You are on page 1of 62

ELECTRICAL DISTRIBUTION SYSTEMS I.

Introduction to the course: this course is provided in a question & answer format and is divided into 5 
chapters, it will become extremely useful to you: 

• If you want to know the parameters of the induction motors, their effect on the starting and 
normal performance of the machine. 
• If you want to analyze an existing a.c. machine or evaluate a new one for its steady state or 
transient state including starting and short circuit. 
• If you want to know the major components in the power distribution systems and how each 
component is defined. 
• If you want to calculate the line and cable constants from the information found in standard 
tables. 
• If you want to know the different types of breakers, starters and switchgear assemblies. Also, if 
you want to know how they are defined. 
• If you want to do the necessary calculations to size the load breaking/interrupting/disconnecting 
devices for normal and fault conditions. 
• If you want to know the types and sources of power line disturbances. Also, if you want to know 
the effects of such disturbances on the major components of the power systems and the methods 
of reducing these damaging effects. 
• If you want to know the effects of using local capacitors in increasing the circuit capacity and 
how to size capacitors to improve the p.f. in motor circuits. 
• If you want to quantify the effect of direct and indirect lightning strokes on overhead distribution 
systems. 
• If you want to know what are the data that have to be available in order to perform any of the 
following studies: TRV, stability, load flow, fault/co­ordination, motor starting, reliability and 
switching transients. 
• If you to know the procedure to calculate the following: basic values including base and p.u. 
values, load flow, fault current/voltage sensitivity, motor starting, reliability studies for simple 
radial systems. 
• If you want to know how steel properties, switchboard instruments, meters, relays are defined 
and what are the major modules of PLC plus the building blocks of an office automation 
system. 
• If you want to know the calculations to be performed if a major power transformer is to be 
protected against short circuits or overloads. 
• If you want to know what are the essential programs and data for the power systems analyst (or 
any other individual involved in electric power distribution and studies ­ for that matter). 
Contents: 
1.  A.C. Electric machines parameters & performance.  
2.  Overhead and undeground distribution systems components.  
3.  Switchgear, circuit breakers, MCC and starters.  
4.  Power line disturbances and power quality.  
5.  Power systems studies. 
Lesson 1: AC electric machines parameters & performance.
1) What are the parameters of the induction motors and what are the tests to be performed on such 
machines to be able to obtain the values of these parameters?
2) How can the performance of an induction motor be analyzed? 
3) What are the important characteristics that are used in defining synchronous machines (in 
general) and synchronous generators (in particular)? Sketch the equivalent circuit under the 
different conditions of operation. 
4) What are the data required from testing to calculate the parameters of synchronous motors? 
5) Sketch the equivalent circuit of single phase transformer and list the required tests (to be 
performed on transformers) to obtain the values of the parameters of the equivalent circuit? 
6) A solved problem regarding the running & starting performance of an induction motor.
7) A solved problem regarding the characteristics of synchronous machines.
8) A solved problem regarding the parameters of single phase transformers.
9) A solved problem regarding the characteristics of 3­winding transformers.
10) Summarize the methods used in calculating the parameters of synchronous and induction 
machines.
Lesson summary
References
1) What are the parameters of the induction motors and what are the tests to be 
performed on such machines to be able to obtain the values of these parameters? 
The parameters of the induction motors are: the stator resistance per phase, stator leakage 
reactance/phase, rotor resistance/phase, rotor leakage reactance/phase, main flux susceptance 
and conductance/phase. For motors under starting conditions the parameters are the same as 
above except the values of the rotor resistance and reactance (referred to the stator) are higher 
(due to skin effect) and lower (due to the skin effect & saturation), respectively. The tests to be 
performed on such machines to be able to calculate the parameters of the machine are the no 
load (open circuit) and locked rotor (short circuit) under full and reduced voltage. The reduced 
voltage test is run to get the unsaturated reactance values (for rotor & stator). The data to be 
collected from the no load test are: Primary voltage, the no load current and power at 75C (or 25 
and corrected to 75); from the locked rotor: the voltage, current and power at 75C; from the 
locked rotor (reduced voltage): the voltage and current. For the first 2 tests, the nominal motor 
voltage is applied, if possible. Fig. 1 shows the equivalent circuit of a S.C.I.M.
R1: stator resistance per phase, X1: stator leakage reactance/phase, R2': rotor resistance/phase 
referred to stator, s: slip, X2': rotor leakage reactance referred to stator, Bm: main flux 
susceptance, Gm: main flux conductance. 

2) How can the performance of an induction motor be analyzed? 
The performance of induction motors can be analyzed by studying the following points: heating 
of winding/iron, efficiency of motor, power factor of machine, pull­out (maximum) torque, 
starting torque, starting currents and the effect of the parameters on such points. a) Heating of 
winding and iron: to reduce winding heating rotor and stator resistances have to be small. 
Though for a high starting torque, the rotor resistance has to be high. To reduce iron losses, the 
main flux has to be low. Note that the main flux and rotor current affect the torque. 
b) Efficiency: to have a high efficiency motor, the windings (copper) and iron losses have to be 
kept to the minimum possible. 
c) Power factor: to achieve a high power factor machine, the leakage reactances (stator and 
rotor) have to be low i.e. low reactive current. To have a high pullout torque, the flux has to be 
high. 
d) Maximum (pull­out) torque: to have a high pull­out torque in induction motors, primary 
(stator) and secondary (rotor) reactances should be kept to a minimum, the rotor resistance will 
only determine the slip of the maximum torque. 
e) Inrush Current: reactances (and for small motors, the resistances) of the rotor and stator 
windings have to be high to have a low inrush current. 
f) Starting torque: the rotor winding resistance has to be high to get a high starting torque, this 
contravenes the efficiency requirement. 
As can be seen from the above, the parameters of induction machines (i.e. their design) are a 
compromise to achieve the optimum starting, pull­out and running performances required by the 
different applications. When a motor is existing and the following data are available: motor HP, 
terminal voltage, frequency, number of poles, stator resistance, windage losses, stray load losses 
and the other motor parameters (or the results of the tests), the following are calculated: the 
rotor current referred to stator (I2'), starting torque (Tst) and the power transferred by the 
rotating field to the rotor (Prot.f) for starting performance analysis. For the running 
performance: the slip(s), stator and rotor currents, the developed torque and power, the 
efficiency and the power transferred by rotating field at rated motor HP and at pull out 
conditions or states are calculated. 
3) What are the important characteristics that are used in defining synchronous machines 
(in general) and synchronous generators (in particular)? Sketch the equivalent circuit 
under the different conditions of operation. 
The characteristics of synchronous machines that define such machines are the no load, short 
circuit, air gap and potier triangle.
To define a generator, the following characteristics to be investigated: no load and air gap, short 
circuit and Potier triangle, load characteristics, external characteristics, regulation curve, short 
circuit ratio and the determination of the direct axis reactance.
a) No load and air gap (unsaturated) ch/cs: it is expressed on a graph with the Y­axis 
representing the armature (stator) e.m.f. (electromotive force) or the pole flux, with the X­axis 
representing the field current (If) or the field m.m.f. (magnetomotive force in Ampereturn). The 
air gap ch/cs is a straight line passing through the origin and the second point is the E (rated 
stator voltage) value at a low field current (unsaturated conditions). The no load characteristics 
under unsaturated condition coincides with the air gap characteristics ­ up to a point. At the 
point where E is the rated induced in the armature by the flux produced from the resultant mmf 
(Mr) the characteristics line is non­linear (bend inward) ­ saturated condition. The resultant mmf 
will constitute of two portions: that part to drive the flux through the air gap and the other part 
to drive the flux through the iron parts of the magnetic path. Fig.2 below shows the air gap, no 
load & short circuit lines vs. If. 
b) Short circuit characteristics (Potier triangle): the S.C. ch/cs represents the armature current 
(Ia) as a function of the field current (If) or of the field mmf (MMF) with the armature 
terminals short circuited. It is taken at synchronous speed of the generator. The S.C. ch/cs is a 
straight line passing through the origin and the second point will have the X­axis equal to the 
field MMF and the Y­ axis equal the armature current. Potier triangle will have the following 
important quantities: armature reaction mmf and the leakage reactance (impedance) of the 
armature. The cos f =0 load characteristics is constructed from the no load ch/cs and Potier 
triangle. 
c) Load characteristics: it is the terminal voltage V as function of field current (If) or field mmf 
(Mf) for constant load current (Ia) and power factor (p.f.). At a fixed load current, the field 
current is required to sustain the no load voltage and it increases with the decrease of cos f, this 
mainly to counteract the armature reaction. Potier triangle can be determined from the no load 
ch/cs and two points on the cos f = 0 load ch/cs. 
d) External characteristics: it is expressed as the terminal voltage (V) as function of the load 
current (Ia) at constant If and p.f. For lagging current, the voltage drop increases as the power 
factor decreases and vice versa for leading current. 
e) Regulation Curve: it describes the field current as function of either the load current with 
constant p.f. or the p.f. at constant current (Ia) ­ provided that the terminal voltage is kept 
constant. The field current increases with the increase in load current (p.f. is constant lets say at 
1 or .8), the field mmf has to increase to compensate for the armature reaction increase. 
f) Short circuit ratio: it is the ratio of the field current required to produce rated voltage on open 
circuit to the field current required to produce rated current on short circuit. The saturated S.C. 
ratio is obtained from the no load curve and the rated armature current (field mmf to produce 
rated V divided by the mmf producing the rated current). To get the unsaturated S.C. ratio, 
divide the MMF value that produces the rated V from the air gap straight line (it is the extension 
of the linear air gap line that is taken from the no load curve) by the MMF producing the rated 
current under short circuit condition. A large SCR indicates a small armature reaction which 
means that the machine is less sensitive to load variations. A small SCR means that the machine 
is more sensitive to load variations. 
g) Determination of direct axis synchronous reactance (Xd): it is obtained from the no load 
linear portion (or air gap line) and S.C. characteristics. The field current induces the nominal 
voltage on the air gap line. When the stator is short circuited and the field current is maintained 
at the same level as with the open circuit condition, the induced emf in the stator is the same as 
with the no load condition but in this case it is consumed by the drop due to the synchronous 
impedance. The unsaturated short circuit ratio is used to calculate Xd, Xd = 1/SCR. 
Fig.2a below shows the equivalent circuit of the synchronous machine under the different 
conditions. 

Xs: stator leakage reactance, Xm: main flux reactance, Xf: field leakage reactance, Xd: damper 
leakage reactance. 
4) What are the data required from testing to calculate the parameters of synchronous 
motors? 
The tests to be performed on the synchronous machine so that the parameters can be calculated 
are: the open circuit (no load) characteristics, short circuit and the air gap line. From the first 
test, two values are obtained: the nominal stator volt at the field current registered; from the 
second: 2 points are obtained (4 values): the nominal stator current and its corresponding field 
current and the stator current (Ia) at the field current obtained from the open circuit test; from 
the final test: the voltage at the field current equal to the one producing the nominal current in 
the previous test. 
5) Sketch the equivalent circuit of single phase transformer and list the required tests (to 
be performed on transformers) to obtain the values of the parameters of the equivalent 
circuit? 
Fig. 3 below shows the equivalent circuit of a single phase transformer. The tests to be 
performed on transformers so that the parameters, which are the primary and secondary 
windings resistances and reactances plus the main flux susceptance and conductance, can be 
calculated are: the no load (open circuited primary ­ H.V. ­ winding) test from which the open 
circuit volt on l.v. side and the no load current are obtained; the S.C. (l.v. ­ winding short 
circuited) from which 3 values are registered the S.C. losses in W (or kw), the rated S.C. 
currentas seen from the primary side and the voltage circulating such current. The primary 
winding resistance (d.c.) should also be measured by an ohmmeter at 25 C. 

R1: primary winding resistance, X1: primary winding leakage reactance, R2': secondary 
winding resistance referred to the primary winding, X2': secondary winding reactance referred 
to the primary, Bm: main flux susceptance, Gm: main flux conductance, r2': load resistance 
referred to the primary winding, x2': load reactance referred to the primary (in primary side 
terms). 

6) A 3 phase induction motor, 3 HP, 440/220 V, 60 HZ, 4­pole, 1750 rpm, has the following 
no­load test results: Vnl = 440 V, Inl=2.36 A, Pnl=211 W; locked rotor (full voltage) results: 
Ilr=29 A, Vlr=440 V, Plr=13.9 KW; locked rotor (reduced voltage): Vlr1=76 V, Ilr1=4.25 A ­ 
unsaturated reactance condition. Assume windage loss=44 W, stray load loss=48 W, skin 
effect factors=1.3 for rotor winding resistance (referred to stator), .97 for rotor reactance 
and stator resistance/phase = 2.26 W. Determine the 6 parameters of the induction motor, 
its starting and running performance data, the transient reactance and the s.c. time 
constant, the s.c. current after 1 and 2 cycles from fault inception. Calculate the duration 
of the inrush current assuming J=2 lb.ft2 for the rotating parts. 
GIVEN: Vprim=440 V, Ioc=2.36 A, Poc=211 W, Vlr=V1=440 V, Ilr=29 a, Plr=13.9 KW, 
Vlrr=76 V, Ilrr=4.25 A, HP=3, r1 @ 25 °C=2.26 OHM, windage loss=44 W, stray load 
loss=48W, skin effect for r2', x2'=1.3, 0.97. 
SATURATED REACTANCE:
Zl=440/[(3).5(29)]=8.73W, Rl=13920/3(29)(29)=5.48 W, 

X=[(8.73)2­(5.48)2].5=6.8 W, r1 @ 75 °C=2.26[(234+75)/(234+25)]=2.69 W, 
r2'=R1­r1(@ 75 °C)=5.48­2.69=2.79 W, X1=X2=X/2=3.4 OHM. 
UNSATURATED REACTANCE: 
Z=76/[(3.5)(4.25)]=10.3 W, X=[(10.3)2­(5.48)2].5=8.72 W, 
X1=X/2=4.36 OHM, Saturation factor = 4.36/3.4=1.3, 
including for skin effect: r2'=2.79/1.3=2.14 OHM, 

X2'=4.36/.97=4.5 W, Xm=[(V1)­(Ioc.X1)]/Ioc=[(440/3.5)­(2.36)(4.36)]/2.36 = 103 OHM, 

Ph+e=Poc­3(Ioc)2(r1 @ 75°C)­windage losses=211­3(2.36)2(2.69)­44=122W. 
Assuming 1/2 the iron losses are due to the main flux. Ph+e=122/2=61W 

