
G
0 1G
Gas
Continuous Very high 2
D
20 1D
Dust
G
1 2G
Gas
Occasionally High 1
D
21 2D
Dust
G
2 3G
Gas
Rarely Normal 0
D
22 3D
Dust

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 9


0 Explosion safety standards and principles
5 Equipment Protection Level

5 Equipment Protection Level

Equipment protection level

Historically it was acceptable to install equipment into specific zones based on the type of protection.

In some cases it has been shown that the type of protection may be divided into different levels of protection that can be correlated
against each zone. A better risk assessment would consider all factors. When using a risk assessment approach instead of the inflexible
approach of the past linking equipment to zones, the inherent ignition risk of the equipment is clearly indicated, no matter what type of
protection is used.

Group I: mines

EPL Ma:
Apparatus for installation in a mine, with a very high safety protection level, that remains functional in an explosion-hazardous
environment, even with an exceptional fault

EPL Mb:
Apparatus for installation in a mine, with a high safety protection level, that will be de-energized in the event of an explosive atmosphere.

Group II: gas

EPL Ga:
Apparatus for installation in an explosion-hazardous gasatmosphere, with a very high protection level, that even in the event of an
exeptional fault of the apparatus, still guarantee the safety level.

EPL Gb:
Apparatus for installation in an explosion-hazardous gasatmosphere, with a high protection level, that in the event of occasional faults of
the apparatus, still guarantee the safety level.

EPL Gc:
Apparatus for installation in an explosion-hazardous gasatmosphere, with a normal protection level, that guarantee this safety level in
the event of normal working.

Group III: dust

EPL Da:
Apparatus for installation in an explosion-hazardous dustatmosphere, with a very high protection level, that even in the event of an
exeptional fault of the apparatus, still guarantee the safety level.

EPL Db:
Apparatus for installation in an explosion-hazardous dustatmosphere, with a high protection level, that in the event of occasional faults
of the apparatus, still guarantee the safety level.

EPL Dc:
Apparatus for installation in an explosion-hazardous dustatmosphere, with a normal protection level, that guarantee this safety level in
the event of normal working.

Relation between EPL and zones

Zone Equipment protection levels (EPLs)


0 Ga
1 Ga or Gb
2 Ga, Gb, or Gc
20 Da
21 Da or Db
22 Da, Db or Dc

10 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
0 Explosion safety standards and principles
5 Equipment Protection Level

Assignment of EPLs to the IEC/EN protection methods

EPL Type of protection Code According to


‘Ga’ Intrinsically safe ‘ia’ IEC 60079-11
Encapsulation ‘ma’ IEC 60079-18
Two independent types of protection each meeting EPL ‘Gb’ IEC 60079-26
Protection of equipment and transmission systems using optical radiation IEC 60079-28
‘Gb’ Flameproof enclosures ‘d’ IEC 60079-1
Increased safety ‘e’ IEC 60079-7
Intrinsically safe ‘ib’ IEC 60079-11
Encapsulation ‘m’ or ‘mb’ IEC 60079-18
Oil immersion ‘o’ IEC 60079-6
Pressurized enclosures ‘p’, ‘px’ or ‘py’ IEC 60079-2
Powder filling ‘q’ IEC 60079-5
Fieldbus intrinsically safe concept (FISCO) IEC 60079-27
Protection of equipment and transmission systems using optical radiation IEC 60079-28
‘Gc’ Intrinsically safe ‘ic’ IEC 60079-11
Encapsulation ‘mc’ IEC 60079-18
Non-sparking ‘n’ or ‘nA’ IEC 60079-15
Restricted breathing ‘nR’ IEC 60079-15
Energy limitation ‘nL’ IEC 60079-15
Sparking equipment ‘nC’ IEC 60079-15
Pressurized enclosures ‘pz’ IEC 60079-2
Fieldbus non-incendive concept (FNICO) IEC 60079-27
Protection of equipment and transmission systems using optical radiation IEC 60079-28
‘Da’ Intrinsically safe ‘iD’ IEC 60079-11
Encapsulation ‘mD’ IEC 60079-18
Protection by enclosure ‘tD’ IEC 60079-31
‘Db’ Intrinsically safe ‘iD’ IEC 60079-11
Encapsulation ‘mD’ IEC 60079-18
Protection by enclosure ‘tD’ IEC 60079-31
Pressurized enclosures ‘pD’ IEC 61241-4
‘Dc’ Intrinsically safe ‘iD’ IEC 60079-11
Encapsulation ‘mD’ IEC 60079-18
Protection by enclosure ‘tD’ IEC 60079-31
Pressurized enclosures ‘pD’ IEC 61241-4

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 11


0 Explosion safety standards and principles
6 Certification

In Europe some test institutes are authorised to carry out tests on explosionproof equipment and to issue the corresponding certificates.

Procedures for certification

The directive 94/9/EC extensively describes the assessment procedures for compliance.
A short overview is given in the following tabel.

Category 1 or M1 + Category 2 or M2 (electrical Category 2 or M2


Category 3
autonomous protective systems equipment and ignition sources) (other apparatus)

or or or or

E.C. Type- Unit E.C. Type- Unit Internal control Unit Unit
of production + verification by Internal control
examination verification by examination verification by verification by
communicate of production
by N.B. N.B. by N.B. N.B. N.B. N.B.
a technical
documentation
to a N.B.
or or

Product
Production QA Product QA by Conformity to
verification by
by N.B. N.B. type
N.B.

12 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes,
junction boxes
1 Enclosures Exd IIB+H2 ................................................................................ 15
1 EJB series - aluminium ..................................................................... 15

2 Enclosures Exd IIC....................................................................................... 18


1 GUB series - aluminium .................................................................... 18
2 EMH series - with window ................................................................. 19

3 Enclosures EExde IIC .................................................................................. 20


1 DE8-WH series - EExd box............................................................... 20
2 DE1-WH series - EExe box............................................................... 21

4 Terminal boxes polyester ............................................................................. 22


1 CONNECTA-P series ........................................................................ 22

5 Enclosures stainless steel ............................................................................ 30


1 AR/AQ series .................................................................................... 30
2 NXT series ........................................................................................ 31

6 Junction boxes Exe plastic ........................................................................... 33


1 BJE series ......................................................................................... 33

7 Construction site boxes ................................................................................ 34


1 Solid rubber....................................................................................... 34
2 Cable reel.......................................................................................... 35
3 Standard construction site box - type Y11138 ................................... 36
4 Transformers ..................................................................................... 37
5 Standard transformer ........................................................................ 38

8 EX-PRESS pressurized enclosures Exp ...................................................... 39


1 Serie FS850S.................................................................................... 39
2 Serie FS840 ...................................................................................... 43

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 13


1 Enclosures, terminal boxes, junction boxes
1 Enclosures Exd IIB+H2
1 EJB series - aluminium

The EJB series flameproof enclosures are available in 12 different sizes,


II 2 G Exd IIB+H2 T6/T5/T4
allowing a suitable housing to be found for every application.
Depending on the customer’s specifications, the boxes can be fitted with II 2(1) G Exd [ia] IIB+H2 T6
terminals, magnetic switches, circuit breakers, electronic components, etc. II 2(2) G Exd [ib] IIB+H2 T6
Specifications II 2 D Ex tD A21 IP65 T85°C/T100°C/T135°C

Material corrosion- and saltwaterresistant aluminium


with polyurethane paint, RAL9002
Zone 1  Zone 21 
Protection IP65 Zone 2  Zone 22 
Seal special grease on the flanges to guarantee the
INERIS02ATEX0071X
IP-degree
Mounting plate galvanised, 3mm thick
Cover bolts stainless steel
Earthing internal and external stainless steel M6 bolt
Ambiant temperature -20°C - +40°C
Mounting the rear is fitted with 4 threaded holes

On request
• control units in cover
• hinges (stainless steel)
• galvanised mounting brackets for wall mounting
• entries with or without glands
• rectangular or round windows
• installation of electric/electronic components
• ambiant temperature -50°C - +55°C

Ordering data
Code Dimensions (hxwxd) (mm) Mounting plate (mm) Useable depth (mm) Weight
EJB-Y-02 298 x 238 x 174 220 x 160 135 10,7 kg
EJB-Y-03 412 x 238 x 177 330 x 155 136 13,4 kg
EJB-Y-04 418 x 302 x 175 325 x 210 132 17,5 kg
EJB-Y-05 480 x 300 x 232 385 x 200 182 20,5 kg
EJB-Y-06 483 x 408 x 238 380 x 300 186 33,0 kg
EJB-Y-08 634 x 365 x 254 520 x 250 204 36,5 kg
EJB-Y-09 535 x 468 x 257 420 x 350 204 40,0 kg
EJB-Y-10 750 x 366 x 292 620 x 240 234 48,5 kg
EJB-Y-11 596 x 505 x 267 470 x 380 203 53,3 kg
EJB-Y-12 805 x 455 x 310 675 x 325 243 73,0 kg
EJB-Y-13 832 x 607 x 314 690 x 470 236 106,0 kg
EJB-Y-13A 832 x 607 x 400 690 x 470 322 124,0 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 15


1 Enclosures, terminal boxes, junction boxes
1 Enclosures Exd IIB+H2
1 EJB series - aluminium

Dimensional sketches

Product code Dimensions


A B C D E F G H I L N P R
EJB-Y-02 298 238 174 230 168 85 135 205 140 250 10 6x1 20
EJB-Y-03 412 238 177 340 167 85 136 330 150 250 10 8x1,25 20
EJB-Y-04 418 302 175 336 220 75 132 300 190 300 10 8x1,25 20
EJB-Y-05 480 300 232 392 209 125 182 350 185 300 10 8x1,25 20
EJB-Y-06 483 408 238 387 311 130 186 355 280 390 10 8x1,25 20
EJB-Y-08 634 365 254 531 262 140 204 495 225 340 10 8x1,25 20
EJB-Y-09 535 468 257 426 363 145 204 410 340 440 10 10x1,5 20
EJB-Y-10 750 366 292 630 248 180 234 580 205 330 14 10x1,5 20
EJB-Y-11 596 505 267 483 394 140 203 445 360 480 14 10x1,5 20
EJB-Y-12 805 455 310 690 336 185 243 640 285 475 14 12x1,75 20
EJB-Y-13 832 607 314 723 500 125 236 630 405 580 14 12x1,75 20
EJB-Y-13A 832 607 400 723 500 225 322 630 405 580 14 12x1,75 20

Accessories
Switches
AC1 660V : 20A Code Schema
AC23 500V : 16A
PSRC220

PSRC420

PSRC-D220

PSRC-C220

Key switches
AC11 220V : 4,5A / 380V : 2,6A / Code Contact block
500V : 2,1A PLF10
In = 10A
020E10 1NO
Contactblocks to be ordered
separately. 020E01 1NC

Push buttons
AC11 220V : 4,5A / 380V : 2,6A / Code Colour Contact block
500V : 2,1A PLA10 black
In = 10A
PLA20 red
Contactblocks to be ordered
separately. PLA30 green
PLC-S red
PLC-S-F red
020E10 1NO
020E01 1NC

16 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
1 Enclosures Exd IIB+H2
1 EJB series - aluminium

Signalling lamps
Lamp fitting Ba9s Code Colour Voltage
max.230V - max.5W PLD20 red
Light bulb to be ordered
PLD10 white
separately.
PLD30 green
PLD40 yellow
PLD50 blue
PLD-LED28VAC/DC 24VAC/DC
PLD-LED130VAC 130VAC
PLD-LED230AC 230VAC

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 17


1 Enclosures, terminal boxes, junction boxes
2 Enclosures Exd IIC
1 GUB series - aluminium

The GUB series flameproof enclosures are available in 7 different sizes.


II 2 G Exd IIC T6/T5/T4
Depending on the customer’s specifications, the boxes can be fitted with
terminals, magnetic switches, circuit breakers, electronic components, etc. II 2(1) G Exd[ia] IIC T6

Specifications II 2(2) G Exd[ib] IIC T6


II 2 D Ex tD A21 IP65 T85°C/T100°C/T135°C
Material corrosion- and saltwater- resistant aluminium
with polyurethane paint, RAL9002
Protection IP65 Zone 1  Zone 21 
Mounting plate aluminium, 2 mm thick Zone 2  Zone 22 
Earthing internal and external stainless steel M6 bolt
INERIS02ATEX0072X
Ambiant temperature -20°C - +40°C
Mounting mounting eyes

On request
• entries with or without glands
• installation of electric/electronic components
• Flat cover for fixing of components (GUB-QL)
• ambiant temperature -50°C - +55°C

Ordering data
Code Dimensions (hxwxd) (mm) Mounting plate (mm) Useable depth (mm) Weight
GUB-Y-00 133 x 133 x 142 Ø80 92 2,16 kg
GUB-Y-01 169 x 169 x 152 Ø120 100 3,62 kg
GUB-Y-02 190 x 190 x 164 Ø145 102 4,72 kg
GUB-Y-03 210 x 210 x 179 Ø160 120 5,95 kg
GUB-Y-04 281 x 232 x 206 Ø180 145 8,90 kg
GUB-Y-05 298 x 257 x 222 Ø195 154 11,86 kg
GUB-Y-06 329 x 293 x 248 Ø235 192 15,75 kg

Dimensional sketches

Product code Dimensions


A B C D E F G H I L M Q*
GUB-Y-00 133 133 142 110 110 60 92 90 110 100 6 80
GUB-Y-01 169 169 152 139 139 65 100 126 150 150 7 120
GUB-Y-02 190 190 164 160 160 65 102 144 170 170 8 145
GUB-Y-03 210 210 179 180 180 75 120 167 190 190 9 160
GUB-Y-04 281 232 206 202 251 97 145 183 260 210 9 180
GUB-Y-05 298 257 222 227 268 105 154 206 275 235 9 195
GUB-Y-06 329 293 248 259 295 142 192 242 305 270 10 235

18 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
2 Enclosures Exd IIC
2 EMH series - with window

The EMH series windows are suited for the installation of digital and
II 2 G Exd IIC T6/T5/T4
analogue instruments with external readout (meters, displays).
II 2(1) G Exd[ia] IIC T6
Specifications
II 2(2) G Exd[ib] IIC T6
Material corrosion- and saltwater- resistant aluminium
II 2 D Ex tD A21 IP65 T85°C/T100°C/T135°C
with polyurethane paint, RAL9002 (EMH90 =
RAL6003)
Protection IP65 Zone 1  Zone 21 
Mounting plate aluminium, 2 mm thick (except EMH90) Zone 2  Zone 22 
Earthing internal and external stainless steel M6 bolt
INERIS02ATEX0072X
Ambiant temperature -20°C - +40°C
Mounting mounting eyes INERIS03ATEX0009

On request
• entries with or without glands
• installation of electric/electronic components
• installation of instruments
• ambiant temperature -50°C - +55°C

Ordering data
Code Dimensions (hxwxd) (mm) Mounting plate (mm) Window (mm) Weight
EMH90-V 84 x 175 x 135 Ø80 1,47 kg
EMH-Y-160 210 x 210 x 158 Ø160 Ø160 5,90 kg
EMH-Y-175 281 x 232 x 184 Ø175 Ø175 8,90 kg
EMH-Y-200 298 x 257 x 198 Ø200 Ø200 11,86 kg
EMH-Y-230 329 x 293 x 236 Ø230 Ø230 15,75 kg

Dimensional sketches

EMH90-V EMH-Y

Product code Dimensions


A B C D E F Q
EMH90-V 84 175 135 66 134 7 80
EMH-Y-160 210 210 158 190 190 8 160
EMH-Y-175 281 232 184 210 260 8 175
EMH-Y-200 298 257 198 235 275 8 200
EMH-Y-230 329 293 236 270 305 10 230

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 19


1 Enclosures, terminal boxes, junction boxes
3 Enclosures EExde IIC
1 DE8-WH series - EExd box

The flameproof enclosures of the DE8-WH (EExd) series are particularly


II 2 G EExd IIC T6/T4
suited for the installation of controls and distributions.
With the addition of an EExe box, controls (push buttons, lamps, etc) and II 2 G EExde IIC T6/T4
terminals can be added, guaranteeing a user-friendliness. II 2 D T85°C - T135°C IP65
The EExd and EExe boxes are connected by means of flameproof bushings
(number of conductors and section need to be specified). Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Material steel with aluminium cover and finish INERIS03ATEX0121X
Protection IP65
Mounting plate twofold, galvanised steel
Earthing with M10 threaded rod
Ambiant temperature -20°C - +40°C
Mounting with 4 mounting feet

On request
• entries with or without glands
• Ø 60 window, centred on cover
• installation of electric/electronic components
• built-on EExe box
• ambiant temperature -20°C - +60°C

Ordering data
Code Dimensions (hxwxd) (mm) Weight
DE8-WH32 330 x 330 x 300 65 kg
DE8-WH43 520 x 520 x 300 125 kg
DE8-WH64 670 x 670 x 300 200 kg
DE8-WH107 1040 x 670 x 360 200 kg

Dimensional sketches

Product code Dimensions


A B C D E F G H I J K L
DE8-WH32 330 330 380 210 420 425 300 264 306 306 250 14
DE8-WH43 520 520 570 400 610 425 300 264 496 496 400 14
DE8-WH64 670 670 720 552 760 425 300 264 646 646 550 14
DE8-WH107 670 1040 720 800 360 317 1016 646 550 14

20 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
3 Enclosures EExde IIC
2 DE1-WH series - EExe box

The flameproof enclosures of the DE8-WH (EExd) series are particularly


II 2 G EExe II T6/T4
suited for the installation of controls and distributions.
With the addition of an EExe box, controls (push buttons, lamps, etc) and II 2 G EExed IIC T6/T4
terminals can be added, guaranteeing a user-friendliness. II 2 G EExem II T6/T4
The EExd and EExe boxes are connected by means of flameproof bushings II 2 G EExemd IIC T6/T4
(number of conductors and section need to be specified). II 2 D T85°C - T135°C IP65
Specifications
Material sheet metal with finish Zone 1  Zone 21 
Protection IP65 / IP66 Zone 2  Zone 22 
Mounting plate optional
INERIS03ATEX0006
Earthing earthing bolt
Ambiant temperature -20°C - +50°C
Mounting fixed connection with EExd box or optional
mounting feet

On request
• installation of terminals, control units
• ambiant temperature -20°C - +60°C
• mounting plate

Ordering data
Code Dimensions (hxwxd) (mm) Weight
DE1-WH330 250 x 330 x 230 8 kg
DE1-WH520 330 x 520 x 230 13 kg
DE1-WH670 520 x 670 x 230 22 kg

Dimensional sketches

Product code Dimensions


A B C
DE1-WH330 330 250 230
DE1-WH520 520 330 230
DE1-WH670 670 520 230

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 21


1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

The polyester terminal boxes of the CONNECTA-P series are available in


II 2 G Exe II T6
23 different sizes.
They are very robust and particularly suited for use in aggressive and II 1 G Exia IIC T6
heavy-duty conditions. II 2(1) G Exe[ia] IIC T6
With their practical sizes and their flexible certification they can be fitted with II 2 D Ex tD A21 IP66 T85°C
terminals and glands of various manufacturers.
These terminal boxes are readily available according to your specifications. Zone 0  Zone 20 
The boxes are available as assembled terminal boxes or in an empty Zone 1  Zone 21 
version, with component certificate.
Zone 2  Zone 22 
Specifications
Protection IP66, EN 60529
Cover bolts stainless steel - loss-free
Seal silicone
Color RAL 9011 black
Material glass-fibre reinforced polyester, graphitised
Surfaceresistance < 10 GΩ, IEC 60079-0
Impact 7Nm (J), IEC 60079-0
Ambiant temperature (for -40°C - +100°C
the empty enclosure)
Toxic behaviour halogen-free On request
Waterabsorption max.0,7%, ASTM D570 • terminals
Weatherresistance UV-resistant • earthing strip
• entries (metric)
• mounting plate in galvanised steel
• mounting feet
• hinges

Ordering data
Code Dimensions (hxwxd) (mm) Weight Mounting dimensions (mm) Mounting
CP0808-U 75 x 80 x 55 0,23 kg 45 x 68 4 x M4
CP0808D-U 75 x 80 x 75 0,3 kg 45 x 68 4 x M4
CP0811-U 75 x 110 x 55 0,295 kg 45 x 98 4 x M4
CP0811D-U 75 x 110 x 75 0,36 kg 45 x 98 4 x M4
CP0816-U 75 x 160 x 55 0,405 kg 45 x 148 4 x M4
CP0816D-U 75 x 160 x 75 0,46 kg 45 x 148 4 x M4
CP0819-U 75 x 190 x 55 0,45 kg 45 x 178 4 x M4
CP0819D-U 75 x 190 x 75 0,53 kg 45 x 178 4 x M4
CP0823-U 75 x 230 x 55 0,575 kg 45 x 218 4 x M4
CP0823D-U 75 x 230 x 75 0,67 kg 45 x 218 4 x M4
CP1032-U 100 x 320 x 80 1,3 kg 45 x 304 4 x M6
CP1212-U 120 x 120 x 90 0,75 kg 82 x 106 4 x M6
CP1222-U 120 x 220 x 90 1,06 kg 82 x 204 4 x M6
CP1616-U 160 x 160 x 90 1,29 kg 110 x 140 4 x M6
CP1626-U 160 x 260 x 90 1,71 kg 110 x 240 4 x M6
CP1636-U 160 x 360 x 90 2,15 kg 110 x 340 4 x M6
CP1656-U 160 x 560 x 90 3,18 kg 110 x 540 4 x M6
CP2526-U 250 x 255 x 120 2,65 kg 200 x 235 4 x M6
CP2526D-U 250 x 255 x 160 3,275 kg 200 x 235 4 x M6
CP2540-U 250 x 400 x 120 3,650 kg 200 x 380 4 x M6
CP2540D-U 250 x 400 x 160 4,8 kg 200 x 380 4 x M6
CP2560-U 250 x 600 x 120 5,235 kg 200 x 580 4 x M6
CP3636-U 360 x 360 x 90 3,67 kg 310 x 340 4 x M6
CP4140-U 405 x 400 x 120 5,58 kg 355 x 380 4 x M6

22 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Dimensional sketches

Product code Exterior dimensions


C/D A/B E
CP0808-U 75 80 55
CP0808D-U 75 80 75
CP0811-U 75 110 55
CP0811D-U 75 110 75
CP0816-U 75 160 55
CP0816D-U 75 160 75
CP0819-U 75 190 55
CP0819D-U 75 190 75
CP0823-U 75 230 55
CP0823D-U 75 230 75
CP1032-U 100 320 80
CP1212-U 120 120 90
CP1222-U 120 220 90
CP1616-U 160 160 90
CP1626-U 160 260 90
CP1636-U 160 360 90
CP1656-U 160 560 90
CP2526-U 250 255 120
CP2526D-U 250 255 160
CP2540-U 250 400 120
CP2540D-U 250 400 160
CP2560-U 250 600 120
CP3636-U 360 360 90
CP4140-U 405 400 120

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 23


1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP0808 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 27 16 3 1
16 9 18 20 2 1
20 3 10 - 25 1
25 5 - - 32
35 - - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
38,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0808D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 32 16 6 2
16 11 21 20 4 2
20 4 12 - 25 1 1
25 6 - - 32 1
35 - - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
38,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0811 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 28 16 5 1
16 9 18 73 20 3 1
20 4 11 21 25 2
25 5 12 - 32
35 3 - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
68,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0811D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 33 16 8 2
16 11 22 86 20 6 2
20 4 13 25 25 2 1
25 6 14 - 32 1
35 4 - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
68,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -

24 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP0816 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 28 16 8 1
16 9 19 74 20 5 1
20 4 11 21 25 3
25 5 12 - 32
35 3 - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
118,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0816D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 34 16 14 2
16 11 22 87 20 10 2
20 4 13 25 25 3 1
25 6 14 27 32 2
35 4 10 27 40
50 - 8 22 50
Useful length on DIN rail = 63 3 10 - 63
118,5 mm 80 4 - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0819 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 28 16 10 1
16 9 19 74 20 6 1
20 4 11 21 25 4
25 5 12 - 32
35 3 - - 40
50 - - - 50
Useful length on DIN rail = 63 - - - 63
148,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0819D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 33 16 16 2
16 11 22 87 20 12 2
20 4 13 25 25 4 1
25 6 14 27 32 3
35 4 10 26 40
50 8 22 50
Useful length on DIN rail = 63 3 10 36 63
148,5 mm 80 4 11 -
100 4 - -
125 - - -
160 - - -
200 - - -
225 - -
250 -

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 25


1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP0823 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 33 16 8 1
16 11 22 86 20 6 1
20 4 13 25 25 8 1
25 6 14 27 32
35 4 10 26 40
50 8 22 50
Useful length on DIN rail = 63 2 10 36 63
188,5 mm 80 3 11 -
100 4 - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP0823D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 33 16 22 2
16 11 22 86 20 14 2
20 4 13 25 - 25 5 1
25 6 14 27 32 4
35 4 10 26 40
50 8 22 50
Useful length on DIN rail = 63 2 10 36 63
188,5 mm 80 3 11 -
100 4 - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP1032 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 39 16 28 4
16 13 26 102 20 20 3
20 5 15 29 25 7 1
25 7 16 32 32 5 1
35 5 12 31 40
Useful length on DIN rail =
50 10 26 50
274,5 mm
63 3 12 43 63
Minimum ordering
80 4 13 48
quantity;
100 5 12 -
please contact us
125 5 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP1212 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 43 16 8 6
16 14 28 111 20 6 4
20 6 16 32 25 2 2
25 8 18 35 32 2 1
35 5 13 - 40 1 1
50 2 - - 50
Useful length on DIN rail = 63 - - - 63
67,5 mm 80 - - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -

26 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP1222 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 46 16 20 6
16 15 30 119 20 14 4
20 6 18 34 25 5 2
25 8 19 37 32 3 1
35 5 14 36 40 3 1
50 2 12 30 50
Useful length on DIN rail = 63 4 14 50 63
166,5 mm 80 5 15 56
100 6 14 -
125 6 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP1616 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 48 16 15 8
16 16 32 125 20 10 6
20 7 19 36 25 4 2
25 9 20 39 32 2 2
35 6 15 38 40 2 1
50 2 12 32 50 1
Useful length on DIN rail = 63 4 14 - 63
103,5 mm 80 5 - -
100 - - -
125 - - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP1626 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 52 16 30 8
16 18 35 136 20 18 6
20 7 20 39 25 7 2
25 9 22 43 32 4 2
35 6 16 41 40 3 1
50 2 13 34 50 3
Useful length on DIN rail = 63 4 16 57 63
205 mm 80 6 17 64
100 7 16 -
125 6 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP1636 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 53 16 42 8
16 18 35 138 20 26 6
20 7 20 40 25 11 2
25 9 22 43 32 6 2
35 6 17 42 40 5 1
50 2 14 35 50 4
Useful length on DIN rail = 63 4 16 58 63
302 mm 80 6 18 65
100 7 17 -
125 7 - -
160 - - -
200 - - -
225 - -
250 -

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 27


1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP1656 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 53 16 66 8
16 18 35 138 20 40 6
20 7 20 40 25 16 2
25 9 22 43 32 10 2
35 9 17 42 40 8 1
50 2 14 35 50 6
Useful length on DIN rail = 63 4 16 58 63
502 mm 80 6 18 65
100 7 17 -
125 7 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP2526 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 70 16 40 27
16 24 47 182 20 24 21
20 10 27 52 25 10 8
25 13 30 57 32 7 5
35 8 22 56 40 4 3
50 3 18 46 50 3 2
Useful length on DIN rail = 63 6 21 76 63 3 2
197 mm 80 8 24 85
100 10 22 -
125 9 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP2526D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 82 16 40 27
16 28 54 211 20 24 21
20 11 31 61 25 10 8
25 15 34 67 32 7 5
35 10 26 65 40 4 3
50 3 21 54 50 3 2
Useful length on DIN rail = 63 7 25 88 63 3 2
197 mm 80 9 27 99
100 12 26 -
125 10 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP2540 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 76 16 64 27
16 26 50 197 20 42 18
20 10 29 57 25 18 8
25 14 32 62 32 12 5
35 9 24 60 40 6 3
50 3 19 50 50 5 2
Useful length on DIN rail = 63 6 23 82 63 5 2
342 mm 80 9 26 92
100 11 24
125 9 24
160 8 21
200 7 19 -
225 3 10 -
250 5 -

28 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
4 Terminal boxes polyester
1 CONNECTA-P series

Max. number of connections = f(current, cross-section)


Number of terminals = number of connections/2
Type
 Dark blue: number of terminals to be defined by manufacturer
 Light blue: no limit on number of terminals
Max. number of glands/plugs
Cross-section (mm²)
CP2540D Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 87 16 64 27
16 30 58 226 20 42 18
20 12 34 65 25 18 8
25 16 37 71 32 12 5
35 11 28 69 40 6 3
50 4 22 57 50 5 2
Useful length on DIN rail 63 7 26 95 63 5 2
= 342mm 80 10 29 106
100 12 28
125 11 28
160 9 25
200 9 21 -
225 3 12 -
250 6 -
Max. number of glands/plugs
Cross-section (mm²)
CP2560 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 78 16 96 27
16 27 52 202 20 66 21
20 11 30 58 25 28 8
25 14 33 64 32 18 5
35 4 25 62 40 10 3
50 3 20 51 50 8 2
Useful length on DIN rail =
63 6 24 85 63 6 2
542 mm
80 9 26 95
Max. section = 240mm²
100 11 25
125 10 25
160 8 22
200 8 19 59
225 3 11 23
250 6 14
Max. number of glands/plugs
Cross-section (mm²)
CP3636 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 77 16 42 30
16 26 51 199 20 26 22
20 11 30 58 25 11 9
25 14 32 63 32 6 6
35 9 24 61 40 5 4
50 3 20 50 50 4
Useful length on DIN rail = 63 6 23 83 63
329 mm 80 9 26 93
100 11 24 -
125 10 - -
160 - - -
200 - - -
225 - -
250 -
Max. number of glands/plugs
Cross-section (mm²)
CP4140 Current (A) Glands Side
1,5 2,5 4 6 10 16 25 35 50 70 95 120 M A/B C/D
10 92 16 64 51
16 31 61 237 20 42 36
20 13 35 69 25 18 16
25 17 39 75 32 12 9
35 11 29 73 40 6 6
50 4 24 60 50 5 5
Useful length on DIN rail = 63 8 28 99 63 5 4
342 mm 80 10 31 111
100 13 29
125 12 29
160 10 26
200 9 22 70
225 3 13 27
250 7 16

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 29


1 Enclosures, terminal boxes, junction boxes
5 Enclosures stainless steel
1 AR/AQ series

The standard version of the stainless steel (316) boxes are fitted with a
II 2 G Exe II T6/T5
removable cover and closed sides.
Upon request, they are also available with a hinged cover and/or gland II 2 G Exia IIC T6/T5
plates. II 2 G Exe ia IIC T6/T5
Specifications II 2 D Ex tD A21 T85°C/T100°C

Material 316 stainless steel


Protection IP66 Zone 1  Zone 21 
Seal neoprene Zone 2  Zone 22 
Mounting plate stainless steel
INERIS01ATEX0005X
Cover bolts stainless steel, loss-free
Earthing M6 bolt (internal and external)
Ambiant temperature -50°C - +55°C
Mounting 4 mounting eyes

On request
• terminals
• entries
• hinged cover
• gland plates

Ordering data
Code Dimensions (hxwxd) (mm) Mounting plate (mm) Weight
AR-2 196 x 133 x 120 87 x 150 4,00 kg
AR-4 266 x 196 x 135 150 x 220 7,00 kg
AR-6 346 x 266 x 135 220 x 300 9,50 kg
AR-8 496 x 346 x 165 300 x 450 13,00 kg
AR-8A 496 x 496 x 165 450 x 450 14,50 kg
AQ-6 266 x 266 x 165 220 x 220 4,50 kg
AQ-8 346 x 346 x 165 300 x 300 5,75 kg

Dimensional sketches

Product code Exterior dimensions


A B C
AR-2 133 196 120
AR-4 196 266 135
AR-6 266 346 135
AR-8 346 496 165
AR-8A 496 496 165
AQ-6 266 266 165
AQ-8 346 346 165

30 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
5 Enclosures stainless steel
2 NXT series

The boxes of the serie NXT are designed for use in difficult circumstances.
II 2 G EExe II T6
These boxes have a standard version in stainless steel (316L) and are fitted
with a hinged cover. II 2 G EExia IIC T6
Gland plates increases the comfort for usage. II 2 D IP66 T...°C
These boxes are being tailor-made assembled under our ASSEMBL-Y
certificate with terminals, pushbuttons,... Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Material 316L stainless steel KEMA01ATEX2109
Protection IP66
Seal chloroprene
Mounting plate 2 mm thickness, painted
Cover bolts M6 in stainless steel, loss-free
Earthing M10 bolt (brass)
Ambiant temperature (for -40°C - +80°C
the empty enclosure)
Mounting 4 mounting eyes ø 11 mm

On request
• gland plates
• terminals
• entries
• push buttons, signalling lamps, switches in cover

Ordering data
Code Dimensions (hxwxd) (mm) Mounting plate (mm) Number of gland plates Weight
NXT221513-S-1 152 x 229 x 130 89 x 190 1 3,3 kg
NXT221513-S-3 152 x 229 x 130 89 x 190 3 3,3 kg
NXT262616-S-1 260 x 260 x 160 220 x 197 1 5,5 kg
NXT262616-S-3 260 x 260 x 160 220 x 197 3 5,5 kg
NXT262620-S-1 260 x 260 x 205 220 x 197 1 5,5 kg
NXT262620-S-3 260 x 260 x 205 220 x 197 3 5,5 kg
NXT303016-S-1 300 x 300 x 160 243 x 267 1 7,0 kg
NXT303016-S-3 300 x 300 x 160 243 x 267 3 7,0 kg
NXT303020-S-1 300 x 300 x 205 243 x 267 1 7,0 kg
NXT303020-S-3 300 x 300 x 205 243 x 267 3 7,0 kg
NXT382616-S-1 380 x 260 x 160 340 x 197 1 8,3 kg
NXT382616-S-3 380 x 260 x 160 340 x 197 3 8,3 kg
NXT382620-S-1 380 x 260 x 205 340 x 197 1 8,3 kg
NXT382620-S-3 380 x 260 x 205 340 x 197 3 8,3 kg
NXT453816-S-1 458 x 382 x 160 319 x 419 1 9,8 kg
NXT453816-S-3 458 x 382 x 160 319 x 419 3 9,8 kg
NXT453820-S-1 458 x 382 x 205 319 x 419 1 9,8 kg
NXT453820-S-3 458 x 382 x 205 319 x 419 3 9,8 kg
NXT484820-S-1 480 x 480 x 205 417 x 441 1 10,4 kg
NXT484820-S-3 480 x 480 x 205 417 x 441 3 10,4 kg
NXT503520-S-1 500 x 350 x 205 287 x 461 1 10,5 kg
NXT503520-S-3 500 x 350 x 205 287 x 461 3 10,5 kg
NXT624520-S-1 620 x 450 x 205 387 x 581 1 17,0 kg
NXT624520-S-3 620 x 450 x 205 387 x 581 3 17,0 kg
NXT745520-S-1 740 x 550 x 205 487 x 701 1 30,4 kg
NXT745520-S-3 740 x 550 x 205 487 x 701 3 30,4 kg
NXT765020-S-1 762 x 508 x 205 445 x 723 1 23,5 kg
NXT765020-S-3 762 x 508 x 205 445 x 723 3 23,5 kg
NXT866420-S-1 860 x 640 x 205 577 x 821 1 29,0 kg
NXT866420-S-3 860 x 640 x 205 577 x 821 3 29,0 kg
NXT916120-S-1 914 x 610 x 205 547 x 875 1 31,0 kg
NXT916120-S-3 914 x 610 x 205 547 x 875 3 31,0 kg
NXT987420-S-1 980 x 740 x 205 677 x 941 1 38,0 kg
NXT987420-S-3 980 x 740 x 205 677 x 941 3 38,0 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 31


