SR4B Generators

Large Frame Generators

PRODUCT INFORMATION
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Arrangement Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8

Marine Certified Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Eleven Compact Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11

Full Stator Cage Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Bus Bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-15

Terminal Extension Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Terminal Strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-19

Digital Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

EMCP II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Class H Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Serviceability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-27

Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

SR4B GENERATORS
Building on a Tradition of Continuous Improvement
The newest Caterpillar® SR4B generators feature customer needs in standby, continuous, and
many customer responsive improvements not harsh environment applications.
available in their predecessor, the Cat SR4
Easier access is provided for the serviceable
generators. And that’s saying a lot, considering
parts. And the generators feature full stator cage
there are more than 250,000 SR4 generators
construction to reduce vibration and provide for
currently operating in installations around the
better cleaning access.
world. But, just because the SR4 gained wide
approval in myriad packaged generator set and The SR4B generators with permanent magnet
marine auxiliary applications over the last excitation can also be equipped with the
years, doesn’t mean we couldn’t make it better. new Caterpillar digital control monitor, a
In fact, driven by the Caterpillar commitment to programmable microprocessor-based system
continuous quality improvement and by listening that allows users to modify voltage regulator
to our customers, we improved it quite a bit. characteristics.
For starters, the new Cat® SR4B generators are All SR4B generators are available in packages
nearly one percent more efficient than their with the new Cat 3500B diesel engine with
super-efficient predecessors in the SR4 family. ratings from 800 to 2000 kW at 1500 to
They are also significantly shorter and more 1800 rpm/min.
compact than the previous models — without
The new SR4B generators from Caterpillar.
any loss of output capability. We have also
A new generation of generators.
tailored these generator designs to specific

4
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

DESIGN FEATURES
Our new world class SR4B full line of • Modular design allows addition of extension
generators offers many features not found on the terminal boxes for low voltage components
SR4. This new line of generators truly focuses on and for adding circuit breakers up to
the requirements of the application. The SR4B 3200 Amps. This allows customer access to
designs have been tailored for standby, top, bottom, left, and right.
continuous, and harsh environment applications • 2/3 pitch is now standard on all 4160V
in response to customers’ needs. generators allowing 2400V delta connection.
2/3 pitch is also available on all others as
• The SR4B is offered in 11 new sizes: custom quote without derate.
690, 691, 692, 693, 695, 696, 822, 824, 825,
826, 827. • Permanent magnet excitation is standard on
all continuous, harsh environment, and
• Permanently mounted bus bars are now medium voltage SR4B generators. This,
standard on all SR4B designs including together with three-phase sensing, provides
medium voltage. These bus bars have six holes superior voltage regulator performance, even
and conform to the standard NEMA pattern. with nonlinear loads.
Optional bus bars are available in European
pattern. • Isolation voltage sensing transformers are now
standard on all permanent magnet SR4B
• Control voltage terminal strips are provided generators for convenient paralleling.
to allow easy customer connections to
regulator, space heater and other devices. • Embedded stator temperature detectors are
also standard on all 400V/480V continuous
• The SR4B has improved efficiencies (as much and all form wound generators.
as 0.9 percent improvement over SR4) and
motor starting capability in excess of 1.9 • The SR4B offers the best selection of standard
SKV•A per continuous kW. voltages in the industry: 380V, 480V, 600V,
2400V, 4160V @ 60 Hz; and 400V, 500V,
• New full cage construction is a rugged design 3300V @ 50 Hz.
offering superior package performance
allowing easier stator maintenance with better • The SR4B design offers better utilization of
cleaning access and improved space heater materials with a more compact design –
location. shorter in length with less overall weight
than SR4 generators of the same rating.
• The SR4B has a more serviceable design with
easier access to the bearing. • The new Caterpillar Digital Voltage Regulator
– Replaceable sleeve for bearing reduces (D.V.R.) is now available on all generators
repair cost and time. with permanent magnet excitation. The D.V.R.
– Leads exit from top of generator instead of offers superior transient response, block
through bearing bracket for improved loading, generator protection, and flexibility.
cooling. The D.V.R. integrates many of the options that
– Optional bearing temperature detectors are were previously panel mounted into one
available. package including KVAR/PF controller,
overexcitation protection, fault detection,
overvoltage protection, undervoltage
protection, and system parameter monitoring.