Gm=Ph+e/3(E1)2={61}/{3[(440/3.5)­(2.36)(4.36)]2}=3.43/10000 MHO 

Rm=Gm.Xm2=[(3.43)/(10000)][103]2=3.66 W 
STARTING AND RUNNING PERFORMANCE:
Base values calculations: Vb= 440/3.5b=3x746/3x254=2.94 A, Zb=254/2.94=86.5 OHM. 
Pb=254x2.94=746 W, Tb=7.04(3)(unit power)/unit speed=7.04x3x746/1800=8.8 LB.ft. 
Parameters for starting performance in p.u: 
r1=2.69/86.5=.0311, r2'=2.79/86.5=.0322, x1=x2'=3.4/86.5=.039 (saturated conditions). 
Parameters for running performance in p.u: 
r1=.0311, r2'=2.14/86.5=.0248, x1=4.36/86.5=.0504, x2'=4.5/86.5=.052 (unsaturated). 
Parameters common to both: 
Xm=103/86.5=1.19, Rm=3.66/86.5=.042 p.u. 
Starting performance: 
r2'(1­s)/s=0 as at standstill s=1=(ns­n)/ns

Z1=(r12+x12)=[(.03)2+(0.039)2]=0.05, tan­1=x1/r1=51.4° Z2'=[(.032)2+(.039)2]=.0506 /_50.6° 

Zm=[(1.19)2+(.042)2] =1.19, tan­11.19/.042= 87.98 ° 
V1=I1.Z1 + (I1)/[(1/Z2')+(Ym)] 
V1=I1[.05 /_51.4°+ (1)/(1/.0506 /_50.6°)+(1/1.19 /_87.98°)]; where Ym= 1/Zm, V1=I1.Zeq, 
V1=1/_0° 
I1=V1/{.05 /_51.4°+{[(.0506)(1.19) /_138.58°]/[.0506 /_50.6°+1.19 /_87.98°]}} 
I2'=I1 [Zm/(Z2'+Zm)]=9.66/_­50.4° 

Prot field=I2'2(r2'/s)= (9.66)2(.0322) = 3p.u.
Tst=3p.u.=3x8.8=26.4 LB.ft
Running Performance:
s=.03, r2'(1­s/s)=.8, Z1 =.0593 /_58.3°, Z2'=.825 /_3.6°, Zm=1.19 /_87.98°, 
I1={1/_0°}/{[.0593/_58.3°]+[(.825 /_3.6° . 1.19 /_87.98°)/(.825 /_3.6°+1.19 /_87.98°)]} 
Input p.f.=cos 38.2=.785 
I2'=1.42/_­38.2°[1.19 /_87.98°/(.825 /_3.6°+1.19 /_87.98°)]=1.12 /_­5.74° 

Prot field = I2'2.(r2'/s) = (1.12)2(.0248/.03)=1.025 p.u. 
Tdeveloped=1.025 p.u.=1.025(8.8)=9.02 LB.ft. 
Mechanical loss Torque=7.04(stray load loss+windage+main flux iron loss)/ns(Torquebase) 
=7.04 (48+44+61)/1800 (8.8)=.068 
Tnet developed=1.025­.068=.957 p.u. x 8.8=8.4 LB.ft. 
Power input=3(1)(1.42)( cos 38.2)=3.35 p.u. 
Losses (stator­copper)=3(1.42)2(.0311)=.189 p.u. 
Losses (rotor­copper)=3(1.12)2 x .0248=.093 p.u. 
No load iron losses=122/746=.163 p.u. 
Losses (stray load)=48/746=.064 p.u. 
Losses (friction & windage)=.059 p.u. 
Total losses=.568 p.u. 
Pdeveloped=3.35­.568=2.78 p.u. x 746=2076 W=2.78 HP 
eff.=2.78/3.35=83% 
slip = 3(1.12)2(.0248)/[3.35­(.189+(.163/2))]=.03 
snormal=3/2.78=.0324 
spullout (@ max Torque)=[(1 + (X1/Xm))(r2')/[X1 + (1 + (X1/Xm))X2'] 
=[(1.0+.0504/1.19)(.0248)/[.0504+(1.042)(.052)]=.246 p.u. 
r2' (1­s/s)=0.0758 (@ s=.246), Z2'=r2' + r2'(1­s/s) + jX2'= {[r2' + r2'(1­s/s)]2 + X2'2}.5

=[(.0248+.0758)2+(.052)2].5=.113/_27.3° tan­1 (.052)/(.0248+.0758) = 27.3 ° 
I1=6.12/_­41°, I2'=5.85/_­36°, Protating field=I2'2(r2'/sp.o.)=3.44 p.u. 
Tp.o.=3.44x8.8=30.2 LB. ft. 
Tdeveloped (@ 3HP & s=.0324)=5250 x 3/1800(1­.0324)=9.02 Lb.ft 
Starting Torque/Normal Torque (rated) = 3/1.025 = 2.92 
Pull out Torque/rated Torque = 3.44/1.025 = 3.36 
Transient Analysis: 
Transient reactance = .0504+[(.052)(1.19)/(.052+1.19)] = X" =. 1p.u. 
P.F. = .785, efficiency = 83%, Ib = 2.94 A 
I1 = 3x746/.785(.83)(440)(1.732) = 4.5 A = 1.53 p.u. 
E1'=1­[(.03+j.1)(1.53 x cos 38.2 ­ j1.53 x sin 38.2)] = .874 p.u. /_­6° 
Initial S.C. current = .874/.1 = 8.74 x 2.94 = 25.7 A 
To' = open circuit transient time constant = (X2+Xm)/2(pi)fr2, where pi = 3.141592654 
T' = To' [X"/(X1+Xm)] = S.C. time constant 

IS.C. = Initial S.C.C. (e­t/T) 
To' = .052+1.19/2(pi)60(.0248)=.133 sec. 
T' = .133(.1)/.124= .011 sec. 
IS.C. (after 1 cycle i.e. .0166 sec.) = 8.74(e.01666/.011) = 2 p.u. 
IS.C. (after 2 cycles) = 8.74(.048) = .43 p.u. 
Starting Time: 
An approximate solution if the load and motor speed­torque curves are not available is as 
follows: 
t = J(rpm1­rpm2)2(pi)/60 g Tn 

J = 2 lb ft2, rpm1 = 1740, rpm2 = 0, g = 32.2 ft/sec, Tst = 26.4, Trated (@ rated HP)= 9.02 
Tn = accelerating torque between rpm2 to rpm1 = Tst+Trated/2 = (26.4+9.02)/2 = 17.7 LB. ft. 
t=.7 sec. 

7) A synchronous machine rated 45 KVA, 3 phase, 220 Vl.l., was tested under open circuit 
(no load) and short circuit (locked rotor), the following were the results: OPEN CIRCUIT: 
Vl.l. = 220 V, Ifield = 2.84 A, SHORT CIRCUIT: Iarm.1 = 118 A (first point), Ifield1 = 2.2 A, 
Iarm.2 = 152 A (second point), Ifield2 = 2.84 A, the machine was tested at a power factor = 0 
from short circuited armature condition to no load condition. The no load and air gap 
plus the short circuit curves can thus be plotted (as shown in question 3, fig.2 above) and 
the characteristics of the machine can be obtained graphically. The air gap line is plotted 
from: Ifield = 2.2 A, Vl.l. = 202 V at rated armature current = 118 A, assume s.c. load losses 
(3­phase losses) = 1.8 KW @ 25 °C, armature resistance @ 25 °C = .0335 W/phase, field 
resistance @ 25 °C = 29.8 W/phase. Calculate the saturated and unsaturated reactance, 
the effective armature resistance and the s.c. ratio. If this machine runs as a motor at V = 
230 V, input power to armature = 45 KW, .8 p.f. leading current, field current = 5.5 A, 
then calculate the efficiency of the motor. 
Line to neutral voltage = 202/1.732 = 116.7V on the air gap line; for the same field current of 
2.2a, on the S.C. line, the armature current = 118 amp. 
The saturated reactance = Xs
The unsaturated reactance= Xs air gap = 116.7/118 = .987 OHM, ratio of unsaturated reactance to 
saturated reactance = .987/.836 = 1.18 
Short circuit ratio = 2.84/2.2 = 1.29 (saturated), Xs(saturated) = 1/1.29 = .775 p.u. 
Air gap field current corresponding to 220v line ­ line armature voltage = (220/202)(2.2)=2.39 

short circuit ratio=2.39/2.2=1.086 p.u. (unsaturated), Xs(unsaturated)=1/1.086=.92 p.u. 
The armature effective resistance: 
S.C. load loss/phase = 1800/3 = 600W/ph. 
ra(eff) = 600/(118)2 = .043 W/phase 
in p.u.: S.C. load loss = 1.8/45 = .04 p.u. 
ra(eff) in p.u. = .04/(1)2 = .04 p.u. 
ratio of a.c./d.c. resistance =.043/0335=1.28 (skin effect and proximity) 
Note: armature resistance of m/cs above few hundreds KVA is less than 0.01 p.u. 
For the m/c operating as a motor with leading power factor: 
Ia = 45/(1.732)(.8) = 141 amp. 
Assume stray load loss of 30% of S.C. load loss = .54 KW 
Resistance for copper winding of armature at 75 °C = 0.335[234+75/234+25] = .04 OHM/ph 
Resistance for copper winding of field at 75 °C = 29.8[(234+75)/(234+25)] = 35.5 OHM/ph 
Armature Cu losses (assume ra = .04 or .035W/ph) = 3 Ia2 ra = 3(141)2 (.04)=2.38 KW 

Field Cu losses = (5.5)2 (35.5) = 1.07 KW E = internal voltage of motor = Vt ­ Ia ra = 
(230/1.732)­(141)(.8+j.6)(.04) = 128.4­j3.4 Vphase 
Vline to line = 220 V at which core losses = 1.2 KW 
Total losses = 2.38+1.07+.56+1.2+.91 = 6.12 KW 
Input = 45+1.07 = 46.07 KW 
Efficiency = 1­(6.12)/(46.07) = 86.7% 
8) Calculate the equivalent circuit parameters for the following single phase transformer. 
The results of the open circuit test ( H.V. wdg open) are: Vo.c. = 347 V, Io.c. = 18 A, Po.c. = 
980 W. The results from the short circuit test (L.V. wdg shorted) are: Vs.c. = 70 V, Is.c. = 
Irated, Ps.c. = 1050 W. The 2­winding transformer ratings are: 2400/347 V, 100 KVA, 
primary winding resistance at 25 °C= .24 W. Also, calculate the regulation and effeciency 
at unity and .8 p.f. full load current. 
Transformer ratio: 2400/346 V, Irated = (100)/2.4 = 41.6 A 
Transformation ratio = a = 2400/346 = 7, Zsc = Vsc/Isc =70/41.6 = 1.68 OHM 

Rsc = Psc/(Isc)2 = 1050/(41.6)2 = .607 OHM 

Xsc = [(1.68)2­(.607)2].5 = 1.57 OHM Rsc (at 75 °C) = .607[(234+75)/(234+25)] = .723 OHM 
r1 (at 75 °C) =.24[234+75/234+25] = .28 OHM 
r2' = Rsc­r1 = .723­.28 = .44 OHM 
X1 = X2' = Xsc/2 = .785 OHM 
From open circuit tests: (L.V. wdg. excited): 
Ph+e = Po.c.­(Io.c./a)2r1 = 980­(18/7)2(.28) = 978 W 
E1 = 2400­(Io.c./a)X1 = 2400­(18/7)(.785) = 2400 V 

Xm = 2400/18/7 = 934 OHM, gm=Ph+e/E12=.00017 MHO 

rm = gm (Xm)2 = .00017 (934)2 = 148 OHM 
Zb = 2400/41.6 = 57.7 OHM, Zpu = 1.68/57.7 = .03 pu 
Xpu = 1.57/57.7 = .027 pu, Rpu = .0125 p.u. 
Regulation and efficiency: 
Regulation at 1p.f.: Reg. = (.0125)+(.027)

9)A 3­winding transformer (primary, secondary, tertiary)­ single phase­ rated 7960 V 
(1000 KVA), 2400 V (500 KVA) & 2400 V (500 KVA). The results of the s.c. tests are as 
follows: 
Test WDG Excited  WDG Short Circuited  Applied Voltage Value  Current In Excited WDG 
1  1  2  252  62.7 
2  1  3  252  62.7 
3  2  3  100  208 
The 3 transformers are connected in a Y­D­D configuration on 13.8/2.4/2.4 KV. When the tertiary 
windings are short circuited (3­phase), calculate the s.c. current and the voltage on the terminals of the 
secondary windings of this bank. 
For primary winding: Vb = 7960 V, Ib = 1000/7.96 = 125.4 A 
For secondary winding: Vb = 2400 V, Ib = 1000/2.4 = 416 A 
For teritiary winding: Vb = 2400, Ib = 416 A 
Test Z between terminals Vpu  Ipu  Zpu = Vpu/Ipu 
1  1­2 252/7960=.0316  62.7/125=.5  .0632
2  1­3 252/7960=.0316  62.7/125=.5  .0632
3  2­3 100/2400=.0416  208/416=.5  .0832
Z1 = 1/2 [.0632+.0632­.0832] = .0216 pu 
Z2 = 1/2 [.0832+.0632­.0632] = .0416 pu 
Z3 = 1/2 [.0632+.0832­.0632] = .0416 pu 
Isc=1/(.0216+.0416)=15.8 p.u. (S.C. teritiary) = 15.8 x 125.4 = 1984 A 
V2 = voltage on secondary bus while teritiary is short circuited = Is.c. x Z3 ­ Isec x Z2, Isec is the load 
current 
= 15.8(.0416)­1(.0416)=62.4­4.16= .5824 p.u. To calculate the S.C. current assuming a base MVA = .5 
MVA = 500 KVA: 
Znew = Zold [KVAnew/KVAold] p.u.
Z3new = .5(.0416) = .0208, Z1new = .5 (.0216) = .0108, Isc = 1/.5 (.0632) = 1/(.0208+.0108) = 31.6 p.u., 
Ibase = 500/7.96 = 62.8 A, Isc = 31.6(62.8) = 1984 A 

10. Summarize the methods used in calculating the parameters of synchronous and induction 
machines. 
Synchronous machines:
•Positive sequence (synchronous parameters): The air gap, no load and short circuit characteristics: the 
machine is run at synchronous speed in the proper direction. The three phase armature terminals are 
kept open and line to line voltage readings are taken at different field current (a rheostat) in the field 
winding is used to vary the field current). The excitation is reduced to a minimum and the 3 phase are 
shorted and the field reading plus the current flowing in one of the lines are taken (to draw the short 
circuit unsaturated characteristics line passing through the origin). 
•Subtransient reactance: short circuit the field through an ammeter, apply a single phase voltage to any 
of the three line terminals, rotate the rotor by hand. At the position indicating maximum field current in 
the field ammeter, half the voltameter reading in the armature circuit divided by the armature current in 
one line (using an ammeter in one of the line terminals) is equal the subtransient direct axis reactance. 
At the minimum field current reading, half the armature voltage divided by the armature current will 
give the subtransient reactance in the q­axis. 
•Negative Sequence reactance: the field is shorted on itself, two phases are connected to each other 
through an ammeter and a single phase voltage is applied to this armature configuration. The field is 
rotated at rated speed and the voltage applied to the armature will correspond to approximately 
circulating the rated machine current. The negative sequence impedance = V/1.7321( I). This method 
can also be used with induction m/cs. 
•Zero sequence impedance: zero sequence impedance is much smaller than the positive and negative 
and in theory is close to zero. The machine is at stand still, the field is open, the six terminals ofthe 
machine are available outside the machine and the three windings are connected in series. A reduced 
voltage is applied across the 3 connected windings and the zero sequence impedance will be equal to 
one third the voltage read on the voltameter divided by the circulated current read on the ammeter in 
the armature circuit. 
Induction Machine:
Steady state reactance: from the three tests, no load (open circuit), locked rotor (short circuit) ­ full 
voltage (for saturated reactance) and locked rotor (short circuit) ­ reduced voltage (for unsaturated 
reactance), the parameters are obtained. 
Transient reactance: is calculated from the parameters of the machine obtained from the above tests. X" 
= [X2(Xm)/(X2+Xm)]+X1. 