1 Enclosures, terminal boxes, junction boxes
5 Enclosures stainless steel
2 NXT series

Dimensional sketches

Product code Exterior dimensions Mounting plate Mounting


A B C D E F G
NXT221513-S-1 152 229 130 190 98 208 152
NXT221513-S-3 152 229 130 190 98 208 152
NXT262616-S-1 260 260 160 220 197 316 170
NXT262616-S-3 260 260 160 220 197 316 170
NXT262620-S-1 260 260 205 220 197 316 170
NXT262620-S-3 260 260 205 220 197 316 170
NXT303016-S-1 306 306 160 267 243 361 203
NXT303016-S-3 306 306 160 267 243 361 203
NXT303020-S-1 306 306 205 267 243 361 203
NXT303020-S-3 306 306 205 267 243 361 203
NXT382616-S-1 380 260 160 341 197 316 250
NXT382616-S-3 380 260 160 341 197 316 250
NXT382620-S-1 380 260 205 341 197 316 250
NXT382620-S-3 380 260 205 341 197 316 250
NXT453816-S-1 458 382 160 419 319 437 305
NXT453816-S-3 458 382 160 419 319 437 305
NXT453820-S-1 458 382 205 419 319 437 305
NXT453820-S-3 458 382 205 419 319 437 305
NXT484820-S-1 480 480 205 441 417 535 327
NXT484820-S-3 480 480 205 441 417 535 327
NXT503520-S-1 500 350 205 461 287 406 350
NXT503520-S-3 500 350 205 461 287 406 350
NXT624520-S-1 620 450 205 581 387 506 450
NXT624520-S-3 620 450 205 581 387 506 450
NXT745520-S-1 740 550 205 701 487 606 540
NXT745520-S-3 740 550 205 701 487 606 540
NXT765020-S-1 762 508 205 723 445 564 508
NXT765020-S-3 762 508 205 723 445 564 508
NXT866420-S-1 860 640 205 821 577 696 570
NXT866420-S-3 860 640 205 821 577 696 570
NXT916120-S-1 914 610 205 875 547 666 559
NXT916120-S-3 914 610 205 875 547 666 559
NXT987420-S-1 980 740 205 941 677 796 700
NXT987420-S-3 980 740 205 941 677 796 700

32 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
6 Junction boxes Exe plastic
1 BJE series

The plastic boxes are made of polycarbonate resin with a high shock
Ex II 2 G Exe II T6
resistance.
The box is supplied complete with terminals and integrated glands. Ex II 2 D Ex tD A21 IP66 T75°C/T80°C

Specifications
Zone 1  Zone 21 
Protection IP66
Zone 2  Zone 22 
Material polycarbonate resin
Color black LCIE99ATEX6003
Mounting with mounting feet LCIE02ATEX6069

Ordering data
Code Terminals Earthing Voltage Cable entry Weight Ambiant temp. Classification
4 terminals connecting 4 interconnected earthing
Ex II 2 G Exe II T6
range per terminal: max. terminals connecting 4 integrated
BJE1 max. 660V 0,35 kg -50°C - +55°C Ex II 2 D Ex tD A21
2x4mm² + 2x2,5mm² range per terminal: max. glands (8-15 mm)
IP66 T75°C
min. 2x1,5mm² 1x4mm² min. 1x1mm²
4 interconnected earthing
4 terminals connecting Ex II 2 G Exe II T6
terminals connecting 4 x M25 (8-18,5
BJE2-19 range per terminal: max. max. 690V 0,6 kg -40°C - +55°C Ex II 2 D Ex tD A21
range per terminal: max. mm)
3x10mm² + 1x4mm² IP66 T80°C
1x10mm²

Dimensional sketches

BJE2-19
BJE1

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 33


1 Enclosures, terminal boxes, junction boxes
7 Construction site boxes
1 Solid rubber

The solid rubber construction site boxes are available in 2 versions:


II 2 G Ex d e IIC T4
- wall-mounted version (type E50)
- portable version with foot (type E70 + E80) II 2 D Ex tD A21 IP65 T..
The housings are impact-, oil-, acid- and heat-resistant and suited for
outdoor installation (IP65). Zone 1  Zone 21 
The distribution boxes are made according to your specifications and can Zone 2  Zone 22 
be fitted with:
KEMA01ATEX2109
- flange sockets
- circuit breakers behind actuating flap
- earth leakage protection behind actuating flap
- transformers
These boxes are being tailor-made assembled under our ASSEMBL-Y
certificate.
Specifications
Protection IP65
Material solid rubber with metal frame
Ambiant temperature -10°C - +40°C

Ordering data
Code Type Construction
E50 wall single
E70 portable double
E80 portable single

Dimensional sketches

E70
E50

E80

34 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
7 Construction site boxes
2 Cable reel

Extension cords can now be readily used and neatly stored with the
II 2 G Exde IIC T4
explosion-proof cable reel.
The plastic E90 reel is available with a maximum of two sockets and a
25-metre-long cable.
Zone 1  Zone 21 
These cable reels are being tailor-made assembled under our ASSEMBL-Y Zone 2  Zone 22 
certificate. KEMA01ATEX2109
Specifications
Protection IP55
Material plastic
Ambiant temperature -10°C - +40°C

Ordering data
Code Type Voltage Current
E90 cable reel max. 250V max. 16A

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 35


1 Enclosures, terminal boxes, junction boxes
7 Construction site boxes
3 Standard construction site box - type Y11138

Explosion proof construction site box type E80 in solid rubber (impact-, oil-,
II 2 G Ex d e m IIC T4
acid- and heat-resistant) with handle and base.
The construction site box is equipped:
on the entry with a 3 m rubber cable 3 x 2,5 mm² with a 230V plug, 1P+N+E
Zone 1  Zone 21 
and on the output with 2 sockets 12V, 2P and 1 socket 230V, 1P+N+E (= Zone 2  Zone 22 
throughwired). KEMA01ATEX2109
Two transformers of 100VA/230V/12V are included.
Primary as well as secondary protections are provided.
The entire box is assembled and wired.
This box is being tailor-made assembled under our ASSEMBL-Y certificate.
Specifications
Protection IP65
Material solid rubber with metal frame
Cable entry 3 m rubber cable 3 x 2,5 mm²
with plug 230V 1P+N+E
Output - 2 sockets 12V 2P
- 1 socket 230V 1P+N+E (troughwiring)
Transformer 2x 100VA 230V/12V
Protection transformer primary and secondary
Ambiant temperature -10°C - +40°C
* Note sockets and plugs ATX (= brand)
Other brands on request.

Ordering data
Code Type
Y11138 construction site box type E80, fixed and wired

Dimensional sketches

36 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
7 Construction site boxes
4 Transformers

The explosion-proof transformers of the CentaurSlamTrans series are


II 2 G Ex e mb IIC T4 Gb
portable and equipped with a sturdy carrying strap. They have an extreme
impact resistance and weigh less than 20kg. II 2 D Ex t IIIC T70°C Db
They are available in a 200VA (10A max) and a 400VA (16A max) version,
with a choice of 4 x 12VAC or 4 x 24VAC sockets (ATX, other brands upon Zone 1  Zone 21 
request). Zone 2  Zone 22 
The primary side is standard equipped with 10m H07RNF cable.
VTT08ATEX029
The power supply is 230VAC, but can be 110VAC on request.
The transformers are both primary and secondary protected.
Specifications
Protection IP66
Material dissipative elastomer and aluminium
Cable entry 230VAC 10m H07RNF
Protection transformer primary and secondary
Dimensions 532 x 356 x 313 mm

On request
• longer cable
• plug
• other brand for sockets
• 110VAC supply
• set complete with lighting fixtures

Ordering data
Code Supply voltage Output Transformer Current Ambiant temperature Weight
CSTR200EX4C23012 230VAC 4 sockets 12V/2P 200VA 230V/12V max. 10A -20°C - +50°C 17kg
CSTR200EX4C23024 230VAC 4 sockets 24V/2P 200VA 230V/24V max. 10A -20°C - +50°C 17kg
CSTR400EX4C23012 230VAC 4 sockets 12V/2P 400VA 230V/12V max. 16A -20°C - +40°C 19kg
CSTR400EX4C23024 230VAC 4 sockets 24V/2P 400VA 230V/24V max. 16A -20°C - +40°C 19kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 37


1 Enclosures, terminal boxes, junction boxes
7 Construction site boxes
5 Standard transformer

This explosion proof transformer of the CentaurSlamTrans serie is a popular


II 2 G Ex e mb IIC T4 Gb
version equipped with
- 230V entry, 10m H07RN-F cable 3G2.5 with plug II 2 D Ex t IIIC T70°C Db
- 3 sockets 12V, 2P
- 1 socket 230V, 2P+E (= throughwired). Zone 1  Zone 21 
Primary as well as secondary protections are provided. Zone 2  Zone 22 
The transformer is particularly suited to combine with the portable worklights
VTT08ATEX029
on 12V.
Specifications
Protection IP66
Material solid rubber with metal frame
Cable entry 230VAC 10m H07RN-F cable 3G2,5 with plug
Protection transformer primary and secondary
Dimensions 532 x 356 x 313 mm
Ambiant temperature -20°C - +40°C

Ordering data
Code Supply voltage Output Transformer Current
- 3 sockets 12V 2P
CSTR400EX23012/V1 230VAC 400VA 230V/12V max. 16A
- 1 socket 230V 2P+E (troughwired, without fuse)

38 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
1 Serie FS850S

Control unit Ex p FS850S:


II 2 G Ex e mb [ib] [px] IIC T4/T6
- compact
- intelligent II 2 D Ex tD [ibD] [pD] A21 IP65 T70°C
- economic
More information in the document “EX-PRESS pressurized enclosures Zone 1  Zone 21 
Exp”. Zone 2  Zone 22 
Specifications BVS06ATEXE088
Protection IP65, without outlet drill
Material aluminium RAL7035
EEx p configuration LC-Display, menu guided
(parameter input) (different languages: German, English, French
and Dutch)
Storage (memory) by EEPROM double saved
Pneumatic pressure 0 ... 18 mbar
range
Switching capacity - AC: U ≤ 250VAC, l ≤ 5A at cos φ > 0,7
- DC: U ≤ 30VDC, l ≤ 5A, P ≤ 150W
Control circuits intrinsically sasfe Ex ib IIC
(for further details see DMT 99ATEXE003)
Consumption ca. 2,5VA without peripherals
Mounting position - position independent
- only intake and outlet of the control unit
should be lined up on a horizontal axis
Ambiant temperature - -20°C - +45°C (T6)
- -20°C - +60°C (T4)

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 39


1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
1 Serie FS850S

Ordering data
Code Voltage Plate orifice (mm) Range (m³/h)
FS850S.0.0.W 230VAC 4 0,5 ... 1,1
FS850S.0.2.W 230VAC 6 1,1 ... 2,7
FS850S.0.4.W 230VAC 10 2,5 ... 6,5
FS850S.0.6.W 230VAC 14 6,0 ... 11,0
FS850S.0.8.W 230VAC 18 9,0 ... 15,0
FS850S.2.0.W 120VAC 4 0,5 ... 1,1
FS850S.2.2.W 120VAC 6 1,1 ... 2,7
FS850S.2.4.W 120VAC 10 2,5 ... 6,5
FS850S.2.6.W 120VAC 14 6,0 ... 11,0
FS850S.2.8.W 120VAC 18 9,0 ... 15,0
FS850S.3.0.W 110VAC 4 0,5 ... 1,1
FS850S.3.2.W 110VAC 6 1,1 ... 2,7
FS850S.3.4.W 110VAC 10 2,5 ... 6,5
FS850S.3.6.W 110VAC 14 6,0 ... 11,0
FS850S.3.8.W 110VAC 18 9,0 ... 15,0
FS850S.4.0.W 42VAC 4 0,5 ... 1,1
FS850S.4.2.W 42VAC 6 1,1 ... 2,7
FS850S.4.4.W 42VAC 10 2,5 ... 6,5
FS850S.4.6.W 42VAC 14 6,0 ... 11,0
FS850S.4.8.W 42VAC 18 9,0 ... 15,0
FS850S.5.0.W 24VAC 4 0,5 ... 1,1
FS850S.5.2.W 24VAC 6 1,1 ... 2,7
FS850S.5.4.W 24VAC 10 2,5 ... 6,5
FS850S.5.6.W 24VAC 14 6,0 ... 11,0
FS850S.5.8.W 24VAC 18 9,0 ... 15,0
FS850S.6.0.W 24VDC 4 0,5 ... 1,1
FS850S.6.2.W 24VDC 6 1,1 ... 2,7
FS850S.6.4.W 24VDC 10 2,5 ... 6,5
FS850S.6.6.W 24VDC 14 6,0 ... 11,0
FS850S.6.8.W 24VDC 18 9,0 ... 15,0

Dimensional sketches

40 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
1 Serie FS850S

Accessories
Magnetic solenoid valve and adjustable Sinter metal throttle
Code Description Voltage Nozzle Housing volume
SVD.L.2-230VAC digital magnetic solenoid valve 42VAC 2,0 mm
SVD.L.3-42VAC digital magnetic solenoid valve 42VAC 3,0 mm
SVD.L.5-42VAC digital magnetic solenoid valve 42VAC 5,0 mm
SVD.L.1.5-42VAC digital magnetic solenoid valve 42VAC 1,5 mm
SVD.L.4-42VAC digital magnetic solenoid valve 42VAC 4,0 mm
SVD.L.5-110VAC digital magnetic solenoid valve 110VAC 5,0 mm
SVD.L.2-110VAC digital magnetic solenoid valve 110VAC 2,0 mm
SVD.L.3-110VAC digital magnetic solenoid valve 110VAC 3,0 mm
SVD.L.4-110VAC digital magnetic solenoid valve 110VAC 4,0 mm
SVD.L.1-24VAC digital magnetic solenoid valve 24VAC 1,0 mm
SVD.L.1-42VAC digital magnetic solenoid valve 42VAC 1,0 mm
SVD.L.2-24VAC digital magnetic solenoid valve 24VAC 2,0 mm
SVD.L.2-24VDC digital magnetic solenoid valve 24VAC 2,0 mm
SVD.L.3-24VDC digital magnetic solenoid valve 24VAC 3,0 mm
SVD.L.4-24VDC digital magnetic solenoid valve 24VAC 4,0 mm
SVD.L.5-24VDC digital magnetic solenoid valve 24VAC 5,0 mm
SVD.L.1.5-24VDC digital magnetic solenoid valve 24VAC 1,5 mm
SVD.L.1-24VDC digital magnetic solenoid valve 24VAC 1,0 mm
SVD.L.1.5-110VAC digital magnetic solenoid valve 110VAC 1,5 mm
SVD.L.3-24VAC digital magnetic solenoid valve 24VAC 3,0 mm
SVD.L.4-24VAC digital magnetic solenoid valve 24VAC 4,0 mm
SVD.L.5-24VAC digital magnetic solenoid valve 24VAC 5,0 mm
SVD.L.1.5-24VAC digital magnetic solenoid valve 24VAC 1,5 mm
SVD.L.1-110VAC digital magnetic solenoid valve 110VAC 1,0 mm
SVD.L.4-230VAC digital magnetic solenoid valve 230VAC 4,0 mm
SVD.L.5-230VAC digital magnetic solenoid valve 230VAC 5,0 mm
SVD.L.3-230VAC digital magnetic solenoid valve 230VAC 3,0 mm
SVD.L.2-230VAC digital magnetic solenoid valve 230VAC 2,0 mm
SVD.L.1-230VAC digital magnetic solenoid valve 230VAC 1,0 mm
SVD.L.1-120VAC digital magnetic solenoid valve 120VAC 1,0 mm
SVD.L.1.5-230VAC digital magnetic solenoid valve 230VAC 1,5 mm
SVD.L.1.5-120VAC digital magnetic solenoid valve 120VAC 1,5 mm
SVD.L.4-120VAC digital magnetic solenoid valve 120VAC 4,0 mm
SVD.L.5-120VAC digital magnetic solenoid valve 120VAC 5,0 mm
SVD.L.2-120VAC digital magnetic solenoid valve 120VAC 2,0 mm
SVD.L.3-120VAC digital magnetic solenoid valve 120VAC 3,0 mm
SVP.5-110VAC proportional magnetic solenoid valve 110VAC > 300 l
SVP.3-110VAC proportional magnetic solenoid valve 110VAC  300 l
SVP.3-120VAC proportional magnetic solenoid valve 120VAC  300 l
SVP.5-230VAC proportional magnetic solenoid valve 230VAC > 300 l
SVP.3-42VAC proportional magnetic solenoid valve 42VAC  300 l
SVP.5-120VAC proportional magnetic solenoid valve 120VAC > 300 l
SVP.5-24VAC proportional magnetic solenoid valve 24VAC > 300 l
SVP.3-230VAC proportional magnetic solenoid valve 230VAC  300 l
SVP.5-24VDC proportional magnetic solenoid valve 24VAC > 300 l
SVP.3-24VDC proportional magnetic solenoid valve 24VAC  300 l
SVP.3-24VAC proportional magnetic solenoid valve 24VAC  300 l
SVP.5-42VAC proportional magnetic solenoid valve 42VAC > 300 l
Fuse
Code Current Voltage Valve
SI850.0 100 mA 230VAC SVD
SI850.1 160 mA 120-110VAC SVD
SI850.2 200 mA 230VAC SVP
SI850.3 315 mA 110VAC-120VAC SVP
SI850.5 630 mA 24VDC-24VAC SVD
SI850.7 1600 mA 24VDC-24VAC SVP

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 41


1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
1 Serie FS850S

Control unit
Code Type Classification
BT851.0 intelligent operation panel for mounting on the front Ex ib IIC T6
BT851.5 intelligent operation panel in fieldhousing Ex ib IIC T6
BT854.0 operation panel for mounting on the front Ex ib IIC T6
BT854.1 operation panel for mounting on the front with key-operated switch Ex ib IIC T6
BT855.0 operation panel in fieldhousing Ex ib IIC T6
BT855.1 operation panel in fieldhousing with key-operated switch Ex ib IIC T6

42 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
2 Serie FS840

The use of pressurized enclosures allows the operation of ‘non explosion


II 3 G Ex nAC [pz] IIC T6
protected’ devices in hazardous areas zone 2 and 22.
The protection type ‘pressurisation’ is based on the principle of maintaining II 3 D Ex [pD 22] IP54 T70°C
a constant pressure using air or a protective gas to prevent an explosive
mixture forming near the apparatus inside the pressurized enclosure. Zone 1  Zone 21 
More information in the document “Reduced Pressurized System ExnP”. Zone 2  Zone 22 
Specifications TUV03ATEX2095X
Protection IP65, without outlet drill
Material aluminium RAL7035
EEx p configuration LC-Display, menu guided
(parameter input) (different languages: German, English, French
and Dutch)
Storage (memory) by EEPROM double saved
Pneumatic pressure 0 ... 22 mbar
range
Switching capacity - AC: U ≤ 250VAC, l ≤ 5A (AC1), P ≤ 1500VA
- DC: U ≤ 30VDC, l ≤ 4A, P ≤ 150W
Consumption ca. 2VA without peripherals
Mounting position position independent (see drawings)
Ambiant temperature - -20°C - +40°C (T6)
- -20°C - +60°C (T5)

Ordering data
Code Voltage
FS840.0 230VAC
FS840.2 115VAC
FS840.6 24VDC

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 43


1 Enclosures, terminal boxes, junction boxes
8 EX-PRESS pressurized enclosures Exp
2 Serie FS840

Dimensional sketches

Accessories
Magnetic solenoid valve and adjustable Sinter metal throttle
Code Description Voltage Nozzle Housing volume
SD840 adjustable Sinter metal throttle
SVD.L.2-230VAC digital magnetic solenoid valve 42VAC 2,0 mm
SVD.L.3-42VAC digital magnetic solenoid valve 42VAC 3,0 mm
SVD.L.5-42VAC digital magnetic solenoid valve 42VAC 5,0 mm
SVD.L.1.5-42VAC digital magnetic solenoid valve 42VAC 1,5 mm
SVD.L.4-42VAC digital magnetic solenoid valve 42VAC 4,0 mm
SVD.L.5-110VAC digital magnetic solenoid valve 110VAC 5,0 mm
SVD.L.2-110VAC digital magnetic solenoid valve 110VAC 2,0 mm
SVD.L.3-110VAC digital magnetic solenoid valve 110VAC 3,0 mm
SVD.L.4-110VAC digital magnetic solenoid valve 110VAC 4,0 mm
SVD.L.1-24VAC digital magnetic solenoid valve 24VAC 1,0 mm
SVD.L.1-42VAC digital magnetic solenoid valve 42VAC 1,0 mm
SVD.L.2-24VAC digital magnetic solenoid valve 24VAC 2,0 mm
SVD.L.2-24VDC digital magnetic solenoid valve 24VAC 2,0 mm
SVD.L.3-24VDC digital magnetic solenoid valve 24VAC 3,0 mm
SVD.L.4-24VDC digital magnetic solenoid valve 24VAC 4,0 mm
SVD.L.5-24VDC digital magnetic solenoid valve 24VAC 5,0 mm
SVD.L.1.5-24VDC digital magnetic solenoid valve 24VAC 1,5 mm
SVD.L.1-24VDC digital magnetic solenoid valve 24VAC 1,0 mm
SVD.L.1.5-110VAC digital magnetic solenoid valve 110VAC 1,5 mm
SVD.L.3-24VAC digital magnetic solenoid valve 24VAC 3,0 mm
SVD.L.4-24VAC digital magnetic solenoid valve 24VAC 4,0 mm
SVD.L.5-24VAC digital magnetic solenoid valve 24VAC 5,0 mm
SVD.L.1.5-24VAC digital magnetic solenoid valve 24VAC 1,5 mm
SVD.L.1-110VAC digital magnetic solenoid valve 110VAC 1,0 mm
SVD.L.4-230VAC digital magnetic solenoid valve 230VAC 4,0 mm
SVD.L.5-230VAC digital magnetic solenoid valve 230VAC 5,0 mm
SVD.L.3-230VAC digital magnetic solenoid valve 230VAC 3,0 mm
SVD.L.2-230VAC digital magnetic solenoid valve 230VAC 2,0 mm
SVD.L.1-230VAC digital magnetic solenoid valve 230VAC 1,0 mm
SVD.L.1-120VAC digital magnetic solenoid valve 120VAC 1,0 mm
SVD.L.1.5-230VAC digital magnetic solenoid valve 230VAC 1,5 mm
SVD.L.1.5-120VAC digital magnetic solenoid valve 120VAC 1,5 mm
SVD.L.4-120VAC digital magnetic solenoid valve 120VAC 4,0 mm
SVD.L.5-120VAC digital magnetic solenoid valve 120VAC 5,0 mm
SVD.L.2-120VAC digital magnetic solenoid valve 120VAC 2,0 mm
SVD.L.3-120VAC digital magnetic solenoid valve 120VAC 3,0 mm

44 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
1 Production quality assurance notification according to ATEX ...................... 47

2 CONNECTA-P : Terminal boxes Exe/Exi ..................................................... 48

3 ASSEMBL-Y : Exe housings with components ............................................ 49

4 EJB-Y : ExdIIB control and distributionpanels.............................................. 51

5 GUB-Y / EMH-Y : ExdIIC control and distributionpanels.............................. 53

6 EX-PRESS : Enclosures (systems) Exp ...................................................... 55

7 Various solutions .......................................................................................... 57

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 45


2 Assembled housings
1 Production quality assurance notification according to ATEX

Our moto? Strong in custom-made equipment!

With our knowledge and know-how, Ysebaert can provide a customer-oriented solution time and again.

Protection methods
Ysebaert provides enclosures which are suited for gas and dust environments.
Common protection methods are Exd, Exp, ExpD, Exe, ExtD, Exi and their mutual combinations.

Certification
All our assembled enclosures have the EC type-examination certificate, category 2G/2D (zone 1/21) or 1G/1D (zone 0/20) if applicable.
This total certificate comprises the empty enclosure, the mechanical process, the built-in components and the wiring.
The enclosures also bear the obligatory CE mark and the number, referring to our production quality assurance certificate.

Production
Our strongest assets are the expert knowledge of our employees and our state-of-the-art machinery. Thanks to our large stock of empty
enclosures and components, your order is always delivered promptly and correctly.

Testing facilities
To guarantee the quality of our assembled enclosures, Ysebaert makes use of testing facilities such as:
- high-voltage testers
- test gases (helium, carbon dioxide) and analysers for purging tests
- impact test set-up
- temperature metres to determine the temperature class
- ring and plug gauges to check the threads
- test switchboard with adjustable power supplies

Mechanical workshop with CNC machnining


centers Engineering and production co-ordination
Piecework but also series production

Wiring acitivities

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 47


2 Assembled housings
2 CONNECTA-P : Terminal boxes Exe/Exi

CONNECTA-P : Terminal boxes Exe/Exi

The CONNECTA-P series terminal boxes are made of glassfibre-reinforced polyester and offers the best price-quality ratio for terminal
boxes in hazardous areas. This comprehensive series is available for dust environments and for Exe and Exi applications and can be
delivered within 48 hours.

As a standard our boxes are equiped with Phoenix terminals andWiska polyamide cable glands (metric Exe or Exi). On request any
other brand of terminals or cable glands can be used when ATEX approved.

When metal glands are used Threaded earth plates provide a safe earth continuity .

CONNECTA-P terminal box Exi with glands and


removable plugs
CONNECTA-P terminal box Exi with
CONNECTA-P terminal box in Exe version screenterminals and earthrail

CONNECTA-P terminal box Exe II T6 with brass


glands and threaded earth plates EExe

48 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
3 ASSEMBL-Y : Exe housings with components

ASSEMBL-Y : Applications with increased safety enclosures (Exe)

General
Only certified components may be installed in enclosures with an increased safety (Exe). This means that terminals, pushbuttons, lights,
automatic fuses, etc. require a component certificate before they can be installed in an Exe enclosure. These components are not
always readily available, resulting in longer delivery periods. One advantage compared to Exd enclosures is the user-friendliness when
installing and maintaining these components.

Classification
Boxes in which only terminals are installed, are given the classification Exe II; if Exd components are also installed, the classification
becomes Exed IIC (or IIB or IIA).
As in the case of EExd, the temperature class is mostly T6, unless determined otherwise in the certificate.

Certification
Thanks to our framework certificate, Ysebaert can always offer you creative, certified solutions which perfectly meet your wishes.
As an independant manufacturerwe can use and combinecomponents of different manufacturers to one optimal technical solution at a
competitive price; all this of course with a complete certificate of conformity.

EX-EMPTY-1/21
This series of tailor-made housings in SS304 (or SS316) distinguishes itself for its almost unlimited dimensions and possibilities to
create special designs (max wxhxd = 4x3x2m).

Examples:
- A detached housing with pedestal and dimensions wxhxd = 1,2 x 2 x 0,5 m
- A writing desk made following your drawings
- A commander housing with doors at the back (suited for building-in in a wall)
- A “real” IP66 housing for outdoor installation of offshore applications

The unique concept of double bit cam locks located outside the area of the sealing, combined with round-welded corners is deduced
from our Exp-housings EX-PRESS-1/21 and guarantees an IP66 protection degree.

Classification of the empty housing:


II 2 G Ex e II
II 2 D Ex tD A21 IP66

Choice of materials
Enclosures with increased safety are mostly made of plastic (polyester, polycarbonate resin, etc.), but also aluminium, steel or stainless
steel are regularly used. When used as a construction site box, solid rubber is also used.

Applications
Applications where Exe boxes are used:
- terminal boxes
- control boxes (pushbuttons, lights, switches)
- transformers
- distribution boards (with automatic switches)
- construction site boxes with sockets and fuses

Bottom side of stainless steel interface panel


with polyamide glands and plugs Housing Exe series NEXT with terminals and
Inside view of a distribution board with Exe nickel plated glands and plugs
housings and Exde circuit breakers.

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 49


2 Assembled housings
3 ASSEMBL-Y : Exe housings with components

Control panel Exdem with stainless steel


housing

Distributionpanel ExdeIICT4
Interface panel Ex II2G Exde[ib]IICT4

Construction site box Ex II2G ExdeIICT4 with


automatic circuitbreakers

Cable reel ExdeIICT6

Control panel Exde with synoptic

Control panel Exde, housing glassfibre


Stainless steel housing with digital displays Exi
reinforced polyester

Stainless steel housing with digital display Exi

50 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
4 EJB-Y : ExdIIB control and distributionpanels

EJB-Y : Control and distributionpanels ExdIIB+H2

General
Standard equipment may be installed in explosion-proof enclosures. Due to the wide-ranging availability of components such as
magnetic switches, automatic fuses, motor circuit breakers, etc. Exd control boxes can be readily constructed. Components that need to
be replaced after some time, are fairly easily available, which makes the storage of a variety of special parts superfluous.
The components within the box can be controlled externally by means of explosion-proof passing troughs/handles; these are used,
for instance, to rearm automatic fuses or earth leakage protections. To allow for built-in instruments, the box’s cover is fitted with a
rectangular or round window. This way, the instruments are visible without having to open the box.
For the assembly of larger switchboards the Exd boxes are electrically interconnected by means of seals and mounted on a frame.
For more information on our empty enclosures, please consult chapter 1.1.1.

Classification
Boxes with a bolted cover like the series EJB-Y usually have classification Exd IIB. In most cases the temperature class is T6, unless
components are built in that generate a lot of heat. When e.g. transformers are installed, the temperature class will be redefined based
on the dissipated output. So, when components are built in, the limit values mentioned in the certificate and its addenda need to be
taken into account.

Choice of materials
Explosion-proof boxes series EJB-Y are made of aluminium or stainless steel. In addition, a protective coat of paint is applied.

Applications
Applications where Exd boxes are used:
- distribution boards
- instrument enclosures
- terminal boxes
- control boxes
- relay and PLC controls
- motor controls (safeties)
- transformers
- Exi modules
- electronics
- customer-specific components

Inside view of an control box ExdIIB

Control box ExdIIB Control box ExdIIB with window

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 51


2 Assembled housings
4 EJB-Y : ExdIIB control and distributionpanels

Inside view of control box ExdIIB with window Inside view of an control box stainless steel 316 Inside view of an control box ExdIIB with HT
ExdIIB transformer

Control box ExdIIB - bottom view

Inside view of control box ExdIIB with PLC Control box stainless steel 316 ExdIIB

Application on site

52 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
5 GUB-Y / EMH-Y : ExdIIC control and distributionpanels

GUB-Y : Control and distributionpanels ExdIIC

General
Standard equipment may be installed in explosion-proof enclosures. Due to the wide-ranging availability of components such as
magnetic switches, automatic fuses, motor circuit breakers, etc. Exd control boxes can be readily constructed. Components that need to
be replaced after some time, are fairly easily available, which makes the storage of a variety of special parts superfluous.
The components within the box can be controlled externally by means of explosion-proof passing troughs/handles; these are used,
for instance, to rearm automatic fuses or earth leakage protections. To allow for built-in instruments, the box’s cover is fitted with a
rectangular or round window. This way, the instruments are visible without having to open the box.
For the assembly of larger switchboards the Exd boxes are electrically interconnected by means of seals and mounted on a frame.

For more information on the empty enclosures, please consult: chapter 1.2.1 for GUB-Y and chapter 1.2.2 for EMH-Y.

Classification
Boxes with ascrew cover usually have classification Exd IIC.
In most cases the temperature class is T6, unless components are built in that generate a lot of heat.
When e.g. transformers are installed, the temperature class will be redefined based on the dissipated output.
So, when components are built in, the limit values mentioned in the certificate and its addenda need to be taken into account.

Combination with Exe box


Explosion-proof boxes can be combined with an Exe connection and control box. This is mainly the case for Exd IIC boxes with external
controls (switches, pushbuttons, etc.); these control components are hard to fit in a screw cover.
The terminals and controls are then mounted on the built-on Exe box.
This box is electrically and mechanically connected to the Exd box by means of explosion-proof bushings. In certain instances, however,
controls can be fitted in a screw cover (IIC enclosure) by mounting a combined flange.

Choice of materials
Explosion-proof boxes series GUB-Y are made of aluminium; in addition, a protective coat of paint is applied.

Applications
Applications where Exd boxes are used:
- distribution boards
- instrument enclosures
- terminal boxes
- control boxes
- relay and PLC controls
- motor controls (safeties)
- transformers
- Exi modules
- electronics
- customer-specific components

Control box ExdIIC

Inside view of a control box ExdIIC

Inside view of a control box ExdIIC

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 53


2 Assembled housings
5 GUB-Y / EMH-Y : ExdIIC control and distributionpanels

Inside view of a control box ExdIIC

Control box ExdIIC series EMH with window


Inside view of a control box ExdIIC

54 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
6 EX-PRESS : Enclosures (systems) Exp

EX-PRESS : Pressurized housings (systems) Exp

General
The Exp protection method is usually opted for when large and bulky devices, special devices and/or heat-generating apparatuses need
to be installed. Exp boxes tend to have an easier access than Exd boxes. If gas group IIC is required, Exp is opted for, because Exd IIC
enclosures are insufficiently large. Of course, compressed air or an inert gas is required for this protection method.
For more information about the different components of an Exp-system, please consult chapter 1.8.1.
For simplified presurized enclosures for zone 2, please consult chapter 1.8.2.

Classification
In most instances an Exp system has a combined classification. A system complete with box and keyboard, for instance, has
classification Ex p ib IIC T4.
An ATEX certificate for a complete assembly delivered by a Notified Body is a demand of directive 94/9/EG for zone 1 and 21 (category
2G and 2D).
Thanks to our framework certificate and comprehensive testing facilities, we can always offer you a creative, certified solution.

Choice of materials
The Exp enclosure is usually made of stainless steel. Great care is required for the air-tightness and mechanical strength of the box.

Applications
Applications where an Exp overpressure system is used:
- installation of analysers
- installation of computers (screen visible behind glass)
- installation of displays/monitors
- large equipment

Inside view of a mobile unit with pressurized


system
Pressurized system with computersystem

Pressurized panel on site

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 55


2 Assembled housings
6 EX-PRESS : Enclosures (systems) Exp

Inside view of a pressurized panel with control


unit inside
Detail of the control unit

Pressurized panel on site

Special housing for integration into a wall

Exp panel

Exp panel

Inside view of Exp housing Rittal with built-in PC

Exp housing Rittal with built-in PC

56 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
2 Assembled housings
7 Various solutions

Various solutions

General
Our longstanding experience inexplosion safety together with our certified Production Quality Assurance System gives us the
opportunity to assemble control and distribution panels under the responsibility of other manufacturers.
In this case the assembled housings are supplied with a label and CE-declaration of the relevant manufacturer.
In this case we can offer less recurrent solutions according to customer requirements without a time consuming and expensive approval
procedure.
For examples we refer to the pictures section.