5
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

Arrangement Numbers
These generators are available in the price list under various PAs and carry the following
arrangement numbers:

4 Pole 400V 50 Hz 3300V 380V 500V 50 Hz


480V 60 Hz 4160V 600V 60 Hz
Harsh Medium Continuous Harsh Continuous
Frame Size Standby Continuous
Environment Voltage (Prime) Environment (Prime)
Winding Type Random 690s-Random Form Form Random Form 690s-Random
820s-Form 820s-Form
690 9Y-0515 9Y-0158 4P-4534
691 9Y-0517 9Y-0160 4P-4542 9Y-1424 9Y-0395 155-5102 4P-4582
691-2 Bearing 121-6849 121-6851 121-6853 121-6855 121-6857 121-6859 121-6861
692 9Y-0520 9Y0162 4P4544 9Y-0453 9Y-0397 155-5104 4P-4584
692-2 Bearing 121-4612 121-4614 121-4616 121-4618 121-4620 121-4622 121-4624
693 9Y-0522 9Y-0164 4P-4546
693-2 Bearing 121-4626 121-4628 121-4630
695 9Y-0524 9Y-0166 4P-4568 9Y-0455 9Y-0399 115-5106 4P-4586
695-2 Bearing 122-1179 122-1181 122-1183 122-1185 122-1187 122-1189 122-1191
696 9Y-0526 9Y-0170 4P-4570
822 9Y-0528 4P-4574 4P-4574 9Y-0457 115-5108 4P-4588
824 9Y-0530 4P-4576 4P-4576 9Y-0460 115-5110 4P-4590
825 9Y-0532 4P-4578 4P-4578 9Y-0462 115-5112 4P-4597
826-2 Bearing 9Y-0534 4P-4580 4P-4580 9Y-0464 115-5114 4P-4599
827-2 Bearing 7E-9696 7E-9696 9Y-0276 115-5116 4P-4601

Notes: Two-bearing versions not shown are available by special request.


Special voltages available upon request.

6
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

690 690 690 Harsh 820 820 820 Harsh Medium


Standby Continuous Environment Standby Continuous Environment Voltage
New compact size – Standard Standard Standard Standard Standard Standard Standard
reduction in length
Improved efficiency Standard Standard Standard Standard Standard Standard Standard
Improved wire Standard Standard Standard Standard Standard Standard Standard
& terminal
identification
ensuring reliable
connections
Class H insulation Standard Standard Standard Standard Standard Standard Standard

Six leads standard Standard Standard Standard Standard Standard Standard Standard
for differential
protection
Isolation Option Standard Standard Option Standard Standard Standard
transformers
Full cage Standard Standard Standard Standard Standard Standard Standard
construction
Six-hole power bus Standard Standard Standard Standard Standard Standard Standard
bars for convenient
customer load
connection
Terminal box with Standard Standard Standard Standard Standard Standard Standard
DIN rail mounted
terminal blocks
More serviceable Standard Standard Standard Standard Standard Standard Standard
design with easier
access to bearing
and other
replaceable parts
Wet, layer wound Standard Standard Standard Standard Standard Standard Standard
rotors individually
tested to 125%
of rated speed
Form wound N/A N/A Standard N/A Standard Standard Standard
Permanent magnet N/A Standard Standard N/A Standard Standard Standard
Generator mounted Option Option Option Option Option Option N/A
circuit breaker box
2/3 Pitch Option Option Option Option Option Option Standard
Digital Voltage N/A Option Option N/A Option Option Option
Regulator
Stator temperature Option– Option– Embedded Option– Embedded Embedded Embedded
detectors Embedded Embedded RTDs 100Ω Pt Embedded RTDs 100Ω Pt RTDs 100Ω Pt RTDs 100Ω Pt
Type J T/C Type J T/C Standard Type J T/C Standard Standard Standard

7
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

690 690 690 Harsh 820 820 820 Harsh Medium


Standby Continuous Environment Standby Continuous Environment Voltage
Bearing temperature Option Option Option Option Option Option Option
detectors
New terminal box Option Option Option Option Option Option Standard
extension with: (Without
- Separate circuit
compartment for breaker
control devices option)
- Modular design
allowing RH or
LH mount
- Optimized for use
with or without
circuit breakers
Manual voltage Option Option Option Option Option Option Option
control
RFI filter Option Option Option Option Option Option Option
Air filter Option Option Option Option Option Option Option

