You are on page 1of 6

XMCK Series

Definite Purpose Contactors

Description
HOMER XMCK series AC Contactors apply to control
electric motor load of air conditioning compressor under 50Hz/60Hz(IEC
standard AC-8a, AC-8b), rated insulation voltage ≤690V, rated current
≤40A(AC-8a or FLA). It also can be used for other home appliance and
similar electric motor load. XMCK series AC contactors conform to UL 508 standard.

Features
1. Economic design solution.
2. Solid configuration design, electric pure steel magnet.
3. Easy coil change..
4. Compact size and configuration.
5. Universal mounting plate allows an easy replacing to other brands. .
6. Heavy duty Silver Metal Oxide composition contacts with longer electrical endurance.
7. Coils are Class F (155℃) temperature insulated with wide range of voltages and 50/60Hz ratings.
8. UL and CCC approved, some models SEMKO, KETI or TÜV plus.

Type model nomenclature - Ordering Information


XM C K - 40 DN 024 D P Z □
1 2 3 4 5 6 7 8 9 10
Number digit 1: Manufacturer’s code
XM – Xiamen Hongmei Electronic Co., Ltd.
Number digit 2: Product Type
C – Contactor
Number digit 3: Design number
K – Design sequence number
Number digit 4: Resistive Amps Rating(RES)– 25, 30, 40, 50
25 – 25A
30 – 30A
40 – 40A
50 – 50A (For XMCK-□2 only, no for XMCK-□D or XMCK-□DN type)
-1-
Number digit 5: Number of Poles – D, DN or 2.
Number digit 5 D DN 2
Number of poles 1-pole 1-pole+shunt 2-pole

Number digit 6: Coil Voltage – 024, 120, 240 or blank, 277


Number digit 6 024 120 240 or blank 277
60Hz 24VAC 110-120VAC 208-240VAC 277VAC
Coil voltage
50Hz 24VAC 110-120VAC 208-240VAC ---
Number digit 7: Terminal – A, B, C or blank, D, E, F
A – Screw w/ quick connect
B – Sems clamp w/ quick connect
C or blank – Slotted & Hex head washer w/ quick connect
D – Box lug w/ quick connect
E – Box lug w/ quick connect (Line side)
Slotted & Hex head washer w/ quick connect (Load side)
F – Slotted & Hex head washer w/ quick connect (Line side)
Box lug w/ quick connect (Load side)
Number digit 8: Cover word – Blank, P
Blank – Cover word shows normal wiring diagram
P – Cover word shows special wiring diagram (reference wiring diagram)

Number digit 9: Nameplate – Blank, T, Z


Blank – Nameplate shows actual product rating
T – Nameplate shows derated product rating
Z – Nameplate shows upgraded product rating(for XMCK-40D or
XMCK-40DN)
Number digit 10: Option
Customer assigned suffix “X” where “X” may be any alphanumeric
character or any combined alphanumeric character.

Characteristics
Conforming to standard IEC60947-4-1, GB14048.4, UL508
UL(USR/CNR) and CCC
Approvals or Certificate
Some models SEMKO, KETI or TÜV plus
Vertical
Operating position
(Metal base mounting)
operation ℃ -25℃ ~ +70℃
Ambient temperature
storage ℃ -40℃ ~ +70℃
Relative humidity 90-95%RH at 40℃
Pollution degree 3
-2-
Performance
XMCK-
Poles D DN 2
Rated insulation voltage V 690
Rated operating voltage V 240/277,480 (60Hz) or 230,400 (50Hz)
Full load ampere(FLA) A 20 25 30 40
Resistive Amps Rating(RES) A 25 30 40 50
Making capacity(230V cosφ0.45) A 12×FLA
Breaking capacity(230V cosφ0.45) A 10×FLA
Switching frequency op/h 360
Electrical endurance(ARI 780/790) cycle 100,000
Mechanical endurance(ARI 780/790) cycle 500,000

Pole Characteristics

Locked Resistive Maximum


Full Load
Number Of Line Rotor Amps Horsepower Catalog
Amps
Poles Voltage Amps Rating Single Number
(FLA) Voltage
(LRA) (RES) Phase
240/277 120
XMCK-25D*
20 1 480 100 25 240/277 1.5
XMCK-25DN*
600 80
240/277 150
XMCK-30D*
25 1 480 125 30 240/277 2
XMCK-30DN*
600 100
240/277 150
25 2 480 125 35 240/277 3 XMCK-302*
600 —
240/277 150
XMCK-40D*
30 1 480 75 40 240/277 2
XMCK-40DN*
600 50
240/277 180
30 2 480 150 40 240/277 3 XMCK-402*
600 —
240/277 240 XMCK-40D*Z
40 1 480 160 50 240/277 3 XMCK-40DN*
600 100 Z
40 240/277 240
30 2 480 150 50 240/277 3 XMCK-502*
— 600 —
Notes: All the models also could be marked or used for the actual applications which have less
contact ratings than the certificated ratings. The rating can be voltage, FLA, LRA or RES.

-3-
Coil characteristics @ 25℃(Cold state)

Inrushed VA Sealed VA Sealed Watts Voltage


Part number
60Hz 50Hz 60Hz 50Hz 60Hz Pick-up Drop-out

XMCK-□D/DN 32 36 8 10 4.5
≤0.8Us ≥0.2Us
XMCK-□2 40 45 11 13 5.5
Notes: Us=24VAC 50/60Hz or 120VAC 50/60Hz or 220VAC/50Hz, 240VAC/60Hz or
277VAC/60Hz. Inrushed VA and Sealed VA test at Us.

Dimensions & Wiring diagram

1- pole

-4-
Dimensions & Wiring diagram

1- pole+shunt

2-pole

-5-
Dimensions & Wiring diagram

XMCK-□D XMCK-□DN XMCK-□2

XMCK-□D*P XMCK-□DN*P XMCK-□2*P

Wiring diagram

Remarks
1)Torque for Screws 25 lb-in/Lugs 25 lb-in.

2)For QC wiring, the female connector should meet IEC 60760, necessary to ensure the reliability
of connection between female connectors and QC terminals.
3)If the actual condition differs from this specification, please contact us for further
discussion.

-6-

You might also like