Housing ExdIICT6

Housing ExdeIICT6 with integrated UPS


(Uninterruptable Power Supply)

Exd housing with built-on Exe box

Housing ExdeIICT6 with window

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 57


3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22 ....................................... 61
1 Surface - polyester enclosure - e84 .................................................. 61
2 Surface - polyester enclosure - e15 .................................................. 62
3 Surface/recessed - steelplate enclosure ........................................... 64
4 Surface - aluminium enclosure - maintenance free .......................... 66
5 Surface mounting - flameproof enclosure ......................................... 67

2 Fluorescent lamp fittings for zone 2 and 22 ................................................. 68


1 nD16 series ....................................................................................... 68

3 Emergency lighting for zone 1, 2, 21 and 22 ............................................... 69


1 Surface mounting - polyester enclosure ........................................... 69
2 Surface mounting - flameproof enclosure ......................................... 70

4 Emergency lighting for zone 2 and 22 ......................................................... 71


1 nD16 series ....................................................................................... 71

5 Induction lightingQL85, ENDURA ................................................................ 72


1 Endura 150W .................................................................................... 72
2 QL85/165W ....................................................................................... 73

6 Autonomous safety lighting for zone 1, 2, 21 and 22 ................................... 74


1 8860 series ....................................................................................... 74

7 Floodlights for zone 1, 2, 21 en 22 ............................................................... 75


1 FL series - IIB+H2 ............................................................................. 75
2 d3000 / d4000 series - IIC................................................................. 76

8 Floodlights for zone 2 and 22 ....................................................................... 77


1 nD27 series ....................................................................................... 77

9 Autonomous hand lamps ............................................................................. 78


1 Type HS4EX ..................................................................................... 78
2 Type KS-8650 ................................................................................... 79

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 59


10 Portable lamps and floodlights ..................................................................... 80
1 KHLE 70EN - 12/24/42V series for zone 1 and 2 ............................. 80
2 Portable lamps - 24V/230V for zone 1, 2, 21 and 22 ........................ 81
3 Portable floodlight for zone 1, 2, 21 and 22 ...................................... 82
4 Portable worklight for zone 1 ............................................................ 83
5 Portable worklight for zone 1, 2, 21 and 22 ...................................... 84
6 Inspection lighting for zone 1, 2, 21 and 22 ...................................... 86

11 Suspension fittings ....................................................................................... 87


1 EVde series....................................................................................... 87

12 Tank inspection lighting ................................................................................ 89


1 USL06 series .................................................................................... 89
2 USL07 series .................................................................................... 90

13 Back lights for level gauges ......................................................................... 91


1 TNCLS series.................................................................................... 91

60 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
1 Surface - polyester enclosure - e84

These fluorescent lamp fittings are suited for standard fluorescent lamps
II 2 G Ex d e q IIC T4
(2 pins) and provided with an electronic 2-channel ballast. The electronic
ballast switches off at the end of the lamplife (according to IEC 61347-2-3). II 2 D Ex tD A21 IP66 T80°C
With its central locking system the fitting can be readily and safely opened,
as the special prism cover is fitted with hinges. Zone 1  Zone 21 
The standard version of the fittings includes 3 cable glands, making Zone 2  Zone 22 
throughwiring possible on one or two sides.
PTB09ATEX2039
Various accessories are available as an option to mount the fitting.
PTB07ATEX2040
Specifications
PTB09ATEX2031
Housing glass-fibre reinforced polyester
Cover polycarbonate resin, with prism optics
Reflector glass-fibre reinforced polyester, white, hinged
Protection IP66
Electronic ballast Exeq, cos φ 0,95, 2-channel
Electrical connection 3P terminal block (max. 6mm²)
Voltage 220-240VAC/DC - 50/60Hz
Lamp holder TLD (2 pins) On request
Switch Exd • throughwiring (2 terminal blocks)
Cable entry 3 M25 entries (complete with 2 glands and 1 • other cable entries
plug), suited for throughwiring
Mounting by means of 2 threaded bushes M8 for:
- ceiling/wall mounting
- chain mounting
- pipe mounting
Impact 20 Joule

Ordering data
Code Power Weight Ambiant temperature
e840118 1x18W 5,3 kg -20°C - +55°C
e840218 2x18W 5,4 kg -20°C - +55°C
e840136 1x36W 7,5 kg -20°C - +60°C
e840236 2x36W 7,6 kg -20°C - +55°C
e840158 1x58W 9,2 kg -20°C - +55°C
e840258 2x58W 9,2 kg -20°C - +55°C

Dimensional sketches

Product code Dimensions


A B
e840118 400 745
e840218 400 745
e840136 700 1355
e840236 700 1355
e840158 700 1655
e840258 700 1655

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 61


3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
2 Surface - polyester enclosure - e15

These fluorescent lamp fittings are suited for standard fluorescent lamps (2
II 2 G Ex d e q IIC T4 (*T6)
pins) and provided with a 2-channel electronic ballast.
The electronic ballast switches off at the end of the lamplife (according to II 2 D Ex tD A21 IP66 T80°C
IEC 61347-2-3).
With its central locking system the fitting can be readily and safely opened, Zone 1  Zone 21 
as the special prism cover is fitted with hinges. Zone 2  Zone 22 
The standard version of the fittings includes 3 cable glands, making
PTB97ATEX2223
throughwiring possible on one or two sides.
PTB97ATEX2224
Various accessories are available as an option to mount the fitting.
PTB97ATEX2225
Specifications
Housing glass-fibre reinforced polyester
Cover polycarbonate resin, with prism optics
Reflector glass-fibre reinforced polyester, white, hinged
Protection IP66
Electronic ballast Exeq, cos φ 0,95, 2-channel
Electrical connection 3P terminal block (max. 6mm²)
Voltage 220-240VAC/DC - 50/60Hz
Lamp holder TLD (2 pins) On request
Switch EExd
Cable entry 3 M25 entries (complete with 2 glands and 1 • throughwiring (2 terminal blocks)
• three-phase connection
plug), suited for throughwiring
• voltage 110-254 VCA/110-230 VCC
Mounting • by means of 2 threaded bushes M8 for:
- ceiling/wall mounting
- chain mounting
- pipe mounting
• tube mounting ø 42 mm
Impact 20 Joule
* Note Type e 15221 (1x20W) and e 15222 (2x20W)
are available on request with temperature
class T6. In this case Ø 38 mm lamps need to
be used and the ambient temperature must not
be higher than 40°C.

Ordering data
Code Power Weight Mounting Ambiant temperature
e15221 1x18W 7,5 kg 2x M8 threaded bushings -20°C - +60°C
e15222 2x18W 8,0 kg 2x M8 threaded bushings -20°C - +60°C
e15241 1x36W 10,2 kg 2x M8 threaded bushings -20°C - +60°C
e15242 2x36W 10,7 kg 2x M8 threaded bushings -20°C - +60°C
e15261 1x58W 13,5 kg 2x M8 threaded bushings -20°C - +50°C
e15262 2x58W 14,0 kg 2x M8 threaded bushings -20°C - +50°C
e15221PM 1x18W 10,0 kg pole mounting -20°C - +50°C
e15222PM 2x18W 10,5 kg pole mounting -20°C - +50°C
e15241PM 1x36W 13,0 kg pole mounting -20°C - +50°C
e15242PM 2x36W 13,5 kg pole mounting -20°C - +50°C
e15261PM 1x58W 13,5 kg pole mounting -20°C - +50°C
e15262PM 2x58W 14,0 kg pole mounting -20°C - +50°C

62 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
2 Surface - polyester enclosure - e15

Dimensional sketches

e15-PM

e15
Product code Dimensions
A B
e15221 600 786
e15222 600 786
e15241 800 1396
e15242 800 1396
e15261 800 1696
e15262 800 1696
e15221PM 260 786
e15222PM 260 786
e15241PM 410 1396
e15242PM 410 1396
e15261PM 410 1696
e15262PM 410 1696

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 63


3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
3 Surface/recessed - steelplate enclosure

These fluorescent lamp fittings are suited for standard fluorescent lamps (2
II 2 G Ex d e q IIC T4 (T6*)
pins) and provided with an electronic ballast.
The electronic ballast switches off at the end of the lamplife (according to II 2 D Ex tD A21 IP65 T80°C
IEC 61347-2-3).
With its central locking system the fitting can be readily and safely opened, Zone 1  Zone 21 
as the cover is fitted with hinges. This fitting is also suitable for mounting in Zone 2  Zone 22 
a spraying booth.
IBExU02ATEX1018
Specifications
Housing steelplate, powder coating, light grey
(RAL7035)
Cover safety glass, hinged
Reflector steelplate, white, hinged
Protection IP65
Electronic ballast Exeq, cos φ 0,95
Electrical connection 3P terminal block (max. 6 mm²) On request
Voltage 220-240VAC/DC - 50/60Hz • throughwiring
Lamp holder TLD (2 pins) • three-phase connection
Switch Exd with optical indication of switch position • version for zone 2 and 22
Cable entry 3 M25 entries (complete with 2 glands and 1
plug)
Mounting - 2 suspension eyes (H8VP)
- 2 ceiling clamps (15AP)
- recessed frame (EB)
- swivelling arm (SA181/182)
* Note Type e18121EVG and e18122EVG are also
available on request with temperature class
T6. In this case Ø 38 mm lamps need to be
used.

Ordering data
Code Power Housing Weight Mounting Ambiant temperature
e18121EVG 1x18W small 11,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18122EVG 2x18W small 11,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18123EVG 3x18W small 13,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18141EVG 1x36W small 19,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18142EVG 2x36W small 19,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18143EVG 3x36W small 21,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18161EVG 1x58W small 22,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18162EVG 2x58W small 22,0 kg 2 x M8 threaded bushings -20°C - +50°C
e18163EVG 3x58W small 24,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18223EVG 3x18W large 16,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18224EVG 4x18W large 16,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18243EVG 3x36W large 24,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18244EVG 4x36W large 24,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18263EVG 3x58W large 29,0 kg 2 x M8 threaded bushings -20°C - +40°C
e18264EVG 4x58W large 29,0 kg 2 x M8 threaded bushings -20°C - +40°C

64 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
3 Surface/recessed - steelplate enclosure

Dimensional sketches

Product code Dimensions


a b c d e f g h
e18121EVG 324 740 786 93 300 373 720 520
e18122EVG 324 740 786 93 300 373 720 520
e18123EVG 324 740 786 93 300 373 720 520
e18141EVG 324 1350 1396 98 400 373 1330 1050
e18142EVG 324 1350 1396 98 400 373 1330 1050
e18143EVG 324 1350 1396 98 400 373 1330 1050
e18161EVG 324 1650 1696 48 400 373 1630 1350
e18162EVG 324 1650 1696 48 400 373 1630 1350
e18163EVG 324 1650 1696 48 400 373 1630 1350
e18223EVG 388 740 786 93 300 437 720 520
e18224EVG 388 740 786 93 300 437 720 520
e18243EVG 388 1350 1396 98 400 437 1330 1050
e18244EVG 388 1350 1396 98 400 437 1330 1050
e18263EVG 388 1650 1696 48 400 437 1630 1350
e18264EVG 388 1650 1696 48 400 437 1630 1350

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 65


3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
4 Surface - aluminium enclosure - maintenance free

These fluorescent lamp fixtures are fitted with pre-mounted long life lamps.
II 2 G Ex e mb II T6
The patented combination of fitting and lamps gives a 10 years operational
warranty. II 2 D Ex tD A21 IP66 T80°C
The sealed-for-life concept guarantees a high IP-degree.
The tempered glass cover will not discolour which provides a high light Zone 1  Zone 21 
output efficiency. Zone 2  Zone 22 
Electrical connection can be made via spring terminals in the integrated
KEMA08ATEX0163
external junction box.
The electronic ballast switches off at the end of the lamplife (EOL).
Two brackets on a guidance rail assure an easy and quick installation.
Brackets for pole, ceiling or suspension mounting are available as an
option.
Specifications
Housing seawater resistant anodized aluminium
Cover tempered glass
Protection IP66
On request
Electronic ballast Exeq, cos φ 0,95
Electrical connection spring terminals in external junction box (max. • 110/120VAC - 50/60Hz
• color temperature 3000K
6 mm²)
• throughwiring
Voltage 220-264VAC - 50/60Hz • emergency lighting
Colour temperature 4000K • frame for recessed installation
Life 10 years (guaranteed mimimum)
Cable entry 2 x M25 entries
Mounting 2 brackets on guidance rail
Ambiant temperature -20°C - +55°C

Ordering data
Code Power Light intensity Weight
TNAML218 2x18W 2600 lumen 6,6 kg
TNAML236 2x36W 6000 lumen 9,4 kg
TNAML258 2x58W 10400 lumen 12,1 kg

Dimensional sketches

Product code Dimensions


A B
TNAML218 720 738
TNAML236 1100 1118
TNAML258 1630 1648

66 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
1 Fluorescent lamp fittings for zone 1, 2, 21 and 22
5 Surface mounting - flameproof enclosure

These fluorescent lamp fittings have a flameproof enclosure (Exd) with


II 2 G Ex d IIC T6
aluminium endcaps and diffuser of polycarbonate (impact resistant).
These fittings are provided with an electronic ballast and are, due to the II 2 D Ex tD A21 IP66 T85°C
maximum classification ExdIICT6, everywhere applicable.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Housing corrosion and seawater resistant aluminium
with polyurethane paint RAL6003 INERIS02ATEX0039
Cover polycarbonate
Reflector steelplate, white
Protection IP66
Electronic ballast cos φ 0,90
Electrical connection 2P+E (4 mm²)
Voltage 220-230VAC - 50/60Hz
Lamp holder TLD (2 pins)
Switch none, supply voltage to be shut down before On request
opening • emergency lighting
Cable entry 2 entries M20 (without glands) • clamps for pole mounting
Mounting 2 mounting clamps • voltages 12...230Vdc ±10 % / 12...240Vac ±10 %
* Note screw cap attached to the housing by a chain

Ordering data
Code Power Weight Ambiant temperature
EVF-P-118 1x18W 6,0 kg -20°C - +50°C
EVF-P-218 2x18W 8,0 kg -20°C - +50°C
EVF-P-136 1x36W 6,0 kg -20°C - +50°C
EVF-P-236 2x36W 9,0 kg -20°C - +50°C
EVF-P-158 1x58W 8,0 kg -20°C - +50°C
EVF-P-258 2x58W 10,0 kg -20°C - +50°C

Dimensional sketches

Product code Dimensions


A B
EVF-P-118 764 630
EVF-P-218 764 630
EVF-P-136 1374 1240
EVF-P-236 1374 1240
EVF-P-158 1679 1545
EVF-P-258 1679 1545

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 67


3 Lighting
2 Fluorescent lamp fittings for zone 2 and 22
1 nD16 series

These fluorescent lamp fittings are suited for standard fluorescent lamps (2
II 3 G ExnAC IIC T4
pins) and provided with an electronic ballast.
Type nD161/162 has stainless steel clamps (one has to be opened with a II 3 D Ex tD A22 IP65 T80-T100°C
screwdriver) and a hinged cover.
This fitting is admitted in zone 2 as well as zone 22 (dust). Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Housing glass-fibre reinforced polyester TUV00ATEX1541
Cover polycarbonate resin, with prism optics
Reflector glass-fibre reinforced polyester, with fixed-on
components
Locking stainless steel clamps, hinged cover
Protection IP65
Electrical connection 2P terminal block (4 mm²)
On request
Voltage 220-240VAC/DC - 0-50/60Hz
Isolation class II (double isolated) • throughwiring (until max. 5x 2,5 mm²)
Lamp holder TLD (2 pins) • switch will disconnect the supply voltage by open-
Cable entry 2 M20 entries (complete with 2 glands and 1 ing the diffuser mirror reflector
• for high ambient temperature until 50°C
plug)
• emergency lighting
* Note with mounting in open air a breather must be • breather (for mounting in open air)
used. For ambient temperatures < -5°C, lamps • version for recessed mounting
with ø 38 mm must be used,

Ordering data
Code Power Weight Ambiant temperature
nD161118EVG 1x18W 2,2 kg -20°C - +40°C
nD161136EVG 1x36W 2,9 kg -20°C - +40°C
nD161158EVG 1x58W 4,3 kg -20°C - +40°C
nD162218EVG 2x18W 2,9 kg -20°C - +40°C
nD162236EVG 2x36W 5,1 kg -20°C - +40°C
nD162258EVG 2x58W 6,3 kg -20°C - +40°C

Dimensional sketches

Product code Dimensions


A B C
nD161118EVG 662 400 110
nD161136EVG 1272 800 110
nD161158EVG 1572 1000 110
nD162218EVG 662 550 197
nD162236EVG 1272 800 197
nD162258EVG 1572 1000 197

68 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
3 Emergency lighting for zone 1, 2, 21 and 22
1 Surface mounting - polyester enclosure

These emergency lighting fittings are suited for standard fluorescent lamps
II 2 G Ex d e q IIC T4
(2 pins) and provided with an electronic ballast.
The maintenance-free NiCd battery guarantees an emergency autonomy of II 2 D Ex tD A21 IP66 T80°C
1 to 3 hours (see ordering data) with 1 lamp and is mounted in a separate
enclosure on top of the fitting. Zone 1  Zone 21 
The electronic emergency power unit is provided with a safety against deep Zone 2  Zone 22 
discharge and a LED, indicating the proper functioning of the charger.
PTB05ATEX2066
Specifications
Housing glass-fibre reinforced polyester
Cover polycarbonate resin, with prism optics
Reflector glass-fibre reinforced polyester, white, hinged
Protection IP66
Electronic ballast Exeq, cos φ 0,95
Electrical connection L1+L1’+N+PE, 6 mm² max.
On request
Voltage 220-254VAC - 50/60Hz
Battery Exe, NiCd 6V, 4Ah or 7Ah • throughwiring (2 terminal blocks)
Autonomy 1 or 3 hours • three-phase connection
Lamp holder TLD (2 pins)
Switch Exd
Cable entry 2 M25 entries (complete with 2 glands and 1
plug), suited for feed-through
Ambiant temperature -20°C - +55°C
Mounting by means of 2 threaded bushes M8 for:
- ceiling/wall mounting
- chain mounting

Ordering data
Code Power Emergency service Autonomy Weight
e14822/1/4 2x18W 1x18W 1 hour 8,9 kg
e14842/1/4 2x36W 1x36W 1 hour 8,9 kg
e14822/3/7 2x18W 1x18W 3 hours 9,3 kg
e14842/3/7 2x36W 1x36W 3 hours 12,7 kg

Dimensional sketches

Product code Dimensions


A B
e14822/1/4 600 913
e14842/1/4 800 1523
e14822/3/7 600 913
e14842/3/7 800 1523

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 69


3 Lighting
3 Emergency lighting for zone 1, 2, 21 and 22
2 Surface mounting - flameproof enclosure

These fluorescent lamp fittings have a flameproof enclosure (Exd) with


II 2 G Ex d IIC T6
aluminium endcaps and diffuser of polycarbonate (impact resistant).
These fittings are provided with an electronic ballast and are, due to the II 2 D Ex tD A21 IP66 T85°C
maximum classification ExdIICT6, everywhere applicable.
The NiCd battery guarantees in emergency function an autonomy of 1 to Zone 1  Zone 21 
1h30 hour. Zone 2  Zone 22 
Available in permanent and non-permanent execution.
INERIS02ATEX0039
Specifications
Housing corrosion and seawater resistant aluminium
with polyurethane paint RAL6003
Cover polycarbonate
Reflector steelplate, white
Protection IP66
Electronic ballast cos φ 0,95
Electrical connection 4 mm² On request
Voltage 230VAC - 50/60Hz
• clamps for pole mounting
Battery NiCd 3,6V 4Ah
• tension 240VAC
Autonomy 1 hour
Lamp holder TLD (2 pins)
Switch none, supply voltage to be shut down before
opening
Cable entry 2 entries M20 (without glands)
Ambiant temperature -20°C - +50°C
Mounting 2 mounting clamps

Ordering data
Code Normal service Emergency service Autonomy Weight
EVF-P-118-LE-NP 1x18W 1 hour 7,7 kg
EVF-P-118-LE-P 1x18W 1x18W 1 hour 8,0 kg
EVF-P-136-LE-NP 1x36W 1 hour 9,7 kg
EVF-P-136-LE-P 1x36W 1x36W 1 hour 10,0 kg
EVF-P-158-LE-NP 1x58W 1 hour 10,7 kg
EVF-P-158-LE-P 1x58W 1x58W 1 hour 11,0 kg
EVF-P-218-LE-P 2x18W 1x18W 1 hour 8,0 kg
EVF-P-236-LE-P 2x36W 1x36W 1 hour 10,0 kg
EVF-P-258-LE-P 2x58W 1x58W 1 hour 11,0 kg

Dimensional sketches

Product code Dimensions


A B
EVF-P-118-LE-P 764 630
EVF-P-218-LE-P 764 630
EVF-P-136-LE-P 1374 1240
EVF-P-236-LE-P 1374 1240
EVF-P-158-LE-P 1679 1545
EVF-P-258-LE-P 1679 1545
EVF-P-118-LE-NP 764 630
EVF-P-136-LE-NP 1374 1240
EVF-P-158-LE-NP 1680 1545

70 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
4 Emergency lighting for zone 2 and 22
1 nD16 series

These fluorescent lamp fittings are suited for standard fluorescent lamps (2
II 3 G Ex nAC IIC T4
pins) and provided with an electronic ballast. The maintenance-free NiCd
battery guarantees in emergency situation an autonomy of 1 to 3 hours (see II 3 D Ex tD A22 IP65 T80°C
ordering data). This fitting is admitted in zone 2 (gas) as well as zone 22
(dust). Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Housing glass-fibre reinforced polyester TUV00ATEX1541
Cover polycarbonate resin, with prism optics
Reflector glass-fibre reinforced polyester, white, hinged
Protection IP65
Electronic ballast electronic
Electrical connection connector L1+L’+N+E, 2,5 mm² max.
Voltage 230V - 50/60 Hz
Battery Exe, NiCd 6V, 4Ah or 7Ah On request
Autonomy 1 or 3 hours • throughwiring (5x 2,5 mm²)
Lamp holder TLD (2 pins)
Switch none, supply voltage to be shut down before
opening
Cable entry 2 entries M20 (complete with 2 glands and 1
plug)
Ambiant temperature 0°C - +30°C 0°C - +40°C (nD162 1...)
Mounting 2 mounting holes

Ordering data
Code Power Light power factor (%) Autonomy Weight
nD161136/22/1EVG 1x36W 22 1 hour 3,6 kg
nD161158/17/1EVG 1x58W 17 1 hour 4,1 kg
nD162118/35/1EVG 1x18W 35 1 hour 3,6 kg
nD162136/22/1EVG 1x36W 22 1 hour 5,5 kg
nD162158/17/1EVG 1x58W 17 1 hour 6,3 kg
nD162218/35/1EVG 2x18W 35 1 hour 3,6 kg
nD162236/22/1EVG 2x36W 22 1 hour 5,3 kg
nD162258/17/1EVG 2x58W 17 1 hour 6,3 kg
nD161136/10/3EVG 1x36W 10 3 hours 3,9 kg
nD162118/20/3EVG 1x18W 20 3 hours 3,9 kg
nD162136/10/3EVG 1x36W 10 3 hours 5,6 kg
nD162218/20/3EVG 2x18W 20 3 hours 3,6 kg
nD162236/10/3EVG 2x36W 10 3 hours 5,6 kg

Dimensional sketches

Product code Dimensions


A B C
nD161136/22/1EVG 1272 800 110
nD161158/17/1EVG 1575 1100 110
nD162118/35/1EVG 662 550 197
nD162136/22/1EVG 1272 800 197
nD162158/17/1EVG 1575 1100 197
nD162218/35/1EVG 662 550 197
nD162236/22/1EVG 1272 800 197
nD162258/17/1EVG 1575 1100 197
nD161136/10/3EVG 1272 800 110
nD162118/20/3EVG 662 550 197
nD162136/10/3EVG 1272 800 197
nD162218/20/3EVG 662 550 197
nD162236/10/3EVG 1272 800 197

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 71


3 Lighting
5 Induction lightingQL85, ENDURA
1 Endura 150W

Induction lighting is characterised by a very long life (at least 60,000


II 2 G Ex d e IIC T4
hours), a direct ignition, flicker-free operation, insensitivity to temperature
fluctuations and is suited for DC voltage.
With its very long life this lighting can be used in hard-to-reach places and
Zone 1  Zone 21 
places where light is absolutely needed (no lamps need to be replaced for Zone 2  Zone 22 
at least 7 years of continuous use). PTB99ATEX2065
Specifications
Housing galvanised steel, painted RAL7035 (grey)
Cover safety glass (impact-resistant), hinged
Reflector mirror reflector made of anodised aluminium
Protection IP65
Electrical connection L+N+PE 2,5mm²
Voltage 220-240VAC/DC -10% +6%, 0/50-60Hz
Cable entry 1 gland and 1 EExe M25 plug
Mounting mounting brackets on the side of the fitting
Specifications lamp On request
Life 60.000 hours • other mounting possibilities
Light intensity 12.000 lumen
Colour reproduction Ra 80 (very good)
Colour temperature 4.000 K

Ordering data
Code Power Weight Ambiant temperature
e2070/150 150W 12 kg -30°C - +40°C

Dimensional sketches

72 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
5 Induction lightingQL85, ENDURA
2 QL85/165W

Induction lighting is characterised by a very long life (at least 60,000


II 2 G Ex d e IIC T6
hours), a direct ignition, flicker-free operation, insensitivity to temperature
fluctuations and is suited for DC voltage.
With its very long life this lighting can be used in hard-to-reach places and
Zone 1  Zone 21 
places where light is absolutely needed (no lamps need to be replaced for Zone 2  Zone 22 
at least 7 years of continuous use). PTB98ATEX1122
Specifications
Housing aluminium with powder coating, RAL7035
(grey)
Cover safety glass fluctuation of temperature
resistant
Protection IP66/67
Electrical connection L+N+PE 6 mm²
Voltage 220-240VAC/DC, 0/50-60Hz
Cable entry 1x M25 with gland
Mounting see mounting accessories
Specifications lamp
Life 60.000 hours On request
Light intensity 85W - 6.000 lumen
• several cable entries
165W - 12.000 lumen
• protection cast guard
• reflector

Ordering data
Code Power Weight Ambiant temperature
d6300/085QLEVG 85W 14,5 kg -20°C - +40°C
d6300/165QLEVG 165W 14,5 kg -20°C - +40°C

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 73


3 Lighting
6 Autonomous safety lighting for zone 1, 2, 21 and 22
1 8860 series

Testing autonomous safety lighting in hazardous areas requires special


II 2 G Ex d IIC T6
procedures and is very labour-intensive.
A safety lighting with active self-test function greatly enhances the safety. II 2 D Ex tD A21 IP66/67 T80°C
The fitting tests its emergency function itself at regular intervals, while the
lamp and battery are permanently checked. Zone 1  Zone 21 
Every six months the battery is completely discharged and recharged, Zone 2  Zone 22 
whereby the battery’s capacity is checked: this also increases the battery’s
LCIE97ATEX6012
life.
Errors are clearly signalled by means of 3 red LEDs (lamp - battery -
electronics).
The user can quickly determine whether the error itself can be corrected
(lamp, battery) or whether the electronics need to be repaired by the
manufacturer.
Its active self-test function allows significant savings on testing costs and
On request
unnecessary replacements.
It is available in a permanent and non-permanent version and with an • pictograms
• variant voltages
autonomy of 1 to 3 hours.
• potential-free make-and-break contacts for exter-
Specifications nal signalling
Housing borosilicate glass with aluminium ends, painted
RAL7038
Seal O-ring
Protection IP66/67
Voltage 230V - 50Hz
Earthing in- and external earthing bolts
Autonomy 1 or 3 hours
Self-test function standard
Cable entry 2 M20x1.5 entries without glands
Mounting with 2 suspension brackets

Ordering data
Code Lamp Autonomy Voltage Weight
8860-EX-A-1-ZT 2xTL 8W 1 hour 230V-50Hz 7.5 kg
8860-EX-A-3-ZT 2xTL 8W 3 hours 230V-50Hz 7.5 kg
8860-EX-B-1-ZT 1xTL 8W 1 hour 230V-50Hz 7.0 kg
8860-EX-B-3-ZT 1xTL 8W 3 hours 230V-50Hz 7.0 kg

Dimensional sketches

74 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
7 Floodlights for zone 1, 2, 21 en 22
1 FL series - IIB+H2

The FL floodlights with built-in ballast are available for halogen and
II 2 G Ex d e IIB+H2 T3
discharge lamps.
The integrated gasket in the flange guarantees a water-tightness of IP65. II 2 D Ex tD A21 IP65 T200°C
The use of stainless steel for the mounting bracket and bolts makes the
floodlight suited for very aggressive environments. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Housing corrosion- and saltwaterproof aluminium with INERIS00ATEX0023X
polyurethane paint (anti-condenstion paint
inside)
Cover bolts stainless steel, loss-free
Seal special fixed cover seal (integrated in the
flange)
Protection IP65
Lamp included (mounted)
Lamp holder E40
Reflector aluminium, polished
Electrical connection Exe connection box with 4 terminals 4 mm²
(through-wiring)
On request
Condensator standard for cos φ 0,90
Earthing in- and external M6 earthing bolt • version in stainless steel
Ambiant temperature -20°C - +40°C • horizontal anti-blinding grid
Mounting bracket stainless steel, adjustable • vertical anti-blinding grid
• ambiant temperature -30°C - +50°C

Ordering data
Code Power Lamp Voltage Weight
FL-50-HA-V-L 500W halogen 220V 19 kg
FL-2x70-HA-V-L 2X70W halogen 24V 20 kg
FL-25-IM-V-C-L 250W metal iodide 230V-50 Hz 22 kg
FL-40-IM-V-C-L 400W metal iodide 230V-50 Hz 23 kg
FL-25-SA-V-C-L 250W high-press. sodium 230V-50 Hz 22 kg
FL-40-SA-V-C-L 400W high-press. sodium 230V-50Hz 23 kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 75


3 Lighting
7 Floodlights for zone 1, 2, 21 en 22
2 d3000 / d4000 series - IIC

Floodlights d3000 and d4000 with built-in ballast are available for halogen
II 2 G Ex d e IIC T2-T3-T4
and discharge lamps.
In case of need, a capacitor box can be mounted on the back side of the II 2 D Ex tD A21 IP67 T100-T270°C
floodlight.
Mounting and replacing of a lamp can be done by opening the screwcover Zone 1  Zone 21 
on the side of it what makes this floodlight suitable for gas group IIC. Zone 2  Zone 22 
Extreme protection class of IP67.
PTB04ATEX1023
Specifications
PTB03ATEX1164
Housing weather-resistant aluminium
Cover bolts stainless steel
Reflector aluminium, anodized
Protection IP67
Electrical connection Exe-connection box with terminals
4 mm² L1 + N + PE
Voltage 220-240VAC - 50/60Hz
Lamp holder E40
Cable entry 1 gland and 1 plug M25 (plastic)
Ambiant temperature -20°C - +40°C
Mounting bracket steel, adjustable

On request
• capacitor
• ambient temperature 55°C
• voltage 120VAC

Ordering data
Code Power Lamp Temp. class Max. surface temp. Weight
d3000/125 125W high pressure mercury vapour T4 120°C 24,2 kg
d3000/150HI 150W halogen metal vapour T4 120°C 25,0 kg
d3000/150HS 150W high pressure sodium vapour T4 130°C 25,0 kg
d3000/250QT 250W halogen T3 170°C 23,0 kg
d3000/250 250W high pressure mercury vapour T3 150°C 25,0 kg
d3000/250HI 250W halogen metal vapour T3 160°C 25,0 kg
d3000/250HS 250W high pressure sodium vapour T3 160°C 25,0 kg
d3000/500QT 500W halogen T2 240°C 23,0 kg
d4000/250 250W high pressure mercury vapour T4 140°C 33,0 kg
d4000/250HI 250W metal vapour T4 140°C 33,0 kg
d4000/250HS 250W high pressure sodium vapour T4 140°C 33,0 kg
d4000/400HI 400W metal vapour T3 200°C 33,5 kg
d4000/400HS 400W high pressure sodium vapour T3 200°C 33,5 kg
d4000/500QT 500W halogen T3 200°C 29,5 kg
d4000/600HS 600W high pressure sodium vapour T3 200°C 38,5 kg
d4000/1000QT 1000W halogen T2 270°C 29,5 kg

Dimensional sketches

d3000 d4000

76 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
8 Floodlights for zone 2 and 22
1 nD27 series

The nD2770 / nD2780 floodlights with built-in ballast are available for
II 3 G Ex nR II T3/T4
halogen and discharge lamps.
They are permitted in zone 2 (gas) aswell as zone 22 (dust). II 3 D Ex tD A22 IP66/67 T130-T200°C

Specifications
Zone 1  Zone 21 
Housing weather-resistant aluminium, RAL9005
Zone 2  Zone 22 
Cover bolts stainless steel
Reflector aluminium, polished TUV00ATEX1653
Protection IP66 / 67
Electrical connection connection box with terminals
L1+N+PE 2,5 mm²
Voltage 220-240VAC - 50/60Hz
Cable entry 1 gland and 1 plug M20
Mounting bracket aluminium, adjustable

On request
• screw clamps 6 mm² (only for nD2780)
• special coating (offshore application)

Ordering data
Max. surface
Code Power Lamp Lamp holder Temp. class temp. Ambiant temperature Weight
nD2770-100-E27 100W halogen E27 T3 160°C -30°C - +50°C 3,4 kg
nD2770-150-E27 150W halogen E27 T3 180°C -30°C - +50°C 3,4 kg
nD2770-080-HGL 80W high pressure mercury vapour E27 T3 170°C -30°C - +50°C 4,5 kg
nD2770-125-HGL 125W high pressure mercury vapour E27 T3 200°C -30°C - +40°C 4,5 kg
nD2770-070-HS 70W high pressure sodium E27 T3 150°C -30°C - +50°C 4,5 kg
nD2770-110-HS 110W high pressure sodium E27 T3 180°C -30°C - +40°C 4,5 kg
nD2780-250-E27 250W halogen E27 T3 150°C -30°C - +50°C 8,0 kg
nD2780-500-E40 500W halogen E40 T3 190°C -30°C - +40°C 8,0 kg
nD2780-150-HS 150W high pressure sodium E40 T4 130°C -30°C - +50°C 9,4 kg
nD2780-250-HS 250W high pressure sodium E40 T3 170°C -30°C - +50°C 10,8 kg
nD2780-400-HS 400W high pressure sodium E40 T3 190°C -30°C - +40°C 13,3 kg
nD2780-250-HGI 250W mercury vapour E40 T3 170°C -30°C - +40°C 10,8 kg
nD2780-400-HGI 400W mercury vapour E40 T3 190°C -30°C - +40°C 13,3 kg

Dimensional sketches

nD2770, nD2780,

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 77


3 Lighting
9 Autonomous hand lamps
1 Type HS4EX

The HS4EX is a multifunctional hand lamp with emergency lighting and


II 2 G EExe ib IIC T4
flashlight functions.
Especially suited as inspection lamp and signalling lamp.
Specific characteristics are:
Zone 1  Zone 21 
- 6 hours of halogen light Zone 2  Zone 22 
- on/off switch TUV07ATEX553783X
- adjustable handle
- weighs only 950 g
- belt clip
- capacity indicator
- automatic charger 230VAC-12/24VDC
- maintenance-free gel battery (no memory effect)
- emergency function in case of mains loss
- automatic switch-over from primary lamp to secondary lamp in case of
malfunctioning primary lamp and excessive battery discharge
- flashlight function
Specifications
Housing impact-resistant plastic
Battery maintenance-free gel battery 4V/3,5Ah
Dimensions 104x245x72mm (LxHxP)
Weight 0,950 kg
Ambiant temperature -20°C - +50°C
Specifications Charger
Supply voltage 230 VAC
12 or 24VDC
Mounting wall mounting
Charger dimensions 114x123x64mm
Charger weight 0,5 kg
Delivery, Set consisting of
Delivery content hand-held floodlight
charger
connection cables 230V and 12/24V
2 ancillary lenses (clear and yellow)