8
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

MARINE CERTIFIED GENERATORS


ABS, BV, DnV, Lloyds
Stator Available
Generator Frame Winding Exc. Voltages
Arng. Group Appl. Size Type Insulation Type 60 Hz 50Hz
9Y-0158 9Y-0157 PP/MAR 690 Random 1 VI & 1 DE P.M. 440 380
4P-4534 4P-4533 H.E./MAR 690 Form Coastal P.M. 440 380
9Y-0160 9Y-0159 PP/MAR 691 Random 1 VI & 1 DE P.M. 440 380
4P-4542 4P-4541 H.E./MAR 691 Form Coastal P.M. 440 380
121-6851 121-6850 PP/MAR 691-2B Random 1 VI & 1 DE P.M. 440 380
121-6853 121-6852 H.E./MAR 691-2B Form Coastal P.M. 440 380
9Y-0162 9Y-0161 PP/MAR 692 Random 1 VI & 1 DE P.M. 440 380
4P-4544 4P-4543 H.E./MAR 692 Form Coastal P.M. 440 380
121-4614 121-4613 PP/MAR 692-2B Random 1 VI & 1 DE P.M. 440 380
121-4616 121-4615 H.E./MAR 692-2B Form Coastal P.M. 440 380
9Y-0164 9Y-0163 PP/MAR 693 Random 1 VI & 1 DE P.M. 440 380
4P-4546 4P-4545 H.E./MAR 693 Form Coastal P.M. 440 380
121-4628 121-4627 PP/MAR 693-2B Random 1 VI & 1 DE P.M. 440 380
121-4630 121-4629 H.E./MAR 693-2B Form Coastal P.M. 440 380
9Y-0166 9Y-0165 PP/MAR 695 Random 1 VI & 1 DE P.M. 440 380
4P-4568 4P-4567 H.E./MAR 695 Form Coastal P.M. 440 380
122-1181 122-1180 PP/MAR 695-2B Random 1 VI & 1 DE P.M. 440 380
122-1183 122-1182 H.E./MAR 695-2B Form Coastal P.M. 440 380
9Y-0170 9Y-0169 PP/MAR 696 Random 1 VI & 1 DE P.M. 440 380
4P-4570 4P-4569 H.E./MAR 696 Form Coastal P.M. 440 380
4P-4574 4P-4573 H.E./MAR 822 Form Coastal P.M. 440 380
4P-4576 4P-4575 H.E./MAR 824 Form Coastal P.M. 440 380
4P-4578 4P-4577 H.E./MAR 825 Form Coastal P.M. 440 380
4P-4580 4P-4579 H.E./MAR 826-2B Form Coastal P.M. 440 380
7E-9696 7E-9695 H.E./MAR 827-2B Form Coastal P.M. 440 380

1 VI & 1 DE: One vacuum impregnation treatment and one overcoat of epoxy
COASTAL: Two vacuum pressure impregnation treatments and one overcoat of epoxy

9
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

ELEVEN SIZES
The SR4B is offered in 11 sizes: 690, 691, 692, • All industry standard voltages from 380 to
693, 695, 696, 822, 824, 825, 826, and 827. Any 5000 volt are available — the best selection
of the 11 frame size diameters are offered with: of standard voltages in the industry: 380V,
480V, 600V, 4160V @ 60 Hz; and 400V,
• The new Cat 3500B diesel engine is standard,
500V, 3300V @ 50 Hz.
with outputs ranging from 800 to 2000 kW.

Left side

10
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

MORE COMPACT
The SR4B generators are significantly shorter requires less material than the standard round
and more compact than their predecessors in lamination, but is also more effective, allowing
part because of their new square stator overall generator length to be reduced with no
lamination design. This new design not only loss in output capability.

Right side

11
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

FULL STATOR CAGE CONSTRUCTION


Cat SR4B generators feature full stator cage Also, the air circulation pattern has been
construction designed to: changed, with air flow now entering from the
bottom as opposed to the sides.
• Increase durability
• Reduce vibration
• Provide better cleaning access for
stator maintenance
• Improve space heater location

Showing cage construction and power connections

12
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

BUS BARS
A bus is a conductor or group of conductors The bus bar in the SR4B generators carries
serving as a common conductor in high current heavy currents that supply several electric
applications — often in the form of a bar. circuits.

Generator lead end

13
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

SIX-HOLE POWER BUS BARS STANDARD

All SR4B generators are equipped with NEMA A European style bus bar with metric
approved six-hole power bus bars for convenient dimensions is also available as an option.
customer load connection.