SUMMARY: 
In this chapter, the parameters and performance of a.c. electric machines were presented. The tests 
performed on such machines to obtain their parameters were given, the parameters and their effects on 
the machines performance were covered, too. Numerical examples were given to show and clarify the 
interrelations between the machine parameters and the performance. The induction machines 
parameters are: stator resistance & reactance, the rotor resistance and reactance, the main flux 
susceptance and conductance. These parameters affect the machine during starting (inrush current & 
starting torque), at nominal load (full load current & nominal torque), and for the maximum (pull­out) 
machine torque. They, also, affect the losses (heating of iron & winding), efficiency and power factor . 
The characteristics of synchronous machines in general and generators in particular presented in this 
chapter were: the air gap and no load (armature emf or pole flux vs. mmf or field current), short circuit 
(armature current vs. field current), load ch/cs (terminal voltage vs. field current provided that the load 
current and the p.f. are kept constant), external (voltage vs. load curent with constant field current & 
p.f.), regulation (field current vs. load current with constant p.f. or field current vs. p.f. with constant 
load current, voltage is kept constant in either case), short circuit ratio (field current producing nominal 
voltage under open circuit condition vs. field current producing rated current under ­ armature ­ short 
circuit condition) and direct­axis synchronous reactance determination (which is equal to 1 divided by 
the SCR). For the transformers, 2 & 3 winding parameters were presented and their effect on 
regulation/efficiency of 2 windings transformers and for 3 windings short circuit plus voltage 
sensitivity of the unfaulted bus were given and emphasized by numerical examples. 

REFERENCES: 
1. Greenwood, Allan "Electrical Transients in Power Systems", Wiley. 
2. Granger & Stevenson "Power System Analysis", McGraw Hill. 
3. Tuma, Jan "Engineering Mathematics Handbook", McGraw Hill. 
4. Fitzgerald, Kingsley & Kusko "Electric Machinery", McGraw Hill. 
5. Kheir, "Automating Power Systems Analysis", Kheir 

Home page of VePi

Lesson 2: Overhead and underground distribution systems components.
1) How would EPR (ethylene propylene rubber) cables, up to 35 KV, be classified?
2) How would underground XLPE (cross linked polyethylene) cables classified? 
3) What are the defining parameters of cables? 
4) What are the factory and site tests to be performed on cables? 
5) What are the defining parameters for low voltage secondary cables? 
6) What are the different types of transformers found in distribution systems? 
7) What are the different types of overhead switches, padmounted switchgear and those of 
lightninig arresters? 
8) What are the standards that govern distribution transformers? How are distribution 
transformers defined? 
9) How are wooden and concrete poles defined? 
10) What are the different applications of oil switches and what are their defining parameters? 
11) How are overhead air switches classified? 
12) How are padmounted switchgear defined? 
13) What are the important parameters by which lightninig arresters are defined? 
14) How would copper conductors be defined? 
15) How would ACSR (aluminum conductor steel reinforced) and ASC (aluminum stranded 
conductor) be defined? 
16) How would AASC (aluminum alloy stranded conductor) and self­dampening/compact 
ACSR be defined? 
17) What are the different types of cable splices and terminations? 
18) What are the different types of connectors and elbows? 
19) What are the design tests performed on the separable connectors? 
20) What are the different types of insulators, their material and characteristics? 
21) What are the functions of DAC (distribution automation and control)? Sketch the typical 
underground distribution arrangements and the overhead distribution system. 
22) What are the major information obtained from a distribution system SCADA? Show a block 
diagram of the major components of a SCADA (system supervisory control & data acquisition). 
Sketch a diagram to show a typical automated distribution system with power and 
communication lines. 
23) What are the basic modules in a PLC (programmable logic controller) system? Sketch a 
front plate of 2 of the basic modules. Sketch a block diagram showing the interrelation of the 
major modules. 
24) A solved problem regarding constants of overhead conductors? 
25) A solved problem regarding constants of underground cables? 
26) A solved problem regarding reflected & refracted powers at a conductor/cable junction? 
27) A solved problem regarding power transformer protection? 
Lesson summary
References
1) How would EPR (ethylene propylene rubber) cables, up to 35 KV, be classified? 
The classification of EPR (up to 35KV) cables is as follows: the voltage class, the conductor 
material/size (which is function of the normal/overload/short circuit current values and the 
installation method/configuration), the insulation thickness (whether 100% or 133%), jacketed 
or unjacketed, neutral size (either full or 1/3 rating), cable in conduit configuration/direct buried 
or concrete encased conduits. 
2) How would underground XLPE (cross linked polyethylene) cables classified? 
The classification of XLPE (up to 46KV) cables is as follows: the voltage class, the conductor 
material/size, insulation thickness, jacketed or unjacketed, neutral (concentric neutral and rating 
full or 1/3 main conductor) or shielded (Cu tape), single or 3­conductor cables, jacket­type 
(whether encapsulated or sleeved), the use of strand­fill or water blocking agent between the 
insulation and jacket. 
3) What are the defining parameters of cables? 
The defining parameters can be classified broadly into dimensional, insulation material 
properties and current carrying capacity. For dimensional parameters, conductor size/number of 
strands/type of strands, diameter over conductor, diameter over insulation, diameter over 
insulation screen, number and size of neutral conductors or tape details (thickness, width & lap 
type) and diameter over the jacket are the defining data. Other important data are: weight/1000 
ft length, size of reels and length/reel. The insulation/jacket defining parameters are: before and 
after aging tensile strength and elongation, hot creep elongation/set, dielectric constant, 
capacitance (SIC) during and after the stability period, insulation resistance constant, water 
absorption properties. The last set of defining parameters are the current levels at the nominal 
voltage under the different operating conditions which are function of: the layout and proximity 
of current carrying cables, the method of laying/pulling of cables, provision of future additional 
loads with their corresponding maximum allowable voltage drop and finally the maximum 
acceptable temperature rise & duration for the cable insulating material. 
4) What are the factory and site tests to be performed on cables? 
The different types of tests that are performed on cables at the factory are: partial discharge, DC 
resistance of central conductor, AC high voltage dielectric withstandability, DC high voltage 
withstandability, insulation resistance, physical dimensions of cable components, cold bend, low 
temperature impact, jacket integrity, water penetration and high temperature drip test for the 
strand fill (if applicable). For conductor shield the tests are: volume resistivity, elongation at 
rupture, void and protrusions, irregularities verification. For the insulation are: tensile strength 
(aged and unaged)/elongation at rupture (aged and unaged)/dissipation factor (or power 
factor)/hot creep (elongation and set)/voids and contamination/solvent extraction (if applicable). 
For the insulation shield are: volume resistivity/elongation at rupture/void and protrusions 
irregularities/strippability at room temperature and at ­25C/water boil test. For the jacket are: 
tensile strength, elongation at rupture (aged and unaged), absorption coefficient (of water), heat 
shock and distortion. On the cable the following tests may be performed: structural stability and 
insulation shrink back for certain insulation materials. The tests performed on site are: visual 
inspection, size/ratings verification and D.C. withstandability tests at voltage level below those 
used in the factory. 
5) What are the defining parameters for low voltage secondary cables? 
The defining parameters for l.v. secondary cables are: material of phase conductor, number of 
strands, class of strand, type of conductor (ie. concentric, compact or compressed), conductor 
size, insulation thickness, over all diameter per cable, overall diameter per assembly (ie. triplex 
or quadruplex), the neutral conductor size (equal to the phase or reduced), if applicable, 
insulation and jacket materials, jacket thickness and the weight per assembly per 1000 ft length. 
6) What are the different types of transformers found in distribution systems? 
The different types of transformers found in distribution systems are: Power (up to 10MVA) 
liquid filled (oil), power (over 10 up to 100 MVA) oil filled with radiators/fans (one or 2 sets), 
single phase distribution transformers/oil filled (with or without radiators/fans) up to 500 KVA, 
three phase distribution transformers/oil filled (with or without radiators/fans) up to 1.5MVA, 
dry type power transformers/3 phase 300 KVA to 2MVA or silicone filled or epoxy resin 
insulated for indoor installations. All oil filled transformers are installed outdoor unless a 
special layout with fire proof (resisting) material and appropriate barriers are used, then indoor 
installation is possible. Distribution transformers can be of the pole mounted, vault or 
padmounted type. The primary voltage of power transformers can be as high as 750 KV, though 
the most common are 345KV, 220KV, 115KV, for distribution transformers as high as 72KV 
though the most common are 34.5, 25KV (27.6KV), 15KV. 
7) What are the different types of overhead switches, padmounted switchgear and those of 
lightninig arresters? 
The different types of overhead switches are: either single or three phase, either manually 
operated or electric/manual operated, either local control or remote/local control, oil insulated 
or air or SF6. The different types of padmounted switchgear are: either manually or 
manually/motor operated, controlled locally or locally/remotely, air or oil or SF6/vacuum 
insulated, protective devices are either fuses or electronic devices. The configuration will, 
generally, have four compartments with any combination of fuse or interrupter, switch, solid or 
empty compartment. The different types of lightning arresters are: station, intermediate, 
distribution (heavy duty, normal or light duty) and may be riserpole type. 
8) What are the standards that govern distribution transformers? How are distribution 
transformers defined? 
The standards that govern distribution transformers are: CSA "Single phase & three phase 
distribution transformers" Std. C2, CSA "Dry type transformers" C9, CSA "Guide for loading 
Dry­type distribution and power transformers" C9.1 and CSA "Insulating oil" C50. The 
distribution transformers are defined as follows: the voltage ratings (insulation class level of 
primary ­h.v.­ winding, the primary and secondary windings rated voltage), short circuit 
capability for a fault on the bushings of the transformer (current value and its corresponding 
duration), dielectric test values (applied voltage for 1 minute, full wave and chopped BIL and 
time to flash over for the chopped), outdoor transformer bushings ratings (defined by their 
insulation class, 60HZ 1 minute/dry, 10 second/wet dielectric withstandability, the full wave and 
chopped BIL), audible sound levels and induced voltage tests. 
9) How are wooden and concrete poles defined? 
The wooden poles are defined as follows: the class (1 to 7­4500LB to 1200 minimum horizontal 
breaking load when applied 2 ft. from pole top), the minimum circumference at pole top level 
(27" to 15"), length of pole (25 to 110 ft, generally), minimum circumference at the ground level 
(distance from butt), the wood species (Western Red Cedar, Southern Yellow Pine, Douglas Fir, 
Western Larch), the treatment against attack from fungi and insects (eg. creosote oil, ammonical 
copper fatty acid, pentachlorphenol or chromated copper arsenates) and the weight per pole. 
The concrete poles are defined accordingly: ultimate load (class A to J, 600 LB to 4500 LB, 
respectively), the length, the manufacturing process (regular or prestressed class), the steel 
reinforcing rods (cage) tensile strength, the diameter, the raceway diameter, spacing and 
diameter of holes in the pole, grounding bars (galvanized or coated) surface treatment. 
10) What are the different applications of oil switches and what are their defining 
parameters? 
The different applications of overhead oil switches in utility distribution systems are: general 
purpose for inductive and resistive loads & capacitor (capacitive current switching). The 
defining parameters are: the rated maximum voltage, the basic impulse level, the dielectric 
withstand, continuous current, inductive load switching, capacitive switching current, making 
current, momentary current, short time current rating; for the control circuit: nominal and range 
of operating voltage, trip coil current. The weight, dimensions, oil volume and speed of 
operation for the switch are also important defining data. The other two devices that may use oil 
as the switching medium are the sectionalizes and reclosers. 
11) How are overhead air switches classified? 
The following is the classification of the air insulated switches according to their breaking type: 
side break switches, vertical break and double break. The different types of mountings for such 
switches are: upright, vertical, triangular, tiered outboard mounting and pedestal. The insulators 
of the switch may be epoxy or porcelain, the base is insulated or steel. 
12) How are padmounted switchgear defined? 
Padmounted switchgear can be defined (specified) accordingly: the insulating material used i.e. 
air insulated, oil or gas, the nominal voltage class, maximum operating voltage, the basic 
impulse level, the current ratings for the different sides i.e. continuous current, load interruption 
(resistive, inductive including no load transformer magnetizing and capacitive including cable 
charging), momentary, fault close, the dimensions of the gear, the opening for the cable entry, 
properties of steel work (like thickness ­gauge, surface treatment and finish), the weight and the 
assembly voltage withstandability tests (A.C. and D.C.). The speed of operation (current time 
curves) for the fuses or protective devices had to be specified. 
13) What are the important parameters by which lightning arresters are defined? 
The important parameters by which L.A. are defined are: duty cycle voltage, impulse test crest 
voltage, power frequency voltage (dry and wet ­ for outdoor installations), impulse current 
rating, maximum continuous operating voltage, switching surges capability, high current/short 
time and low current/long duration rating, material of housing, design of internals ie. gapped or 
gapless elements (non­linear resistance material).
14) How would copper conductors be defined? 
The construction of copper conductors is defined as follows: cross section area, class of 
conductor (indication of degree of flexibility), number of wires, diameter of wire, tensile 
strength, elongation, diameter of conductor, type (concentric lays, compact or compressed) and 
weight per 1000 ft. 
15) How would ACSR (aluminum conductor steel reinforced) and ASC (aluminum 
stranded conductor) be defined? 
The defining parameters for aluminium conductor steel reinforced designs are: the Al area, the 
total conductor area, steel/Al area ratio, number of Al wires, diameter of Al wire, area of steel 
wire, diameter of steel wire, diameter of core (steel), diameter of conductor, tensile strength, 
AWG size, total conductor weight per 1000 ft. and the ratio of Al weight to the total weight. The 
defining parameters for aluminium stranded conductors are: the aluminum conductor area, the 
quantity (number) of Al wires, diameter of each wire, the diameter of the conductor, the tensile 
strength, the elongation and the total weight of conductor per 1000 ft. 
16) How would AASC (aluminum alloy stranded conductor) and self­dampening/compact 
ACSR be defined? 
The defining parameters for Aluminium alloy stranded conductors are: Al alloy area and the 
equivalent Al area, number of Al alloy wire, diameter per wire, overall diameter of conductor, 
AWG/KCMIL, weight/1000 ft, tensile strength and elongation. The defining parameters for self­
dampening conductors and compact ACSR are: aluminium area, total conductor area, steel to Al 
area (ratio), number of Al wires, number of steel wires, core (steel) diameter, overall conductor 
diameter, conductor weight/1000 ft length, ratio of Al weight to total weight, tensile strength 
and elongation. 
17) What are the different types of cable splices and terminations? 
The different types of cable splices are: tapped, heat shrinkable and cold shrinkable. The major 
components of a splice are: cable adapters, splice housing, conductor contact, conductive insert, 
retaining rings/tube, interference fit and grounding eye. The different types of cable 
terminations are: the fully taped, moulded stress cone and tape, one piece moulded cable 
termination, porcelain terminators, heat shrinkables and potheads. 
18) What are the different types of connectors and elbows? 
The different types of connectors are: the mechanical (for Al and/or Cu conductors), the 
compression, the wedge (to connect main conductors to taps), hot line clamps (the main 
overhead to equipment connection) and the stirrups (wedged or bolted). The two types of 
separable connectors (elbows) are the dead break and load break. The major components of 
elbows are: the connector, the moulded insulating body, cable adapter, the test point, the semi­
conducing shield, semi­conducting insert, grounding tabs the pulling eye, the probe (for load 
break, it is field replaceable with abelative material arc follower). 
19) What are the design tests performed on the separable connectors? 
The design tests performed on the elbows are: partial discharge inception and extinction levels 
(corona), withstand power frequency voltage capability (a.c. and d.c.), impulse voltage 
withstand level, short time current rating, switching test, fault closure rating, current cycling for 
insulated and uninsulated connectors, cable pullout from elbow (connector), operating force, 
pulling eye operation, test point cap pulling test, shielding test, interchangeability, accelerated 
thermal and sealing life, test point capacitance (voltage presence indication) test. 
20) What are the different types of insulators, their material and characteristics? 
The different types of insulators are: the pin, the suspension and the post (vertical and 
horizontal). The different insulators materials are: porcelain, glass, fibreglass, polymer and 
silicone. The properties of insulators can be broadly classified into: mechanical, electrical, 
environmental and maintenance. The mechanical can further be classified into: different loads 
the insulators is subjected to due to weights of supported components, short circuit, ice, etc. 
(normal, design, cyclic, torsional, overloads ­ exceptional), safety factors, single or multiple 
insulator assemblies and aging effect on strength of insulator. The electrical parameters defining 
the insulators are: BIL, power frequency withstandability (dry, wet and flashover level), leakage 
distance, power arcs effect, performance under steep front voltage wave, clearances and 
performance under contamination. The environmental characteristics can be further broke down 
into: insulator ageing under ultra­violet rays and dry arcing, type of contamination, radio 
interference voltage, washing requirements, corrosive environments and temperature range. 
21) What are the functions of DAC (distribution automation and control)? Sketch the 
typical underground distribution arrangements and the overhead distribution system. 
Distribution automation and control functions can be classified into: load management, real 
time operational management and remote metering. The first function may be subclassified into: 
discretionary load switching, peak load pricing, load shedding and cold load pick­up. The 
second function is subclassified into: load reconfiguration, voltage regulation, transformer load 
management, feeder load management, capacitor control, fault indication/location/isolation, 
system analysis/studies, state/condition monitoring and remote connect/disconnect of services. 
Fig. 4 shows the underground arrangements and fig. 5 shows the typical overhead system.
22) What are the major information obtained from a distribution system SCADA? Show a 
block diagram of the major components of a SCADA (system supervisory control & data 
acquisition). Sketch a diagram to show a typical automated distribution system with power 
and communication lines. 
The major information obtained from a SCADA in a power distribution system are: indications 
(eg. state change like opening or closing of circuit breakers, load break switches, reclosures, 
disconnects, operation of a relay or fault indicators) of events or alarms, levels (eg. oil level, tap 
changer position, reading from pressure gauges), pulses (eg. energy meter counters), 
measurands (eg. current, voltage, power reading, temperature of oil or windings, leakage 
current). Fig. 6 shows a typical SCADA and fig. 7 shows a single line for an automated system. 
23) What are the basic modules in a PLC (programmable logic controller) system? Sketch 
a front plate of 2 of the basic modules. Sketch a block diagram showing the interrelation of 
the major modules. 
The basic modules of a PLC system are: the processor, the input/output (they can further be 
classified into digital and analog), process control (proportional/integral/derivative), stepper 
motor, interface modules (they can be further classified into: local and remote, local and remote 
transfer, network, network transfer, multimedia network interface, peripheral devices (they 
include loader/monitor, process control stations, CRT programmers, hand held programmers, 
tape loader). Fig. 8 shows the front plates of the local and remote interface units, fig. 9 shows a 
typical block diagram including the racks, interface/ input/ output/ network interface modules. 
24)For an overhead conductor with size = 556.5 MCM, aluminum core with 19 strands 
and operating voltage of 25 KV, calculate the reactance at 60 c/s and 50HZ per 1000 ft, the 
resistance (AL1350) per 1000 ft, the capacitance, charging current/1000ft and surge 
impedance. 
Given: Conductor details: 556.5 MCM/19 strands/Al 1359. 
Nominal voltage: 25 KV, frequency: 60 & 50 c/s, length 1000 ft, conductor diameter: .855" 
(from tables), area: .437 inch2 (from tables or 7.854(1000)(556.5)/(10+7) = .437 in.2) 
L = (2)/(10+7)[ln(d/r')] H/m = (2/10+7)ln 12(2)/.855(.7788) (at 1 ft spacing) 
L= 7.17(1000)/3.28(10+6) = 2185/10000000 H/1000ft. 
XL = 2 pi 60 L = .082 OHM @ 60 c/s and XL = .068 OHM @ 50 c/s , where pi=3.141592654
R = .0927 microOHM ft (1000)/.437/(12)(12) = .0305 ­ ignoring skin effect, taking into account 
approximate skin effect then R = .0305(1.15) = .035 OHM 
C = 1/ (10+9)(18)(ln d/r)F/m = 1/ (10+9)(18)(ln 12/.855/2) = .0166/10+9 
C = .0166(1000)/3.28(10+9) F/1000ft = 5.08(10­9) farad/1000ft 
XC = 1/2 pi f C = 5.22 (10+5) OHM, 