Ordering data
Code Primary lamp Secondary lamp Autonomy
HS4EX halogen 4,0V/2W light bulb 3,7V/1,1W 6 hours

Dimensional sketches

78 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
9 Autonomous hand lamps
2 Type KS-8650

The KS-8650 is a small and lightweight LED hand lamp with 3 steps.
II 2 G Ex ia IIC T4
The autonomy depends on the used light intensity, and differs between 10
and 27 hours.
The belt clip and included wristband facilitate the fixing.
Zone 1  Zone 21 
Zone 2  Zone 22 
Specifications
Housing impact-resistant plastic IBEXU08ATEX1118
Protection IP67
Battery lithium battery 3,2V/3Ah
Weight 0,160 kg
Ambiant temperature -20°C - +60°C
Delivery content handlamp
charger
wristband

On request
• green or yellow housing

Ordering data
Code Lamp Power Autonomy Temperature class
KS-8650 LED 3000 / 2000 / 1000 lux 10 / 14 / 27 hours T4

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 79


3 Lighting
10 Portable lamps and floodlights
1 KHLE 70EN - 12/24/42V series for zone 1 and 2

The KHLE 70EN portable lamps are fitted with a halogen lamp of 12, 24 or
II 2 G EEx de IIC T3/T4
42V, providing a powerful beam of light.
The lamp is used during inspections, maintenance and cleaning of boilers,
silos, etc.
Zone 1  Zone 21 
The standard version includes a lamp, carrying strap, on/off switch, trumpet Zone 2  Zone 22 
gland and a rubber protection against shocks. BVS03ATEXE279
A cable with plug is available on request.
Specifications
Housing light metal, handle made of impact-resistant
plastic, rubber protection
Protection IP54
Lamp halogen
Lamp holder H3
Features - leather carrying strap
- on/off switch
- trumpet gland

Ordering data
Code Power Voltage Temperature class Weight
KHLE70EN12/55 55W 12V T4 2,5kg
KHLE70EN24/70 70W 24V T3 2,5kg
KHLE70EN42/65 65W 42V T3 2,5kg

Dimensional sketches

80 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
10 Portable lamps and floodlights
2 Portable lamps - 24V/230V for zone 1, 2, 21 and 22

The e8310 lamps are suited for incandescent lamps up to 60W and
II 2 G Ex e II T3-T4
voltages of 24-42V AC/DC and 220-230V AC/DC.
The standard version is fitted with a handle, rubber protection rings and a II 2 D Ex tD A21 IP65 T145°C
galvanised protective guard.
A cable with plug can be mounted on request. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Housing handle and protection rings made of rubber, PTB01ATEX2144
guard of galvanised steel
Protection IP65
Lamp incandescent lamp (not included)
Lamp holder E27
Isolation class II (double insulation)
Ambiant temperature -20°C - +40°C

Ordering data
Code Power Voltage Temperature class Weight
e8310ATEX 25W 220-230V T4 2,3kg
e8310ATEX 40W 220-230V T4 2,3kg
e8310ATEX 60W 220-230V T4 2,3kg
e8310ATEX 25W 24-42V T3 2,3kg
e8310ATEX 40W 24-42V T3 2,3kg
e8310ATEX 60W 24-42V T3 2,3kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 81


3 Lighting
10 Portable lamps and floodlights
3 Portable floodlight for zone 1, 2, 21 and 22

The portable floodlight is extremely suitable as temperary (additional)


II 2 G Ex d IIC T3/T4
lighting during maintenance activities.
II 2 D Ex tD A21 IP66 T142°C/T120°C
Specifications
Housing aluminium (grey painted) Zone 1  Zone 21 
Seal O-ring
Protection IP66
Zone 2  Zone 22 
Electrical connection 2 x 2 x 2,5 mm² LCIE02ATEX6227
Voltage 12-24V AC/DC
Earthing internal and external earthing bolt
Lamp halogen
Lamp holder H3
Cable entry M20
Ambiant temperature -40°C - +55°C
Mounting bracket adjustable

On request
• built-in transformer for power supply 230V and
110V
• ambient temperature up to +55°C

Ordering data
Code Power Voltage Temperature class Weight
LG-95149 55W 12VAC/DC T4 8 kg
LG-95150 70W 24VAC/DC T4 8 kg

Dimensional sketches

82 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
10 Portable lamps and floodlights
4 Portable worklight for zone 1

The Slam Hornet 3x40W Ex Worklight allows you to have a high, 180°
II 2 G EEx em II T3
spread, light output at a low power consumption.
The unit withstands thermal and mechanical shocks and is suitable for use
in the most harsh environments.
Zone 1  Zone 21 
This fixture can stand on the ground in a number of different positions or Zone 2  Zone 22 
can be attached to scaffolding/staging as a more permanent fixture. VTT03ATEX042
The outer polycarbonate tube has an anti-static protective film which is
replaceable, thus assuring optimum light output.
The Slam Hornet 3x40W Worklight can be equipped with output sockets
allowing units to be linked together.
Specifications
Housing polycarbonate enclosure around an aluminium
frame
Protection IP54
Dimensions 750 x 300 x 250 mm
Ballast electronic
Electrical connection 10m cable type H07RN-F
Lamp 3 fluorescent tubes
Life +/- 10.000 hours
Light intensity 10.500 lumen On request
Consumption 120W
Weight 10 kg • carrying strap
• plug
Ambiant temperature -20°C - +40°C
• recessed sockets
• magnets for easy attachment to metal structures
• other type of cable
• other cable length
• metallic cable gland
• suply voltage 42VAC/DC or 110VAC/DC

Ordering data
Code Voltage Power
SH340-32210Z000 24VAC/DC 3x40W
SH340-63210Z000 230VAC/DC 3x40W

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 83


3 Lighting
10 Portable lamps and floodlights
5 Portable worklight for zone 1, 2, 21 and 22

Due to its low weight and the included carrying strap, the Slam Hornet Ex
II 2 G Ex e mb IIC T3 Gb
Worklight is truly portable!
It is extremely reliable, requires virtually no maintenance and has a high II 2 D Ex t IIIC T90°C Db IP66
light output.
The electronic components of the Slam Hornet are protected by Zone 1  Zone 21 
encapsulation. Zone 2  Zone 22 
All the mountings are flexible and the alloy profile give the unit immense
VTT08ATEX066
strength.
The outer polycarbonate tube has an anti-static protective film which is
replaceable, thus assuring optimum light output.
The Slam Hornet can be equipped with an output socket allowing units to
be linked together.
Specifications
Housing polycarbonate enclosure around an aluminium
frame
On request
Protection IP66
Ballast electronic • plug
Electrical connection 5m cable type H07RN-F • recessed socket
Lamp compact fluorescent lamp • magnets for easy attachment to metal structures
• other type of cable
Life +/- 10.000 hours
• other cable length
Ambiant temperature -20°C - +40°C • suply voltage 42VAC/DC or 110VAC/DC

Ordering data
Code Voltage Power Light intensity Weight
SH118-12205Z000 12VAC 1x18W 1200 lumen 0,75 kg
SH218-12205Z000 12VAC 2x18W 2400 lumen 1,5 kg
SH118-22205Z000 12VDC 1x18W 1200 lumen 0,75 kg
SH118-32205Z000 24VAC/DC 1x18W 1200 lumen 0,75 kg
SH118-63205Z000 230VAC/DC 1x18W 1200 lumen 0,75 kg
SH136-22205Z000 12VDC 1x36W 2900 lumen 1,65 kg
SH136-32205Z000 24VAC/DC 1x36W 2900 lumen 1,65 kg
SH136-63205Z000 230VAC/DC 1x36W 2900 lumen 1,65 kg
SH236-32205Z000 24VAC/DC 2x36W 5800 lumen 2,70 kg
SH236-63205Z000 230VAC/DC 2x36W 5800 lumen 2,70 kg
SHL236-22205Z000 12VDC 2x36W 5800 lumen 3,00 kg
SHL236-32205Z000 24VAC/DC 2x36W 5800 lumen 3,00 kg
SHL236-63205Z000 230VAC/DC 2x36W 5800 lumen 3,00 kg

84 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
10 Portable lamps and floodlights
5 Portable worklight for zone 1, 2, 21 and 22

Dimensional sketches

Product code Dimensions


L Ø
SH118-12205Z000 335 115
SH218-12205Z000 575 115
SH118-22205Z000 335 115
SH118-32205Z000 335 115
SH118-63205Z000 335 115
SH136-22205Z000 535 115
SH136-32205Z000 535 115
SH136-63205Z000 535 115
SH236-32205Z000 865 115
SH236-63205Z000 865 115
SHL236-22205Z000 1020 115
SHL236-32205Z000 1020 115
SHL236-63205Z000 1020 115

Mounting accessories
Code Description Picture

SH-B double bracket

SH-H hook

SH-HC centered hook

SH-HG handle

SH-M magnet

SH-O eye mounting

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 85


3 Lighting
10 Portable lamps and floodlights
6 Inspection lighting for zone 1, 2, 21 and 22

The Slam Hornet 3x3W LED is designed and certified to the latest
II 2 G Ex e mb op is IIC T4 Gb
standards and is suitable for use in zone 1, 2, 21 and 22.
Its limited size and low weight make this lamp ideal for use in narrow II 2 D Ex t IIIC IP66 T75°C Db
spaces
Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Housing polycarbonate VTT09ATEX001
Protection IP66
Lamp high intensity LED
Electrical connection 5m cable
Life +/- 50.000 hours
Weight 0,65 kg
Ambiant temperature -20°C - +40°C

On request
• version for zone 0

Ordering data
Code Voltage Power
SH3x3LED-24-IIC 24VAC/DC 3x3W
SH3x3LED-42-IIC 42VAC/DC 3x3W
SH3x3LED-110-IIC 110VAC/DC 3x3W
SH3x3LED-230-IIC 230VAC 3x3W

Dimensional sketches

86 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
11 Suspension fittings
1 EVde series

The suspension fittings of the EV series are available for discharge lamps.
II 2 G Ex d e IIC T3/T4/T5
The ballast and starter are built in, making a separate enclosure
superfluous. II 2 D Ex tD A21 IP65 T200°C/T135°C/T100°C
The Exe connection box and the mounting bracket grant a quick installation.
A variety of options are available, including protective guard, reflector, Zone 1  Zone 21 
refractor, etc. Zone 2  Zone 22 
Specifications INERIS01ATEX0019X
Housing corrosion- and saltwaterresistant aluminium
with polyurethane painting RAL6003
Protection IP65
Electronic ballast standard for cos φ 0,90
Electrical connection Exe connection box with 4 terminals of 4mm² +
earthing clamp
Cable entry 2 entries M25
Ambiant temperature -30°C - +40°C
Mounting with adjustable stainless steel bracket

On request
• ambient temperature -40°C - +60°C

Ordering data
Code Power Lamp Temperature class Max. surface temp. Weight
EVde2-HG050-VCL 50W mercury discharge lamp T4 135°C 5,4 kg
EVde2-HG080-VCL 80W mercury discharge lamp T4 135°C 5,5 kg
EVde3-HG125-VCL 125W mercury discharge lamp T3 200°C 7,4 kg
EVde4-HG250-VCL 250W mercury discharge lamp T3 200°C 14,8 kg
EVde5-HG400-VCL 400W mercury discharge lamp T3 200°C 17,8 kg
EVde2-NA070-VCL 70W high-pressure sodium T4 135°C 6,0 kg
EVde4-NA100-VCL 100W high-pressure sodium T3 200°C 7,6 kg
EVde4-NA150-VCL 150W high-pressure sodium T3 200°C 8,4 kg
EVde4-NA250-VCL 250W high-pressure sodium T3 200°C 15,0 kg
EVde5-NA400-VCL 400W high-pressure sodium T3 200°C 18,0 kg
EVde4-IM250-VCL 250W metal iodide T3 200°C 15,0 kg
EVde5-IM400-VCL 400W metal iodide T3 200°C 18,0 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 87


3 Lighting
11 Suspension fittings
1 EVde series

Dimensional sketches

EVde2 - 4 EVde5
Product code Dimensions
A B C D
EVde2-HG050-VCL 163 467 680 160
EVde2-HG080-VCL 163 467 680 160
EVde3-HG125-VCL 195 472 686 160
EVde4-HG250-VCL 220 535 748 160
EVde5-HG400-VCL 281 758 972 160
EVde2-NA070-VCL 163 467 680 160
EVde4-NA100-VCL 220 535 748 160
EVde4-NA150-VCL 220 535 748 160
EVde4-NA250-VCL 220 535 748 160
EVde5-NA400-VCL 281 758 972 160
EVde4-IM250-VCL 220 535 748 160
EVde5-IM400-VCL 281 758 972 160

88 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
12 Tank inspection lighting
1 USL06 series

The compact USL tank inspection lighting is especially designed to


II 2 G EExde IIC T3/T4
illuminate the interior of boilers, tanks, reactors, etc. and fits on all common
sight glass fittings. II 2 D IP67 T195°C/T130°C

Specifications
Zone 1  Zone 21 
Housing corrosion-resistant aluminium alloy G-Al Si 12
Zone 2  Zone 22 
Mg
Seal O-ring (VITON) PTB99ATEX1157 (zone 1+2)
Protection IP67 BVS06ATEXE009 (zone 21+22)
Lamp halogen lamp
Earthing in- and exterior earthing bolt
Cable entry Exe connection box with M20 trumpet gland
Ambiant temperature -20°C - +40°C
Mounting by means of 1 included central hinged bracket
made of stainless steel (M8 fastener)
Sight glass fittings the fittings fit on sight glass fittings from size
DN50

On request
• built-in timer (switch-on time 5 min.)

Ordering data
Code Halogen lamp Supply voltage Lamp holder Transformer Timer (5 min) Temp. class Weight
USL06EX01220 12V-20W 12V GY6.35   T4 1.8 kg
USL06EX01220T 12V-20W 12V GY6.35   T4 1.8 kg
USL06EX02420 24V-20W 24V G4   T4 1.8 kg
USL06EX02420T 24V-20W 24V G4   T4 1.8 kg
USL06EX23020 12V-20W 230V GY6.35   T4 2.4 kg
USL06EX23020T 12V-20W 230V GY6.35   T4 2.4 kg
USL06EX01235 12V-35W 12V GY6.35   T4 1.8 kg
USL06EX01235T 12V-35W 12V GY6.35   T4 1.8 kg
USL06EX01250 12V-50W 12V GY6.35   T3 1.8 kg
USL06EX01250T 12V-50W 12V GY6.35   T3 1.8 kg
USL06EX02450 24V-50W 24V GY6.35   T3 1.8 kg
USL06EX02450T 24V-50W 24V GY6.35   T3 1.8 kg
USL06EX23050 230V-50W 230V GZ10   T4 1.8 kg
USL06EX23050T 230V-50W 230V GZ10   T4 1.8 kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 89


3 Lighting
12 Tank inspection lighting
2 USL07 series

The compact USL tank inspection lighting is especially designed to


II 2 G EExde IIC T3/T4
illuminate the interior of boilers, tanks, reactors, etc. and fits on all common
sight glass fittings. II 2D IP67 T195°C/T130°C/T120°C/T80°C

Specifications
Zone 1  Zone 21 
Housing corrosion-resistant aluminium alloy G-Al Si 12
Zone 2  Zone 22 
Mg
Seal O-ring (VITON) PTB01ATEX1031 (zone 1+2)
Protection IP65 DMT01ATEXE144 (zone 21+22)
Lamp halogen lamp
Earthing in- and exterior earthing bolt
Cable entry Exe connection box with M20 trumpet gland
Ambiant temperature -20°C - +40°C
Mounting by means of 2 included hinged brackets made
of stainless steel (M8 fastener)
Sight glass fittings the fittings fit on sight glass fittings from size
DN50

On request
• built-in timer (switch-on time 5 min.)
• temperature class T6

Ordering data
Code Halogen lamp Supply voltage Lamp holder Transformer Timer (5 min) Temp. class Weight
USL07EX01250 12V-50W 12V GY6.35   T4 2.5 kg
USL07EX01250T 12V-50W 12V GY6.35   T4 2.5 kg
USL07EX02450 24V-50W 24V GY6.35   T4 2.5 kg
USL07EX02450T 24V-50W 24V GY6.35   T4 2.5 kg
USL07EX23035 12V-35W 230V GY6.35   T4 3.5 kg
USL07EX23035T 12V-35W 230V GY6.35   T4 3.5 kg
USL07EX23050 12V-50W 230V GY6.35   T4 3.5 kg
USL07EX23050T 12V-50W 230V GY6.35   T4 3.5 kg
USL07EX23075 230V-75W 230V GZ10   T3 2.5 kg
USL07EX23075T 230V-75W 230V GZ10   T3 2.5 kg
USL07EX2x23050 230V-50W 230V GZ10   T4 2.5 kg
USL07EX2x23050T 230V-50W 230V GZ10   T4 2.5 kg

Dimensional sketches

90 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
3 Lighting
13 Back lights for level gauges
1 TNCLS series

The TNCLS back lights for level gauges is mounted behind the gauge glass
II 2 G EExem II T4
and makes use of the latest LED technology.
The fitting can be easily installed and adapted to all common gauge
glasses.
Zone 1  Zone 21 
The long life of the LEDs, the stainless steel enclosure and the low energy Zone 2  Zone 22 
consumption guarantee a maintenance-free operation. DNV2002OSLATEX0195
The LEDs are also resistant to vibrations.
Specifications
Housing stainless steel 316L
Protection IP66
LED colour yellow
Consumption ± 3VA per module
Electrical connection 4x2,5mm²
Voltage 220-254VAC - 50/60Hz On request
Earthing M6 bolt (inside and outside)
• cable entries on the side
Cable entry 2 x M25 entries (above and below) • red diodes
Ambiant temperature -20°C - +45°C • special fastening sets for high or low temperature
Mounting brackets • other voltages
- 1 pair for 1 module - 110-127VAC - 50/60Hz
- max. 62VDC
- 2 pairs or more in case of several modules

Ordering data
Code Visual length Number of modules Weight
TNCLS27-1 250 1 2,3 kg
TNCLS30-1 280 1 2,5 kg
TNCLS34-1 320 1 2,7 kg
TNCLS36-1 340 1 2,8 kg
TNCLS27-2 520 2 4,3 kg
TNCLS30-2 580 2 4,6 kg
TNCLS34-2 660 2 5,1 kg
TNCLS36-2 700 2 5,3 kg
TNCLS27-3 790 3 6,2 kg
TNCLS30-3 880 3 6,7 kg
TNCLS34-3 1000 3 7,3 kg
TNCLS36-3 1060 3 7,5 kg
TNCLS30-4 1180 4 8,5 kg

Dimensional sketches

Product code Dimensions


A
TNCLS27-1 270
TNCLS30-1 300
TNCLS34-1 340
TNCLS36-1 360
TNCLS27-2 540
TNCLS30-2 600
TNCLS34-2 680
TNCLS36-2 720
TNCLS27-3 810
TNCLS30-3 900
TNCLS34-3 1020
TNCLS36-3 1080
TNCLS30-4 1200

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 91


4 Signalling
1 Flashlights .................................................................................................... 95
1 TNFCDM series ................................................................................ 95

2 Rotating lights .............................................................................................. 96


1 dHR series ........................................................................................ 96

3 Signal lights .................................................................................................. 97


1 WAR EVCC-series ............................................................................ 97
2 WAR EVde-series ............................................................................. 98

4 Signal horns ................................................................................................. 99


1 dHH series ........................................................................................ 99
2 dHE series ...................................................................................... 100

5 Alarm bells ................................................................................................. 101


1 dHW series ..................................................................................... 101

6 Speakers .................................................................................................... 102


1 dHS series ...................................................................................... 102

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 93


4 Signalling
1 Flashlights
1 TNFCDM series

The standard version of the TNFCDM flashlight is made of stainless steel.


II 2 G EExd IIC T4
The long-life xenon lamp, combined with a high mechanical integrity and
corrosion resistance, significantly reduce maintenance costs. II 2 D T127°C

Specifications
Zone 1  Zone 21 
Housing stainless steel 316L
Zone 2  Zone 22 
Protection IP66
Lamp Xenon discharge lamp NEMKO01ATEX430
Flash energy 5 joules
Flashfrequency 1Hz
Starter current 1A
Color red, green, yellow, clear or blue
Weight 2,5 kg
Cable entry M25 (without gland)
Ambiant temperature -50°C - +60°C
Mounting by means of a bracket

On request
• T5

Ordering data
Code Color Voltage Nominal current
TNFCDM-060DC-R red 12-60 VDC 380-200mA
TNFCDM-060DC-G green 12-60 VDC 380-200mA
TNFCDM-060DC-Y yellow 12-60 VDC 380-200mA
TNFCDM-060DC-C clear 12-60 VDC 380-200mA
TNFCDM-060DC-B blue 12-60 VDC 380-200mA
TNFCDM-110AC-R red 110-127VAC ± 20% - 50/60Hz 100mA
TNFCDM-110AC-G green 110-127VAC ± 20% - 50/60Hz 100mA
TNFCDM-110AC-Y yellow 110-127VAC ± 20% - 50/60Hz 100mA
TNFCDM-110AC-C clear 110-127VAC ± 20% - 50/60Hz 100mA
TNFCDM-110AC-B blue 110-127VAC ± 20% - 50/60Hz 100mA
TNFCDM-230AC-R red 220-254VAC (190-272V) - 50/60Hz 100mA
TNFCDM-230AC-G green 220-254VAC (190-272V) - 50/60Hz 100mA
TNFCDM-230AC-Y yellow 220-254VAC (190-272V) - 50/60Hz 100mA
TNFCDM-230AC-C clear 220-254VAC (190-272V) - 50/60Hz 100mA
TNFCDM-230AC-B blue 220-254VAC (190-272V) - 50/60Hz 100mA

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 95


4 Signalling
2 Rotating lights
1 dHR series

The dHR rotating lights are robust and have a very high intensity due to the
II 2 G Ex d e IIC T5
halogen lamp used.
II 2 D Ex tD A21 IP66 T95°C
Specifications
Housing glass-fibre reinforced polyester Zone 1  Zone 21 
Lens polycarbonate
Protection IP66
Zone 2  Zone 22 
Lamp 20W halogen PTB02ATEX1098
Frequency 60/min
Color red, blue, yellow, green
Terminal 1,5 mm2
Weight 3,5 kg
Cable entry 2 x M20 (1 gland, 1 plug, plastic)
Ambiant temperature -20°C - +40°C
Mounting wall or ceiling mounting with bracket

On request
• 12VDC
• temperature class T6

Ordering data
Code Color Voltage Nominal current
dHR1-120AC-R red 110/120V 50/60Hz 0,20 A
dHR1-120AC-G green 110/120V 50/60Hz 0,20 A
dHR1-120AC-B blue 110/120V 50/60Hz 0,20 A
dHR1-120AC-Y yellow 110/120V 50/60Hz 0,20 A
dHR1-230AC-R red 230V 50/60Hz 0,10 A
dHR1-230AC-G green 230V 50/60Hz 0,10 A
dHR1-230AC-B blue 230V 50/60Hz 0,10 A
dHR1-230AC-Y yellow 230V 50/60Hz 0,10 A
dHR1-024-R red 24V AC/DC 0,90 A
dHR1-024-G green 24V AC/DC 0,90 A
dHR1-024-B blue 24V AC/DC 0,90 A
dHR1-024-Y yellow 24V AC/DC 0,90 A

Dimensional sketches

96 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
4 Signalling
3 Signal lights
1 WAR EVCC-series

The EVCC-WAR series signal light is equiped with an Exd connection box.
II 2 G Ex d IIC T5
The EVde-WAR series have an Exe connection box (see next page).
They are being fitted with a PL lamp of 11W. II 2 D Ex tD A21 IP65 T100°C

Specifications
Zone 1  Zone 21 
Housing aluminium with polyurethane paint, RAL6003
Zone 2  Zone 22 
Lens acrylate
Protection IP65 INERIS01ATEX0019X
Lamp PL lamp of 11W with E27 lamp holder
(lamp not included)
Color red, green, orange
Voltage 230VAC
Weight 3,3 kg
Cable entry 2 x M25 entries
Ambiant temperature -30°C - +40°C
Mounting with connection box

Ordering data
Code Lamp Color
EVCC-WAR011-V-R 11W PL red
EVCC-WAR011-V-G 11W PL green
EVCC-WAR011-V-O 11W PL orange

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 97


4 Signalling
3 Signal lights
2 WAR EVde-series

The EVde-WAR series signal light have an Exe connection box.


II 2 G Ex d e IIC T3/T4
They are being fitted with a PL lamp of 11W.
II 2 D Ex tD A21 IP65 T200°C/T135°C
Specifications
Housing aluminium with polyurethane paint, RAL6003 Zone 1  Zone 21 
Lens metacrylate
Protection IP65
Zone 2  Zone 22 
Lamp PL lamp of 11W with E27 lamp holder INERIS01ATEX0019X
(lamp not included)
Color red, green, orange
Voltage 230VAC
Weight 3,3 kg
Cable entry 2 x M25 entries
Ambiant temperature -30°C - +40°C
Mounting by means of included bracket (stainless steel)

Ordering data
Code Lamp Color
EVde-WAR011-V-R 11W PL red
EVde-WAR011-V-G 11W PL green
EVde-WAR011-V-O 11W PL orange

Dimensional sketches

98 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
4 Signalling
4 Signal horns
1 dHH series

The dHH horns are particularly powerful and suited for continuousous
II 2 G Ex de IIC T6
usage.
They are also available with an optional telephone relay. II 2 D Ex tD A21 IP66 T80°C

Specifications
Zone 1  Zone 21 
Housing glass-fibre reinforced polyester
Zone 2  Zone 22 
Protection IP66
Color black RAL 9005 PTB01ATEX1133
Sound intensity 105dB(A) at 1m
Switch-on time 100%
Terminal 1,5 mm²
Weight ± 3,5 kg
Cable entry 2 x M20 (1 gland, 1 plug, plastic)
Ambiant temperature -20°C - +70°C
Mounting wall or ceiling mounting with bracket

On request
• 6V - 12V - 24V - 42V - 48V - 60V AC 50Hz
• 120V - 240V AC 60Hz
• 6V - 12V - 48V - 60V - 220V DC

Ordering data
Code Voltage Nominal current type
dHH1-110AC 110 V 50 Hz 0,15 A without telephone relay
dHH1-230AC 230 V 50 Hz 0,07 A without telephone relay
dHH2-024DC 24 VDC 0,30 A without telephone relay
dHH2-048DC 110 VDC 0,08 A without telephone relay
dHHR1-230AC 230V 50Hz 0,07 A with telephone relay

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 99


4 Signalling
4 Signal horns
2 dHE series

A variant on the loudspeaker is the signal horn made of glass-fibre


II 2 G Ex demb IIC T6
reinforced polyester, with no less than 31 different tones.
Depending on the signal, the horn delivers a sound intensity of up to 116
dBA.
Zone 1  Zone 21 
The variety of signals increases its usefulness and decreases the possibility Zone 2  Zone 22 
of confusion with other signalling devices. PTB03ATEX1232
Specifications
Housing glass-fibre reinforced polyester
Protection IP66
Color RAL7024, loudspeaker part black
Sound intensity max. 119 dBA, 8 levels
Switch-on time 100%
Terminal 4 x 2,5mm²
Weight ± 6 kg
Cable entry 2 x M20 (1 cable gland, 1 plug)
Ambiant temperature -20°C - +40°C
Mounting wall or ceiling mounting with bracket

Ordering data
Code Voltage
dHE1 85 - 265V AC / 50-60Hz
dHE2 21,6 - 75V DC

Dimensional sketches

100 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
4 Signalling
5 Alarm bells
1 dHW series

The dHW series alarm bells are particularly powerful and robust and suited
II 2 G Ex de IIC T6
for continuousous usage.
They are also available with an optional telephone relay. II 2 D Ex tD A21 IP66 T80°C

Specifications
Zone 1  Zone 21 
Housing glass-fibre reinforced polyester
Zone 2  Zone 22 
Protection IP66
Color RAL 7024 (grey) PTB01ATEX1134
Sound intensity 105dB(A) at 1m
Switch-on time 100%
Terminal 1,5 mm²
Weight 3,5 kg
Cable entry 2 x M20 (1 gland, 1 plug, plastic)
Ambiant temperature -20°C - +40°C
Mounting wall or ceiling mounting with bracket

On request
• 12V - 24V - 42V - 48V - 60V AC 50Hz
• 120V - 240V AC 60Hz
• 6V - 12V - 48V - 60V - 220V DC

Ordering data
Code Voltage type
dHW1-110AC 110 V 50 Hz without telephone relay
dHW1-230AC 230 V 50 Hz without telephone relay
dHW2-024DC 24 VDC without telephone relay
dHW2-110DC 110 VDC without telephone relay
dHWR1-230AC 230V 50 Hz with telephone relay

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 101


4 Signalling
6 Speakers
1 dHS series

A revolutionary concept for explosionproof devices are the explosionproof


II 2 G Ex demb IIC T4
speakers made of glass-fibre reinforced polyester.
In combination with stainless steel screws and suspension brace, this II 2 D Ex tD A21 IP66 T130°C
product is virtually immune to corrosion.
The speakers are adjustable in 6 power versions and can be used in zones Zone 1  Zone 21 
1, 2, 21 and 22 and in all gas groups IIA, IIB and IIC. Zone 2  Zone 22 
Specifications PTB03ATEX1231
Housing glass-fibre reinforced polyester
Color black RAL 9005
Protection IP66
Sound intensity - 107dBA with 1W at 1m
- 119dBA with 25W at 1m
Frequency 230Hz to 10kHz
Power adjustable up to max. 25W
Terminal 6 x 2,5mm²
Transformer standard 100V
Cable entry 2 x M20
Weight ± 3,5 kg
On request
Ambiant temperature -55°C - +80°C
Mounting wall or ceiling mounting with bracket • temperature class T5 or T6

Ordering data
Code Max. power
dHS 25W

Dimensional sketches

102 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets
and plugs
1 Control units Ex d e m ................................................................................ 105
1 Fixed mounting ............................................................................... 105
2 Pendant control stations ................................................................. 107

2 Fire alarms ................................................................................................. 109


1 XAW-S series .................................................................................. 109

3 Position switches.........................................................................................110
1 XCW series ......................................................................................110

4 Sockets and plugs .......................................................................................112


1 16 A Wall sockets .............................................................................112
2 16 A Couplings .................................................................................113
3 16 A Built-in wall sockets..................................................................114
4 16 A Plugs ........................................................................................115
5 32 A Wall sockets .............................................................................116
6 32 A Couplings .................................................................................117
7 32 A Built-in wall sockets..................................................................118
8 32 A Plugs ........................................................................................119
9 63 A Wall sockets ............................................................................ 120
10 63 A Plugs ....................................................................................... 121
11 125 A Wall sockets .......................................................................... 122
12 125 A Plugs ..................................................................................... 123

5 Installation switches ................................................................................... 124


1 Installation switches 16A - 250VCA ................................................ 124

6 Work switches & safety switches ............................................................... 125


1 10 - 180A work switches ................................................................. 125
2 10 - 180A safety switches ............................................................... 127

7 Motor circuit breakers................................................................................. 129


1 Motor circuit breakers 0,1 - 25A ...................................................... 129

8 Foot switches ............................................................................................. 130


1 Foot switches .................................................................................. 130

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 103


5 Switches, control units, sockets and plugs
1 Control units Ex d e m
1 Fixed mounting

The ASSEMBL-Y series control boxes are made of plastic.


II 2 G Ex d e m IIC T6
The standard boxes can hold up to 3 units.
Control boxes with more than 3 units are custom-made products and must II 2 D IP65 T85°C
be requested.
The choice of control boxes is very large, allowing a suitable solution to be Zone 1  Zone 21 
found for every application. Zone 2  Zone 22 
Specifications KEMA01ATEX2109
Protection IP 65
Mounting with 4 mounting holes
Material glass-fibre reinforced polyester
Ambiant temperature -20°C - +40°C

On request
• Ampere meter

Ordering data
Code Number of units Dimensions (hxwxd) (mm) Gland entry Weight
AS-CP0811D-1 1 110 x 75 x 75 1 x M25 0,360 kg
AS-CP0816D-2 2 160 x 75 x 75 1 x M25 0,460 kg
AS-CP0823D-3 3 230 x 75 x 75 1 x M25 0,670 kg

Spare parts
Signalling lamps
LED indication lamps Code Colour Voltage
life of 100,000 hours XLW5-AV013 clear 24-415VAC/DC
LED included
XLW5-AV033 green 24-415VAC/DC
XLW5-AV043 red 24-415VAC/DC
XLW5-AV053 yellow 24-415VAC/DC
XLW5-AV063 blue 24-415VAC/DC
LED for clear, red, yellow
ZBW-V1 24-415VAC/DC
or blue lamp
ZBW-V3 LED for green lamp 24-415VAC/DC
Push buttons
In = 3A (240VAC) Code Colour Contact block
1 contactblock included XBW5-AP21S black 1NO
XBW5-AP31S green 1NO
XBW5-AP41S red 1NO
XBW5-AP51S yellow 1NO
XBW5-AP61S blue 1NO
XBW5-AP42S red 1NC
ZBW-E101 1NO
ZBW-E102 1NC

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 105


5 Switches, control units, sockets and plugs
1 Control units Ex d e m
1 Fixed mounting

Switches
In = 3A (240VAC) Code Description Schema

XBW5-AJ21 0-1

XBW5-AJ33 1-0-2

XBW5-AJ41 01

XBW5-AJ53 102

XBW5-AJ73 10-2

XBW5-AJ83 1-02

Key switches
In = 3A (240VAC) Code Description Schema
key is removable in 0 position
XBW5-AG21 0-I

Mushroom-shaped pushbuttons
In = 3A (240VAC) Code Colour Contact block
1 contactblock included XBW5-AS142 red 1NC
XBW5-AS542 red 1NC
ZBW-E101 1NO
ZBW-E102 1NC

106 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
1 Control units Ex d e m
2 Pendant control stations

Pendant control stations are sometimes used in hazardous zones.