Customer side showing NEMA hole pattern.

14
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

BUS BARS CENTER MOUNTED

Standard NEMA Hole Pattern

88.9
76.2
60.5

16
0
12.7

198.9
110

154.4

221.2
0

Standard on all SR4B generators


Bus Bar Assm. 115-3056

Optional European Style


Mounting Holes

89
76
63.3

13.3
0
12.5
181.5

306.5
0

231.5

281.5

Connection Group 118-9430


Replaces STD Assm. 115-3056
All dimensions are metric.

15
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

TERMINAL EXTENSION BOX

The modular design of the new Caterpillar SR4B Optional terminal extension boxes allow for:
generators allows for the optional addition of
• Adding circuit breakers up to
extension terminal boxes with:
3200 Amps
• Separate compartment for control • Customer access to top, bottom, left,
devices and right of unit
• RH or LH mount
• Optimized for use with or without
circuit breakers

Shown with optional low voltage extension box

16
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

MAIN TERMINAL STRIP

Cat® P/N 115-5142

5 5
6 6 Droop CT
11 26
13 30
12 28 P.M. Exc.
20 20
22 22 Sensing
24 24
31 31 Power T/F
30 30

H1 H1
H2 H2 Spc. Htr.
H3 H3
H4 H4

Spare (2)
Shunt Trip (2)

BGR1 BGR1 Exc. End RTD


BGW1 BGW1

BGR2 BGR2
BGW2 BGW2 Drive End RTD
F1 F1
F2 F2 Exc. Field
Gnd Gnd

17
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

THERMOCOUPLE TERMINAL BOX

Cat® P/N 115-5138

TC1 + TC1 +
TC1 - TC1 -
TC2 + TC2 +
TC2 - TC2 -
Main T/C
TC3 + TC3 +
TC3 - TC3 -

TC4 + TC4 +
TC4 - TC4 -
TC5+ TC5 +
TC5 - TC5 -
Spare T/C
TC6 + TC6 +
TC6 - TC6 -

Spare (4)

N.O. N.O.
N.C. N.C. Air Filter
COM COM

18
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

RTD TERMINAL STRIP

Cat® P/N 115-5139

R1 R1
W1 W1
C1 C1
R2 R2
W2 W2 Main RTD
C2 C2
R3 R3
W3 W3
C3 C3

R4 R4
W4 W4
C4 C4
R5 R5
W5 W5 Spare RTD
C5 C5
R6 R6
W6 W6
C6 C6

Spare (4)

N.O. N.O.
N.C. N.C. Air Filter
COM COM

19
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

DIGITAL VOLTAGE REGULATOR


The SR4B generators with permanent magnet The D.V.R. system features:
excitation can also be equipped with the new
• A touch-pad entry system
Caterpillar Digital Voltage Regulator (D.V.R.)
— a programmable microprocessor-based • LCD display
system that allows customers to modify voltage
regulator characteristics. The D.V.R. can provide • Either reactive droop or cross-
voltage regulation of ±0.25 percent from no load current compensation operating
to full load, with a drift of less than 0.5 percent modes
for any 40° C change in temperature.
• True RMS three-phase sensing is
The D.V.R. offers: provided and single-phase sensing is
• Superior transient response available.
• Block loading
Among the programmable features are:
• Generator protection
• Voltage droop
• Flexibility
• Voltz per-hertz behavior in two
The D.V.R. also offers many of the options that separate frequency ranges each
were formerly panel mounted into one package providing from 1.0 to 10 V/Hz voltage
including: droop
• KVAR/PF controller
• Overexcitation protection
• Fault detection
• Overvoltage protection
• Undervoltage protection
• System parameter monitoring

20
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

EMCP II
Cat SR4B generator sets can be specified with a Modular Control Panel (EMCP II) used on
new Customer Communications Module (CCM). 3500B or 3500 generator sets. By accessing the
This module allows the customer to use a remote module, as many as eight EMCP II equipped
personal computer to communicate via a direct generator sets can be remotely started, stopped,
connection of a telephone modem with a and monitored.
second-generation Caterpillar Electronic

1 1
2 2
2 2

2 GND 2 31 31
32 32
3 3 GND GND
4 4 33 33
5 34 34 50 50
5
6 6 34 34 50 50
7 7 35 35 50 50
8 8 35 35 51 51
9 9 52 52
36 36
10 10 53 53
37 37
11 11
38 38 L1 L1
12 12
39 39 L3 L3
13 13
14 14
15 15 40 40
16 16 41 41
17 17
42 42
18 18
19 19 43 43
20 20 44 44
21 21 45 45
22 22 46 46
23 23
47 47
24 24
25 25