charging current = 25000/1.732(5.2)(10+5) = .028 amp/1000ft 
Z = surge impedance under these conditions = (L/C).5)= 207 OHM 
25) For an underground XLPE cable, size = 250 MCM, aluminum 1350 core with 37 
strands and operating on 25 KV system, calculate the reactance at 60 & 50 HZ per 1000 ft, 
resistance per 1000 ft, capacitance, surge impedance, charging current/1000 ft, speed of 
propagation of the wave and the insulation resistance. 
Given: cable data: 250 MCM, XLPE, AL1350, 37 strands, 25 KV, 1000 ft length, conductor 
dia.: .575 in, area = .196 in2), dia. over insulation: 1.16 ", e = 3.5, where e is the dielectric 
constant 
L = (2/10+7)[ln 12(2)/(.575)(.7788) = 2427/(10+7) H/1000 ft at 1 ft spacing 
XL = .092 OHM @ 60 c/s and .076 OHM @ 50 c/s 
R/1000 ft = .0927(1000)(144)/.196 = .068 OHM (1.15) = .078 OHM 
C = 3.5/)10+9)(18)(ln 1.16/.575) = .277/(10 )F/m(1000)/3.28 = 84/(10+9) F/1000ft 
L at insulation neutral or sheath = 2 ln 1.16/.575(.7788)/(10+7) = 2 (10­7) H/m 
Z = surge impedance = (L/C).5) = 27 OHM, XC = 1/2 pi C 60 = 31578 OHM/1000ft 
Charging current for 1000 ft cable length =(25000/1.732)(31578) = .46 amp. 
v = speed of propagation = (1)/(LC).5) = 1.34(10+8) m/sec. 
Volumetric insulation resistance = (ra) (ln 1.16/.575)/(2pl)(12)(2.54), where ra is the resistivity 
or specific resistance of the dielectric 
assume ra = 6(10+14), Rvolumetric = 6(10+14)(.7)/191511 = 2193 MegaOHM/1000 ft. 
26) If the overhead conductor and the underground cable of problems 24 & 25 are 
connected in series and a voltage wave of 25 KV is travelling through the overhead portion, 
calculate the reflected and refracted powers at the junction point. 
Zline = 207, Zcable = 27, KV = 25 
reflacted voltage = (27­207)25/1.732(207+27) = ­11.1 KV 
refracted voltage = (2)(27)(25)/1.732(207+27) = 3.33 KV 
refracted power = 3 (Vph)(Vph)/Zcable = 3(3.33)(3.33)/27 = 1232 KW 
reflected power = 3(­11.1)(­11.1)/207 = 1785 KW 
27) Provide the differential and gas accumulation/sudden release protection to a 100 MVA 
power transformer, 220/25KV with +/­16% tap changer. Assume that the available relays 
have a pick­up setting between 20­50% of relay rating with an adjustable slope of 20­50% 
and another with fixed slope and restrained pick­up between 20 and 50% and 
unrestrained pick­up of 8, 13, 20 x relay nominal current. The pressure gas relays have two 
settings, for the trip 5.2 ­ 17.2 KPa and for the alarm 200­400 CC. The tap changer gas 
pressure trip can be set between 35­390 KPa. 
I excitation = 5% of full load primary, C.T. error = 2.5%, relay rating = 5A, C.T. primary 
current = 1.5 x full load current of transformer. 
I primary = 100 (1000)/(220)(1.732) = 262 A 
I secondary = 262 x 220/25 = 2300 A 
Using a 1200/800/200:5A C.T. on the primary side (the C.Ts are delta connected), 3500 : 5A 
C.T. on secondary side (the C.Ts are wye connected) of the power transformer. Turns ratio of 
C.T. on primary winding = 800/5 = 160, on secondary = 3500/5 = 700. Relay current due to 
primary C.T. at f.l. = (262/160) 1.732 = 2.8 amp, relay current due to secondary C.T. at f.l. = 
2300/700 = 3.28 amp, relay current ratio = 3.28/2.8 = 1.17. Mismatch at midpoint changer and 
full load = 17%. 
At 220 + 16% = 255KV tap, maintaining secondary voltage at 25KV, primary full load current 
= 100 (1000)/255 (1.732) = 226 amp, relay current = 226/160(1.732) = 2.45amp.,voltage of 25 
KV on the secondary while primary = 220 ­ 16 % = 185 KV primary full load current = 
100(1000)/185(1.732) = 312 amp., relay current = 312/160 (1.732) = 3.4 A 
Mismatch for + 16% = 3.28/2.45, mismatch for ­16% = 3.28/3.4 which are 34 % and ­4 %, 
respectively. The maximum mismatch = 34 %, add 6 % as safety margin. Thus the slope 
adjustment = 40 % (range is 20 to 50 %). The pick­up level under full load current = 
inacccuracies + esciting current + allowance for the limited restraint at emergency load through 
currents = 2.5(5/100) + (1.732)(5(262)/160)(100) + (3.28­2.45) = .125 + .14 + .83 = 1.1 amp, the 
pick­up setting = 40%(5) = 2 A (range 20 to 50 %). 
The unrestrained instantaneous triping current = 13 x 5 = 65 amp. secondary relay current. 

VERIFICATIONS: 

• Assuming a 100 MVAbase and 220/25 KVbase, Ibase (@ primary side) = 100/1.732)(220) = 
262 amp., Ibase (@ secondary side) = 2300 amp. 
• Assuming an infinite source, 11% impedance transformer, a 3­phase fault on the secondary of 
the transformer beyond the differential protection zone will produce 9 p.u. fault current (1/.11), 
Iprimary = 2358 amp., Isec. = 20700 amp. The current from the primary side into the relay = 
(1.732)2358/160 25.5 amp., from the secondary side = 20700//700 = 29.6 amp. A mismatch of 
29.6/25.5 = 16 %. 
• Assuming the tap changer to be at 220KV + 16% = 255 KV and the impedance = 14%, the short 
circuit fault current of a 3­phase fault = 1/.14 = 7.16 p.u., full load primary current = 232 amp., 
SCC on the primary side = 1661 A, SCC on the secondary side = 16468 A, relay current from 
primary side = 1661(1.732)/160 = 18 A, relay current from the secondary side = 16468/700 = 
23.5, the mismatch = 30%. 
• Assuming the tap changer at 220 KV ­ 16% = 185 KV and the impedance = 8%, a 3­phase fault 
current = 1/.08 = 12.5 p.u., primary current = 312 A, SCC on primary side = 3900 A, SCC on 
secondary side = 28750 A, relay current from prim. side = 42.2 A, relay current from sec. side = 
41.1 A, mismatch = 3% 
GAS RELAYS: 
Main tank alarm = 200 cc, main tank trip = 17 KPa above static head at relay level, tap changer trip = 
100 KPa. 