II 2 GD EExed IIC T4/T6 - T85°C/T135°C
The XAW-P series provides an effective solution.
You can choose from 8 standard versions or configure your own unit.
The control stations come with the necessary instructions, a cable boot and
Zone 1  Zone 21 
a metal suspension bracket as mechanical pull relief. Zone 2  Zone 22 
Specifications INERIS03ATEX0122
Protection IP65
Material glass-fibre reinforced polyester
Nominal current 10A (thermal)
Cable boot for cable Ø 10 - 20mm
Ambiant temperature -20°C - +40°C

Ordering data

Code Number of units Contact elements Functions Weight

XAW-P271 2 1NO 0,94 kg

XAW-P281 2 1NO+1NC 1,00 kg

XAW-P471 4 1NO 1,29 kg

XAW-P481 4 1NO+1NC 1,40 kg

XAW-P671 6 1NO 1,65 kg

XAW-P681 6 1NO+1NC 1,80 kg

XAW-P871 8 1NO 2,00 kg

XAW-P881 8 1NO+1NC 2,25 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 107


5 Switches, control units, sockets and plugs
1 Control units Ex d e m
2 Pendant control stations

Dimensional sketches

Product code Dimensions


b b1
XAW-P271 409 220
XAW-P281 409 220
XAW-P471 499 310
XAW-P481 499 310
XAW-P671 589 400
XAW-P681 589 400
XAW-P871 679 490
XAW-P881 679 490

Spare parts
Code Description
ZBW-E101 Normally open contact
ZBW-E102 Normally closed contact
XAW-P9411 White detachable pushbutton
XAW-P9412 Black detachable pushbutton
XAW-P9414 Red detachable pushbutton
XAW-P960 Rubber cable boot with metal suspension brace

108 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
2 Fire alarms
1 XAW-S series

The XAW-S fire alarms are an addition to the ASSEMBL-Y control units.
II 2 G EExed IIC T6
The pushbutton can be manually or automatically operated after the glass
has been broken. II 2 D IP65 T85°C
The fire alarms come complete with a hammer to break the glass.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Protection IP65
Mounting with 2 or 4 mounting holes INERIS03ATEX0122
Cable entry 1 gland (for a cable of 8 to 13 mm)
Material housing glass-fibre reinforced polyester
Ambiant temperature -25°C - +40°C

Ordering data
Code Contact control Contacts glass intact Weight
XAW-S111 automatic after breaking of the glass 1NO 0,95 kg
XAW-S121 automatic after breaking of the glass 1NC 0,95 kg
XAW-S151 automatic after breaking of the glass 1NO+1NC 0,98 kg
XAW-S211 manually after breaking of the glass 1NO 0,95 kg
XAW-S221 manually after breaking of the glass 1NC 0,95 kg
XAW-S251 manually after breaking of the glass 1NO+1NC 0,98 kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 109


5 Switches, control units, sockets and plugs
3 Position switches
1 XCW series

The XCW stop limit switches are compact and come with an integrated
II 2 G EExd IIC T6
cable.
They are mounted either with the body or with the control button. II 2 D IP66 T85°C

Specifications
Zone 1  Zone 21 
Protection IP66
Zone 2  Zone 22 
Material aluminium, painted
Rated voltage 500V INERIS03ATEX0083
Nominal current 6A
Connection integrated 1-metre cable, 5x0,75mm²
Mechanical life 106 operations
Ambiant temperature -20°C - +60°C

On request
• longer integrated cable

Ordering data
Code Service control Operation Contact blocks Diagram Mounting Weight

For head motion. Speed


XCW-A110 metal switch cam between 0,001 en 0,05 1NO+1NC body 0,240 kg
m/s.

For 30° cam motion.


switch cam with
XCW-A102 Speed between 0,001 en 1NO+1NC body 0,245 kg
steel roll
0,1 m/s.

For 30° cam motion.


switch cam with
XCW-A103 Speed between 0,001 en 1NO+1NC body 0,245 kg
steel roll, 90° turned
0,1 m/s.

For 30° cam motion.


XCW-A115 lever with plastic roll Maximum speed of 1,5 1NO+1NC body 0,245 kg
m/s.

For head motion. Speed


XCW-F110 metal switch cam between 0,001 en 0,05 1NO+1NC head 0,260 kg
m/s.

For 30° cam motion.


switch cam with
XCW-F102 Speed between 0,001 en 1NO+1NC head 0,265 kg
steel roll
0,1 m/s.

For 30° cam motion.


switch cam with
XCW-F103 Speed between 0,001 en 1NO+1NC head 0,265 kg
steel roll, 90° turned
0,1 m/s.

110 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
3 Position switches
1 XCW series

Dimensional sketches

XCW-A110
C 0 XCW-A102
C 0

XCW-A103
XCW A103 XCW-A115
XCW A115

XCW-F110
XCW F110 XCW-F102

XCW-F103

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 111


5 Switches, control units, sockets and plugs
4 Sockets and plugs
1 16 A Wall sockets

The sockets are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 2x4mm²
Earthing 3 terminals (fed-through)
Protection IP66 (with or without connected plug)
Cable entries 3xM20
supplied with 1 gland (6,5-14,5 mm) and 2
plugs
Material high-quality, impact-resistant plastic
Ambiant temperature -40°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
C16-024-2 2P 16A 24 VAC 0,56 kg
C16-024-3 2P+E 16A 24 VAC 0,62 kg
C16-110-3 2P+E 16A 110/130 VAC 0,61 kg
C16-230-3 2P+E 16A 220/240 VAC 0,61 kg
C16-230-4 3P+E 16A 220/240 VAC 1,50 kg
C16-230-5 3P+N+E 16A 220/240 VAC 1,60 kg
C16-400-4 3P+E 16A 380/415 VAC 1,50 kg
C16-400-5 3P+N+E 16A 380/415 VAC 1,60 kg

Dimensional sketches

Product code Dimensions


A B C D
C16-024-2 120 202 133 272
C16-024-3 120 202 133 272
C16-110-3 120 202 133 272
C16-230-3 120 202 133 272
C16-230-4 140 240 145 310
C16-230-5 140 240 145 310
C16-400-4 140 240 145 310
C16-400-5 140 240 145 310

112 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
2 16 A Couplings

The couplings are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 4mm²
Protection IP66 (with or without connected plug)
Cable entries for cable of 6,5-14,5mm
Material polyamide
Ambiant temperature -20°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
K16-024-2 2P 16A 24 VAC 0,40 kg
K16-024-3 2P+E 16A 24 VAC 0,40 kg
K16-110-3 2P+E 16A 110/130 VAC 0,39 kg
K16-230-3 2P+E 16A 220/240 VAC 0,39 kg
K16-230-4 3P+E 16A 220/240 VAC 0,58 kg
K16-230-5 3P+N+E 16A 220/240 VAC 0,60 kg
K16-400-4 3P+E 16A 380/415 VAC 0,61 kg
K16-400-5 3P+N+E 16A 380/415 VAC 0,62 kg

Dimensional sketches

Product code Dimensions


A B C D E F G Ø
K16-024-2 42 46 54 80 160 130 210 39
K16-024-3 42 46 54 80 160 130 210 39
K16-110-3 42 46 54 80 160 130 210 39
K16-230-3 42 46 54 80 160 130 210 39
K16-230-4 56 60 68 90 160 150 230 49,5
K16-230-5 56 60 68 90 160 150 230 49,5
K16-400-4 56 60 68 90 160 150 230 49,5
K16-400-5 56 60 68 90 160 150 230 49,5

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 113


5 Switches, control units, sockets and plugs
4 Sockets and plugs
3 16 A Built-in wall sockets

The built-in wall sockets are fitted with an integrated interruption of the poles
II 2 G Ex d e IIC T6/T5
by a double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 2x4mm²
Protection IP66 (with or without connected plug)
Material high-quality, impact-resistant plastic
Ambiant temperature -20°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
I16-024-2 2P 16A 24 VAC 0,25 kg
I16-024-3 2P+E 16A 24 VAC 0,25 kg
I16-230-3 2P+E 16A 220/240 VAC 0,27 kg
I16-400-4 3P+E 16A 380/415 VAC 0,36 kg
I16-400-5 3P+N+E 16A 380/415 VAC 0,39 kg

Dimensional sketches

Product code Dimensions


A B C D E
I16-024-2 54 80 160 76 56
I16-024-3 54 80 160 76 56
I16-230-3 54 80 160 76 56
I16-400-4 68 90 160 76 56
I16-400-5 68 90 160 76 56

114 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
4 16 A Plugs

The sockets are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 2,5mm²
Cable entries for cable of 6,5-14,5mm
Material polyamide
Ambiant temperature -40°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
S16-024-2 2P 16A 24 VAC 0,20 kg
S16-024-3 2P+E 16A 24 VAC 0,20 kg
S16-110-3 2P+E 16A 110/130 VAC 0,20 kg
S16-230-3 2P+E 16A 220/240 VAC 0,20 kg
S16-230-4 3P+E 16A 220/240 VAC 0,23 kg
S16-230-5 3P+N+E 16A 220/240 VAC 0,28 kg
S16-400-4 3P+E 16A 380/415 VAC 0,22 kg
S16-400-5 3P+N+E 16A 380/415 VAC 0,27 kg

Dimensional sketches

Product code Dimensions


A B C
S16-024-2 58 152 49,5
S16-024-3 58 152 49,5
S16-110-3 58 152 49,5
S16-230-3 58 152 49,5
S16-230-4 66 154 55,5
S16-230-5 73 166 62
S16-400-4 66 154 55,5
S16-400-5 73 166 62

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 115


5 Switches, control units, sockets and plugs
4 Sockets and plugs
5 32 A Wall sockets

The sockets are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 2x6mm²
Earthing 3 terminals (fed-through)
Protection IP66 (with or without connected plug)
Cable entries 3xM25
supplied with 1 gland (8-18,5mm) and 2 plugs
Material high-quality, impact-resistant plastic
Ambiant temperature -40°C - +50/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
C32-230-3 2P+E 32A 220/240 VAC 1,89 kg
C32-230-4 3P+E 32A 220/240 VAC 1,89 kg
C32-400-4 3P+E 32A 380/415 VAC 2,00 kg
C32-400-5 3P+N+E 32A 380/415 VAC 2,00 kg
C32-500-4 3P+E 32A 500 VAC 2,00 kg

Dimensional sketches

Product code Dimensions


A B C D
C32-230-3 140 275 155 370
C32-230-4 140 275 155 370
C32-400-4 140 275 155 370
C32-400-5 140 275 165 375
C32-500-4 140 275 155 370

116 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
6 32 A Couplings

The couplings are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 6mm²
Protection IP66 (with or without connected plug)
Cable entries for cable of 14-18mm
Material polyamide
Ambiant temperature -20°C - +50/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
K32-400-4 3P+E 32A 380/415 VAC 0,82 kg

Dimensional sketches

Product code Dimensions


A B C D E F G Ø
K32-400-4 56 56 74 103 210 150 260 56

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 117


5 Switches, control units, sockets and plugs
4 Sockets and plugs
7 32 A Built-in wall sockets

The built-in wall sockets are fitted with an integrated interruption of the poles
II 2 G Ex d e IIC T6/T5
by a double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 2x6mm²
Protection IP66 (with or without connected plug)
Material high-quality, impact-resistant plastic
Ambiant temperature -20°C - +50/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
I32-400-4 3P+E 32A 380/415 VAC 0,65 kg

Dimensional sketches

Product code Dimensions


A B C D E
I32-400-4 74 103 210 110 60

118 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
8 32 A Plugs

The sockets are fitted with an integrated interruption of the poles by a


II 2 G Ex d e IIC T6/T5
double-safety device. When the plug is pulled, there will be:
- an automatic and simultaneous interruption of every phase in a first II 2 D Ex tD A21 IP66 T68°C
explosion-proof chamber
- voltage-free separation of the pins in a second explosion-proof chamber Zone 1  Zone 21 
The cover can be locked in 3 positions: Zone 2  Zone 22 
- with connected plug under tension
LCIE02ATEX6068
- with connected plug voltage free
- without plug, cover closed
For safety reasons, only the mentioned explosion-proof plugs fit in the
sockets. The explosion-proof plugs do fit in normal sockets in accordance
with CEE17.
Specifications
Connection 6mm²
Cable entries for cable of 14-18mm
Material polyamide
Ambiant temperature -40°C - +50/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
S32-230-3 2P+E 32A 220/240 VAC 0,50 kg
S32-230-4 3P+E 32A 220/240 VAC 0,50 kg
S32-400-4 3P+E 32A 380/415 VAC 0,43 kg
S32-400-5 3P+N+E 32A 380/415 VAC 0,50 kg
S32-500-4 3P+E 32A 500 VAC 0,43 kg

Dimensional sketches

Product code Dimensions


A B C
S32-230-3 80 170 67
S32-230-4 80 170 67
S32-400-4 80 170 67
S32-400-5 80 195 74
S32-500-4 80 170 67

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 119


5 Switches, control units, sockets and plugs
4 Sockets and plugs
9 63 A Wall sockets

The 63A sockets and plugs differ construction-wise from the versions with
II 2 G Ex d e IIC T6/T5
less power.
The voltage is cut off by means of a lockable switch instead of an internal II 2 D Ex tD A21 IP66 T90°C
switching mechanism.
The auxiliary contact can be integrated into the control circuit. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Connection 35mm² LCIE99ATEX6004
Protection IP65
Cable entries 1 gland M50 and 1 plug M25
Material enclosure made of impact-resistant plastic and
polyamide socket
Ambiant temperature -30°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Break power (kW-AC3) Weight
C63-230-4 3P+PE 63A 200-250 VAC 15 8 kg
C63-400-4 3P+PE 63A 380-415 VAC 22 8 kg
C63-400-5 3P+N+PE 63A 380-415 VAC 22 8 kg
C63-500-4 3P+PE 63A 480-500 VAC 18,5 8 kg

Dimensional sketches

120 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
10 63 A Plugs

The 63A sockets and plugs differ construction-wise from the versions with
II 2 G Ex d e IIC T6/T5
less power.
The voltage is cut off by means of a lockable switch instead of an internal II 2 D Ex tD A21 IP66 T90°C
switching mechanism.
The auxiliary contact can be integrated into the control circuit. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Connection 35mm² LCIE99ATEX6004
Protection IP65
Cable entries 1 gland M50 and 1 plug M25
Material polyamide
Ambiant temperature -30°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
S63-230-4 3P+PE 63A 200-250 VAC 1 kg
S63-400-4 3P+PE 63A 380-415 VAC 1 kg
S63-400-5 3P+N+PE 63A 380-415 VAC 1 kg
S63-500-5 3P+PE 63A 480-500 VAC 1 kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 121


5 Switches, control units, sockets and plugs
4 Sockets and plugs
11 125 A Wall sockets

The 125A sockets and plugs differ construction-wise from the versions with
II 2 G Ex d e IIC T6/T5
less power.
The voltage is cut off by means of a lockable switch instead of an internal II 2 D Ex tD A21 IP66 T90°C
switching mechanism.
The auxiliary contact can be integrated into the control circuit. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Connection 120mm² LCIE99ATEX6031
Protection IP66
Cable entries 1 gland M63 and 1 plug M25
Material enclosure in stainless steel 316L, socket in
polyamide
Ambiant temperature -30°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Break power (kW-AC3) Weight
C125-400-4 3P+PE 125A 480-500 VAC 15 16 kg
C125-400-5 3P+N+PE 125A 480-500 VAC 22 16 kg

Dimensional sketches

122 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
4 Sockets and plugs
12 125 A Plugs

The 63-125 sockets and plugs differ construction-wise from the versions
II 2 G Ex d e IIC T6/T5
with less power.
The voltage is cut off by means of a lockable switch instead of an internal II 2 D Ex tD A21 IP66 T90°C
switching mechanism.
The auxiliary contact can be integrated into the control circuit. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Connection 120mm² LCIE99ATEX6031
Protection IP66
Cable entries 1 gland M63 and 1 plug M25
Material polyamide
Ambiant temperature -30°C - +40/55°C

Ordering data
Code No. of poles Nom. current Voltage Weight
S125-400-4 3P+PE 125A 480-500 VAC 1,1 kg
S125-400-5 3P+N+PE 125A 480-500 VAC 1,1 kg

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 123


5 Switches, control units, sockets and plugs
5 Installation switches
1 Installation switches 16A - 250VCA

These installation switches meet the current demands regarding ease of


II 2 G Ex d e IIC T6
use (large control surface) and connection space.
A protective flange prevents unwanted operation. II 2 D Ex tD A21 IP66 T80°C

Specifications
Zone 1  Zone 21 
Material impact-resistant plastic
Zone 2  Zone 22 
Protection IP66
Connection terminals 2 x 2,5 mm² (earthing 4 x 2,5 mm²) PTB98ATEX3121
Rated voltage 250VAC
Nominal current 16A
Cable entry M25 gland (for cable of Ø 8-17mm)
Ambiant temperature -55°C - +40°C
Mounting 2 mounting holes

Ordering data
Code Diagram Gland entries

GHG2732000R0017 1 x M25

GHG2732000R0018 2 x M25

GHG2736000R0011 1 x M25

Dimensional sketches

124 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
6 Work switches & safety switches
1 10 - 180A work switches

Safety switches are used to cut power to electrical installations during


II 2 G Ex d e IIC T6
maintenance or other work.
Safety switches (EMERGENCY STOP function) are characterised by their II 2 G Ex d e ia II C T6
yellow/red padlock bracket and a forced opening of the main contacts II 2 D Ex tD A21 IP66 T80°C
(according to EN60024-1); standard safety switches have a black padlock
bracket. Zone 1  Zone 21 
The switches can be locked with 3 padlocks. Zone 2  Zone 22 
The enclosures are made of glass-fibre reinforced polyester and so are
PTB00ATEX1074
suited for applications in aggressive and heavy-duty conditions.
PTB99ATEX1161
Specifications
PTB00ATEX1091
Protection IP66
PTB99ATEX1164

Ordering data
Code Material Terminal No. of poles Nom. current (A) Gland entries Weight Ambiant temp.
impact-resistant
GHG2610005R0009 2 x 2,5 mm² 3+1NO 10 2xM25 + 1xM20 0,55 kg -55°C - +52°C
polyamide
glass-fibre reinforced
GHG2622301R0001 2 x 4 mm² 3+1NO 20 2xM32 + 1xM25 1,50 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2622601R0001 2 x 4 mm² 6+1NO/NC 20 4xM32 + 1xM25 2,30 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2632301R0001 2 x 16 mm² 3+1NO 40 2xM40 + 1xM25 2,30 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2630050R0001 2 x 16 mm² 6+1NO/NC 40 4xM40 + 1xM25 6,50 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2640020R0001 2 x 25 mm² 3+1NO/NC 80 2xM50 + 1xM25 6,50 kg -36°C - +52°C
polyester
glass-fibre reinforced
GHG2640021R0001 2 x 25 mm² 6+1NO/NC 80 4xM50 + 1xM25 9,00 kg -36°C - +52°C
polyester
glass-fibre reinforced
GHG2650010R0001 1 x 50/70 mm² 3+1NO/NC 125 2xM63 + 1xM25 16,00 kg -55°C - +45°C
polyester
glass-fibre reinforced
GHG2660006R0001 1 x 120 mm² 3+1NO/NC 180 2xM63 + 1xM25 16,50 kg -55°C - +45°C
polyester

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 125


5 Switches, control units, sockets and plugs
6 Work switches & safety switches
1 10 - 180A work switches

Dimensional sketches

10A

20A / 40A-3P

40A-6P / 80A / 125A / 180A


Product code Dimensions
A B C D E F G H I
GHG2610005R0009 84 68,5 102 61,5 112 5,5 8,5 80
GHG2622301R0001 110 96 170 150 129 7 13
GHG2622601R0001 140 123-126 225 197 156 7 8
GHG2632301R0001 140 123-126 225 197 156 7 8
GHG2630050R0001 271 247 271 247 275 7 11 12 211
GHG2640020R0001 271 247 271 247 275 7 11 12 211
GHG2640021R0001 271 247 271 247 295 7 11 12 211
GHG2650010R0001 271 247 544 520 275 7 11 12 211
GHG2660006R0001 271 247 544 520 275 7 11 12 211

Switching capacity at AC3


I nom 230V 400V 500V 690V
10A 10A 10A 10A -
20A 20A 20A 16A 10A
40A 40A 40A 40A 30A
80A 80A 80A 80A 80A
125A 125A 125A 125A 110A
180A 180A 180A 150A 125A

126 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
6 Work switches & safety switches
2 10 - 180A safety switches

Safety switches are used to cut power to electrical installations during


II 2 G Ex d e IIC T6
maintenance or other work.
Safety switches (EMERGENCY STOP function) are characterised by their II 2 G Ex d e ia II C T6
yellow/red padlock bracket and a forced opening of the main contacts II 2 D Ex tD A21 IP66 T80°C
(according to EN60024-1); standard safety switches have a black padlock
bracket. Zone 1  Zone 21 
The switches can be locked with 3 padlocks. Zone 2  Zone 22 
The enclosures are made of glass-fibre reinforced polyester and so are
PTB00ATEX1074
suited for applications in aggressive and heavy-duty conditions.
PTB99ATEX1161
Specifications
PTB00ATEX1091
Protection IP66
PTB99ATEX1164

Ordering data
Code Material Terminal No. of poles Nom. current (A) Gland entries Weight Ambiant temp.
impact-resistant
GHG2610005R0010 2 x 2,5 mm² 3+1NO 10 2xM25 + 1xM20 0,55 kg -55°C - +52°C
polyamide
glass-fibre reinforced
GHG2622301R0002 2 x 4 mm² 3+1NO 20 2xM32 + 1xM25 1,50 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2622601R0002 2 x 4 mm² 6+1NO/NC 20 4xM32 + 1xM25 2,30 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2632301R0002 2 x 16 mm² 3+1NO 40 2xM40 + 1xM25 2,30 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2630050R0002 2 x 16 mm² 6+1NO/NC 40 4xM40 + 1xM25 6,50 kg -55°C - +55°C
polyester
glass-fibre reinforced
GHG2640020R0002 2 x 25 mm² 3+1NO/NC 80 2xM50 + 1xM25 6,50 kg -36°C - +52°C
polyester
glass-fibre reinforced
GHG2640021R0002 2 x 25 mm² 6+1NO/NC 80 4xM50 + 1xM25 9,00 kg -36°C - +52°C
polyester
glass-fibre reinforced
GHG2650010R0002 1 x 50/70 mm² 3+1NO/NC 125 2xM63 + 1xM25 16,00 kg -55°C - +45°C
polyester
glass-fibre reinforced
GHG2660006R0002 1 x 120 mm² 3+1NO/NC 180 2xM63 + 1xM25 16,50 kg -55°C - +45°C
polyester

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 127


5 Switches, control units, sockets and plugs
6 Work switches & safety switches
2 10 - 180A safety switches

Dimensional sketches

10A

20A / 40A-3P

40A-6P / 80A / 125A / 180A


Product code Dimensions
A B C D E F G H I
GHG2610005R0010 84 68,5 102 61,5 112 5,5 8,5 80
GHG2622301R0002 110 96 170 150 129 7 13
GHG2622601R0002 140 123-126 225 197 156 7 8
GHG2632301R0002 140 123-126 225 197 156 7 8
GHG2630050R0002 271 247 271 247 275 7 11 12 211
GHG2640020R0002 271 247 271 247 275 7 11 12 211
GHG2640021R0002 271 247 271 247 295 7 11 12 211
GHG2650010R0002 271 247 544 520 275 7 11 12 211
GHG2660006R0002 271 247 544 520 275 7 11 12 211

Switching capacity at AC3


I nom 230V 400V 500V 690V
10A 10A 10A 10A -
20A 20A 20A 16A 10A
40A 40A 40A 40A 30A
80A 80A 80A 80A 80A
125A 125A 125A 125A 110A
180A 180A 180A 150A 125A

128 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
5 Switches, control units, sockets and plugs
7 Motor circuit breakers
1 Motor circuit breakers 0,1 - 25A

Motor circuit breakers are used to secure (thermally and magnetically)


II 2 G Ex d e IIC T5/T6
explosion-proof motors against overload, short-circuits and phase loss.
The characteristics are: the forced opening of the main contacts, the II 2 D Ex tD A21 IP66 T80°C
padlock bracket for 3 padlocks and the clear indication of the position of the
switch. Zone 1  Zone 21 
The enclosures are made of glass-fibre reinforced polyester and are thus Zone 2  Zone 22 
suited for applications under aggressive and heavy-duty conditions.
PTB99ATEX1162
Specifications
Material glass-fibre reinforced polyester
Protection IP 66
Connection up to 10mm²
(2,5 mm² for secondary contacts)
Rated voltage max. 690V
Nominal current max. 25A (secondary contact 2A)
Weight ± 2,5 kg On request
• undervoltage protection 230V or 400V
- decommutation between protection 15-75% Vc
- commutation from V < 80% Vc

Ordering data
Code Setting range Auxiliary contact Gland entries Temp. class Ambiant temp.
GHG6351101R0101 0.1 A - 0.16 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0101 0.1 A - 0.16 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0102 0.16 A - 0.25 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0102 0.16 A - 0.25 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0103 0.25 A - 0.40 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0103 0.25 A - 0.40 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0104 0.40 A - 0.63 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0104 0.40 A - 0.63 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0105 0.63 A - 1.0 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0105 0.63 A - 1.0 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0106 1.0 A - 1.6 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0106 1.0 A - 1.6 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0107 1.6 A - 2.5 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0107 1.6 A - 2.5 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0108 2.5 A - 4.0 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0108 2.5 A - 4.0 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0109 4.0 A - 6.3 A 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351102R0109 4.0 A - 6.3 A 1NO + 1NC 2 x M25 (Ø8-17mm) T6 -20°C - +40°C
GHG6351101R0110 6.3 A - 9.0 A 2 x M32 (Ø12-21mm) T6 -20°C - +40°C
GHG6351102R0110 6.3 A - 9.0 A 1NO + 1NC 2 x M32 (Ø12-21mm) T6 -20°C - +40°C
GHG6351101R0111 9.0 A - 12.5 A 2 x M32 (Ø12-21mm) T6 -20°C - +40°C
GHG6351102R0111 9.0 A - 12.5 A 1NO + 1NC 2 x M32 (Ø12-21mm) T6 -20°C - +40°C
GHG6351101R0112 12.5 A - 16 A 2 x M32 (Ø12-21mm) T6 -20°C - +55°C
GHG6351102R0112 12.5 A - 16 A 1NO + 1NC 2 x M32 (Ø12-21mm) T6 -20°C - +55°C
GHG6351101R0113 16 A - 20 A 2 x M32 (Ø12-21mm) T5 -20°C - +55°C
GHG6351102R0113 16 A - 20 A 1NO + 1NC 2 x M32 (Ø12-21mm) T5 -20°C - +55°C
GHG6351101R0114 20 A - 25 A 2 x M32 (Ø12-21mm) T5 -20°C - +55°C
GHG6351102R0114 20 A - 25 A 1NO + 1NC 2 x M32 (Ø12-21mm) T5 -20°C - +55°C

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 129


5 Switches, control units, sockets and plugs
8 Foot switches
1 Foot switches

These installation switches meet the current demands regarding ease of


II 2 D Ex tD A21 IP66 T85°C
use (large control surface) and connection space.
A protective flange prevents unwanted operation.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Material zink alloy (Zamak)
Protection IP66 INERIS04ATEX0042
Rated voltage max. 250VAC
Mechanical life 5 million cycles
Cable entry 1 PG16 gland (for cable of Ø 5-13mm)
1 plug PG16
Ambiant temperature -20°C - +60°C

Ordering data
Code Contact blocks Service control Colour
XPEWM110 1 NO+NC 1 step blue
XPEWR110 1 NO+NC 1 step orange
XPEWM111 2 NC+NO 1 step blue
XPEWR111 2 NC+NO 1 step orange
XPEWM211 2 NC+NO 2 step blue
XPEWR211 2 NC+NO 2 step orange

Dimensional sketches

130 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
6 Heating
1 Tubular heaters .......................................................................................... 133
1 FAW & FAW-C series for zone 1 and 2 ........................................... 133
2 FWD & FWDT series for zone 1, 2, 21 and 22 ............................... 135

2 Electric heaters .......................................................................................... 137


1 FLR series....................................................................................... 137

3 Enclosure heaters ...................................................................................... 138


1 HEF series ...................................................................................... 138

4 Thermostat ................................................................................................. 139


1 HFT series - internally adjustable ................................................... 139
2 AFT series - externally adjustable................................................... 140

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 131


6 Heating
1 Tubular heaters
1 FAW & FAW-C series for zone 1 and 2

These finned tubular heaters are designed to heat, among other things,
II 2 G Ex e II T3/T4
analysis chambers, small work, storage areas and similar applications,
warehouses, ... located in zone 1 or 2 hazardous areas where the
flammable atmosphere is a group IIA, IIB or IIC gas.
Zone 1  Zone 21 
The standard version comes with a protective cage and is suited for floor Zone 2  Zone 22 
mounting. LCIE00ATEX6013X
Special brackets for wall mounting are available on request.
Specifications
Earthing in- and external earthing bolt
Protection IP66
Protective grid standard
Elements individually replaceable
Cable entry 1x M20 x 1,5
Mounting floor mounting by means of supplied mounting
feet
Ambiant temperature -60°C - +40°C
On request
• if required the heaters can be controlled of remote
mounted thermostats available for use in safe or
hazardous areas
• enclosure in stainless steel (FAW)
• T2 : -60°C - +60°C
• other tensions
• brackets for wall mounting

Ordering data
Code Range Housing Voltage Power Temp. class No. of supports Weight
FAWC0250-T3-240 Compact stainless steel 240V 250W T3 2 5 kg
FAWC0500-T3-240 Compact stainless steel 240V 500W T3 2 6 kg
FAWC0750-T3-240 Compact stainless steel 240V 750W T3 2 6 kg
FAWC1000-T3-240 Compact stainless steel 240V 1000W T3 2 9 kg
FAW0250-T3-240 Standard lightweight coated mild steel 240V 250W T3 2 8 kg
FAW0500-T3-240 Standard lightweight coated mild steel 240V 500W T3 2 10 kg
FAW0750-T3-240 Standard lightweight coated mild steel 240V 750W T3 2 12 kg
FAW1000-T3-240 Standard lightweight coated mild steel 240V 1000W T3 3 14 kg
FAW1500-T3-240 Standard lightweight coated mild steel 240V 1500W T3 3 20 kg
FAW2000-T3-240 Standard lightweight coated mild steel 240V 2000W T3 3 32 kg
FAW2500-T3-240 Standard lightweight coated mild steel 240V 2500W T3 3 38 kg
FAW3000-T3-240 Standard lightweight coated mild steel 240V 3000W T3 3 42 kg
FAW0250-T4-240 Standard lightweight coated mild steel 240V 250W T4 3 13 kg
FAW0500-T4-240 Standard lightweight coated mild steel 240V 500W T4 3 17 kg
FAW0750-T4-240 Standard lightweight coated mild steel 240V 750W T4 3 21 kg
FAW1000-T4-240 Standard lightweight coated mild steel 240V 1000W T4 3 33 kg
FAW1250-T4-240 Standard lightweight coated mild steel 240V 1250W T4 3 38 kg
FAW1500-T4-240 Standard lightweight coated mild steel 240V 1500W T4 3 42 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 133


6 Heating
1 Tubular heaters
1 FAW & FAW-C series for zone 1 and 2

Dimensional sketches

Product code Dimensions


A B C
FAWC0250-T3-240 350 160 282
FAWC050-T3-240 350 160 282
FAWC0750-T3-240 615 160 545
FAWC1000-T3-240 615 160 545
FAW0250-T3-240 971 160 860
FAW0500-T3-240 971 160 860
FAW0750-T3-240 971 160 860
FAW1000-T3-240 1221 160 1120
FAW1500-T3-240 1741 160 1640
FAW2000-T3-240 1741 272 1640
FAW2500-T3-240 1741 272 1640
FAW3000-T3-240 1741 272 1640
FAW0250-T4-240 1886 160 1784
FAW0500-T4-240 1886 160 1784
FAW0750-T4-240 1886 160 1784
FAW1000-T4-240 1886 272 1784
FAW1250-T4-240 1886 272 1784
FAW1500-T4-240 1886 272 1784

134 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
6 Heating
1 Tubular heaters
2 FWD & FWDT series for zone 1, 2, 21 and 22

These finned tubular heaters are designed for use in small work or storage
II 2 G Ex d IIC T2-T4
areas which are located in zone 1 and 2 or zone 21 and 22 hazardous
areas where the flammable atmosphere is a IIA, IIB or IIC gas group. The II 2 D Ex tD A21 IP66 T300°C-T135°C
FWDT range comes with an easy to adjust external thermostat 0-40°C.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Protection IP66
Elements individually replaceable LCIE04ATEX6016X
Voltage 230-254V
Mounting floor or wall mounting by means of supplied
mounting feet
Ambiant temperature -60°C - +40°C

On request
• enclosure in stainless steel (FWD)
• T2 : -60°C - +60°C
• 110V

Ordering data
Code Housing Power Temp. class Max. surface temp. Thermostat Cable entry Weight
FWD-500-T3-230 lightweight coated mild steel 500W T3 200°C  2 x M20 9 kg
FWD-1000-T3-230 lightweight coated mild steel 1000W T3 200°C  2 x M20 12 kg
FWD-1500-T3-230 lightweight coated mild steel 1500W T3 200°C  2 x M20 17 kg
FWD-2000-T3-230 lightweight coated mild steel 2000W T3 200°C  2 x M20 20 kg
FWD-500-T4-230 lightweight coated mild steel 500W T4 135°C  2 x M20 12 kg
FWD-750-T4-230 lightweight coated mild steel 750W T4 135°C  2 x M20 17 kg
FWD-1000-T4-230 lightweight coated mild steel 1000W T4 135°C  2 x M20 20 kg
FWDT-500-T3-230 powder coated aluminium 500W T3 200°C  2 x M25 9 kg
FWDT-1000-T3-230 powder coated aluminium 1000W T3 200°C  2 x M25 12 kg
FWDT-1500-T3-230 powder coated aluminium 1500W T3 200°C  2 x M25 17 kg
FWDT-2000-T3-230 powder coated aluminium 2000W T3 200°C  2 x M25 20 kg
FWDT-500-T4-230 powder coated aluminium 500W T4 135°C  2 x M25 12 kg
FWDT-750-T4-230 powder coated aluminium 750W T4 135°C  2 x M25 17 kg
FWDT-1000-T4-230 powder coated aluminium 1000W T4 135°C  2 x M25 20 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 135


6 Heating
1 Tubular heaters
2 FWD & FWDT series for zone 1, 2, 21 and 22

Dimensional sketches

FWD

FWDT
Product code Dimensions
A B
FWD-500-T3-230 800 670
FWD-1000-T3-230 1300 1170
FWD-1500-T3-230 1900 1770
FWD-2000-T3-230 2450 2320
FWD-500-T4-230 1300 1170
FWD-750-T4-230 1900 1770
FWD-1000-T4-230 2450 2320
FWDT-500-T3-230 800 670
FWDT-1000-T3-230 1300 1170
FWDT-1500-T3-230 1900 1770
FWDT-2000-T3-230 2450 2320
FWDT-500-T4-230 1300 1170
FWDT-750-T4-230 1900 1770
FWDT-1000-T4-230 2450 2320

136 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
6 Heating
2 Electric heaters
1 FLR series

These electric heaters are designed to heat, among other things, analysis
II 2 G Ex d IIC T6
chambers, small work, storage areas and similar applications, warehouses,
... located in zone 1 and 2 (gas) and zone 21 and 22 (dust). II 2 D Ex tD A21 IP66 T85°C
The equipment is formed of a metallic enclosure including a liquid (water
and glycol) heated by an immerged heater. Zone 1  Zone 21 
These heaters can be ordered with or without an external adjustable Zone 2  Zone 22 
thermostat mounted on the equipment.
LCIE00ATEX6012X
Specifications
Housing coated steel
Elements Incoloy 825
Protection IP66
Voltage 240V AC (single phase)
Cable entry 2x M25 x 1,5
Mounting floor mounting by welded-on feet brackets
Ambiant temperature -20°C - +40°C