26 26

27 27
28 28
29 29
30 GND 30

EMCP II DC Connections EMCP II – EUI Only EMCP II AC Connections


Cat® P/N 115-5141 Cat® P/N 115-5137 Cat® P/N 115-5140

21
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

CLASS H INSULATION
Because the SR4B generators are tailored to Form-wound windings are standard on 820
specific customer needs in standby, continuous, frame continuous and harsh environment
and harsh environment applications, new generators. Embedded stator temperature sensors
vacuum impregnated Class H insulation is are standard on all 400/480 volt continuous units
standard on all SR4B generators: form wound, and all-form wound models with the exception
Vacuum Pressure Impregnation (VPI); and of 600V units.
random wound, Vacuum Impregnation (VI).
• Low cost
• Reliability

Rotor: 4-pole, 690 frame

22
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

EASIER SERVICEABILITY
Serviceability Modular Capability
• Easier access to all serviceable parts • Attachments (see pages 24-27) easily added
and removed (relays, fuses, etc.)
• Replaceable sleeve bearing reduces
repair time Isolation Transformers
• Standard on all SR4B permanent magnet
generators for convenient paralleling

23
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

ATTACHMENTS
REGULATOR GROUPS
Self Excited Generators
(Standby Only)
Attachment Type STD OPT
Description VR3 VR3F
LA No. LA-0459
Consist
Add: 121-6204 121-6205
Less: 121-6204

Permanent Magnet Generators


(Prime Power & Harsh Environment)
Attachment Type STD OPT OPT OPT
Description VR3 VR3F DVR-Basic DVR-VAR/PF
LA No. LA-0458 LA-0456 LA-0457
Consist
Add: 121-6200 121-6201 121-6202 121-6203
Less: 121-6200 121-6200 121-6200

MANUAL VOLTAGE CONTROL


Shipped loose, to be installed by customer
Self Excited 7C-2700
Permanent Magnet 5N-0591

BEARING TEMPERATURE DETECTORS


Includes sensor and mounting hardware to provide monitoring of bearing’s outer race.

Single Bearing
Platinum (100 Ohm) 6I-4906
Copper (10 Ohm) 6I-4907
Two Bearing
Platinum (100 Ohm) 6I-4908
Copper (10 Ohm) 6I-4909

AIR FILTERS
Provides filtering of incoming air at rear of generator down to 10 microns. Replaces
lower rear screen assembly and installs differential pressure switch, unwired.
690 Frame 121-5422
820 Frame 121-5423

RFI FILTER
Radio Frequency Interference filter. Meets Common Market Directive 82/499/EEC,
German VDE 875/10.84 A2 Level N, and British BS800 standards; and MIL-STD 461B
(conducted, radiated and susceptibility).
690 and 820 Frame Sizes 121-5421

24
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

ATTACHMENTS
CONNECTION GROUPS
Provided standard on all generators except medium voltage. Standard customer
interface to low voltage connections located at rear of generator. Shock mounted shelf
isolates the low voltage terminal strips and other electrical components.
Controls & Interconnect
Basic 121-9638 Std. on all standby and 380, 600 volt prime power
generators
Basic + Stator T/Cs 121-9639 Std. on all 480 volt random wound, prime power
generators
Basic + Stator RTDs 121-9640 Std. on all harsh environment generators

Extension Box - Low Voltage


Provides separate compartment for wiring low voltage attachments & components.
Standard attachment on all medium voltage (2400, 3300, & 4160 V) generators.
Requires removal of controls & interconnect connection group which is standard on all
low voltage generators, installs terminal strips and routes wires in box. Uses side panel
from main terminal box on generator.
LA No. LA-0463
Consist
Box Assm. 115-2512
Instructions 122-3487
Less:
Bracket Assm. 121-9641
Shock Mounts
Multi page drawing showing different hardware configurations. Shows all cases; i.e.
with EMCP II terminal strips and various generator options. Page 1: Main. Page 2: Main
+Thermocouples. Page 3: Main + RTDs. Page 4: Main + EMCP II connections

Cable Access
Provides an extension box with removable top, bottom, and front panels to allow easier
routing of customer cables to bus bars.
690 and 820 Frame Sizes 122-1194
Cannot be used with circuit breakers