SUMMARY: 
In this chapter, the defining parameters, classifications, tests and typical configurations of distribution 
systems components were presented. The general properties of medium voltage EPR & XLPE cables 
were given plus factory & site tests. For low voltage secondary cables, the defining parameters were 
listed. For transformers, a broad classification was given. The defining parameters and the CSA 
standards that govern the ratings, design, manufacturing and testing of distribution transformers were 
presented. Other components found in overhead and underground distribution systems were covered 
from their types and defining parameters point of view. These components are: lightning arresters, 
conductors, terminations, splices, connectors, elbows and insulators. Distribution systems automation 
and SCADA were presented by covering the functions and data collected from such systems. Typical 
systems were given to clarify this topic. The major modules found in a typical PLC (programmable 
logic controllers) installation were presented. The numerical examples at the end of this chapter showed 
how the line and cable constants (inductance, capacitance, resistance, inductive/capacitive reactances, 
surge impedance, charging current and propagation speed) and the effect of the surge impedance on 
travelling waves are calculated. They also demonstrated a method to select/adjust/verify the settings of 
relays (differential & gas) used in the protection of power transformers. 

REFERENCES: 
1. Wildi, T "Electrotechnique", Les Presses de l'Université Laval. 
2. CSA, "Canadian Electricity Code", Part 1, std C22.1. 
3. CSA, "Single phase & three phase distribution transformers", std C2. 
4. Gonen "Electric power distribution systems engineering", McGraw Hill. 
5. Kurtz, "The lineman's & cableman's Handbook", McGraw Hill. 
6. Perry, "Chemical Engineers handbook", McGraw Hill. 
7. ICEA S­66­524, "Cross linked thermosetting polyethylene insulated wire & cable for the 
transmission & distribution of electrical energy". 
8. ASTM 2.03, "Non­ferrous metal products ­ electrical conductors. 
9. Brady, "Materials handbook", Mcgraw Hill. 
10.Kheir, "Computer Programming for Power System Analysts", Kheir. 

Home page of VePi


Lesson 3: Switchgear, circuit breakers, MCCS and contactors.
1) What are the defining parameters for low voltage circuit breakers?
2) What are the defining parameters for medium voltage circuit breakers? 
3) What are the different types of interrupting media used in m.v.c.b.? What are the common 
properties for such quenching media? 
4) What are the different types of switchgear assemblies and what are the subclassification of 
each type? What are the standards governing switchgear assemblies & circuit breakers? What 
are the types of batteries found in such equipment? Give a brief description of each type. 
5) What are the defining parameters for low voltage alternating current magnetic 
contactors/starters? 
6) What are the defining parameters of l.v. combination starters? 
7) What are the defining parameters for full voltage 2­speed starters? 
8) What are the defining parameters of low voltage, reduced voltage starter units? 
9) What would a table defining the motor protection circuit breakers have as headings? 
10) What would a table defining motor protection fuses have as headings? 
11) What are the headings of a table defining m.v. controllers? 
12) What are the general properties of constructional and stainless steels? 
13)What are the different types of switchboard instruments and the different mechanisms? What 
are the defining parameters for such devices? 
14) What are the defining parameters for KWH, KVAR and solid state meters? 
15) What are the different constructions of protective relays? Give the defining parameters for 
the different types of the following relays: overcurrent, over/undervoltage, differential and 
distance. 
16) A solved problem regarding the sizing of the breaking devices of a switchgear assembly. 
Lesson summary
References
1) What are the defining parameters for low voltage circuit breakers? 
The defining parameters of low voltage circuit breakers are: the rated voltage, the circuit breaker 
current rating, symmetrical interrupting capacity (with instantaneous and delayed integral 
protective relays), close and latch rating for ½ a second, the sensors current ratio, the functions 
of protection on the integral overcurrent protective device, electrically/manually operated or 
manually only, the weight and dimensions of circuit breakers, the indicators of the integral 
protective device (if available). For electrically operated breakers, the range of operating 
voltages and currents plus the nominal values for the solenoids/motors/trip coils are important 
parameters, too. 
2) What are the defining parameters for medium voltage circuit breakers? 
The defining parameters of medium voltage circuit breakers are: the voltage ratings (nominal, 
maximum and minimum), the 3­phase MVA breaker rating, the rated current, the K factor 
(Max./Min. ratio), symmetrical interrupting ratings (at maximum, nominal and minimum 
voltage) in KA, the asymmetrical factor, the short time rating, the close and latch, the insulation 
level (power frequency, impulse level), the weight, the dimensions, the interrupting medium, the 
TRV capability, any arcing medium monitoring devices, circuit breaker closing time, tripping 
time, interrupting time, spring charging time, the control voltages (nominal and range), the 
spring charging current, close coil current requirement, the trip coil current rating and surges 
switching capabilities. 
3) What are the different types of interrupting media used in m.v.c.b.? What are the 
common properties for such quenching media? 
The interrupting media used in medium voltage circuit breakers are: air, oil SF6 and vacuum. 
The general properties of fluids used in arc extinguishing chambers in m.v. c.b. are: high 
dielectric strength of the gas or liquid, thermally and chemically stable, non­inflammable, high 
thermal conductivity, low dissociation temperature, short thermal time constant, should not 
produce conducting material during arcing. Gases used so far in m.v. c.b. can be classified into 
simple (air) or electronegative (SF6). 
4) What are the different types of switchgear assemblies and what are the subclassification 
of each type? What are the standards governing switchgear assemblies & circuit breakers? 
What are the types of batteries found in such equipment? Give a brief description of each 
type. 
The different types for switchgear assemblies are: indoor and outdoor. The subclassification for 
the indoor is: standard, sprinkler proof, arc proof, dust proof, seismic proof, metalclad 
construction vs. metal enclosed, enclosure with or without a drip hood; for the outdoor is: walk 
in, walk in with working area, walk­in double row, non­walk in with or without working area, 
enclosure for cable/bus entry or transformer throat, enclosure with thermal insulation/isle 
heaters and finally indoor cubicle design installed in an outdoor house. 
The standards that govern circuit breakers/switchgear design testing and application are: ANSI 
C37 series including .09 "Test procedure for A.C. high voltage circuit breakers rated on a 
symmetrical current basis", .04 "Rating structure for A.C. high voltage circuit breakers rated on 
a symmetrical current basis", .06 "Preferred ratings and related required capabilities for A.C. 
high voltage circuit breakers rated on a symmetrical current basis", .20 "Switchgear 
assemblies", IEC 56 "High voltage A.C. circuit breakers", IEC 60 series "High voltage test 
techniques", IEC 694 "Common clauses for high voltage switchgear and controlgear", 
C22.2#31" switchgear assemblies" and CAN3­C13 "Instrument transformers.". 
The different types of stationary batteries used in conjunction with these equipment are: lead 
acid and nickel cadmium. The first has three possibilities of positive plates which are: the 
pasted, multitubular and plante type. The negative plates will be of the pasted type, the grid for 
the plante and multitubular is made of lead antimony and that for the pasted is made of either 
lead antimony or lead calcium. The active material in the +ve plate is lead oxide and in the ­ve 
plate is sponge lead. The electrolyte is a solution of diluted sulphuric acid with specific gravity 
of approximately 1.2. For the nickel­cad batteries, the plates may be of the pocket or the sintered 
type. The active material (nickel hydrated for the +ve plate and cadmium sponge for the ­ve) is 
placed in nickel plated steel holders. The electrolyte is a solution of potassium hydroxide diluted 
in water with a specific gravity of 1.16 to 1.19 at 25 C. 
5) What are the defining parameters for low voltage alternating current magnetic 
contactors/starters? 
The defining ratings for low voltage alternating current magnetic contactors/starters are: the 
NEMA size, the voltage rating, the maximum HP for single phase and three phase motors (for 
both nonplugging/nonjogging and plugging/jogging applications), the continuous current rating 
of the contactor/starter, the service limit, transformer switching capability rating for single and 
three phase applications, the capacitive switching capability (in volt and KVAR), the 
dimensions, the weights, the overload protective element type and rating. 
6) What are the defining parameters of l.v. combination starters? 
The defining parameters of low full voltage combination starter units: the starter size, the 
maximum motor HP at the different standard voltages (200v, 230, 460 and 575v), whether the 
unit is reversing or non­reversing, the fuse or circuit breaker size (used as a protection against 
short circuit or protection/load break device), the size of the unit in inches or space factor, the 
weight of the unit, method of attachment to riser bus bars of MCC (bolt­on or plug in) and size 
plus type of motor overload protection element/relay. 
7) What are the defining parameters for full voltage 2­speed starters? 
The defining parameters for full voltage 2­speed starter units are: the starter size, the HP 
(maximum) at the different nominal voltages, the circuit breaker or fuse size for the short circuit 
protection, the dimension in inches or space factor for the 1­winding and 2­winding motor 
starter unit, unit weight, method of attachment to MCC and the type plus size of o/c protection 
device. 
8) What are the defining parameters of low voltage, reduced voltage starter units? 
The defining parameters of low voltage reduce voltage starter units (applicable to part winding 
and auto­transformer units): the starter size, the maximum motor HP at the different rated 
voltages, the circuit breaker or fuse rating, the dimensions or space factor for the units, the 
weight, the size plus type of the o/l element, the installation method in the MCC. 
9) What would a table defining the motor protection circuit breakers have as headings? 
The table will have the following headings: 3­phase motor HP, the motor full load current at the 
different nominal voltages, the circuit breaker continuous current, the different adjustments (eg. 
7x/11x/13x), the weight and dimension, the adjustable range. 
10) What would a table defining motor protection fuses have as headings? 
The fuses for motor protection table will have the following: the maximum motor HP rating, the 
motor full load current rating, the fuse size for the different voltage classes, the fuse type (50KA 
interrupting fuse, HRC­200 KA I.c., code fuse ­ 10KA or size L over 600a ­ 200KA), the fuse 
weight. 
11) What are the headings of a table defining m.v. controllers? 
The table for a medium voltage controller (contactor and fuse) will have the following headings: 
the contactor maximum continuous current, the interrupting capacity (at the specified KV), the 
designation, the voltage rating and range, the interrupting capacity of the fuse (in KA and MVA 
@ the rated voltage), the maximum HP motor rating for the motor design/p.f./voltage/controller 
current rating, the dielectric withstand voltage, the controller ­type (full voltage, reversing vs 
non­reversing, reduced voltage ­ auto transformer vs reactor). The m.v. fuses for controllers can 
be defined when the following values are given: the motor locked rotor current, motor full load 
current x service factor, the maximum continuous current rating of the fuse inside the 
compartment, the fuse size, the peak current let through characteristics. 
12) What are the general properties of constructional and stainless steels? 
The mechanical properties of constructional steels are: the ASTM designations, the thickness 
range, yield point, elongation as a percent of the length (eg. in 8 inches), tensile strength and 
weldability. Those for stainless steel are: A1SI designation, condition, .2% yield point, 
elongation in 2 inches length, tensile strength and area reduction. 
13)What are the different types of switchboard instruments and the different 
mechanisms? What are the defining parameters for such devices? 
The different types of switchboard instruments: voltmeters, wattmeters (single phase and 
polyphase), varmeters, power factor meters, frequency meters, ammeters. The different 
mechanisms are: taut band suspension, repulsion vane, electrodynamic, D'Arsonval/zener diode. 
The defining parameters: impedance, input resistance, inductance, voltampere/W/RVA/p.f. of 
mechanism (burden), mechanism type (self­contained or transformer), instrument transformer 
ratio, scale and units/scale division. 
14) What are the defining parameters for KWH, KVAR and solid state meters? 
The defining parameters of KWH meters are: type of meter and number of elements, connection 
method, weight/dimension, burden data for each type/elements number (phase, potential circuit 
and current circuit), KVA attachment data (meter, volt, scale/multiplier, amp range), disk 
constant­WH/disk revolution, register ratio. Those for KVAR are: burden (potential and current 
circuits), weight and dimensions (for the different designs), temperature rise, ratings and 
enclosures for the different types/numbers of elements. Those for solid state meters are: 
potential input ratings (input voltage, impedance, burden, overload capability, current input 
ratings (burden, input current and impedance, overload), weight & dimensions, control power 
requirements, communication capability (protocol, baud rate, standards), measured parameters 
(measurands). 
15) What are the different constructions of protective relays? Give the defining 
parameters for the different types of the following relays: overcurrent, over/undervoltage, 
differential and distance. 
Relays can be classified based on their construction into electromechanical (magnetic induction, 
magnetic attraction, thermal and D'Arsonval), solid state and microprocessor/digital based. 
The defining parameters for electromechanical based o/c relays are: weight and dimensions, 
type of relay time current characteristics curves (inverse definite minimum time, short time, 
very inverse, extremely inverse), current tap range, time dial range, operating time, burden and 
thermal ratings (continuous current, 1 sec. rating and power factor, at tap setting, at 3 times tap, 
at 10 times tap and at 20 times tap). Those for o/c solid state relays are: weight and dimensions, 
current rating, frequency, d.c. supply voltage and burden, burden on C.T., setting range for the 
instantaneous and time delay functions, time multiplier setting, operating times for time delay 
and instantaneous functions. The parameters for the microprocessor based are: weight and 
dimensions, rated current, setting range, rated current for the ground fault unit and the setting 
range, operating times, burden, overload capacity, control power voltage and burden, resetting 
times and contacts ratings. 
The defining parameters for the over/undervoltage electromechanical relays are: the weight and 
dimensions, the continuous input voltage rating, the short time (eg. 2 minute) voltage rating, the 
taps' range, burden, time dial range. Those, for the solid state are: weight and dimension, input 
voltage ratings, pick­up range, drop­out setting range, time delay setting (pick­up and drop­ out), 
control (auxiliary) supply voltage and range. 
The defining parameters for a electromechanical differential relays are: the weight and 
dimensions, the application i.e. transformer differential or motor or generator differential 
protection, number of phases i.e. single or three phase, number of operate and restraint circuits, 
minimum trip current, burden, operating time, type i.e. fixed or variable percentage (biased) 
relay, current inputs.
The defining parameters for solid state percentage (biased) relays with instantaneous tripping 
and harmonics restraint: weight and dimensions including interposing relays (if any), the 
currents input, overload capacity, frequency, interposing C.T. ratio (if any), burden, operating 
current, restraint current settings, unrestrained current setting range, operate time, reset ratio, 
order of harmonics restrained i.e. 2nd or 5th, auxiliary power voltage and power consumption, 
burden of operating and restraint circuits. 
The defining parameters for the electromechanical distance relays are: the weight and 
dimensions, characteristics type i.e. impedance/reactance/admittance/angle impedance 
(OHM)/offset MHO/modified impedance/complex/elliptical/quadrilateral, relay reach, taps, 
variation in reach and maximum torque angle over the range of taps, burden on instrument 
transformers. Those for solid state relays, the parameters are: weight and dimensions, input 
circuits, burden, control voltage and consumption, characteristics torque (angle), reset ratio. 
16) A unit substation is connected to the utility line through a 25KV circuit breaker which 
feeds a 5 MVA transformer, 5% impedance 3­phase, 25KV/600v. The low voltage winding 
of the transformer is connected through a 600v main breaker to a low voltage switchgear. 
The switchgear has 3 circuit breakers feeding each a 400 HP motor, .25 reactance, 1800 
RPM. A fourth circuit breaker is feeding a 750 KVA, 4.5% impedance 600/208v and the 
last breaker in this lineup feeds the other 600/347v loads (2 MVA). For a fault (L­L­L) on 
the main bus, calculate the fault current with and without motor contribution and give the 
contribution of each motor. Calculate also the motor breaker fault current for a fault on 
the motor terminals. Assume on infinite source. Give the breakers' size on the low voltage 
side of transformer, give a typical unit substation layout.