On request
• loose thermostat
• other voltages

Ordering data
Code Power Thermostat Weight
FLR1 1000W  47 kg
FLR1-A 1000W  47 kg
FLR2 2000W  94 kg
FLR2-A 2000W  94 kg
FLR3 3000W  140 kg
FLR3-A 3000W  140 kg

Dimensional sketches

Product code Dimensions


A B C
FLR1 540 495 360
FLR2 1080 1035 900
FLR3 1620 1575 1440
FLR1-A 540 495 360
FLR2-A 1080 1035 900
FLR3-A 1620 1575 1440

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 137


6 Heating
3 Enclosure heaters
1 HEF series

The HEF range of enclosure heaters has been designed for


II 2 G Ex e II T4
anticondensation, frost protection and temperature control where control
panels and monitoring cabinets are located within zone 1 & 2 (gas).
This heater has a low surface temperature and is self-regulating.
Zone 1  Zone 21 
Mounting of the heater can be in any orientation. Zone 2  Zone 22 
Specifications LCIE02ATEX6123X
Housing stainless steel
Voltage 240V AC (single phase)
Mounting mounting feet for M6 fixing
Ambiant temperature -50°C - +80°C

On request
• 110V (single phase)

Ordering data
Code Power Weight
HEF30/240 30W 0,7 kg
HEF50/240 50W 1,0 kg
HEF100/240 100W 1,5 kg
HEF200/240 200W 3,0 kg
HEF500/240 500W 6,5 kg

Dimensional sketches

Product code Dimensions


A B C D E F G
HEF30/240 130 73 center 1 N/A N/A N/A
HEF50/240 266 100 60 3 N/A 142 22
HEF100/240 290 180 140 4 75 165 50
HEF200/240 550 180 100 5 243 215 35
HEF500/240 700 340 300 5 300 275 50

138 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
6 Heating
4 Thermostat
1 HFT series - internally adjustable

The HFT is designed for the temperature control of work or storage areas,
II 2 G Ex d IIC T6
in conjunction with a Hazardous Area air heater.
Specifications
Zone 1  Zone 21 
Housing stainless steel Zone 2  Zone 22 
Protection IP67
Earthing internal and external LCIE99ATEX6017X
Voltage max. 250V
Current 16A
Cable entry 2 x M20
Mounting 2 x M6
Ambiant temperature -60°C - +60°C

Ordering data
Code Range Voltage
HFT40 0°C - +40°C 250V
HFT60 0°C - +60°C 250V

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 139


6 Heating
4 Thermostat
2 AFT series - externally adjustable

The AFT is designed for the temperature control of work or storage areas, in
II 2 G Ex d IIC T6
conjunction with a Hazardous Area air heater.
This thermostat is externally adjustable. II 2 D Ex tD A21 IP6X T85°C

Specifications
Zone 1  Zone 21 
Housing stainless steel
Zone 2  Zone 22 
Protection IP67
Earthing internal and external LCIE99ATEX6017X
Voltage max. 250V
Current 16A
Cable entry 2 x M20
Mounting 2 x M6
Ambiant temperature - 60°C - + 60°C

Ordering data
Code Range Voltage
AFT40 0°C - +40°C 250V
AFT60 0°C - +60°C 250V

Dimensional sketches

140 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
7 Man - machine interface
1 Digital indicator........................................................................................... 143
1 D122 series ..................................................................................... 143

2 Message display ........................................................................................ 146


1 TA125 series ................................................................................... 146

3 Modular Ex-PC ........................................................................................... 148


1 PC100 series .................................................................................. 148

4 Keyboard and Trackball ............................................................................. 150


1 KB/TB/KI 153 series........................................................................ 150

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 141


7 Man - machine interface
1 Digital indicator
1 D122 series

The digital indicator D122 indicates measured values of intrinsically safe


II 2 (1) G Ex ia IIC T6 Gb
current circuits from 4 up to 20 mA in hazardous areas.
The device is powered by measure circuit, therefore an extra power supply
or batteries are unnescessary.
Zone 1  Zone 21 
The indicator measures the current, scales the measured value and Zone 2  Zone 22 
displays finally the result on the LCD.
The internal 24 bit A/D conversion achieves a stable indication even at 4 1/2
digit resolution.
For trend analysis, the measured signal is also be displayed on a 41
segment bargraph. It’s possible to scale the bargraph separately.
The indicator D122 is available in several housings.
Furthermore with alarm monitoring option the indicator has two intrinsically
safe alarm outputs. These outputs change their state, when the measured
value exceeds its alarm limits. On request
It is possible to configure the outputs as normal open or normal closed • alarm monitoring: two intrinsically safe alarm
circuits. outputs
Additional the alarm limits appear graphically on a second bargraph. On • additional limit bargraph
one look you’re sure that the measured value is in its limits. • limit function with hysteresis and time delay
• normal open or normal closed circuit principle
There’s also the possibility to use the display as “counter” which gives the
• curve fitting
sum of the measured values (type D122.Z) • ambiant temperature -20°C - +60°C
• version for zone 21 and 22
Ergonomics:
• μ-processor technology for extensive configuration
• scaleable by keyboard and display, without reference current
• separately scaleable bargraph (zoom)
• current control button
• keeps the configuration by turn off
• ability to change configuration during operation
• exchangeable dimension signs
Specifications
Protection Front panel up to IP55 - with sealed keyboard
IP65
Housing According to control panel
standard DIN43700
Decimal points selectable by keyboard
Limit monitoring By means of intrinsically safe control circuits
(e.g. NAMUR or DIN19234)
Alarm limits display via bargraph, flashing ‘max.’ or ‘min.’ display
(only types A.0, A.3 en A.5)
Measurement circuit see certificate TÜV99ATEX1488
limits
Alarm terminal limits see certificate TÜV99ATEX1488
Measurement circuit intrinsically safe measurement circuit 4-20 mA,
voltage drop ca. 1V
Current control button direct display of the current in measurement
circuit
Symbols selectable with defined symbols
Temperature coefficient < 0,01 % of measure range / K
Ambiant temperature -10°C - +45°C

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 143


7 Man - machine interface
1 Digital indicator
1 D122 series

Ordering data
Code Description Material Digital height Display indication Display range Bargraph Digital output
glass fibre 4 1/2-digits -19999 ...
D122.A.0.0 indicator 15 mm 41 segments
reinforced noryl 7-segment LCD +19999
glass fibre 4 1/2-digits -19999 ... with 2 digital
D122.A.0.2 indicator 15 mm 41 segments
reinforced noryl 7-segment LCD +19999 outputs
glass fibre 4 1/2-digits -19999 ... with reset input
D122.A.0.3 indicator 15 mm 41 segments
reinforced noryl 7-segment LCD +19999 and pulse output
glass fibre 4 1/2-digits -19999 ...
D122.A.3.0 indicator 30 mm 41 segments
reinforced noryl 7-segment LCD +19999
glass fibre 4 1/2-digits -19999 ... with 2 digital
D122.A.3.2 indicator 30 mm 41 segments
reinforced noryl 7-segment LCD +19999 outputs
glass fibre 4 1/2-digits -19999 ... with reset input
D122.A.3.3 indicator 30 mm 41 segments
reinforced noryl 7-segment LCD +19999 and pulse output
4 1/2-digits -19999 ...
D122.A.5.0 indicator ABS 30 mm 41 segments
7-segment LCD +19999
4 1/2-digits -19999 ... with 2 digital
D122.A.5.2 indicator ABS 30 mm 41 segments
7-segment LCD +19999 outputs
4 1/2-digits -19999 ... with reset input
D122.A.5.3 indicator ABS 30 mm 41 segments
7-segment LCD +19999 and pulse output

D122.A.6.0 indicator ABS 50 mm 3 1/2-digits LCD -1999 ... +1999

with 2 digital
D122.A.6.2 indicator ABS 50 mm 3 1/2-digits LCD -1999 ... +1999
outputs
with reset input
D122.A.6.3 indicator ABS 50 mm 3 1/2-digits LCD -1999 ... +1999
and pulse output
glass fibre 5-digits 00000 ...
D122.Z.0.0 totalizer 15 mm 41 segments
reinforced noryl 7-segment LCD +19999
glass fibre 5-digits 00000 ... with 2 digital
D122.Z.0.2 totalizer 15 mm 41 segments
reinforced noryl 7-segment LCD +19999 outputs
glass fibre 5-digits 00000 ... with reset input
D122.Z.0.3 totalizer 15 mm 41 segments
reinforced noryl 7-segment LCD +19999 and pulse output
glass fibre 5-digits 00000 ...
D122.Z.3.0 totalizer 30 mm 41 segments
reinforced noryl 7-segment LCD +19999
glass fibre 5-digits 00000 ... with 2 digital
D122.Z.3.2 totalizer 30 mm 41 segments
reinforced noryl 7-segment LCD +19999 outputs
glass fibre 5-digits 00000 ... with reset input
D122.Z.3.3 totalizer 30 mm 41 segments
reinforced noryl 7-segment LCD +19999 and pulse output
5-digits 00000 ...
D122.Z.5.0 totalizer ABS 30 mm 41 segments
7-segment LCD +19999
5-digits 00000 ... with 2 digital
D122.Z.5.2 totalizer ABS 30 mm 41 segments
7-segment LCD +19999 outputs
5-digits 00000 ... with reset input
D122.Z.5.3 totalizer ABS 30 mm 41 segments
7-segment LCD +19999 and pulse output
5-digits 00000 ...
D122.Z.6.0 totalizer ABS 50 mm 41 segments
7-segment LCD +19999
5-digits 00000 ... with 2 digital
D122.Z.6.2 totalizer ABS 50 mm 41 segments
7-segment LCD +19999 outputs
5-digits 00000 ... with reset input
D122.Z.6.3 totalizer ABS 50 mm 41 segments
7-segment LCD +19999 and pulse output

144 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
7 Man - machine interface
1 Digital indicator
1 D122 series

Dimensional sketches

D122.*.0
D122. .0 D122.*.3

D122.*.6

D122.*.5

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 145


7 Man - machine interface
2 Message display
1 TA125 series

The field text display TA125 indicates arbitrary messages, warnings or hints
II 2 G Ex ib IIC T6 Gb (TA125)
in the hazardous area zone 1.
It’s large (58 x 244 mm), reflective display with a figure height of 15 mm can II 2 D Ex t IIIC T70°C Db IP65 (TA125)
easily be read up to a distance of five meters. II (2) G [Exib] IIC (Gb) (TI125)
The display is organised into 4 rows with 40 characters per each row.
The TA125 receives the messages for instance from a PC or DCS located Zone 1  Zone 21 
in safe area. Zone 2  Zone 22 
The interface TI125 serves as intrinsically safe barrier and power supply.
It can be equiped with several bus modules (RS232, RS485, RS422,
Profibus DP, Interbus and Modbus).
The distance to the TA125 could be up to 300 meters with a data rate of
38,4 kbit/s. Use bigger wire diameter for longer distances.
It is possible to connect many text display to one bus (theoretical up to 256).
Each one with a different text content.
Additionaly the TA125 has an intrinsically safe passive alarm output. With
this it is possible to connect a further alarming device.
With the three digital inputs you can acknowledge a message or an alarm or
you can request further information on the spot in hazardous area.
The TA125 stores up to 32 kByte of messages in a internal EEprom.
You can program the prestored messages with the bundled windows
software ‘TEXT LINK’.
There are two ways to display the prestored texts: the serial interface or
applying a defined bit pattern to binary address inputs of the TI125 (option).
Specifications On request

TA125 • On demand the number of digital intrinsically


Protection IP65 safe inputs can expand up to 12. (connection of a
keyboard)
Material aluminium, lacquered 7035
Mounting zone 1
EX-limits • digital output: Ui=30V, li=160mA, Pi=0,85W
• digital input: Uo=6V, lo=1mA
Transmission speed up to 38,4 kbits/s
Connection to TI125 2 x 2 x 0,25 mm² (or bigger diameter)
Ambiant temperature -20°C - +45/65°C
TI125
Protection IP40
Material aluminium
Mounting safe area
Mounting 35 mm rail acc. DIN EN 50022
Ambiant temperature -20°C - +60°C

146 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
7 Man - machine interface
2 Message display
1 TA125 series

Ordering data
Option binary Character
Code Description Protection Interface module address input Voltage height Text display Viewing area
TA125 display IP65 15 mm 4 x 40 characters 68 x 244 mm
TI125.0.0.0 interface IP40 RS485/RS232/RS422 without 230VAC
TI125.0.0.1 interface IP40 RS485/RS232/RS422 present 230VAC
TI125.0.1.0 interface IP40 Modbus without 230VAC
TI125.0.1.1 interface IP40 Modbus present 230VAC
TI125.0.2.0 interface IP40 Profibus DP without 230VAC
TI125.0.2.1 interface IP40 Profibus DP present 230VAC
TI125.3.0.0 interface IP40 RS485/RS232/RS422 without 110VAC
TI125.3.0.1 interface IP40 RS485/RS232/RS422 present 110VAC
TI125.3.1.0 interface IP40 Modbus without 110VAC
TI125.3.1.1 interface IP40 Modbus present 110VAC
TI125.3.2.0 interface IP40 Profibus DP without 110VAC
TI125.3.2.1 interface IP40 Profibus DP present 110VAC
TI125.6.0.0 interface IP40 RS485/RS232/RS422 without 24VDC
TI125.6.0.1 interface IP40 RS485/RS232/RS422 present 24VDC
TI125.6.1.0 interface IP40 Modbus without 24VDC
TI125.6.1.1 interface IP40 Modbus present 24VDC
TI125.6.2.0 interface IP40 Profibus DP without 24VDC
TI125.6.2.1 interface IP40 Profibus DP present 24VDC

Dimensional sketches

TA

TI

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 147


7 Man - machine interface
3 Modular Ex-PC
1 PC100 series

The PC100 is the user interface of an industrial PC designed for use in


II 2 G Ex eb qb ib [ib] IIC T4
zone 1. The PC is located in the safe area.
There are no more intrinsically safe barriers necessary - the PC is unlimited
network capable. A later update to a more powerful PC is possible at any
Zone 1  Zone 21 
time. Zone 2  Zone 22 
The PC is connected with a video-remote control to the PC100.
For the remote control usually a 4 x 2 AWG24 (CAT 5/6) cable is
recommended, but alternatively a glass fibre can be used.
The customer don’t have to follow the rules for intrinsically safe wiring,
because the connection is not intrinsically safe: the power supply (e.g.
230VAC) of the display is connected to the integrated Ex e-terminal box.
Therefore no Exi-multi power supplies are necessary.
The intrinsically safe keyboard and stainless steel trackball (both IP65) are
connected to the PC100 with a plug.
The modules above are integrated in a graceful designed commander
housing. The housing is manufactured of stainless steel with a protection
class of IP65. Therefore it can be used in pharmaceutical or food
production. On request
It is also possible to integrate the PC100 modules in an existing control
• display 8,4» or 10,4»
panel. • housing material: steel lacked or aluminium
The PC100 gives his user the degree of freedom and flexibility, he needs • several mounting possibilities of commander
now and in the future. housing
• optical waveguide to PC
Specifications
• voltage 110VAC or 24VDC
Protection IP65 • housing without writing desk
Material stainless steel
Voltage 230VAC
Mounting zone 1

Ordering data
Code Display Touch screen Front window Housing
PC100.0.0.0.1.1.0 15” TFT (XGA) without anti reflection coating design housing with writing desk
PC100.0.0.0.1.1.1 15” TFT (XGA) integrated touch screen anti reflection coating design housing with writing desk
PC100.0.3.0.1.1.0 19” TFT (SXGA) without anti reflection coating design housing with writing desk
PC100.0.3.0.1.1.1 19” TFT (SXGA) integrated touch screen anti reflection coating design housing with writing desk
PC100.0.4.0.1.1.0 21” TFT (SXGA) without anti reflection coating design housing with writing desk
PC100.0.4.0.1.1.1 21” TFT (SXGA) integrated touch screen anti reflection coating design housing with writing desk
PC100.0.5.0.1.1.0 22” TFT (SXGA) without anti reflection coating design housing with writing desk
PC100.0.5.0.1.1.1 22” TFT (SXGA) integrated touch screen anti reflection coating design housing with writing desk
PC100.0.6.0.1.1.0 24” TFT (SXGA) without anti reflection coating design housing with writing desk
PC100.0.6.0.1.1.1 24” TFT (SXGA) integrated touch screen anti reflection coating design housing with writing desk

148 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
7 Man - machine interface
3 Modular Ex-PC
1 PC100 series

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 149


7 Man - machine interface
4 Keyboard and Trackball
1 KB/TB/KI 153 series

Thanks to the KI153 interface it is possible to use 2 USB devices in an EX-


II 2 G Ex ib IIC T4 Gb (KB153/TB153)
zone.
Hereby it is possible to use an intrinsically keyboard and trackball in a zone II (2) G [Exib Gb] IIC (KI153)
1.
Both devices are available as panel mounting aswell as completely Zone 1  Zone 21 
recessed in a housing. Zone 2  Zone 22 
Specifications
keyboard
Connection USB
Protection IP65
EX-limits Ui= 5,8V, li= 204mA, Pi= 0,392W, Ci= 25μF,
Li= ignorent small
Mounting zone 1
Ambiant temperature -20°C - +50°C
trackball
Connection USB
Protection IP65
Service controle including 2 cursor push buttons
EX-limits Ui= 5,8V, li= 204mA, Pi= 0,392W, Ci= 25μF,
Li= ignorent small
Mounting zone 1
Ambiant temperature 0°C - +50°C
interface
Connection 1 or 2 x USB (only suitable for low speed)
Protection IP40
Mounting safe area
Ambiant temperature -20°C - +40°C

On request
• zone 22

Ordering data
Code Description Housing No. of USB channels Language layout Diam. trackball
KB153.0.0 keyboard recessed German
KB153.0.1 keyboard recessed US
KB153.1.0 keyboard surface German
KB153.1.1 keyboard surface US
TB153.0.0 trackball recessed 38 mm
TB153.1.0 trackball surface 38 mm
KI153.0 interface 1
KI153.1 interface 2

150 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
7 Man - machine interface
4 Keyboard and Trackball
1 KB/TB/KI 153 series

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 151


8 Cable glands and accessories
1 Glands ........................................................................................................ 155
1 Exd / Exe metal - single compression: PA ...................................... 155
2 Exd / Exe metal - double compression: PAP .................................. 158
3 Exd / Exe metal - double compression for lead cable: PPAP ......... 162
4 Ex barrier metal - single compression: PA/B................................... 166
5 Ex barrier metal - double compression: PAP/B ............................... 170
6 Ex barrier metal - double compression for lead cable: PPAP/B ...... 174
7 Exe-plastic / metric thread .............................................................. 178

2 Plugs .......................................................................................................... 180


1 Exd brass ........................................................................................ 180
2 Exe brass ........................................................................................ 181
3 Exe plastic....................................................................................... 182

3 Reducers and adapters .............................................................................. 183


1 Exd / Exe brass ............................................................................... 183
2 Exe plastic....................................................................................... 185

4 Accessories ................................................................................................ 187


1 Earth tags brass .............................................................................. 187
2 Lock nuts......................................................................................... 188
3 Gaskets plastic................................................................................ 189

5 Special passing troughs ............................................................................. 190


1 Drainage valve ................................................................................ 190
2 Coupling for air/gas ......................................................................... 191

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 153


8 Cable glands and accessories
1 Glands
1 Exd / Exe metal - single compression: PA

Suited for armoured and non-armoured cables.Sealing on outer sheath of


II 2 G Ex d IIC / Ex e II
the cable.Mechanical protection IP66 in all positions.
Sizes 1 and 2 available in reduced version. II 2 D Ex tD A21 IP66

Specifications
Zone 1  Zone 21 
Material cable gland brass OT 58
Zone 2  Zone 22 
Protection IP66
Seal neoprene INERIS03ATEX0028
Thread NPT in accordance with ANSI B2.1
Metric - pitch 1,5
Ambiant temperature -20°C - +80°C

On request
• copper-free aluminium (type ../A)
• stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
• nickel-plated brass (type ../N)
• ambiant temperature -40°C

Ordering data
Product code Thread Cable diameter
Min Max
PA1R07M M20 4 7
PA1R07N 1/2”NPT 4 7
PA1R09M M20 7 9,5
PA1R09N 1/2”NPT 7 9,5
PA1R12M M20 9 12
PA1R12N 1/2”NPT 9 12
PA2R12M M25 9 12
PA2R12N 3/4”NPT 9 12
PA2R14M M25 12 14,5
PA2R14N 3/4”NPT 12 14,5
PA2R17M M25 14 17
PA2R17N 3/4”NPT 14 17
PA3.17M M32 14 17
PA3.17N 1”NPT 14 17
PA3.20M M32 17 20
PA3.20N 1”NPT 17 20
PA3.23M M32 20 23
PA3.23N 1”NPT 20 23
PA4.23M M40 20 23
PA4.23N 1 1/4”NPT 20 23
PA4.26M M40 23 26
PA4.26N 1 1/4”NPT 23 26
PA4.29M M40 26 29
PA4.29N 1 1/4”NPT 26 29
PA4.32M M40 29 32
PA4.32N 1 1/4”NPT 29 32
PA4.35M M40 32 35
PA4.35N 1 1/4”NPT 32 35
PA5.23M M50 20 23
PA5.23N 1 1/2”NPT 20 23
PA5.26M M50 23 26
PA5.26N 1 1/2”NPT 23 26
PA5.29M M50 26 29
PA5.29N 1 1/2”NPT 26 29
PA5.32M M50 29 32
PA5.32N 1 1/2”NPT 29 32

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 155


8 Cable glands and accessories
1 Glands
1 Exd / Exe metal - single compression: PA

Product code Thread Cable diameter


Min Max
PA5.35M M50 32 35,5
PA5.35N 1 1/2”NPT 32 35,5
PA6.35M M63 32 35,5
PA6.35N 2”NPT 32 35,5
PA6.39M M63 36 39
PA6.39N 2”NPT 36 39
PA6.42M M63 39 42
PA6.42N 2”NPT 39 42
PA6.47M M63 44 47
PA6.47N 2”NPT 44 47
PA7.47M M75 44 47
PA7.47N 2 1/2”NPT 44 47
PA7.52M M75 50 52
PA7.52N 2 1/2”NPT 50 52
PA8.57M M85 52 57
PA8.57N 3”NPT 52 57
PA8.61M M85 57 61
PA8.61N 3”NPT 57 61
PA8A.65M M85 61 65
PA8A.65N 3”NPT 61 65
PA8A.68M M85 65 68
PA8A.68N 3”NPT 65 68
PA10.73M M110 68 73
PA10.73N 4”NPT 68 73
PA10.78M M110 74 78
PA10.78N 4”NPT 74 78

Dimensional sketches

PA3-10 PA3-10

Product code Dimensions


D F G H
PA1R07M 17 50 27 31
PA1R09M 17 50 27 31
PA1R12M 17 50 27 31
PA2R12M 17 50 32 37
PA2R14M 17 50 32 37
PA2R17M 17 50 32 37
PA3.17M 21 64 43 46
PA3.20M 21 64 43 46
PA3.23M 21 64 43 46
PA4.23M 21 64 59 63
PA4.26M 21 64 59 63
PA4.29M 21 64 59 63
PA4.32M 21 64 59 63
PA4.35M 21 64 59 63
PA5.23M 21 64 59 63
PA5.26M 21 64 59 63
PA5.29M 21 64 59 63
PA5.32M 21 64 59 63
PA5.35M 21 64 59 63
PA6.35M 23 69 68 74
PA6.39M 23 69 68 74
PA6.42M 23 69 68 74
PA6.47M 23 69 68 74

156 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
1 Exd / Exe metal - single compression: PA

Product code Dimensions


D F G H
PA7.47M 26 71 82 88
PA7.52M 26 71 82 88
PA8.57M 26 88 100 118
PA8.61M 26 88 100 118
PA8A.65M 26 88 100 118
PA8A.68M 26 88 100 118
PA10.73M 28 94 128
PA10.78M 28 94 128
PA1R07N 17 50 27 31
PA1R09N 17 50 27 31
PA1R12N 17 50 27 31
PA2R12N 17 50 32 37
PA2R14N 17 50 32 37
PA2R17N 17 50 32 37
PA3.17N 21 64 43 46
PA3.20N 21 64 43 46
PA3.23N 21 64 43 46
PA4.23N 21 64 59 63
PA4.26N 21 64 59 63
PA4.29N 21 64 59 63
PA4.32N 21 64 59 63
PA4.35N 21 64 59 63
PA5.23N 21 64 59 63
PA5.26N 21 64 59 63
PA5.29N 21 64 59 63
PA5.32N 21 64 59 63
PA5.35N 21 64 59 63
PA6.35N 23 69 68 74
PA6.39N 23 69 68 74
PA6.42N 23 69 68 74
PA6.47N 23 69 68 74
PA7.47N 26 71 82 88
PA7.52N 26 71 82 88
PA8.57N 26 88 100 118
PA8.61N 26 88 100 118
PA8A.65N 26 88 100 118
PA8A.68N 26 88 100 118
PA10.73N 28 94 128
PA10.78N 28 94 128

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 157


8 Cable glands and accessories
1 Glands
2 Exd / Exe metal - double compression: PAP

Suited for armoured cables.


II 2 G Ex d IIC / Ex e II
Sealing on inner and outer sheaths of the cable.
Compression of the armouring. II 2 D Ex tD A21 IP66
Mechanical protection IP66 in all positions.
Sizes 1 and 2 available in reduced version. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Material cable gland brass OT 58 INERIS03ATEX0028
Protection IP66
Seal neoprene
Thread NPT in accordance with ANSI B2.1
Metric - pitch 1,5
Ambiant temperature -20°C - +80°C

On request
• copper-free aluminium (type ../A)
• stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
• nickel-plated brass (type ../N)
• ambiant temperature -40°C

Ordering data
Product Code Thread Cable diameter
A B
Min Max Min Max
PAP1R0713M M20 4 7 9 13
PAP1R0713N 1/2”NPT 4 7 9 13
PAP1R0718M M20 4 7 13 18
PAP1R0718N 1/2”NPT 4 7 13 18
PAP1R0913M M20 7 9,5 9 13
PAP1R0913N 1/2”NPT 7 9,5 9 13
PAP1R0918M M20 7 9,5 13 18
PAP1R0918N 1/2”NPT 7 9,5 13 18
PAP1R1213M M20 9 12 9 13
PAP1R1213N 1/2”NPT 9 12 9 13
PAP1R1218M M20 9 12 13 18
PAP1R1218N 1/2”NPT 9 12 13 18
PAP2R1219M M25 9 12 15 19
PAP2R1219N 3/4”NPT 9 12 15 19
PAP2R1223M M25 9 12 18 23
PAP2R1223N 3/4”NPT 9 12 18 23
PAP2R1419M M25 12 14,5 15 19
PAP2R1419N 3/4”NPT 12 14,5 15 19
PAP2R1423M M25 12 14,5 18 23
PAP2R1423N 3/4”NPT 12 14,5 18 23
PAP2R1719M M25 14 17 15 19
PAP2R1719N 3/4”NPT 14 17 15 19
PAP2R1723M M25 14 17 18 23
PAP2R1723N 3/4”NPT 14 17 18 23
PAP3.1723M M32 14 17 20 23
PAP3.1723N 1”NPT 14 17 20 23
PAP3.1726M M32 14 17 23 26
PAP3.1726N 1”NPT 14 17 23 26
PAP3.1729M M32 14 17 24 29
PAP3.1729N 1”NPT 14 17 24 29
PAP3.2023M M32 17 20 20 23
PAP3.2023N 1”NPT 17 20 20 23
PAP3.2026M M32 17 20 23 26
PAP3.2026N 1”NPT 17 20 23 26
PAP3.2029M M32 17 20 24 29
PAP3.2029N 1”NPT 17 20 24 29

158 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
2 Exd / Exe metal - double compression: PAP

Product Code Thread Cable diameter


A B
Min Max Min Max
PAP3.2323M M32 20 23 20 23
PAP3.2323N 1”NPT 20 23 20 23
PAP3.2326M M32 20 23 23 26
PAP3.2326N 1”NPT 20 23 23 26
PAP3.2329M M32 20 23 24 29
PAP3.2329N 1”NPT 20 23 24 29
PAP4.2335M M40 20 23 30 35
PAP4.2335N 1 1/4”NPT 20 23 30 35
PAP4.2635M M40 23 26 30 35
PAP4.2635N 1 1/4”NPT 23 26 30 35
PAP4.2935M M40 26 29 30 35
PAP4.2935N 1 1/4”NPT 26 29 30 35
PAP4.3241M M40 29 32 36 41
PAP4.3241N 1 1/4”NPT 29 32 36 41
PAP4.3541M M40 32 35,5 36 41
PAP4.3541N 1 1/4”NPT 32 35,5 36 41
PAP5.2335M M50 20 23 30 35
PAP5.2335N 1 1/2”NPT 20 23 30 35
PAP5.2635M M50 23 26 30 35
PAP5.2635N 1 1/2”NPT 23 26 30 35
PAP5.2935M M50 26 29 30 35
PAP5.2935N 1 1/2”NPT 26 29 30 35
PAP5.3241M M50 29 32 36 41
PAP5.3241N 1 1/2”NPT 29 32 36 41
PAP5.3541M M50 32 35,5 36 41
PAP5.3541N 1 1/2”NPT 32 35,5 36 41
PAP6.3547M M63 32 35,5 42 47
PAP6.3547N 2”NPT 32 35,5 42 47
PAP6.3947M M63 36 39 42 47
PAP6.3947N 2”NPT 36 39 42 47
PAP6.4250M M63 39 42 46 50
PAP6.4250N 2”NPT 39 42 46 50
PAP6.4255M M63 39 42 50 55
PAP6.4255N 2”NPT 39 42 50 55
PAP6.4755M M63 44 47 50 55
PAP6.4755N 2”NPT 44 47 50 55
PAP7.4759M M75 44 47 55 59
PAP7.4759N 2 1/2”NPT 44 47 55 59
PAP7.5259M M75 50 52 55 59
PAP7.5259N 2 1/2”NPT 50 52 55 59
PAP8.5770M M85 52 57 65 70
PAP8.5770N 3”NPT 52 57 65 70
PAP8.6170M M85 57 61 65 70
PAP8.6170N 3”NPT 57 61 65 70
PAP8A.6578M M85 61 65 70 78
PAP8A.6578N 3”NPT 61 65 70 78
PAP8A.6878M M85 65 68 70 78
PAP8A.6878N 3”NPT 65 68 70 78
PAP10.7385M M110 68 73 78 85
PAP10.7385N 4”NPT 68 73 78 85
PAP10.7892M M110 74 78 85 92
PAP10.7892N 4”NPT 74 78 85 92

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 159


8 Cable glands and accessories
1 Glands
2 Exd / Exe metal - double compression: PAP

Dimensional sketches

PAP3-10
PAP1R-2R
Product code Dimensions
D F G H
PAP1R0713M 17 62 27 31
PAP1R0713N 17 62 27 31
PAP1R0718M 17 62 27 31
PAP1R0718N 17 62 27 31
PAP1R0913M 17 62 27 31
PAP1R0913N 17 62 27 31
PAP1R0918M 17 62 27 31
PAP1R0918N 17 62 27 31
PAP1R1213M 17 62 27 31
PAP1R1213N 17 62 27 31
PAP1R1218M 17 62 27 31
PAP1R1218N 17 62 27 31
PAP2R1219M 17 62 32 37
PAP2R1219N 17 62 32 37
PAP2R1223M 17 62 32 37
PAP2R1223N 17 62 32 37
PAP2R1419M 17 62 32 37
PAP2R1419N 17 62 32 37
PAP2R1423M 17 62 32 37
PAP2R1423N 17 62 32 37
PAP2R1719M 17 62 32 37
PAP2R1719N 17 62 32 37
PAP2R1723M 17 62 32 37
PAP2R1723N 17 62 32 37
PAP3.1723M 21 88 43 46
PAP3.1723N 21 88 43 46
PAP3.1726M 21 88 43 46
PAP3.1726N 21 88 43 46
PAP3.1729M 21 88 43 46
PAP3.1729N 21 88 43 46
PAP3.2023M 21 88 43 46
PAP3.2023N 21 88 43 46
PAP3.2026M 21 88 43 46
PAP3.2026N 21 88 43 46
PAP3.2029M 21 88 43 46
PAP3.2029N 21 88 43 46
PAP3.2323M 21 88 43 46
PAP3.2323N 21 88 43 46
PAP3.2326M 21 88 43 46
PAP3.2326N 21 88 43 46
PAP3.2329M 21 88 43 46
PAP3.2329N 21 88 43 46
PAP4.2335M 21 88 59 63
PAP4.2335N 21 88 59 63
PAP4.2635M 21 88 59 63
PAP4.2635N 21 88 59 63
PAP4.2935M 21 88 59 63
PAP4.2935N 21 88 59 63
PAP4.3241M 21 88 59 63
PAP4.3241N 21 88 59 63
PAP4.3541M 21 88 59 63
PAP4.3541N 21 88 59 63

160 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
2 Exd / Exe metal - double compression: PAP

Product code Dimensions


D F G H
PAP5.2335M 21 88 59 63
PAP5.2335N 21 88 59 63
PAP5.2635M 21 88 59 63
PAP5.2635N 21 88 59 63
PAP5.2935M 21 88 59 63
PAP5.2935N 21 88 59 63
PAP5.3241M 21 88 59 63
PAP5.3241N 21 88 59 63
PAP5.3541M 21 88 59 63
PAP5.3541N 21 88 59 63
PAP6.3547M 23 92 68 74
PAP6.3547N 23 92 68 74
PAP6.3947M 23 92 68 74
PAP6.3947N 23 92 68 74
PAP6.4250M 23 92 68 74
PAP6.4250N 23 92 68 74
PAP6.4255M 23 92 68 74
PAP6.4255N 23 92 68 74
PAP6.4755M 23 92 68 74
PAP6.4755N 23 92 68 74
PAP7.4759M 26 92 82 88
PAP7.4759N 26 92 82 88
PAP7.5259M 26 92 82 88
PAP7.5259N 26 92 82 88
PAP8.5770M 26 115 100 118
PAP8.5770N 26 115 100 118
PAP8.6170M 26 115 100 118
PAP8.6170N 26 115 100 118
PAP8A.6578M 26 115 100 118
PAP8A.6578N 26 115 100 118
PAP8A.6878M 26 115 100 118
PAP8A.6878N 26 115 100 118
PAP10.7385M 28 117 128
PAP10.7385N 28 117 128
PAP10.7892M 28 117 128
PAP10.7892N 28 117 128

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 161


8 Cable glands and accessories
1 Glands
3 Exd / Exe metal - double compression for lead cable: PPAP

Suited for armoured cables with lead sheaths.