Delta Connection
Changes generator output to Delta operation instead of Wye (Star).
TECHNICAL: Only f/u/w medium voltage generators and other 2/3 pitch stators.
All 2/3 pitch generators 121-5132

25
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

ATTACHMENTS
High Output Current
F/u/w larger frame size generators to allow customer connections of output currents
requiring more than 1 sq. in of copper. Not f/u/w generator mounted circuit breakers.
690 and 820 Frame Sizes 121-5424
Cannot be used with circuit breakers

European Hole Spacing


Uses extra long bus bars with six holes, two rows of three, spaced 50mm apart vertically
and horizontally. Removes standard NEMA hole pattern bus bars.
690 and 820 Frame Sizes 118-9430

CSA
Connects the neutral bus bar to the frame of the generator so it can be connected to
ground at one convenient location.
F/u/w Circuit Breakers 121-9480
Not f/u/w Circuit Breakers 121-9481

RELAY GROUP – SPACE HEATER


Allow automatic power up of space heaters when gen set is not in operation and
disconnects power once engine is running.
690 and 820 Frame Sizes 122-0335
Requires EMCPII signal. Customer supplies 115-230 VAC

SPARE PARTS KITS – MARINE CERTIFIED


Consisting of mandatory spares for essential machinery per Marine Classification
Society requirements for unrestricted, oceangoing service (Only one kit is required for
multi-engine applications with identical engines and generators.) Not installed.
690 Frames 115-5136
820 Frames 121-9272
Remember to have two bearings available for 820s and different sizes for 690s.

26
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

ATTACHMENTS
CIRCUIT BREAKERS
Rating 1200 A 1600 A 2000 A 2500 A 3200 A
LA No. LA-0464 LA-0465 LA-0466 LA-0467 LA-0468
Consist
Circuit Breaker Group 106-5664 105-7926 114-4674 105-7928 105-7929
Panel Assm. 122-4869 122-0317 122-0317 122-0317 122-0317
Connection Group 122-0328 122-0329 122-0320 122-0331 122-0332
Wiring Group-Shunt Trip 122-0320 122-0320 122-0320 122-0320 122-0320
Mounting Group 122-3488 122-0319 122-0319 122-0319 122-0319

Rating 1200 A 1600 A 2000 A 2500 A 3200 A


LA No. LA-0471
Consist
Circuit Breaker Group 106-5661
Panel Assm. 122-4869 122-0317 122-0317 122-0317 122-0317
Connection Group 122-0329 122-0330 122-0331 122-0332 122-0334
Wiring Group-Shunt Trip 122-0320 122-0320 122-0320 122-0320 122-0320
Mounting Group 122-3488 122-0319 122-0319 122-0319 122-0319

Option
In order to accommodate output connections and proper bend radii on customer cables,
this box can be used to extend the circuit breaker or extension boxes to the floor.
Box Group - Bottom CB 122-0352

27
P R O D U C T I N F O R M AT I O N – S R 4 B G E N E R AT O R S

SR4B GENERATORS
Nearly one percent more efficient than their The new Cat Digital Voltage Regulator (D.V.R.)
predecessors in the SR4 family, our new world- is now available on all generators with
class SR4B generators offer many features not permanent magnet excitation for:
found in the SR4 and all of which are important
• Superior transient response
selling points. What’s more, the SR4B designs
have been tailored for standby, continuous, and • Superior block loading
harsh environment applications in response to
• Generator protection
customer needs. New features include:
• Flexibility
• Eleven sizes
• A much more compact design — shorter The D.V.R. effectively integrates many of the
in length and lighter options that were previously panel mounted into
one package including:
• The best selection of standard voltages in
the industry — from 380V @ 60Hz to • KVAR/PF controller
3300V @ 50Hz
• Overexcitation protection
• Permanently mounted standard NEMA
• Fault detection
pattern bus bars
• Overvoltage protection
• Full cage construction for better access and
ease of stator maintenance • Undervoltage protection
• More serviceable design and easy access to • System parameter monitoring
the bearing
• Modular design allows addition of low
voltage extension boxes and circuit breakers
• Permanent magnet excitation with three-
phase sensing is standard on all continuous,
harsh environment, and medium voltage
SR4B generators
• Isolation voltage sensing transformers
standard for ease of paralleling

28
LEKX6203 Printed in the U.S.A.