MVAbase = 5, KVbase (primary side of power transformer) = 25, KVbase (secondary side) = .6, 
Ibase = 5 (1000)/1.732(.6) = 4811 amp= full load current. Full load current on primary side = 
4811(600)/25000 = 115 amp. Fault current for 3­phase fault on main bus = 1/.05 = 20 p.u. = 
20(4811) =96 KA (from suply side). 
Xmotor = .25 (5000/350) = 3.5 p.u. (assuming motor p.f. = .85) 
3 motors cotribution for a 3­phase fault on main bus = 1/1.16 = .85 p.u. = .85(4811 = 4089 amp. 
Total fault current = 96 + 4 = 100 KA 
Contribution per motor = .283 (4811) = 1370 amp. 
For L­L­L fault on motor terminals, the fault current through the motor breaker = 2(1.37) + 96 = 
98.7 KA. 
Motor full load current = 400(746)/1.732(.85)(.9)(600) = 375 amp. (assuming a motor efficiency 
of .9) 
F.L. current to 750 KVA transformer = 750 (1000)/1.732(600) = 722 amp. 
F.L. current to the 2 MVA load = 2000/1.732(.6) = 1924 amp. 
For the main low voltage circuit breaker: 
Continuous curent (frame size) = 5000 amp., I.C. = 120 KA 
For the motors circuit breakers (fused or current limiting): 
Continuous current = 800 Amp, I.C. = 100 KA , Sensors ratio + 400/5 amp. 
For the 750 KVA transformer (fused or current limiting): 
Continuous current = 1600 amp., I.C. = 100 KA, Sensor = 800/5 amp. 
For the 2 MVA load (fused or current limiting): 
Continuous current = 2000 amp., I.C. = 100 KA, Sensor = 2000/5 amp. 
Fig. 11 shows the typical layout. 

SUMMARY: 
In this chapter, circuit breakers, switchgear assemblies, starters and controllers were presented 
from the definition, standards and brief description points of view. For low voltage circuit 
breakers, the coverage included the ratings of the power and electric control circuits. For 
medium voltage circuit breakers and switchgear assemblies, the coverage included the breakers 
interrupting media, breakers ratings, governing standards, different types of switchgear 
assemblies and types of stationary batteries found in such assemblies. For l.v. starters, the 
coverage included the defining parameters for the following devices: contactors, combination 
starters (full voltage/single speed, full voltage/two speed, autotransformer/part winding reduced 
voltage), motor protection fuses and magnetic element only circuit breakers). For medium 
voltage starters, the coverage included the contactors and fuse defining parameters. Certain 
related miscellaneous topics were also covered briefly like the general properties of 
constructional & stainless steel, switchboard instruments types & mechanisms, meters defining 
parameters and relays types & defining parameters. 
The numerical example at the end of this unit clarified the selection of breakers in a 
hypothetical unit substation including the continuous current, interrupting capacity and sensors 
ratio for each breaker. 

References: 

1. Wildi, T. "Electrotechnique", Les Presses de l'Université Laval. 
2. IEEE "Recommended practice for protection & co­ordination of industrial & commercial power 
systems" std 242. 
3. CSA "Switchgear assemblies" std C22.2 no. 31. 
4. CSA "Instrument transformers" std CAN3­C13. 
5. Wadhwa, C. "Electrical power systems", Wiley. 
6. Kheir "Computer programming for power systems analysts", Kheir. 

Home page of VePi


Lesson 4: Power line disturbances.
1) What are the disturbances found in power systems?
2) What are the sources of disturbances in power systems? Sketch 4 examples for the sources of 
disturbances. 
3) What are the effects of such disturbances on the major elements of power systems? 
4) What are the indicators of the quality of power in a plant? 
5) What are the methods used to reduce these disturbances? Sketch two of the devices used in 
reducing the steady state disturbances.What are the major standards that are power quality 
related? 
6) What are the major hardware components in an office automation system? What are the 
major responsibilities of an operating system? What are the different types local area networks 
and what are the different types of transmission media used with LANs. 
7) A solved problem regarding the effect of applying capacitors in improving the power factor of 
a circuit.
8) A solved problem regarding the quantification of lightning strokes.
Lesson summary
References
1)What are the disturbances found in power systems? 
Disturbances found in power lines can be classified into steady state and transients. Steady state 
can further be classified into harmonics and voltage notching. The transients disturbances can 
be further classified into: brown outs (undervoltage), overvoltage, sags, surges, frequency 
variations, power line noise, radio frequency interference. 
2) What are the sources of disturbances in power systems? Sketch 4 examples for the 
sources of disturbances. 
The sources of steady state and/or transient disturbances originate from outside the premises as 
well from inside. The sources can be classified broadly into environmental (eg. lightning), 
operational (eg. switching), failure (eg. arcing grounds) conditions. The sources of steady state 
disturbances can be arc furnaces, welders, saturable reactors, rectifiers, thyristor controlled 
loads, variable voltage/frequency drives, uninterruptable power supply, magnetizing currents. 
The sources for transient disturbances can be inductive/capacitive loads switching, photocopiers, 
air conditioners, motors (switching ­ starting and stopping), ballasts, light switches. Fig. 12 
shows 4 examples for sources of disturbances in power systems.
3) What are the effects of such disturbances on the major elements of power systems? 
The effects that the steady state disturbances have on the major electrical equipment are: 
_Motor and generators: at harmonic frequencies, copper and iron losses increase and 
consequently the insulation temperature. At extreme conditions, generators can hunt and motors 
are subjected to pulsating torques. 
_Transformers: operating under sustained overvoltage conditions means more copper and iron 
losses, thus overheating. Due to the non­linear characteristics of the iron core, overexciting the 
transformer will cause the steady state exciting current to increase significantly (it is the point 
on the flat portion of the voltage/exciting current curve of the core). This current is reach in 
third & fifth harmonics, thus hormonics are injected into the system. 
_Power cables: overvoltages will stress the insulation. Due to resonance conditions (between the 
cable capacitance and load inductance) from other than fundamental (high harmonics order), 
the cable may be subjected to a high resonant voltage which may starts partial discharge in the 
voids found in the insulating material The partial discharge may eventually leads to the failure 
of the cable. Harmonics may cause higher skin effect thus overheating of conductor and the 
insulation will operate continuously under higher temperatures. 
_Capacitors: at resonance frequency, higher then rated voltage may be imposed on the unit and 
higher than rated current may flow through the capacitor blowing fuses or overheating the unit. 
_Switchgear and motor control centres: overheating due to increased losses may cause a 
reduction in the insulation life. 
_Protective relaying: nuisance tripping or no tripping of electromechanical relays (due to torque 
of harmonic components), maloperation of none ­ RMS sensing (peak) solid state relays. 
_Meters and instruments: positive and negative errors are possible in electromechanical meter 
readings. 
_Electronic equipment: misoperation or erratic operation of microprocessor based and solid 
state devices when high harmonics and voltage notching are present in the circuits feeding such 
devices. 
_Circuit breakers: harmonics can cause the breaker insulation to be stressed due to overvoltage 
and current carrying parts to be operated at higher than normal temperatures. This may lead to 
failure of circuit breakers while in the closed or opened position. 
_Communications: when communication lines are in close proximity to high harmonics content 
power lines, interference may occur with data and signals transmitted on the communication 
lines, sparious system responses at the receiving end may occur. 
_Other devices like ballasts may fail, clocks and paging systems may malfunction. 
The effects of transients are: 
_Motors: may fail if subjected to prolonged period of undervoltages, overvoltages will stress the 
insulation and eventually will cause the insulation to fail. 
_Heaters and lighting: Overvoltage will cause the device to run hot and if left for a long period 
it may burn itself out. 
_Electronic devices are susceptible to noise and spikes. Failure in power supplies/boards and 
burning of chips will be the result. 
_Transformers: overvoltage for prolonged times will stress the insulation (and may eventually 
cause a failure) and will increase the harmonic (higher order) level in the system. Spikes may 
cause an insulation failure. 
_Supervisory control equipment: may malfunction from electromagnetic interference. 
4) What are the indicators of the quality of power in a plant? 
The indicators of the quality of power in the plant are: 
_The length of feeder to which the service is connected. It is importanat to know whether the 
line is an overhead or an underground one or a mix of both, if the last what is the proportionality 
of overhead to the total feeder length. If it is an overhead line, the degree of exposure to trees, 
lightninig, traffic and contaminants may indicate the quality of power to be expected. On the 
other hand, if underground cables are used the, method of laying/pulling cables may give an 
indication of the quality. The operation philosophy of the utility including fault 
indication/isolation/restoration, maintenance procedures and cables fault handling may also 
indicate the average number of failures and the duration per failure for the feeder. 
_Utility philosophy regarding the use of reclosures, sectionalizes, voltage regulators, lightning 
arresters, capacitors and the adjustments of overcurrent relays on the feeders/reclosers and fuse 
sizing. Certain components improve the quality but others may jeoperdize it or the availability 
of the power source. 
_The total number of feeders connected to the transformer station bus under normal and 
emergency situations as a fault on any feeder will affect the voltage on the station bus. 
_The site has any equipment that would pump dirty power into the system. The knowledge of 
the equipment connected to the same feeder that may cause harmonics, spikes, sags, etc..... to be 
injected into the system or superimposed on the normal voltage is important to know if power 
quality is an isue. 
5) What are the methods used to reduce these disturbances? Sketch two of the devices used 
in reducing the steady state disturbances. What are the major standards that are power 
quality related? 
The mitigation methods to produce the effects of such disturbances are: 
For steady state disturbances: shunt filters, series filters, zero sequence filter, phase 
multiplication, harmonics injection, the design of the power system, reactors or isolation 
transformer, reducing system impedance. Fig. 13 shows two types of such devices. 
For transients disturbances: built­in filters, dedicated lines/isolated grounds, regulation 
transformers, isolation transformers, saturated transformers, ferroresonant transformers, ultra 
isolation ferroresonant transformers, line conditioners, clamping devices, standby power 
sources, uninterruptable power supplies (UPS). 
The standards that are related to power quality are: ANSI/IEEE 519 "Recommended practices 
and requirements for harmonic control in electrical power systems" (formerly Guide for 
harmonic control and reactive compensation at static power converter), IEC 1004 series 
"Electromagnetic compatability" and ANSI 62 series "Surge arresters for A.C. power circuits" 
plus CSA 233 series "Surge arresters for A.C. systems". 
6) What are the major hardware components in an office automation system? What are 
the major responsibilities of an operating system? What are the different types local area 
networks and what are the different types of transmissipn media used with LANs. 
The major hardware components are: the motherboard, microprocessor (CPU), disk drives, 
monitors and adapters (they include monochrome display and adapter, colour graphics, 
enhanced colour display, video graphics array, supervideo graphics cards), keyboards, plotters, 
printers, modems and other input devices like mouse, joystick and interfaces (for SCADA 
systems or from PLC systems). The operating system is responsible for initializing the system, 
performing start­up tests, opening and copying the necessary files into memory, giving control 
to the user and software run under the operating system. Local area networks types are: 
contention type, reservation or round robin or in general can be classified into distributed or 
centralized control. The transmission media may be any of the following: twisted pair copper 
cable, co­axial cable, fiber optics or line of sight. 
7) A 20 HP motor, 575v, 3­phase, .75 p.f., .85 efficiency, calculate the capacitor rating to 
improve the power factor to .95, the increase in current flow through the motor circuit to 
other connected loads provided that the apparent power remains the same in both cases. 
Motor KW at .75 p.f. = 20(.746) = 14.9 KW 
KVA at .75 p.f. = 19.866, KVAR = [KVA2 ­ KW2].5 = 13.14 
Motor KW at .95 p.f. = 14.9 KW, KVA = 14.9/.95 = 15.68 
KVAR2 = [15.682 ­ 14.92].5 = 4.88 
KVAR1 ­ KVAR2 = 13.14 ­ 4.88 = 8.26 KVAR = capacitor rating. 
KW = [19.8662 ­ 4.882].5 = 19.25 KW 
The additional power that may be transferred due to the local capacitor = 
19.25 ­ 14.9 = 4.35 KW 
At unity p.f. the additional current = 4.35/(575)(3)/(1.732) = 4.36 amp. 
Motor f.l. current at .95 p.f. = 20(.746)/(1.732)(.95)(.85)575 = 18.5 amp. 
8) A short overhead line rated 25KV nominal and is supported on wooden poles at 40 ft 
from ground with 400KV dry BIL. Calculate the stroke current that will cause this line to 
flash over if the indirect lightning strike hits 20 ft from the phase conductor. Calculate the 
distance between the lightning arresters so that a 20KA lightning strike of 8/20 µsec will 
not cause the line to flashover. Repeat the inter L.A. distance if the wave shape assumes 
4/10 µs. 
V = 20.h.k.Ia/y; where V is the voltage that will cause a flashover = 400 KV, k = 1.2, h is the 
height of conductor from ground level = 40 ft, y is the distance of the stroke from the conductor, 
Ia is the stroke current. 
Ia = 400(20)/20(1.2)(40) = 8.33 KA 
Assume a 200 ohm line surge (characteristics) impedance, voltage build­up at point of hitting = 
Z(I)/2 = 200(20)/2 = 2000 KVpeak 
The voltage rises to peak value in 8 µs. Thus the rate of rise of this wave = 
2000/8 = 250 KV/µs. 
The insulation level of 400 KV is reached in 400/250 = 1.6µs. 
The distance between arresters = 1.6(.9)(984)/2 = 700 ft 
The distance for 4/10 µs wave = 350 ft 

SUMMARY: 
In this chapter the line disturbances were presented. The types, sources, effects on the 
equipment in the power systems and the metigation methods of steady state and transient 
disturbances were given. The indicators that may be used in evaluating or analyzing the quality 
of power to be expected at any location were listed. The standards that govern the design of the 
equipment in order to minimize their dangereous effects of pumping harmonics or causing 
voltage notches were listed. The standards that govern the protecting devices that would protect 
the equipment from the effects of such disturbances were also given. Also, the major elements 
of an office automation system were presented. These elements can generate dirty power or be 
affected (its electronic components & devices) from dirty power generated elsewhere in the 
interconnected power system. The first of the last two numerical examples showed the effect of 
the application of local capacitors with motors. Capacitors will improve the p.f. and will 
increase the capacity of the feeder circuit. The second numerical example quantified in a simple 
manner the effect of and the flashover levels of indirect and direct lightninig strokes. 