II 2 G Ex d IIC / Ex e II
Sealing on inner and outer sheath of the cable.
Compression of the cable’s armouring. II 2 D Ex tD A21 IP66
With lead plate for earthing continuousity.
Mechanical protection IP66 in all positions. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Material cable gland brass OT 58 INERIS03ATEX0028
Protection IP66
Seal neoprene
Thread NPT in accordance with ANSI B2.1Metric -
pitch 1,5
Ambiant temperature -20°C - +80°C

On request
• copper-free aluminium (type ../A)
• stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
• nickel-plated brass (type ../N)
• ambiant temperature -40°C

Ordering data
Product code Thread Cable diameter
A B
Min Max Min Max
PPAP1R0713M M20 4 7 9 13
PPAP1R0713N 1/2”NPT 4 7 9 13
PPAP1R0718M M20 4 7 13 18
PPAP1R0718N 1/2”NPT 4 7 13 18
PPAP1R0913M M20 7 9,5 9 13
PPAP1R0913N 1/2”NPT 7 9,5 9 13
PPAP1R0918M M20 7 9,5 13 18
PPAP1R0918N 1/2”NPT 7 9,5 13 18
PPAP1R1213M M20 9 12 9 13
PPAP1R1213N 1/2”NPT 9 12 9 13
PPAP1R1218M M20 9 12 13 18
PPAP1R1218N 1/2”NPT 9 12 13 18
PPAP2R1219M M25 9 12 15 19
PPAP2R1219N 3/4”NPT 9 12 15 19
PPAP2R1223M M25 9 12 18 23
PPAP2R1223N 3/4”NPT 9 12 18 23
PPAP2R1419M M25 12 14,5 15 19
PPAP2R1419N 3/4”NPT 12 14,5 15 19
PPAP2R1423M M25 12 14,5 18 23
PPAP2R1423N 3/4”NPT 12 14,5 18 23
PPAP2R1719M M25 14 17 15 19
PPAP2R1719N 3/4”NPT 14 17 15 19
PPAP2R1723M M25 14 17 18 23
PPAP2R1723N 3/4”NPT 14 17 18 23
PPAP3.1723M M32 14 17 20 23
PPAP3.1723N 1”NPT 14 17 20 23
PPAP3.1726M M32 14 17 23 26
PPAP3.1726N 1”NPT 14 17 23 26
PPAP3.1729M M32 14 17 24 29
PPAP3.1729N 1”NPT 14 17 24 29
PPAP3.2023M M32 17 20 20 23
PPAP3.2023N 1”NPT 17 20 20 23
PPAP3.2026M M32 17 20 23 26
PPAP3.2026N 1”NPT 17 20 23 26
PPAP3.2029M M32 17 20 24 29
PPAP3.2029N 1”NPT 17 20 24 29

162 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
3 Exd / Exe metal - double compression for lead cable: PPAP

Product code Thread Cable diameter


A B
Min Max Min Max
PPAP3.2323M M32 20 23 20 23
PPAP3.2323N 1”NPT 20 23 20 23
PPAP3.2326M M32 20 23 23 26
PPAP3.2326N 1”NPT 20 23 23 26
PPAP3.2329M M32 20 23 24 29
PPAP3.2329N 1”NPT 20 23 24 29
PPAP4.2335M M40 20 23 30 35
PPAP4.2335N 1 1/4”NPT 20 23 30 35
PPAP4.2635M M40 23 26 30 35
PPAP4.2635N 1 1/4”NPT 23 26 30 35
PPAP4.2935M M40 26 29 30 35
PPAP4.2935N 1 1/4”NPT 26 29 30 35
PPAP4.3241M M40 29 32 36 41
PPAP4.3241N 1 1/4”NPT 29 32 36 41
PPAP4.3541M M40 32 35,5 36 41
PPAP4.3541N 1 1/4”NPT 32 35,5 36 41
PPAP5.2335M M50 20 23 30 35
PPAP5.2335N 1 1/2”NPT 20 23 30 35
PPAP5.2635M M50 23 26 30 35
PPAP5.2635N 1 1/2”NPT 23 26 30 35
PPAP5.2935M M50 26 29 30 35
PPAP5.2935N 1 1/2”NPT 26 29 30 35
PPAP5.3241M M50 29 32 36 41
PPAP5.3241N 1 1/2”NPT 29 32 36 41
PPAP5.3541M M50 32 35,5 36 41
PPAP5.3541N 1 1/2”NPT 32 35,5 36 41
PPAP6.3547M M63 32 35,5 42 47
PPAP6.3547N 2”NPT 32 35,5 42 47
PPAP6.3947M M63 36 39 42 47
PPAP6.3947N 2”NPT 36 39 42 47
PPAP6.4250M M63 39 42 46 50
PPAP6.4250N 2”NPT 39 42 46 50
PPAP6.4255M M63 39 42 50 55
PPAP6.4255N 2”NPT 39 42 50 55
PPAP6.4755M M63 44 47 50 55
PPAP6.4755N 2”NPT 44 47 50 55
PPAP7.4759M M75 44 47 55 59
PPAP7.4759N 2 1/2”NPT 44 47 55 59
PPAP7.5259M M75 50 52 55 59
PPAP7.5259N 2 1/2”NPT 50 52 55 59
PPAP8.5770M M85 52 57 65 70
PPAP8.5770N 3”NPT 52 57 65 70
PPAP8.6170M M85 57 61 65 70
PPAP8.6170N 3”NPT 57 61 65 70
PPAP8A.6578M M85 61 65 70 78
PPAP8A.6578N 3”NPT 61 65 70 78
PPAP8A.6878M M85 65 68 70 78
PPAP8A.6878N 3”NPT 65 68 70 78
PPAP10.7385M M110 68 73 78 85
PPAP10.7385N 4”NPT 68 73 78 85
PPAP10.7892M M110 74 78 85 92
PPAP10.7892N 4”NPT 74 78 85 92

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 163


8 Cable glands and accessories
1 Glands
3 Exd / Exe metal - double compression for lead cable: PPAP

Dimensional sketches

PPAP3-10
PPAP1R-2R
Product code Dimensions
D F G H
PPAP1R0713M 17 62 27 31
PPAP1R0713N 17 62 27 31
PPAP1R0718M 17 62 27 31
PPAP1R0718N 17 62 27 31
PPAP1R0913M 17 62 27 31
PPAP1R0913N 17 62 27 31
PPAP1R0918M 17 62 27 31
PPAP1R0918N 17 62 27 31
PPAP1R1213M 17 62 27 31
PPAP1R1213N 17 62 27 31
PPAP1R1218M 17 62 27 31
PPAP1R1218N 17 62 27 31
PPAP2R1219M 17 62 32 37
PPAP2R1219N 17 62 32 37
PPAP2R1223M 17 62 32 37
PPAP2R1223N 17 62 32 37
PPAP2R1419M 17 62 32 37
PPAP2R1419N 17 62 32 37
PPAP2R1423M 17 62 32 37
PPAP2R1423N 17 62 32 37
PPAP2R1719M 17 62 32 37
PPAP2R1719N 17 62 32 37
PPAP2R1723M 17 62 32 37
PPAP2R1723N 17 62 32 37
PPAP3.1723M 21 88 43 46
PPAP3.1723N 21 88 43 46
PPAP3.1726M 21 88 43 46
PPAP3.1726N 21 88 43 46
PPAP3.1729M 21 88 43 46
PPAP3.1729N 21 88 43 46
PPAP3.2023M 21 88 43 46
PPAP3.2023N 21 88 43 46
PPAP3.2026M 21 88 43 46
PPAP3.2026N 21 88 43 46
PPAP3.2029M 21 88 43 46
PPAP3.2029N 21 88 43 46
PPAP3.2323M 21 88 43 46
PPAP3.2323N 21 88 43 46
PPAP3.2326M 21 88 43 46
PPAP3.2326N 21 88 43 46
PPAP3.2329M 21 88 43 46
PPAP3.2329N 21 88 43 46
PPAP4.2335M 21 88 59 63
PPAP4.2335N 21 88 59 63
PPAP4.2635M 21 88 59 63
PPAP4.2635N 21 88 59 63
PPAP4.2935M 21 88 59 63
PPAP4.2935N 21 88 59 63
PPAP4.3241M 21 88 59 63
PPAP4.3241N 21 88 59 63
PPAP4.3541M 21 88 59 63
PPAP4.3541N 21 88 59 63

164 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
3 Exd / Exe metal - double compression for lead cable: PPAP

Product code Dimensions


D F G H
PPAP5.2335M 21 88 59 63
PPAP5.2335N 21 88 59 63
PPAP5.2635M 21 88 59 63
PPAP5.2635N 21 88 59 63
PPAP5.2935M 21 88 59 63
PPAP5.2935N 21 88 59 63
PPAP5.3241M 21 88 59 63
PPAP5.3241N 21 88 59 63
PPAP5.3541M 21 88 59 63
PPAP5.3541N 21 88 59 63
PPAP6.3547M 23 92 68 74
PPAP6.3547N 23 92 68 74
PPAP6.3947M 23 92 68 74
PPAP6.3947N 23 92 68 74
PPAP6.4250M 23 92 68 74
PPAP6.4250N 23 92 68 74
PPAP6.4255M 23 92 68 74
PPAP6.4255N 23 92 68 74
PPAP6.4755M 23 92 68 74
PPAP6.4755N 23 92 68 74
PPAP7.4759M 26 92 82 88
PPAP7.4759N 26 92 82 88
PPAP7.5259M 26 92 82 88
PPAP7.5259N 26 92 82 88
PPAP8.5770M 26 115 100 118
PPAP8.5770N 26 115 100 118
PPAP8.6170M 26 115 100 118
PPAP8.6170N 26 115 100 118
PPAP8A.6578M 26 115 100 118
PPAP8A.6578N 26 115 100 118
PPAP8A.6878M 26 115 100 118
PPAP8A.6878N 26 115 100 118
PPAP10.7385M 28 117 128
PPAP10.7385N 28 117 128
PPAP10.7892M 28 117 128
PPAP10.7892N 28 117 128

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 165


8 Cable glands and accessories
1 Glands
4 Ex barrier metal - single compression: PA/B

Our barrier glands are composed identically to the classic PA-glands.


II 2 G Exd IIC / Exe II
However an extra metal ring is added in the body which will be filled with a
compound. II 2 D ExtD A21 IP66
Whether you should use a barrier gland or not can be deducted from the
flowchart below. Zone 1  Zone 21 
Suited for non-armoured cables. Zone 2  Zone 22 
Sealing on outer sheath of the cable.
INERIS03ATEX0028
Mechanical protection IP66 in all positions.
Sizes 1 and 2 available in reduced version.
Specifications
Material cable gland brass OT 58
Protection IP66
Seal neoprene
On request
Thread NPT in accordance with ANSI B2.1
Metric - pitch 1,5 • copper-free aluminium (type ../A)
Ambiant temperature -20°C - +80°C • stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
• nickel-plated brass (type ../N)
• ambiant temperature -40°C

166 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
4 Ex barrier metal - single compression: PA/B

Ordering data
Product code Thread Cable diameter
Min Max
PA1R07M/B M20 4 7
PA1R07N/B 1/2”NPT 4 7
PA1R09M/B M20 7 9,5
PA1R09N/B 1/2”NPT 7 9,5
PA1R12M/B M20 9 12
PA1R12N/B 1/2”NPT 9 12
PA2R12M/B M25 9 12
PA2R12N/B 3/4”NPT 9 12
PA2R14M/B M25 12 14,5
PA2R14N/B 3/4”NPT 12 14,5
PA2R17M/B M25 14 17
PA2R17N/B 3/4”NPT 14 17
PA3.17M/B M32 14 17
PA3.17N/B 1”NPT 14 17
PA3.20M/B M32 17 20
PA3.20N/B 1”NPT 17 20
PA3.23M/B M32 20 23
PA3.23N/B 1”NPT 20 23
PA4.23M/B M40 20 23
PA4.23N/B 1 1/4”NPT 20 23
PA4.26M/B M40 23 26
PA4.26N/B 1 1/4”NPT 23 26
PA4.29M/B M40 26 29
PA4.29N/B 1 1/4”NPT 26 29
PA4.32M/B M40 29 32
PA4.32N/B 1 1/4”NPT 29 32
PA4.35M/B M40 32 35
PA4.35N/B 1 1/4”NPT 32 35
PA5.23M/B M50 20 23
PA5.23N/B 1 1/2”NPT 20 23
PA5.26M/B M50 23 26
PA5.26N/B 1 1/2”NPT 23 26
PA5.29M/B M50 26 29
PA5.29N/B 1 1/2”NPT 26 29
PA5.32M/B M50 29 32
PA5.32N/B 1 1/2”NPT 29 32
PA5.35M/B M50 32 35,5
PA5.35N/B 1 1/2”NPT 32 35,5
PA6.35M/B M63 32 35,5
PA6.35N/B 2”NPT 32 35,5
PA6.39M/B M63 36 39
PA6.39N/B 2”NPT 36 39
PA6.42M/B M63 39 42
PA6.42N/B 2”NPT 39 42
PA6.47M/B M63 44 47
PA6.47N/B 2”NPT 44 47
PA7.47M/B M75 44 47
PA7.47N/B 2 1/2”NPT 44 47
PA7.52M/B M75 50 52
PA7.52N/B 2 1/2”NPT 50 52
PA8.57M/B M85 52 57
PA8.57N/B 3”NPT 52 57
PA8.61M/B M85 57 61
PA8.61N/B 3”NPT 57 61
PA8A.65M/B M85 61 65
PA8A.65N/B 3”NPT 61 65
PA8A.68M/B M85 65 68
PA8A.68N/B 3”NPT 65 68
PA10.73M/B M110 68 73
PA10.73N/B 4”NPT 68 73
PA10.78M/B M110 74 78
PA10.78N/B 4”NPT 74 78

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 167


8 Cable glands and accessories
1 Glands
4 Ex barrier metal - single compression: PA/B

Dimensional sketches

PA3-10 PA3-10

Product code Dimensions


D F G H
PA1R07M/B 17 50 27 31
PA1R09M/B 17 50 27 31
PA1R12M/B 17 50 27 31
PA2R12M/B 17 50 32 37
PA2R14M/B 17 50 32 37
PA2R17M/B 17 50 32 37
PA3.17M/B 21 64 43 46
PA3.20M/B 21 64 43 46
PA3.23M/B 21 64 43 46
PA4.23M/B 21 64 59 63
PA4.26M/B 21 64 59 63
PA4.29M/B 21 64 59 63
PA4.32M/B 21 64 59 63
PA4.35M/B 21 64 59 63
PA5.23M/B 21 64 59 63
PA5.26M/B 21 64 59 63
PA5.29M/B 21 64 59 63
PA5.32M/B 21 64 59 63
PA5.35M/B 21 64 59 63
PA6.35M/B 23 69 68 74
PA6.39M/B 23 69 68 74
PA6.42M/B 23 69 68 74
PA6.47M/B 23 69 68 74
PA7.47M/B 26 71 82 88
PA7.52M/B 26 71 82 88
PA8.57M/B 26 88 100 118
PA8.61M/B 26 88 100 118
PA8A.65M/B 26 88 100 118
PA8A.68M/B 26 88 100 118
PA10.73M/B 28 94 128
PA10.78M/B 28 94 128
PA1R07N/B 17 50 27 31
PA1R09N/B 17 50 27 31
PA1R12N/B 17 50 27 31
PA2R12N/B 17 50 32 37
PA2R14N/B 17 50 32 37
PA2R17N/B 17 50 32 37
PA3.17N/B 21 64 43 46
PA3.20N/B 21 64 43 46
PA3.23N/B 21 64 43 46
PA4.23N/B 21 64 59 63
PA4.26N/B 21 64 59 63
PA4.29N/B 21 64 59 63
PA4.32N/B 21 64 59 63
PA4.35N/B 21 64 59 63
PA5.23N/B 21 64 59 63
PA5.26N/B 21 64 59 63
PA5.29N/B 21 64 59 63
PA5.32N/B 21 64 59 63
PA5.35N/B 21 64 59 63
PA6.35N/B 23 69 68 74
PA6.39N/B 23 69 68 74

168 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
4 Ex barrier metal - single compression: PA/B

Product code Dimensions


D F G H
PA6.42N/B 23 69 68 74
PA6.47N/B 23 69 68 74
PA7.47N/B 26 71 82 88
PA7.52N/B 26 71 82 88
PA8.57N/B 26 88 100 118
PA8.61N/B 26 88 100 118
PA8A.65N/B 26 88 100 118
PA8A.68N/B 26 88 100 118
PA10.73N/B 28 94 128
PA10.78N/B 28 94 128

Compound
Code Description
kit 100g, consisting of:
PAP-COMPOUND-1
bottle A, bottle B, gloves, syringe, stirring rod, mixing jar
kit 300g, consisting of:
PAP-COMPOUND-3
bottle A, bottle B, gloves, 3 syringes, 3 stirring rods, 3 mixing jars

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 169


8 Cable glands and accessories
1 Glands
5 Ex barrier metal - double compression: PAP/B

Our barrier glands are composed identically to the classic PAP-glands.


II 2 G Exd IIC / Exe II
However an extra metal ring is added in the body which will be filled with a
compound. II 2 D ExtD A21 IP66
Whether you should use a barrier gland or not can be deducted from the
flowchart below. Zone 1  Zone 21 
Suited for armoured cables. Sealing on inner and outer sheaths of the Zone 2  Zone 22 
cable. Compression of the armouring. Mechanical protection IP66 in all
INERIS03ATEX0028
positions. Sizes 1 and 2 available in reduced version.
Specifications
Material cable gland brass OT 58
Protection IP66
Seal neoprene
On request
Thread NPT in accordance with ANSI B2.1
Metric - pitch 1,5 • copper-free aluminium (type ../A)
Ambiant temperature -20°C - +80°C • stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
• nickel-plated brass (type ../N)
• ambiant temperature -40°C

Ordering data
Product Code Thread Cable diameter
A B
Min Max Min Max
PAP1R0713M/B M20 4 7 9 13
PAP1R0713N/B 1/2”NPT 4 7 9 13
PAP1R0718M/B M20 4 7 13 18
PAP1R0718N/B 1/2”NPT 4 7 13 18
PAP1R0913M/B M20 7 9,5 9 13
PAP1R0913N/B 1/2”NPT 7 9,5 9 13
PAP1R0918M/B M20 7 9,5 13 18
PAP1R0918N/B 1/2”NPT 7 9,5 13 18
PAP1R1213M/B M20 9 12 9 13
PAP1R1213N/B 1/2”NPT 9 12 9 13
PAP1R1218M/B M20 9 12 13 18
PAP1R1218N/B 1/2”NPT 9 12 13 18

170 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
5 Ex barrier metal - double compression: PAP/B

Product Code Thread Cable diameter


A B
Min Max Min Max
PAP2R1219M/B M25 9 12 15 19
PAP2R1219N/B 3/4”NPT 9 12 15 19
PAP2R1223M/B M25 9 12 18 23
PAP2R1223N/B 3/4”NPT 9 12 18 23
PAP2R1419M/B M25 12 14,5 15 19
PAP2R1419N/B 3/4”NPT 12 14,5 15 19
PAP2R1423M/B M25 12 14,5 18 23
PAP2R1423N/B 3/4”NPT 12 14,5 18 23
PAP2R1719M/B M25 14 17 15 19
PAP2R1719N/B 3/4”NPT 14 17 15 19
PAP2R1723M/B M25 14 17 18 23
PAP2R1723N/B 3/4”NPT 14 17 18 23
PAP3.1723M/B M32 14 17 20 23
PAP3.1723N/B 1”NPT 14 17 20 23
PAP3.1726M/B M32 14 17 23 26
PAP3.1726N/B 1”NPT 14 17 23 26
PAP3.1729M/B M32 14 17 24 29
PAP3.1729N/B 1”NPT 14 17 24 29
PAP3.2023M/B M32 17 20 20 23
PAP3.2023N/B 1”NPT 17 20 20 23
PAP3.2026M/B M32 17 20 23 26
PAP3.2026N/B 1”NPT 17 20 23 26
PAP3.2029M/B M32 17 20 24 29
PAP3.2029N/B 1”NPT 17 20 24 29
PAP3.2323M/B M32 20 23 20 23
PAP3.2323N/B 1”NPT 20 23 20 23
PAP3.2326M/B M32 20 23 23 26
PAP3.2326N/B 1”NPT 20 23 23 26
PAP3.2329M/B M32 20 23 24 29
PAP3.2329N/B 1”NPT 20 23 24 29
PAP4.2335M/B M40 20 23 30 35
PAP4.2335N/B 1 1/4”NPT 20 23 30 35
PAP4.2635M/B M40 23 26 30 35
PAP4.2635N/B 1 1/4”NPT 23 26 30 35
PAP4.2935M/B M40 26 29 30 35
PAP4.2935N/B 1 1/4”NPT 26 29 30 35
PAP4.3241M/B M40 29 32 36 41
PAP4.3241N/B 1 1/4”NPT 29 32 36 41
PAP4.3541M/B M40 32 35,5 36 41
PAP4.3541N/B 1 1/4”NPT 32 35,5 36 41
PAP5.2335M/B M50 20 23 30 35
PAP5.2335N/B 1 1/2”NPT 20 23 30 35
PAP5.2635M/B M50 23 26 30 35
PAP5.2635N/B 1 1/2”NPT 23 26 30 35
PAP5.2935M/B M50 26 29 30 35
PAP5.2935N/B 1 1/2”NPT 26 29 30 35
PAP5.3241M/B M50 29 32 36 41
PAP5.3241N/B 1 1/2”NPT 29 32 36 41
PAP5.3541M/B M50 32 35,5 36 41
PAP5.3541N/B 1 1/2”NPT 32 35,5 36 41
PAP6.3547M/B M63 32 35,5 42 47
PAP6.3547N/B 2”NPT 32 35,5 42 47
PAP6.3947M/B M63 36 39 42 47
PAP6.3947N/B 2”NPT 36 39 42 47
PAP6.4250M/B M63 39 42 46 50
PAP6.4250N/B 2”NPT 39 42 46 50
PAP6.4255M/B M63 39 42 50 55
PAP6.4255N/B 2”NPT 39 42 50 55
PAP6.4755M/B M63 44 47 50 55
PAP6.4755N/B 2”NPT 44 47 50 55
PAP7.4759M/B M75 44 47 55 59
PAP7.4759N/B 2 1/2”NPT 44 47 55 59

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 171


8 Cable glands and accessories
1 Glands
5 Ex barrier metal - double compression: PAP/B

Product Code Thread Cable diameter


A B
Min Max Min Max
PAP7.5259M/B M75 50 52 55 59
PAP7.5259N/B 2 1/2”NPT 50 52 55 59
PAP8.5770M/B M85 52 57 65 70
PAP8.5770N/B 3”NPT 52 57 65 70
PAP8.6170M/B M85 57 61 65 70
PAP8.6170N/B 3”NPT 57 61 65 70
PAP8A.6578M/B M85 61 65 70 78
PAP8A.6578N/B 3”NPT 61 65 70 78
PAP8A.6878M/B M85 65 68 70 78
PAP8A.6878N/B 3”NPT 65 68 70 78
PAP10.7385M/B M110 68 73 78 85
PAP10.7385N/B 4”NPT 68 73 78 85
PAP10.7892M/B M110 74 78 85 92
PAP10.7892N/B 4”NPT 74 78 85 92

Dimensional sketches

PAP3-10
PAP1R-2R
Product code Dimensions
D F G H
PAP1R0713M/B 17 62 27 31
PAP1R0713N/B 17 62 27 31
PAP1R0718M/B 17 62 27 31
PAP1R0718N/B 17 62 27 31
PAP1R0913M/B 17 62 27 31
PAP1R0913N/B 17 62 27 31
PAP1R0918M/B 17 62 27 31
PAP1R0918N/B 17 62 27 31
PAP1R1213M/B 17 62 27 31
PAP1R1213N/B 17 62 27 31
PAP1R1218M/B 17 62 27 31
PAP1R1218N/B 17 62 27 31
PAP2R1219M/B 17 62 32 37
PAP2R1219N/B 17 62 32 37
PAP2R1223M/B 17 62 32 37
PAP2R1223N/B 17 62 32 37
PAP2R1419M/B 17 62 32 37
PAP2R1419N/B 17 62 32 37
PAP2R1423M/B 17 62 32 37
PAP2R1423N/B 17 62 32 37
PAP2R1719M/B 17 62 32 37
PAP2R1719N/B 17 62 32 37
PAP2R1723M/B 17 62 32 37
PAP2R1723N/B 17 62 32 37
PAP3.1723M/B 21 88 43 46
PAP3.1723N/B 21 88 43 46
PAP3.1726M/B 21 88 43 46
PAP3.1726N/B 21 88 43 46
PAP3.1729M/B 21 88 43 46
PAP3.1729N/B 21 88 43 46
PAP3.2023M/B 21 88 43 46
PAP3.2023N/B 21 88 43 46
PAP3.2026M/B 21 88 43 46
PAP3.2026N/B 21 88 43 46
PAP3.2029M/B 21 88 43 46

172 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
5 Ex barrier metal - double compression: PAP/B

Product code Dimensions


D F G H
PAP3.2029N/B 21 88 43 46
PAP3.2323M/B 21 88 43 46
PAP3.2323N/B 21 88 43 46
PAP3.2326M/B 21 88 43 46
PAP3.2326N/B 21 88 43 46
PAP3.2329M/B 21 88 43 46
PAP3.2329N/B 21 88 43 46
PAP4.2335M/B 21 88 59 63
PAP4.2335N/B 21 88 59 63
PAP4.2635M/B 21 88 59 63
PAP4.2635N/B 21 88 59 63
PAP4.2935M/B 21 88 59 63
PAP4.2935N/B 21 88 59 63
PAP4.3241M/B 21 88 59 63
PAP4.3241N/B 21 88 59 63
PAP4.3541M/B 21 88 59 63
PAP4.3541N/B 21 88 59 63
PAP5.2335M/B 21 88 59 63
PAP5.2335N/B 21 88 59 63
PAP5.2635M/B 21 88 59 63
PAP5.2635N/B 21 88 59 63
PAP5.2935M/B 21 88 59 63
PAP5.2935N/B 21 88 59 63
PAP5.3241M/B 21 88 59 63
PAP5.3241N/B 21 88 59 63
PAP5.3541M/B 21 88 59 63
PAP5.3541N/B 21 88 59 63
PAP6.3547M/B 23 92 68 74
PAP6.3547N/B 23 92 68 74
PAP6.3947M/B 23 92 68 74
PAP6.3947N/B 23 92 68 74
PAP6.4250M/B 23 92 68 74
PAP6.4250N/B 23 92 68 74
PAP6.4255M/B 23 92 68 74
PAP6.4255N/B 23 92 68 74
PAP6.4755M/B 23 92 68 74
PAP6.4755N/B 23 92 68 74
PAP7.4759M/B 26 92 82 88
PAP7.4759N/B 26 92 82 88
PAP7.5259M/B 26 92 82 88
PAP7.5259N/B 26 92 82 88
PAP8.5770M/B 26 115 100 118
PAP8.5770N/B 26 115 100 118
PAP8.6170M/B 26 115 100 118
PAP8.6170N/B 26 115 100 118
PAP8A.6578M/B 26 115 100 118
PAP8A.6578N/B 26 115 100 118
PAP8A.6878M/B 26 115 100 118
PAP8A.6878N/B 26 115 100 118
PAP10.7385M/B 28 117 128
PAP10.7385N/B 28 117 128
PAP10.7892M/B 28 117 128
PAP10.7892N/B 28 117 128

Compound
Code Description
kit 100g, consisting of:
PAP-COMPOUND-1
bottle A, bottle B, gloves, syringe, stirring rod, mixing jar
kit 300g, consisting of:
PAP-COMPOUND-3
bottle A, bottle B, gloves, 3 syringes, 3 stirring rods, 3 mixing jars

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 173


8 Cable glands and accessories
1 Glands
6 Ex barrier metal - double compression for lead cable: PPAP/B

Our barrier glands are composed identically to the classic PPAP-glands.


II 2 G Exd IIC / Exe II
However an extra metal ring is added in the body which will be filled with a
compound. II 2 D ExtD A21 IP66
Whether you should use a barrier gland or not can be deducted from the
flowchart below. Zone 1  Zone 21 
Suited for armoured cables with lead sheaths. Zone 2  Zone 22 
Sealing on inner and outer sheath of the cable.
INERIS03ATEX0028
Compression of the cable’s armouring. With lead plate for earthing
continuousity.
Mechanical protection IP66 in all positions.
Specifications
Material cable gland brass OT 58
On request
Protection IP66
Seal neoprene • copper-free aluminium (type ../A)
Thread NPT in accordance with ANSI B2.1 • stainless steel 316 (type ../S6)
• stainless steel 304 (type ../S4)
Metric - pitch 1,5
• nickel-plated brass (type ../N)
Ambiant temperature -20°C - +80°C • ambiant temperature -40°C

Ordering data
Product code Thread Cable diameter
A B
Min Max Min Max
PPAP1R0713M/B M20 4 7 9 13
PPAP1R0713N/B 1/2”NPT 4 7 9 13
PPAP1R0718M/B M20 4 7 13 18
PPAP1R0718N/B 1/2”NPT 4 7 13 18
PPAP1R0913M/B M20 7 9,5 9 13
PPAP1R0913N/B 1/2”NPT 7 9,5 9 13
PPAP1R0918M/B M20 7 9,5 13 18
PPAP1R0918N/B 1/2”NPT 7 9,5 13 18
PPAP1R1213M/B M20 9 12 9 13
PPAP1R1213N/B 1/2”NPT 9 12 9 13
PPAP1R1218M/B M20 9 12 13 18
PPAP1R1218N/B 1/2”NPT 9 12 13 18

174 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
6 Ex barrier metal - double compression for lead cable: PPAP/B

Product code Thread Cable diameter


A B
Min Max Min Max
PPAP2R1219M/B M25 9 12 15 19
PPAP2R1219N/B 3/4”NPT 9 12 15 19
PPAP2R1223M/B M25 9 12 18 23
PPAP2R1223N/B 3/4”NPT 9 12 18 23
PPAP2R1419M/B M25 12 14,5 15 19
PPAP2R1419N/B 3/4”NPT 12 14,5 15 19
PPAP2R1423M/B M25 12 14,5 18 23
PPAP2R1423N/B 3/4”NPT 12 14,5 18 23
PPAP2R1719M/B M25 14 17 15 19
PPAP2R1719N/B 3/4”NPT 14 17 15 19
PPAP2R1723M/B M25 14 17 18 23
PPAP2R1723N/B 3/4”NPT 14 17 18 23
PPAP3.1723M/B M32 14 17 20 23
PPAP3.1723N/B 1”NPT 14 17 20 23
PPAP3.1726M/B M32 14 17 23 26
PPAP3.1726N/B 1”NPT 14 17 23 26
PPAP3.1729M/B M32 14 17 24 29
PPAP3.1729N/B 1”NPT 14 17 24 29
PPAP3.2023M/B M32 17 20 20 23
PPAP3.2023N/B 1”NPT 17 20 20 23
PPAP3.2026M/B M32 17 20 23 26
PPAP3.2026N/B 1”NPT 17 20 23 26
PPAP3.2029M/B M32 17 20 24 29
PPAP3.2029N/B 1”NPT 17 20 24 29
PPAP3.2323M/B M32 20 23 20 23
PPAP3.2323N/B 1”NPT 20 23 20 23
PPAP3.2326M/B M32 20 23 23 26
PPAP3.2326N/B 1”NPT 20 23 23 26
PPAP3.2329M/B M32 20 23 24 29
PPAP3.2329N/B 1”NPT 20 23 24 29
PPAP4.2335M/B M40 20 23 30 35
PPAP4.2335N/B 1 1/4”NPT 20 23 30 35
PPAP4.2635M/B M40 23 26 30 35
PPAP4.2635N/B 1 1/4”NPT 23 26 30 35
PPAP4.2935M/B M40 26 29 30 35
PPAP4.2935N/B 1 1/4”NPT 26 29 30 35
PPAP4.3241M/B M40 29 32 36 41
PPAP4.3241N/B 1 1/4”NPT 29 32 36 41
PPAP4.3541M/B M40 32 35,5 36 41
PPAP4.3541N/B 1 1/4”NPT 32 35,5 36 41
PPAP5.2335M/B M50 20 23 30 35
PPAP5.2335N/B 1 1/2”NPT 20 23 30 35
PPAP5.2635M/B M50 23 26 30 35
PPAP5.2635N/B 1 1/2”NPT 23 26 30 35
PPAP5.2935M/B M50 26 29 30 35
PPAP5.2935N/B 1 1/2”NPT 26 29 30 35
PPAP5.3241M/B M50 29 32 36 41
PPAP5.3241N/B 1 1/2”NPT 29 32 36 41
PPAP5.3541M/B M50 32 35,5 36 41
PPAP5.3541N/B 1 1/2”NPT 32 35,5 36 41
PPAP6.3547M/B M63 32 35,5 42 47
PPAP6.3547N/B 2”NPT 32 35,5 42 47
PPAP6.3947M/B M63 36 39 42 47
PPAP6.3947N/B 2”NPT 36 39 42 47
PPAP6.4250M/B M63 39 42 46 50
PPAP6.4250N/B 2”NPT 39 42 46 50
PPAP6.4255M/B M63 39 42 50 55
PPAP6.4255N/B 2”NPT 39 42 50 55
PPAP6.4755M/B M63 44 47 50 55
PPAP6.4755N/B 2”NPT 44 47 50 55
PPAP7.4759M/B M75 44 47 55 59
PPAP7.4759N/B 2 1/2”NPT 44 47 55 59

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 175


8 Cable glands and accessories
1 Glands
6 Ex barrier metal - double compression for lead cable: PPAP/B

Product code Thread Cable diameter


A B
Min Max Min Max
PPAP7.5259M/B M75 50 52 55 59
PPAP7.5259N/B 2 1/2”NPT 50 52 55 59
PPAP8.5770M/B M85 52 57 65 70
PPAP8.5770N/B 3”NPT 52 57 65 70
PPAP8.6170M/B M85 57 61 65 70
PPAP8.6170N/B 3”NPT 57 61 65 70
PPAP8A.6578M/B M85 61 65 70 78
PPAP8A.6578N/B 3”NPT 61 65 70 78
PPAP8A.6878M/B M85 65 68 70 78
PPAP8A.6878N/B 3”NPT 65 68 70 78
PPAP10.7385M/B M110 68 73 78 85
PPAP10.7385N/B 4”NPT 68 73 78 85
PPAP10.7892M/B M110 74 78 85 92
PPAP10.7892N/B 4”NPT 74 78 85 92

Dimensional sketches

PPAP3-10
PPAP1R-2R
Product code Dimensions
D F G H
PPAP1R0713M/B 17 62 27 31
PPAP1R0713N/B 17 62 27 31
PPAP1R0718M/B 17 62 27 31
PPAP1R0718N/B 17 62 27 31
PPAP1R0913M/B 17 62 27 31
PPAP1R0913N/B 17 62 27 31
PPAP1R0918M/B 17 62 27 31
PPAP1R0918N/B 17 62 27 31
PPAP1R1213M/B 17 62 27 31
PPAP1R1213N/B 17 62 27 31
PPAP1R1218M/B 17 62 27 31
PPAP1R1218N/B 17 62 27 31
PPAP2R1219M/B 17 62 32 37
PPAP2R1219N/B 17 62 32 37
PPAP2R1223M/B 17 62 32 37
PPAP2R1223N/B 17 62 32 37
PPAP2R1419M/B 17 62 32 37
PPAP2R1419N/B 17 62 32 37
PPAP2R1423M/B 17 62 32 37
PPAP2R1423N/B 17 62 32 37
PPAP2R1719M/B 17 62 32 37
PPAP2R1719N/B 17 62 32 37
PPAP2R1723M/B 17 62 32 37
PPAP2R1723N/B 17 62 32 37
PPAP3.1723M/B 21 88 43 46
PPAP3.1723N/B 21 88 43 46
PPAP3.1726M/B 21 88 43 46
PPAP3.1726N/B 21 88 43 46
PPAP3.1729M/B 21 88 43 46
PPAP3.1729N/B 21 88 43 46
PPAP3.2023M/B 21 88 43 46
PPAP3.2023N/B 21 88 43 46
PPAP3.2026M/B 21 88 43 46
PPAP3.2026N/B 21 88 43 46
PPAP3.2029M/B 21 88 43 46

176 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
6 Ex barrier metal - double compression for lead cable: PPAP/B

Product code Dimensions


D F G H
PPAP3.2029N/B 21 88 43 46
PPAP3.2323M/B 21 88 43 46
PPAP3.2323N/B 21 88 43 46
PPAP3.2326M/B 21 88 43 46
PPAP3.2326N/B 21 88 43 46
PPAP3.2329M/B 21 88 43 46
PPAP3.2329N/B 21 88 43 46
PPAP4.2335M/B 21 88 59 63
PPAP4.2335N/B 21 88 59 63
PPAP4.2635M/B 21 88 59 63
PPAP4.2635N/B 21 88 59 63
PPAP4.2935M/B 21 88 59 63
PPAP4.2935N/B 21 88 59 63
PPAP4.3241M/B 21 88 59 63
PPAP4.3241N/B 21 88 59 63
PPAP4.3541M/B 21 88 59 63
PPAP4.3541N/B 21 88 59 63
PPAP5.2335M/B 21 88 59 63
PPAP5.2335N/B 21 88 59 63
PPAP5.2635M/B 21 88 59 63
PPAP5.2635N/B 21 88 59 63
PPAP5.2935M/B 21 88 59 63
PPAP5.2935N/B 21 88 59 63
PPAP5.3241M/B 21 88 59 63
PPAP5.3241N/B 21 88 59 63
PPAP5.3541M/B 21 88 59 63
PPAP5.3541N/B 21 88 59 63
PPAP6.3547M/B 23 92 68 74
PPAP6.3547N/B 23 92 68 74
PPAP6.3947M/B 23 92 68 74
PPAP6.3947N/B 23 92 68 74
PPAP6.4250M/B 23 92 68 74
PPAP6.4250N/B 23 92 68 74
PPAP6.4255M/B 23 92 68 74
PPAP6.4255N/B 23 92 68 74
PPAP6.4755M/B 23 92 68 74
PPAP6.4755N/B 23 92 68 74
PPAP7.4759M/B 26 92 82 88
PPAP7.4759N/B 26 92 82 88
PPAP7.5259M/B 26 92 82 88
PPAP7.5259N/B 26 92 82 88
PPAP8.5770M/B 26 115 100 118
PPAP8.5770N/B 26 115 100 118
PPAP8.6170M/B 26 115 100 118
PPAP8.6170N/B 26 115 100 118
PPAP8A.6578M/B 26 115 100 118
PPAP8A.6578N/B 26 115 100 118
PPAP8A.6878M/B 26 115 100 118
PPAP8A.6878N/B 26 115 100 118
PPAP10.7385M/B 28 117 128
PPAP10.7385N/B 28 117 128
PPAP10.7892M/B 28 117 128
PPAP10.7892N/B 28 117 128

Compound
Code Description
kit 100g, consisting of:
PAP-COMPOUND-1
bottle A, bottle B, gloves, syringe, stirring rod, mixing jar
kit 300g, consisting of:
PAP-COMPOUND-3
bottle A, bottle B, gloves, 3 syringes, 3 stirring rods, 3 mixing jars

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 177


8 Cable glands and accessories
1 Glands
7 Exe-plastic / metric thread

Suited for armoured and non-armoured cables.