References: 
1. Greenwood, Allan "Electrical transients in power systems", Wiley. 
2. Wadhwa, C.L. "Electrical power systems", Wiley. 
3. IEEE "Recommended practice for power system analysis", std 399. 

Home page of VePi


Lesson 5: Power systems studies.
1) What are the general requirements for any power systems study?
2) What are the data required to perform TRV calculations? 
3) What are the data required to perform a stability study? 
4) What are the data required to perform fault calculations? To perform a coordination study, 
what are the required data? 
5) What are the data required to perform load flow studies? What are the iterative methods that 
may be used in the calculations? 
6) What are the required data for switching transients studies? 
7) What are the different types of motor starting studies? What are the reequired data to perform 
such studies? 
8) What are the major components in an industrial system reliability study? What are the 
required data to perform such studies and what is the outcome? 
9) What are the components of a distribution utility system?What are the required data and what 
is the outcome of such studies? 
10) What are the general data required to perform steady state and transient state stability 
calculations? 
11) What are the building blocks of an electrical power systems studies information system? 
12) A solved problem regarding the principle calculations involved when analyzing a power 
distribution system. 
13)What are the essential computer programs for the power systems analyst? 
Lesson summary
References
1) What are the general requirements for any power systems study? 
The general requirements that are common for all power systems study are: the single line 
diagram for the plant (or part of) under study, the rating/type/make for all system elements 
within the study boundaries, any available test reports or manuals and the elementary 
(schematic) or connection (wiring) diagrams. 
2) What are the data required to perform TRV calculations? 
The data required to perform a TRV study are: the effective inductances and capacitances at the 
TRV frequencies (from the nominal voltage frequency) for bushings, buses, power and 
instrument transformers near the circuit breaker to be switched; the number of lines or cables 
connected to the bus at the time of fault, their equivalent surge impedance, length, termination 
and interconnection; the type of fault, magnitude of fault current and the values contributed 
from the local sources. 
3) What are the data required to perform a stability study? 
The data required to perform a stability study are: 
_System data: impedance of lines, cables, reactors and any other series components; KVA 
rating, impedance, voltage ratings, ratio, winding connection, available taps, type of tap changer 
control and tap step size; short circuit capacity of utility supply, KVAR of capacitor banks 
(major ones); description of normal and emergency (contingency) switching arrangements. 
_Load data: real and reactive loads on all significant load buses in the system. 
_Rotating machine data: mechanical and electrical power ratings, inertia constant of all rotating 
parts, speed, active/reactive power (for generators) or speed/torque characteristics (if motor), no 
load/air gap and locked rotor characteristics curves, reactances and time constants, 
damping/excitation/governor/steam systems (if applicable) limits and time constraints for major 
synchronous machines. For minor synchronous machines, the following data would be required: 
mechanical/electrical power ratings, inertia speed and direct axis synchronous reactance. For 
major induction machines, the required data are: mechanical/electrical ratings, inertia, load­
speed­torque curves, positive and negative sequence circuit data and description of motor 
starting arrangements. For minor induction machine the required data are the 
electrical/mechanical power the sequence equivalent impedance circuit and starting 
arrangements (if any). 
_Type of disturbances to be studied for example: initial switching status, fault conditions, other 
switching operations. The limits of acceptable voltage, currents and power swings are also 
important for such studies. Protective relays data,setting and operating times/including clearing 
time of switching devices are also required to compare with the study outcome to verify the 
transient stability state for the specific operation (condition). 
4) What are the data required to perform fault calculations? To perform a coordination 
study, what are the required data? 
The data required to perform fault calculations are: the positive/negative/zero sequence 
impedances of the system under study, to achieve this requirement the following data have to be 
available: size, length and method of laying for all cables in the system under study, the 
overhead conductors size, type and configuration, transformers KVA/impedance (with its 
base)/tap changer limits and step size/impedance per tap step/primary and secondary 
voltage/method of neutral grounding and pertinent data, for the induction or synchronous 
motors: the rating/subtransient reactance/transient reactance/speed/X to R ratio, the current 
limiting reactors (if any). 
For the coordination study the following data are essential: the relays current­time 
characteristics curves, fuses total clearing time­current/minimum melting time­current 
characteristics curves, total available 3­phase short circuit current in the system, damage curves 
for cables/transformers, inrush currents to induction motors and their durations, inrush current 
for transformers and duration, relays burden data, instrument transformers 
saturation/excitation/accuracy/ratio/taps number and ratios data. 
5) What are the data required to perform load flow studies? What are the iterative 
methods that may be used in the calculations? 
The pertinent data required for load flow studies are: for generators: active (real) power and the 
maintained (constant) voltage, for loads: the real and reactive power (scheduled and constant 
over the period of the study), for the slack bus: the voltage and phase angle at the bus (both are 
kept constant over the period of the study), the admittance matrix of the modelled network (this 
will include the admittance of interconnecting power lines and the shunt branches), for the 
transformers: ratings, tap steps and number (if applicable). 
Any of the following iterative methods may be used: Gauss­Seidel, Newton­Raphson or Fast 
decoupled method. 
6) What are the required data for switching transients studies? 
The required data for switching transients studies are: 
_Utility information: series resistance and reactance, zero sequence and + ve sequence parallel 
capacitance, minimum and maximum available and future short circuit levels, maximum and 
minimum voltages and operation description/reclosing procedure. 
_Transformers data: ratings, connections, windings arrangement details, tap changers details, 
(steps, limits), leakage reactance and resistance (+ ve and zero sequence), no load voltage vs 
exciting current, base voltage/current, neutral grounding details. 
_Capacitor data: MVAR or microfarad, voltage rating, connections, neutral grounding details, 
switching device details, tunning reactors data (if applicable). 
_Cables and conductors: length, size, arrangement, conduit details, insulation/shield/sheath 
details. 
_Surge arresters: location, ratings. 
_Grounding resistors: ratings impedance. 
_Reactors: ratings, impedance (for all taps). 
_Rotating machines: regulator type (if applicable) and subtransient/transient reactances. 
_Operating modes: sequence and condition of each operation of switching devices, action of 
protective scheme against overvoltage and undervoltage. 
7) What are the different types of motor starting studies? What are the reequired data to 
perform such studies? 
The different types of motor starting studies are: voltage drop (snap shot), detailed voltage 
profile (time dependent bus voltage analysis) and motor torque/acceleration time analysis. 
The data required may vary function of the degree of the detail (the depth) of the study: utility 
and generator impedances, transformers impedance, cables sizes/number/material/conduit 
type/reactance/resistance, overhead conductors sizes/type/quantity/material/resistance and 
reactance, load type (constant impedance or apparent power or current)/power factor/load 
factor/inrush characteristics, load and motor rotating parts inertia, inertia of mechanical 
coupling or any gearing, speed torque characteristics of both motor and load, speed vs current 
and power factor curves. 
8) What are the major components in an industrial system reliability study? What are the 
required data to perform such studies and what is the outcome? 
The major components that may be included in a reliability study for an industrial system are: 
m.v. circuit breakers, m.v. disconnect switches, power or distribution transformers, underground 
cables and cable splices, cable terminations, low voltage circuit breakers, low voltage and 
medium voltage switchgear assemblies (with insulated or uninsulated bus) and utility service. 
The data required to perform a reliability study are: the failure rates (failures per year) and hours 
of downtime/failure for each equipment or component included in the study. The output has to 
be a number proportional to the forced number of hours of down time per year for the system 
under study. 
9) What are the components of a distribution utility system? What are the required data 
and what is the outcome of such studies? 
The major components that can be considered in a distribution, utility, system are: the power 
transformer in the transformer station, the high voltage disconnect switch, the medium voltage 
circuit breakers and switchgear assemblies, the insulators, the cable terminations, the overhead 
conductors/underground cables and splices, the padmounted switchgear and the distribution 
transformers. The data required to perform a reliability study for such a system are: the number 
of taps (branches) off the main feeder, the number of segments per line or tap, the length per 
segment, the exposure factor per segment, the conductor factor per segment, the upstream 
device (fuse, breaker, recloser, sectionalizer) factor for each segment and the weighted number 
of customers interrupted when the segment fails. Also, the following data are required: number 
of failures per year and number of hours per failure for each components in the system including 
the overhead and underground distribution network. The output will have two types of numbers 
one proportional to the annual interruption time and the second proportional to customer hours 
of interruption. 
10) What are the general data required to perform steady state and transient state 
stability calculations? 
For a steady state stability (i.e. before a fault condition or switching operation, for example), the 
data required are: the voltage at both buses that have the power flowing in between, the 
impedance of the line and the angle difference between the transmitting and receiving buses. 
The following data would be required to perform a transient state stability study: 
_During switching or faults: power out of generator, self­conductance of buses, transfer 
admittance between all the connected buses, angular displacement of each two adjacent buses 
(machines or infinite bus), resistance and reactance between each two connected buses, the 
generator constants (if applicable). 
_Post fault clearing: the same data as for during the fault condition. 
11) What are the building blocks of an electrical power systems studies information 
system? 
The information system that is used to perform power systems studies must have (but not limited 
to): reliability data (failures and hours/failure for different equipment, typical reactance values 
for induction and synchronous machines, resistance and reactance values of Copper and 
Aluminum conductors, reactance values of typical 3­phase cable circuits in different conduit 
materials, X/R ratio of transformers/ S.C.I.M./ synchronous machines, capacitance values 
(lumped) for power transformers/bushings/generator armature/instrument transformers, 
allowable ampacities and correction factors for burried and in air cables, properties of cross 
linked polyethylene and ethylene propylene rubber insulated cables, properties of Teck and l.v. 
(secondary) cables, general properties of XLPE/EPR/PVC, typical dimensions of pole 
mounted/low profile padmounted/padmounted (for radial and loop applications)/liquid filled 
and dry type transformers, transformer ratings and tests performed, wooden and concrete pole 
data, oil/air/SF6 switches data, sectionalizers and reclosers data, air insulated/oil/ vacuum­SF6 
padmounted switchgear data, lightning anesters ratings, construction details and properties of 
copper and aluminium conductors, steel properties, rigid bus properties, l.v. and m.v. circuit 
breaker ratings, weights of circuit breakers, dimensions/weights of switchgear assemblies, 
control voltage/current and operating times of m.v.c.b., spacings in air for control/low 
voltage/medium voltage circuits, switchgear test voltages, maximum temperature rise for 
switchgear assemblies, metering/relaying accuracies for l.v. and m.v. instrument transformers, 
burden/accuracy limits/partial discharge test values/dielectric test values/temperature limits for 
instrument transformers ratings and burden information for switchboard instruments, 
WH/VAH/solid state meters data, data of the following relays: distance/ differential/ 
overcurrent/ overvoltage/ undervoltage/ synchrocheck/ phase sequence/ phase unbalance/ 
current balance/ negative sequence time overcurrent/ reverse power directional/ loss of 
excitation/ directional/ reclosing/ frequency/ motor protection/ feeder protection, induction 
motors data, contactors/starters/fuses/magnetic trip only circuit breakers/p.f. correction 
capacitors/exciters data and ratings. 
12) Data for hypothetical system shown in fig.14:

I­ Tr1: 2­winding transformer: 
Primary / secondary winding voltage ratings: 220 KV/25 KV, apparent power rating for each 
winding: 20 MVA (ONAN), impedance in p.u. based on above MVA: .11, X/R ratio: 20, BIL: 
900/150 KV, capacitance of H.V. winding to low voltage winding & ground with l.v. wdg 
grounded: 6000 pf, capacitance of 800 A bushing: 500 pf (line to ground), core & winding 
design: 7­legged shell & disc. 
II­ 25 KV bus duct (bd):Rated current: 
1200 A, bus material: copper, Size of bus: 1/4 " by 21/2 ", BIL: 125 KV, capacitance per phase: 
10 pf/ft, total bus length/phase: 90 ft, enclosure gauge: 11. 
III­ M.V. circuit breakers: Rated voltage:
25 KV, Min./max. volt.: 21.7/28 KV, rated continuous current: 1200 A, I.C. @ nominal voltage: 
23 KA, BIL: 125 KV, close & latch: 60 KA, interrupting time: 5 cycles, spring charging voltage 
range: 90­130 V d.c., spring charging motor current: 10 A, spring charging duration: 2 sec., 
close coil voltage range: 90­130 V d.c., close coil current: 5 A, Trip coil voltage range: 70­140 
V d.c., Trip coil current rating: 5 A, Closing time: 6 cycles, Tripping time: 2 cycles. 
IV­ Overhead line (segment oh1): 
Conductor material & size: Al 1350 & 556.5, Strands quantity/Ø in mil: 19/171, Post insulators 
voltage: 34 KV, BIL: 200 KV, Wooden pole class: 4, Material: western red cedar, Length of 
pole: 65 ft, Span: 120 ft, Configuration of line: vertical plane (3 ft between phase A & B and B 
& C, 6 ft between A & C). 
V­ Overhead line (segment oh2): same as segment 1 
VI­ Underground section, ug1 (fuse + L.A. + cable length):
­Fuse cutout (f1): Fuse type & speed: 65 K 
­Termination: (t1): Rated voltage: 25 KV, Type: heat shrinkable. 
­Lightning arresters: MCOV: 15 KV, Duty cycle: 18 KV, Type: intermediate. 
­Cable: Insulation: XLPE,  Ɛ= 3.5, Conductor: Al, Length: 1000 ft, Size: 4/0 
­Splice(sp):Rated voltage: 25 KV, Type cold shrinkable. 
VII­ Customer substation:­Power transformer:Apparent power: 5 MVA, Primary/secondary 
winding voltage: 25/.6 KV, Impedance on 5 MVA base: 7 %, X/R ratio: 12, Primary winding 
BIL: 150 KV, Core & winding design: 3­legged & disc. ­Motors:Nominal volage: 600 V, 
Horsepower (collectively­for all connected motors): 4000 HP, RPM (all motors): 1800 ­Heating 
& lighting loads:Active power: .5 KW, rated voltage: 347 V.Assuming a 5 MVA constant power 
load connected to bus 2 and 5 MVA to bus3, perform a load flow study on this system. Ignoring 
motor contribution, calculate the fault currents for the following conditions: L­L­L at bus 3 & 5, 
perform voltage sensitivity calculations and give separately the motor contribution level in each 
case; L­G, L­L & L­L­G at bus 3. Calculate the voltage on all buses if all 4000 HP motors to 
start simultaneously (under above load conditions on buses 2 & 3), specify the method used. 
Calculate a failure rate per year for the utility and the industrial distribution systems. Specify 
whether the number of failures per year per component & the number of outage hours per 
incident (failure) are assumed or obtained from tables, and if the last indicate which ones. 
Note: The transformer windings connection type & the neutral connection of the neutral to 
ground (if accessible or applicable) affect the equivalent zero sequence network of the system. 
The zero sequence network comes to play only when the fault incudes a connection to ground 
like single phase to ground, double line to ground or 3­phase to ground fault. Fig. 15 provides 
the equivalent zero sequence networks for the common transformer connections, from it other 
zero sequence networks for other connections can be deducted. 
I­ Basic calculations: 
1) For the overhead lines: calculate the inductance in H/1000 ft., the capacitance in F/1000 ft. 
then calculate the reactance and capacitance of the line. 
2) For the underground segments: calculate the constants mentioned above plus the sectio 
resistance. 
OVERHEAD LINE (SEGMENTS 1 & 2): 