II 2 G Exe II
Sealing on outer sheath of the cable.
Maximum strain relief because of a patented lamella system. II 2 D Ex tD A21
Irreversible threads prevent stripping under high torque and protect against
vibration. Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Protection IP68 - 5 bar (30 min) PTB05ATEX1068X
Material cable gland polyamide (self-extinguishing)
Material closure EPDM
Material O-ring EPDM
Ambiant temperature -40°C - +75°C

On request
• PG or NPT thread

Ordering data
Product code Thread Cable diameter
Min Max
GPEM1 M16 x 1.5 4 9
GPEM2 M20 x 1.5 6 13
GPEM3 M25 x 1.5 7 17
GPEM4 M32 x 1.5 13 21
GPEM5 M40 x 1.5 17 28
GPEM6 M50 x 1.5 23 35
GPEM7 M63 x 1.5 31 48
GPIM1 M16 x 1.5 4 9
GPIM2 M20 x 1.5 6 13
GPIM3 M25 x 1.5 7 17
GPIM4 M32 x 1.5 13 21
GPIM5 M40 x 1.5 17 28
GPIM6 M50 x 1.5 23 35
GPIM7 M63 x 1.5 31 48

178 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
1 Glands
7 Exe-plastic / metric thread

Dimensional sketches

Product code Dimensions


A B SW
GPEM1 31 - 37 9 20
GPEM2 36 - 45 10 24
GPEM3 38 - 47 10 29
GPEM4 42 - 51 12 36
GPEM5 52 - 65 12 46
GPEM6 59 - 72 14 55
GPEM7 64 - 78 15 68
GPIM1 31 - 37 9 20
GPIM2 36 - 45 10 24
GPIM3 38 - 47 10 29
GPIM4 42 - 51 12 36
GPIM5 52 - 65 12 46
GPIM6 59 - 72 14 55
GPIM7 64 - 78 15 68

Accessories
Code Description
BS8 Plug for cable 8mm
MFV12 Plug for cable 12mm
MFV17 Plug for cable 17mm
MFV21 Plug for cable 21mm

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 179


8 Cable glands and accessories
2 Plugs
1 Exd brass

Plugs are used to safely seal unused openings in enclosures and


II 2 GD Exd II C
apparatuses.There are two types:- R18; the plug is screwed in on the
outside and fastened with a hexagonal spanner on the inside (on request). -
RX18; the plug is screwed in and fastened with a hexagonal spanner on the
Zone 1  Zone 21 
outside (standard model). Zone 2  Zone 22 
Specifications SIRA00ATEX1073U
Marking All plugs are marked with a certificate number
and size.
Material brass
Thread - NPT in accordance with ANSI B2.1
- Metric
Protection IP65
Ambiant temperature -190°C - +400°C

On request
• aluminium
• stainless steel
• nickel-plated brass
• steel
• thread: PG, BSP (conical & parallel), ET (electrical
thread)

Ordering data
Code Thread
PBDM1X M16x1,5
PBDM2X M20x1,5
PBDM3X M25x1,5
PBDM4X M32x1,5
PBDM5X M40x1,5
PBDM6X M50x1,5
PBDM7X M63x1,5
PBDM8X M75x1,5
PBDN0X 1/4” NPT
PBDN1X 1/2” NPT
PBDN2X 3/4” NPT
PBDN3X 1” NPT
PBDN4X 1 1/4” NPT
PBDN5X 1 1/2” NPT
PBDN6X 2” NPT
PBDN7X 2 1/2” NPT
PBDN8X 3” NPT
PBDN9X 3 1/2” NPT
PBDN10X 4” NPT

180 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
2 Plugs
2 Exe brass

Plugs are used to safely seal unused openings in enclosures and


II 2 GD Exe II
apparatuses. The plug is screwed in and fastened with a hexagonal Allen
key on the outside.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Marking All plugs are marked with a certificate number
and size. SIRA00ATEX1073U
Material brass
Thread - NPT in accordance with ANSI B2.1
- metric
Protection IP68
Ambiant temperature -50°C - +120°C

On request
• aluminium
• stainless steel
• nickel-plated brass
• steel
• thread: PG, BSP (conical & parallel), ET (electrical
thread)

Ordering data
Code Thread
PBEM1 M16x1.5
PBEM2 M20x1.5
PBEM3 M25x1.5
PBEM4 M32x1.5
PBEM5 M40x1.5
PBEM6 M50x1.5
PBEM7 M63x1.5
PBEM8 M75x1.5
PBEN0 1/4” NPT
PBEN1 1/2” NPT
PBEN2 3/4” NPT
PBEN3 1” NPT
PBEN4 1 1/4” NPT
PBEN5 1 1/2” NPT
PBEN6 2” NPT
PBEN7 2 1/2” NPT
PBEN8 3” NPT
PBEN9 3 1/2” NPT
PBEN10 4” NPT

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 181


8 Cable glands and accessories
2 Plugs
3 Exe plastic

Plugs are used to safely seal unused openings in enclosures and


II 2 G Exe II
apparatuses. The plug is screwed in and fastened with a spanner on the
outside. II 2 D Ex tD A21

Specifications
Zone 1  Zone 21 
Marking All plugs are marked with a certificate number
Zone 2  Zone 22 
and size.
Material nylon PTB06ATEX1032X
Thread Metric
Protection IP66
Ambiant temperature -20°C - +80°C

On request
• PG or NPT thread

Ordering data
Code Thread
PPEM1 M16x1,5
PPEM2 M20x1,5
PPEM3 M25x1,5
PPEM4 M32x1,5
PPEM5 M40x1,5
PPEM6 M50x1,5
PPEM7 M63x1,5
PPEM8 M75x1,5

Dimensional sketches

Product code Dimensions


A B SW1 SW2
PPEM1 16 9,5 20 10
PPEM2 17,5 11,6 24 10
PPEM3 17 11 29 10
PPEM4 16,5 11 36 10
PPEM5 18 10 46 10
PPEM6 21 10 55 10
PPEM7 24 10 68 10

182 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
3 Reducers and adapters
1 Exd / Exe brass

Reducers and adapters are used as a transition piece in case of differing


II 2 GD Exde II C
threads in enclosures and glands (or plugs).
With reducers the male thread is larger than the female thread.
With adapters, however, the male thread is smaller than the female thread
Zone 1  Zone 21 
and is limited to 1 step (e.g. M20 -> M25). Zone 2  Zone 22 
Specifications SIRA00ATEX1073U
Marking All reducers and adapters are marked with a
certificate number and size.
Material brass
Thread - NPT in accordance with ANSI B2.1
- Metric
- PG
Protection IP65
Ambiant temperature -50°C - +120°C
On request
• aluminium
• stainless steel
• nickel-plated brass
• steel
• thread: BSP (conical & parallel), ET (electrical
thread)

Ordering data

male thread metric - female thread metric


 = reductie  = adapter
Male M16 M20 M25 M32 M40 M50 M63 M75
Female
M16 ABDM1M1 RBDM2M1 RBDM3M1 RBDM4M1 RBDM5M1 RBDM6M1 RBDM7M1 RBDM8M1

M20 ABDM1M2 ABDM2M2 RBDM3M2 RBDM4M2 RBDM5M2 RBDM6M2 RBDM7M2 RBDM8M2

M25 ABDM2M3 ABDM3M3 RBDM4M3 RBDM5M3 RBDM6M3 RBDM7M3 RBDM8M3

M32 ABDM3M4 ABDM4M4 RBDM5M4 RBDM6M4 RBDM7M4 RBDM8M4

M40 ABDM4M5 ABDM5M5 RBDM6M5 RBDM7M5 RBDM8M5

M50 ABDM5M6 ABDM6M6 RBDM7M6 RBDM8M6

M63 ABDM6M7 ABDM7M7 RBDM8M7

M75 ABDM7M8 ABDM8M8

male thread metric - female thread NPT


 = reductie  = adapter
Male M16 M20 M25 M32 M40 M50 M63 M75
Female
1/2”NPT ABDM1N1 ABDM2N1 RBDM3N1 RBDM4N1 RBDM5N1 RBDM6N1 RBDM7N1 RBDM8N1

3/4”NPT ABDM2N2 ABDM3N2 RBDM4N2 RBDM5N2 RBDM6N2 RBDM7N2 RBDM8N2

1”NPT ABDM3N3 ABDM4N3 RBDM5N3 RBDM6N3 RBDM7N3 RBDM8N3

1 1/4” NPT ABDM4N4 ABDM5N4 RBDM6N4 RBDM7N4 RBDM8N4

1 1/2” NPT ABDM5N5 ABDM6N5 RBDM7N5 RBDM8N5

2” NPT ABDM6N6 ABDM7N6 RBDM8N6

2 1/2” NPT ABDM7N7 ABDM8N7

3” NPT ABDM8N8

3 1/2” NPT

4” NPT

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 183


8 Cable glands and accessories
3 Reducers and adapters
1 Exd / Exe brass

male thread PG - female thread metric


 = reductie  = adapter
Male PG7 PG9 PG11 PG13,5 PG16 PG21 PG29 PG36 PG42 PG48
Female
M16 ABDP0M1 ABDP1M1 ABDP2M1 RBDP3M1 RBDP4M1 RBDP5M1 RBDP6M1 RBDP7M1 RBDP8M1 RBDP9M1

M20 ABDP2M2 ABDP3M2 ABDP4M2 RBDP5M2 RBDP6M2 RBDP7M2 RBDP8M2 RBDP9M2

M25 ABDP3M3 ABDP4M3 ABDP5M3 RBDP6M3 RBDP7M3 RBDP8M3 RBDP9M3

M32 ABDP5M4 RBDP6M4 RBDP7M4 RBDP8M4 RBDP9M4

M40 ABDP6M5 RBDP7M5 RBDP8M5 RBDP9M5

M50 RBDP7M6 ABDP8M6 RBDP9M6

M63 ABDP7M7 ABDP8M7 ABDP9M7

M75 ABDP9M8

male thread PG - female thread NPT


 = reductie  = adapter
Male PG7 PG9 PG11 PG13,5 PG16 PG21 PG29 PG36 PG42 PG48
Female
1/2”NPT ABDP0N1 ABDP1N1 ABDP2N1 ABDP3N1 ABDP4N1 RBDP5N1 RBDP6N1 RBDP7N1 RBDP8N1 RBDP9N1

3/4”NPT ABDP3N2 ABDP4N2 ABDP5N2 RBDP6N2 RBDP7N2 RBDP8N2 RBDP9N2

1”NPT ABDP5N3 RBDP6N3 RBDP7N3 RBDP8N3 RBDP9N3

1 1/4” NPT ABDP6N4 RBDP7N4 RBDP8N4 RBDP9N4

1 1/2” NPT ABDP7N5 ABDP8N5 RBDP9N5

2” NPT ABDP8N6 ABDP9N6

2 1/2” NPT ABDP9N7

3” NPT

3 1/2” NPT

4” NPT

male thread NPT - female thread metric


 = reductie  = adapter
Male 1/2”NPT 3/4”NPT 1”NPT 1 1/4” NPT 1 1/2” NPT 2” NPT 2 1/2” NPT 3” NPT 3 1/2” NPT 4” NPT
Female
M16 RBDN1M1 RBDN2M1 RBDN3M1 RBDN4M1 RBDN5M1 RBDN6M1 RBDN7M1 RBDN8M1 RBDN9M1 RBDN10M1

M20 ABDN1M2 RBDN2M2 RBDN3M2 RBDN4M2 RBDN5M2 RBDN6M2 RBDN7M2 RBDN8M2 RBDN9M2 RBDN10M2

M25 ABDN1M3 ABDN2M3 RBDN3M3 RBDN4M3 RBDN5M3 RBDN6M3 RBDN7M3 RBDN8M3 RBDN9M3 RBDN10M3

M32 ABDN2M4 ABDN3M4 RBDN4M4 RBDN5M4 RBDN6M4 RBDN7M4 RBDN8M4 RBDN9M4 RBDN10M4

M40 ABDN3M5 ABDN4M5 RBDN5M5 RBDN6M5 RBDN7M5 RBDN8M5 RBDN9M5 RBDN10M5

M50 ABDN4M6 ABDN5M6 RBDN6M6 RBDN7M6 RBDN8M6 RBDN9M6 RBDN10M6

M63 ABDN5M7 ABDN6M7 RBDN7M7 RBDN8M7 RBDN9M7 RBDN10M7

M75 ABDN6M7 ABDN7M7 RBDN8M8 RBDN9M8 RBDN10M8

male thread NPT - female thread NPT


 = reductie  = adapter
Male 1/2”NPT 3/4”NPT 1”NPT 1 1/4” NPT 1 1/2” NPT 2” NPT 2 1/2” NPT 3” NPT 3 1/2” NPT 4” NPT
Female
1/2”NPT ABDN1N1 RBDN2N1 RBDN3N1 RBDN4N1 RBDN5N1 RBDN6N1 RBDN7N1 RBDN8N1 RBDN9N1 RBDN10N1

3/4”NPT ABDN1N2 ABDN2N2 RBDN3N2 RBDN4N2 RBDN5N2 RBDN6N2 RBDN7N2 RBDN8N2 RBDN9N2 RBDN10N2

1”NPT ABDN2N3 ABDN3N3 RBDN4N3 RBDN5N3 RBDN6N3 RBDN7N3 RBDN8N3 RBDN9N3 RBDN10N3

1 1/4” NPT ABDN3N4 ABDN4N4 RBDN5N4 RBDN6N4 RBDN7N4 RBDN8N4 RBDN9N4 RBDN10N4

1 1/2” NPT ABDN4N5 ABDN5N5 RBDN6N5 RBDN7N5 RBDN8N5 RBDN9N5 RBDN10N5

2” NPT ABDN5N6 ABDN6N6 RBDN7N6 RBDN8N6 RBDN9N6 RBDN10N6

2 1/2” NPT ABDN6N7 ABDN7N7 RBDN8N7 RBDN9N7 RBDN10N7

3” NPT ABDN7N8 ABDN8N8 RBDN9N8 RBDN10N8

3 1/2” NPT ABDN9N9 RBDN10N9

4” NPT ABDN9N10 ABDN10N10

184 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
3 Reducers and adapters
2 Exe plastic

Reducers and adapters are used as a transition piece in case of differing


II 2 G Exe II
threads in enclosures and glands (or plugs).
With reducers the male thread is larger than the female thread. II 2 D Ex tD A21
With adapters, however, the male thread is smaller than the female thread
and is limited to 1 step (e.g. M20 -> M25). Zone 1  Zone 21 
Specifications Zone 2  Zone 22 
Marking All reducers and adapters are marked with a SIRA00ATEX1073U
certificate number and size. PTB04ATEX1040X
Material nylon (polyamide)
Thread - NPT in accordance with ANSI B2.1
- Metric
- PG
Protection IP66
Ambiant temperature -20°C - +60°C

On request
• brass
• aluminium
• stainless steel
• nickel-plated brass
• steel
• thread: BSP (conical & parallel), ET (electrical
thread)

Ordering data

male thread metric - female thread metric


 = reductie  = adapter
Male M16 M20 M25 M32 M40 M50 M63 M75
Female
M16 APEM1M1 RPEM2M1 RPEM3M1 RPEM4M1 RPEM5M1 RPEM6M1 RPEM7M1 RPEM8M1

M20 APEM1M2 APEM2M2 RPEM3M2 RPEM4M2 RPEM5M2 RPEM6M2 RPEM7M2 RPEM8M2

M25 APEM2M3 APEM3M3 RPEM4M3 RPEM5M3 RPEM6M3 RPEM7M3 RPEM8M3

M32 APEM3M4 APEM4M4 RPEM5M4 RPEM6M4 RPEM7M4 RPEM8M4

M40 APEM4M5 APEM5M5 RPEM6M5 RPEM7M5 RPEM8M5

M50 APEM5M6 APEM6M6 RPEM7M6 RPEM8M6

M63 APEM6M7 APEM7M7 RPEM8M7

M75 APEM7M8 APEM8M8

male thread metric - female thread NPT


 = reductie  = adapter
Male M16 M20 M25 M32 M40 M50 M63 M75
Female
1/2”NPT APEM1N1 APEM2N1 RPEM3N1 RPEM4N1 RPEM5N1 RPEM6N1 RPEM7N1 RPEM8N1

3/4”NPT APEM2N2 APEM3N2 RPEM4N2 RPEM5N2 RPEM6N2 RPEM7N2 RPEM8N2

1”NPT APEM3N3 APEM4N3 RPEM5N3 RPEM6N3 RPEM7N3 RPEM8N3

1 1/4” NPT APEM4N4 APEM5N4 RPEM6N4 RPEM7N4 RPEM8N4

1 1/2” NPT APEM5N5 APEM6N5 RPEM7N5 RPEM8N5

2” NPT APEM6N6 APEM7N6 RPEM8N6

2 1/2” NPT APEM7N7 APEM8N7

3” NPT APEM8N8

3 1/2” NPT

4” NPT

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 185


8 Cable glands and accessories
3 Reducers and adapters
2 Exe plastic

male thread PG - female thread metric


 = reductie  = adapter
Male PG7 PG9 PG11 PG13,5 PG16 PG21 PG29 PG36 PG42 PG48
Female
M16 APEP0M1 APEP1M1 APEP2M1 RPEP3M1 RPEP4M1 RPEP5M1 RPEP6M1 RPEP7M1 RPEP8M1 RPEP9M1

M20 APEP2M2 APEP3M2 APEP4M2 RPEP5M2 RPEP6M2 RPEP7M2 RPEP8M2 RPEP9M2

M25 APEP3M3 APEP4M3 APEP5M3 RPEP6M3 RPEP7M3 RPEP8M3 RPEP9M3

M32 APEP5M4 RPEP6M4 RPEP7M4 RPEP8M4 RPEP9M4

M40 APEP6M5 RPEP7M5 RPEP8M5 RPEP9M5

M50 RPEP7M6 APEP8M6 RPEP9M6

M63 APEP7M7 APEP8M7 APEP9M7

M75 APEP9M8

male thread PG - female thread NPT


 = reductie  = adapter
Male PG7 PG9 PG11 PG13,5 PG16 PG21 PG29 PG36 PG42 PG48
Female
1/2”NPT APEP0N1 APEP1N1 APEP2N1 APEP3N1 APEP4N1 RPEP5N1 RPEP6N1 RPEP7N1 RPEP8N1 RPEP9N1

3/4”NPT APEP3N2 APEP4N2 APEP5N2 RPEP6N2 RPEP7N2 RPEP8N2 RPEP9N2

1”NPT APEP5N3 RPEP6N3 RPEP7N3 RPEP8N3 RPEP9N3

1 1/4” NPT APEP6N4 RPEP7N4 RPEP8N4 RPEP9N4

1 1/2” NPT APEP7N5 APEP8N5 RPEP9N5

2” NPT APEP8N6 APEP9N6

2 1/2” NPT APEP9N7

3” NPT

3 1/2” NPT

4” NPT

male thread NPT - female thread metric


 = reductie  = adapter
Male 1/2”NPT 3/4”NPT 1”NPT 1 1/4” NPT 1 1/2” NPT 2” NPT 2 1/2” NPT 3” NPT 3 1/2” NPT 4” NPT
Female
M16 RPEN1M1 RPEN2M1 RPEN3M1 RPEN4M1 RPEN5M1 RPEN6M1 RPEN7M1 RPEN8M1 RPEN9M1 RPEN10M1

M20 APEN1M2 RPEN2M2 RPEN3M2 RPEN4M2 RPEN5M2 RPEN6M2 RPEN7M2 RPEN8M2 RPEN9M2 RPEN10M2

M25 APEN1M3 APEN2M3 RPEN3M3 RPEN4M3 RPEN5M3 RPEN6M3 RPEN7M3 RPEN8M3 RPEN9M3 RPEN10M3

M32 APEN2M4 APEN3M4 RPEN4M4 RPEN5M4 RPEN6M4 RPEN7M4 RPEN8M4 RPEN9M4 RPEN10M4

M40 APEN3M5 APEN4M5 RPEN5M5 RPEN6M5 RPEN7M5 RPEN8M5 RPEN9M5 RPEN10M5

M50 APEN4M6 APEN5M6 RPEN6M6 RPEN7M6 RPEN8M6 RPEN9M6 RPEN10M6

M63 APEN5M7 APEN6M7 RPEN7M7 RPEN8M7 RPEN9M7 RPEN10M7

M75 APEN6M8 APEN7M8 RPEN8M8 RPEN9M8 RPEN10M8

male thread NPT - female thread NPT


 = reductie  = adapter
Male 1/2”NPT 3/4”NPT 1”NPT 1 1/4” NPT 1 1/2” NPT 2” NPT 2 1/2” NPT 3” NPT 3 1/2” NPT 4” NPT
Female
1/2”NPT APEN1N1 RPEN2N1 RPEN3N1 RPEN4N1 RPEN5N1 RPEN6N1 RPEN7N1 RPEN8N1 RPEN9N1 RPEN10N1

3/4”NPT APEN1N2 APEN2N2 RPEN3N2 RPEN4N2 RPEN5N2 RPEN6N2 RPEN7N2 RPEN8N2 RPEN9N2 RPEN10N2

1”NPT APEN2N3 APEN3N3 RPEN4N3 RPEN5N3 RPEN6N3 RPEN7N3 RPEN8N3 RPEN9N3 RPEN10N3

1 1/4” NPT APEN3N4 APEN4N4 RPEN5N4 RPEN6N4 RPEN7N4 RPEN8N4 RPEN9N4 RPEN10N4

1 1/2” NPT APEN4N5 APEN5N5 RPEN6N5 RPEN7N5 RPEN8N5 RPEN9N5 RPEN10N5

2” NPT APEN5N6 APEN6N6 RPEN7N6 RPEN8N6 RPEN9N6 RPEN10N6

2 1/2” NPT APEN6N7 APEN7N7 RPEN8N7 RPEN9N7 RPEN10N7

3” NPT APEN7N8 APEN8N8 RPEN9N8 RPEN10N8

3 1/2” NPT APEN9N9 RPEN10N9

4” NPT APEN9N10 APEN10N10

186 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
4 Accessories
1 Earth tags brass

Earth tags provide the possibility of an earthing connection between gland


Zone 1  Zone 21 
and box, by means of a flexible wire. The standard version is made of
brassand, if necessary, can be nickel-plated or stainless steel.
Zone 2  Zone 22 
Specifications
Marking not applicable
can be mounted in every zone
Material brass

On request
• stainless steel
• brass nickel plated
• PG thread

Ordering data
Code Thread
EBNM1 M16
EBNM2 M20
EBNM3 M25
EBNM4 M32
EBNM5 M40
EBNM6 M50
EBNM7 M63
EBNM8 M75
EBNN0 1/4” NPT
EBNN1 1/2” NPT
EBNN2 3/4” NPT
EBNN3 1” NPT
EBNN4 1 1/4” NPT
EBNN5 1 1/2” NPT
EBNN6 2” NPT
EBNN7 2 1/2” NPT
EBNN8 3” NPT
EBNN9 3 1/2” NPT
EBNN10 4” NPT

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 187


8 Cable glands and accessories
4 Accessories
2 Lock nuts

The standard version of the hexagonal lock nuts are made of nickel plated
Zone 1  Zone 21 
brass or plastic.
Zone 2  Zone 22 
Specifications
Marking not applicable
can be mounted in every zone

On request
• NPT or PG thread

Ordering data
Code Thread Material
LPNM1 M16 x 1.5 plastic
LPNM2 M20 x 1.5 plastic
LPNM3 M25 x 1.5 plastic
LPNM4 M32 x 1.5 plastic
LPNM5 M40 x 1.5 plastic
LPNM6 M50 x 1.5 plastic
LPNM7 M63 x 1.5 plastic
LNNM1 M16 x 1.5 brass nickel plated
LNNM2 M20 x 1.5 brass nickel plated
LNNM3 M25 x 1.5 brass nickel plated
LNNM4 M32 x 1.5 brass nickel plated
LNNM5 M40 x 1.5 brass nickel plated
LNNM6 M50 x 1.5 brass nickel plated
LNNM7 M63 x 1.5 brass nickel plated
LNNM8 M75 x 1.5 brass nickel plated

188 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
4 Accessories
3 Gaskets plastic

Gaskets between gland and box increase the watertightness of threaded


Zone 1  Zone 21 
connections. They are available in various sizes.
Zone 2  Zone 22 
Specifications
Marking not applicable
can be mounted in every zone
Material plastic, red fibre

Ordering data
Code Thread
WPNM1 M16
WPNM2 M20
WPNM3 M25
WPNM4 M32
WPNM5 M40
WPNM6 M50
WPNM7 M63
WPNM8 M75
WPNN0 1/4” NPT
WPNN1 1/2” NPT
WPNN2 3/4” NPT
WPNN3 1” NPT
WPNN4 1 1/4” NPT
WPNN5 1 1/2” NPT
WPNN6 2” NPT
WPNN7 2 1/2” NPT
WPNN8 3” NPT
WPNN9 3 1/2” NPT
WPNN10 4” NPT

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 189


8 Cable glands and accessories
5 Special passing troughs
1 Drainage valve

Drainage valves are used to drain condensation in enclosures. They also


II 2 GD EExd IIC T6
serve as ventilation. They are available for EExd and EExe enclosures.
Type ECR1 is only approved in housings type EJB and GUB. II 2 G EExe II

Specifications
Zone 1  Zone 21 
Material plastic or stainless steel
Zone 2  Zone 22 
Thread metric or NPT
PTB01ATEX1128X

Ordering data
Code Classification Material Thread Protection Ambiant temp.
ECR1 EExd IIC T6 stainless steel 3/8”
DPEM3 EExe II polyamide M25x1,5 IP54 -20°C - +40°C

190 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
8 Cable glands and accessories
5 Special passing troughs
2 Coupling for air/gas

In order to feed through air or gas in an explosion-proof EExd enclosure


II 2 GD EExd IIC
a special coupling must be used, guaranteeing the protection of the EExd
enclosure.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Connection 2 connections 1/4” BSP(P)
Feed-through section max. 3mm² INERIS03ATEX9014U
Material brass or stainless steel
Thread M20x1,5
Allowed media air/gaz
Protection IP65
Ambiant temperature max. +300°C

Ordering data
Code Thread Material Weight
XW8-TL1 M20x1,5 brass 0,200 kg
XW8-TL1 INOX M20x1,5 stainless steel 304 0,200 kg

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 191


9 Miscellaneous
1 Telephones ................................................................................................. 195
1 dST series for zone 1, 2, 21 and 22 ................................................ 195
2 Serie dFT for zone 2 and 22 ........................................................... 196
3 Accessories..................................................................................... 197

2 Earth monitoring system ............................................................................ 198


1 Earth monitoring system ................................................................. 198

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 193


9 Miscellaneous
1 Telephones
1 dST series for zone 1, 2, 21 and 22

Explosionproof telephones may be inevitable in hazardous zones.


II 2 G Ex e m [ib] IIC T6/T5
The dST series offers the ideal solution for use in heavy-duty conditions.
The large keys of type dST1 allow operation with gloves. II 2 D Ex tD A21 IP66 T80°C/T100°C

Specifications
Zone 1  Zone 21 
Housing glass-fibre reinforced polyester
Zone 2  Zone 22 
Protection IP66
Terminals 2,5mm²
Line voltage 24V DC - 66V DC
Line current 15mA DC - 100mA DC
Ringing voltage 24-90V AC (21-54Hz ringing frequency)
30-90V AC (16,6-54Hz ringing frequency)
Call signal 90 dB(A)/1m 10 different melodies
Telephone system PD - DTMF
Noise suppression > 3 dB
Handsfree until 68 dB / 1 m
Gland entry 2 cable glands M20 + 2 plugs M20
Weight 5,5 kg
Ambiant temperature -25°C - +40/60°C

On request
• extra horn for ringing signal AS1
• extra visual-audible sounder for telephone VS1
• additional earpiece set EP1
• headset kit HS1

Ordering data
Code Description Keypad Display
in stainless steel, 21 keys with ABC-letters for name
dST1 telephone with key pad and display alphanumeric
input
emergency telephone (connects directly to main
dST2 none none
PABX) without key pad and display

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 195


9 Miscellaneous
1 Telephones
2 Serie dFT for zone 2 and 22

Explosionproof telephones may be inevitable in hazardous zones.


II 3 G Ex nA nL IIC T5
The dFT series offers the ideal solution for use in zone 2 and 22 and in
heavy-duty conditions. II 3 D Ex tD A22 IP65 T80°C
The large keys allow operation with gloves.
Zone 1  Zone 21 
Specifications
Zone 2  Zone 22 
Housing polycarbonate (yellow, red, gray or black)
Protection IP65
Terminals 2,5mm²
Line voltage 24V DC - 66V DC
Call signal 95 dB(A)/1m
Telephone system MFV
Gland entry 1 cable gland M20 + 1 plug M20 + 2 plugs M12
Weight 2,3 kg
Ambiant temperature -20°C - +55°C

Ordering data
Code Description Keypad Display
dFT3 telephone with key pad and display 21 keys with ABC-letters for name input alphanumeric

Dimensional sketches

196 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be
9 Miscellaneous
1 Telephones
3 Accessories

In combination with the ex-proof telephones, several accessories can be


II 2 G Ex mb e [ib] IIC T6
used.
Specifications
Zone 1  Zone 21 
Housing aluminium Zone 2  Zone 22 
Protection IP66
Terminals 1,5mm²
Call signal 90dB
Ambiant temperature -20°C - +40°C

On request
• additional earpiece set EP1
• headset kit HS1

Ordering data
Code Description Cable entry Weight Acoustic signalling Visual signalling
extra horn for ringing
AS1 1 x M20 x 1,5 0,9 kg loudspeaker
signal
Extra visual-audible 2 xenon tubes 1J
VS1-R 2 x M20 x 1,5 1,5 kg loudspeaker
sounder for telephone, red (230VAC)

Dimensional sketches

www.ysebaert.be ● info@ysebaert.be ● T +32(0)3 328 06 60 ● F +32(0)3 328 06 80 197


9 Miscellaneous
2 Earth monitoring system
1 Earth monitoring system

The monitoring units are widely applicable and very trustworthy:


II 1/2 G EExia/d IIC T6
- Specific monitoring systems: detection of resistance or capacity
- Safe discharging of sparks with high energy level: inside the enclosures of II 2 D IP66 T85°C
the monitoring unit.
- Permanent electrostatic monitoring of the object. Zone 1  Zone 21 
- Intrinsically safe permanent guarding of the earth connection. Zone 2  Zone 22 
- Red/green signal lamps for local status indication of the earth connection.
- Volt-free contacts for remote control, for instance for turning on a pump.
Specifications
Housing cast aluminium
Finisching Alodine 1200, colour natural or RAL 7032
Protection IP66
Voltage 230/115VAC ±10% 50/60Hz 0,4W
24VDC ±20% 0,4W
Volt-free contact 1 change over contact, 1A at 250V AC1
Features red lamp = no earthing
green lamp = proper earthing
Gland entry 4 x M20 x 1,5
Ambiant temperature -10°C - +40°C On request
• Control unit in an industrial housing (IP65, for
industrial use, incl. Ex zone 22)

Ordering data
Code Application Operation Weight
This is a system with resistance recognition, R <20 ohm. Once the clamp has been
for general use (barrels, trucks, attached to the metal object, a low resistance is detected between the two jaws of the
S604/EX 10 kg
metal objects,...) clamp. The monitoring unit is activated (green indication lamp on an volt-free contact for
remote control).

This is a system with capacity recognition and R <20 ohm. First the capacity of the
S704/EX for trucks truck is tested. When this is within the prescribed limits, the monitoring unit is activated. 10 kg
Since this system cannot be misled, it offers a high degree of security.

Dimensional sketches

Accessories
Code Description
CL1 clamp, large format, 260 mm, aluminium
CM1 clamp, medium format, 210 mm, stainless steel
CS1 clamp, small format, 162 mm, stainless steel
CR01/10 cable, 10m, 3x1.5mm²
CR1/55 automatic reel, 24m cable, 3x1.5mm², IP55

198 For certificates, spare parts, light intensity diagrams, etc., please consult our website: www.ysebaert.be