L = 2(10­7) ln[(3)(3)(6)].3333333/(.855)(.7788)/2 = 2(2.56)/(3.28)(10000)(.12) = 187 (10­7) 
Henry/120 ft 
XL = 2 π f L = .007 OHM 

C = 10­9(120/3.28) /18(ln[(3)(3)(6)].3333333/.855/2) = 1.36(10­9) Farad/120 ft 
XC = 1/2 C f π = .0019(10+9) OHM 
UNDERGROUND SECTION: 
Φ (over insulation) = 1.08", Φ (over conductor) = .521" 
L = 2(10­7) [ln 1.08/(.521)(.7788)] (1000/3.28) = .597/(10000) H/1000ft 
XL = .0225 Ω 

C = 3.5(10­9)(1000/3.28)/18 (ln (1.08/.521) = 81.3(10­9) F/1000 ft 
XC = 32627 Ω 
R/1000 ft = .0927 (1000)(144)/.166 = .0804 W/1000ft 
3)Base values: 
Select MVAbase and KVbase on the primary of the first transformer from the source side in the 
system under study. A common value of MVA base is 100 but in this problem it is chosen to be 
20 MVA (the MVA rating of the transformer). MVAbase will remain constant for all the system 
sections, the base KV will be transformed from one side to the other of the transformer 
according to the transformer ratio. KVbase (@ bus 1) = 25, KVbase (@ bus 5 ) = .6 
Ibase1 = 20(1000)/1.732(25) = 461 amp., Ibase2 = 19245 amp. 
Zbase1 = KVbase(KVbase)/MVAbase = 25(25)/20 = 31.25 Ω , Zbase2 = .6(.6)/20 = .018 OHM 
REACTANCE & IMPEDANCE DIAGRAMS:are shown in fig. 16 

PER UNIT VALUES:
Positive sequence: 
tr1: X1 =.11, R1 = .0055 
oh1 & oh2: X1 = .007/31.25 = .00022, R1 = [1/556.5(7.854)(10000)][144(.092)] = 30.5 µ Ω/ft = 
.00366 Ω /120 ft = .00012 p.u. 
ug1: X1 = .00072, R1 = .0025 
tr2: X1 = .07(20/5)(1/31.25) = .28, R1 = .023 
M: X1 = .2 (20000/350) = 11.4 
Negative sequence: 
All ­ve sequence values are equal to +ve sequence values for stationary components i.e. 
conductors, cables,transformers. Assume for motors X2 = .15 rating as a base @ 20 MVA, 
X2 = 8.6 p.u. 
Zero sequence: 
oh1 & oh2: Xo = .0022 
ug1: Xo = .0014 
tr1: Xo = .11 
tr2: Xo = .28 
M: Xo = .04 (20000/350) = 2.3 p.u. 
II­ Load flow studies: 
All values are in p.u. 
r12 = r23 = .00012, x12 = x23 = .00022, r34 = .0025, x34 = .00072, r45 = .023, x45 = .28 
P at bus 2 (scheduled) = P at bus 3 = ­4.25 MW 
Q at bus 2 (scheduled) = Q at bus 3 = ­2.6 MVAR 
P at bus 5 = ­3.48 (including all motors) 
Q at bus 5 = ­1.84 (motor load only, as other loads have p.f. = 1) 
V at buses 1, 2, 3, 4, 5 =1 for the first iteration. 
d at buses 1, 2, 3, 4, 5 = 0 for the first iteration 
Z12 = .00025, Z23 =.00025, Z34 = .0026, Z45 = .281 Home page of VePi

2)
an12 = tan ­1 x12/r12 = 61, an23 = tan ­1 x23/r23 = 61, an34 = 90 ­ tan ­1 x34/r34 = 74, 
an45 = tan ­1 x45/r45 
g12 = y12 cos ­an12, g23 = y23 cos ­an23, g34 = y34 cos ­an34, g45 = y45 cos ­an45 
b12 = y12 sin ­an12, b23 = ­y23 sin ­an23, b34 = y343 sin ­an34, b45 = y45 sin ­an45 
Fig. 17 below showes the impedance diagram with the resistance & reactance values of the 
different system elements. 
The above circuit can be further reduced to 4 buses by combining the impedances between bus 3 
& 4 and bus 4 & 5 as there is no load connected to bus 4. In this case an34 = ATN x34/r34. All 
the equtions then has to reflect this reduction in the number of buses and the impedance 
(admittance) combination. 
gb11 = g12, gb22 = g12 + g23, gb33 = g g23 + g34, gb44 = g34 + g45, gb55 = g45. 
gb12 = ­g12, gb21 = ­g12, gb23 = ­g23gb32 = ­g23, gb34 = gb43 = ­g34, gb45 = gb54 = ­g45. 
bb11 = b12, bb22 = b12 + b23, bb33 = b23 + b34, bb44 = b34 + b45, bb55 = b45. 
bb12 = bb21 = ­b12, bb23 = bb32 = ­b23, bb34 = bb43 = ­b34, bb45 = bb54 = ­b45. 
Note: the * is equivalent to the multiplication sign x. In quite a few programing languages the 
astrix means multiplication to the language compiler. 
pb2 = ((gb22) * ((v2) ^ 2)) + ((v2 * v1) * (­y12 * COS(­an12 + d1 ­ d2)) + (v2 * v3) * (­ 
y23 * COS(­an23 + d3 ­ d2))) 
pb3 = ((gb33) * ((v3) ^ 2)) + ((v2 * v3) * (­y23 * COS(­an23 + d2 ­ d3)) + (v3 * v4) * (­ 
y34 * COS(­an34 + d4 ­ d3))) 
pb4 = ((gb44) * ((v4) ^ 2)) + ((v4 * v3) * (­y34 * COS(­an34 + d3 ­ d4)) + (v5 * v4) * (­ 
y45 * COS(­an45 + d5 ­ d4))) 
pb5 = ((gb55) * ((v5) ^ 2)) + ((v5 * v4) * (­y45 * COS(­an45 + d4 ­ d5))) 
diffp2 = ((p2 / 100) ­ pb2) / v2 
diffp3 = ((p3 / 100) ­ pb3) / v3 
diffp4 = ((p4 / 100) ­ pb4) / v4 
diffp5 = ((p5 / 100) ­ pb5) / v5 
y110 = bb22 / bb22 
y120 = ­bb23 / ­bb22 
y130 = ­bb24 / ­bb22 
y140 = ­bb25 / ­bb22 
y220 = ­bb33 ­ (­bb32) * (­bb23) / (­bb22) 
y230 = ­bb34 ­ (­bb32) * (­bb24) / (­bb22) 
y240 = ­bb35 ­ (­bb32) * (­bb25) / ­bb22 
y320 = ­bb43 ­ (­bb42) * (­bb23) / ­bb22 
y330 = ­bb44 ­ (­bb42) * (­bb24) / ­bb22 
y340 = ­bb45 ­ (­bb42) * (­bb25) / ­bb22 
y420 = ­bb53 ­ (­bb52) * (­bb23) / ­bb22 
y430 = ­bb54 ­ (­bb52) * (­bb24) / ­bb22 
y440 = ­bb55 ­ (­bb52) * (­bb25) / ­bb22 
y221 = y220 / y220 
y231 = y230 / y220 
y241 = y240 / y220 
y331 = y330 ­ (y320) * (y230) / y220 
y341 = y340 ­ (y320) * (y240) / y220 
y431 = y430 ­ (y420) * (y230) / y220 
y441 = y440 ­ (y420) * (y240) / y220 
y332 = y331 / y331 
y342 = y341 / y331 
y442 = y441 ­ (y431) * (y341) / y331 
int1 = diffp2 / ­bb22 
int2 = (diffp3 ­ (­bb32 * int1)) / y220 
int3 = (diffp4 ­ (­bb42 * int1) ­ (int2 * y320)) / y331 
int4 = (diffp5 ­ (­bb52 * int1) ­ (int2 * y420) ­ (int3 * y431)) / y442 
dd5 = int4 
dd4 = int3 ­ (dd5 * y342) 
dd3 = int2 ­ (dd4 * y231) ­ (dd5 * y241) 
dd2 = int1 ­ (dd3 * y120) ­ (y130 * dd4) ­ (y140 * dd5) 
d21 = d2 + dd2 
d31 = d3 + dd3 
d41 = d4 + dd4 
d51 = d5 + dd5 
dq2 = (1 / v2) * ((q2 / 100) + ((bb22) * (v2 ^ 2)) + ((v1 * v2) * (­y12 * SIN(­an12 + d1 
­ d21))) + ((v3 * v2) * (­y23 * SIN(­an23 + d31 ­ d21)))) 
dq3 = (1 / v3) * ((q3 / 100) + ((bb33) * (v3 ^ 2)) + ((v3 * v2) * (­y23 * SIN(­an23 + 
d21 ­ d31))) + ((v3 * v4) * (­y34 * SIN(­an34 + d41 ­ d31)))) 
dq4 = (1 / v4) * ((q4 / 100) + ((bb44) * (v4 ^ 2)) + ((v4 * v3) * (­y34 * SIN(­an34 ­ 
d41 + d31))) + ((v5 * v4) * (­y45 * SIN(­an45 + d51 ­ d41)))) 
dq5 = (1 / v5) * ((q5 / 100) + ((bb55) * (v5 ^ 2)) + ((v4 * v5) * (­y45 * SIN(­an45 + 
d41 ­ d51)))) 
intv1 = dq2 / ­bb22 
intv2 = (dq3 ­ (­bb32 * intv1)) / y220 
intv3 = (dq4 ­ (­bb42 * intv1) ­ (intv2 * y320)) / y331 
intv4 = (dq5 ­ (­bb52 * intv1) ­ (intv2 * y420) ­ (intv3 * y431)) / y442 
dv5 = intv4 
dv4 = intv3 ­ (dv5 * y342) 
dv3 = intv2 ­ (dv4 * y231) ­ (dv5 * y241) 
dv2 = intv1 ­ (dv3 * y120) ­ (y130 * dv4) ­ (y140 * dv5) 
v21 = v2 + dv2 
v31 = v3 + dv3 
v41 = v4 + dv4 
v51 = v5 + dv5 
d21, d31, d41, d51, v21, v31, v41, v51 values are used as the phase angles and bus voltages for 
the second iteration and the above process is repeated. The above process is repeated until the 
active and reactive power mismatches at the different buses are zero or within an acceptable low 
range. The final voltage and angle (d) levels can then be used to calculate the active and reactive 
power flow between the buses. A program can be written using the above model to enable the 
completion of this load flow study. 
III­ Fault studies: 
• L­L­L fault on bus 3:only +ve sequencce reacance is considered in this case (fig.18) 

Using the circuit reduction method (rather than the impedance bus model that most suits 
performing such studies on personal computers) and assuming a prefault voltage (Vf) = 1 p.u. 
I fault = 1/Zeq = 1/.11044 = 9 p.u. = 9 (461) = 4175 amp. 
Motor Contribution: 
Xm = 11.4, equivalent for all motors (Xeq) = 1/[(1/11.4)(10)] = 1.14 p.u. 
Motor contribution for a 3 phase fault on bus 3 = 1/(.28 + .00072 + +1.14) = .7 p.u. = .7 (461) = 
323 amp. 
Voltage Sensitivity (ignoring motor contribution): 
Voltage on bus 1 = Vf [1­ (.11/.11044)] = .004 p.u. = 100V 
Voltage on bus 2 = .002 p.u. = 50 V 
• L­L­L fault at bus 5: fig. 18 shows the +ve sequence X diagram. 
Ifault = 1/.39 = 2.5 p.u. (ignoring motor contribution) 
motor contribution current = 1/1.14 = .88 p.u. 
Fault current = 2.5 (19254) + .88 (19254) = 48135 + 16943 = 65 KA 
Voltage on bus 1 = 1[ 1­(.11/.39)] = .72 p.u. 
Voltage on bus 2 = voltage at bus 3 = .71 p.u. 
voltage on bus 4 = .7 p.u. 
• L­G fault at bus 3: 
equivalent +ve sequence reactance = .11044 p.u. = equivalent ­ve sequence reactance 
zero sequence equivalent = .1108 p.u. 
Ifault = 3/.3352 = 8.9 p.u. = 4100 amp. 
• L­L fault on bus 3: 
Zeq1 = Zeq2 = .11044 
fault current = .866(2)(1)/.22088 = 7.83 p.u. = 3614 amp. 
• L­L­G fault on bus 3: 
I1 = Z2(Z0)/(Z2+Z0), I2 = Vf/(I1+Z1), I3 = Vf ­ (I2)(Z1), Ifault = 3 (I3)/Z1 
I1 = (.1144)(.11044)/(.1144+.11044) = .056, I2 = 1/(.056+.11044) = 6 
I3 = 1 ­ (6)(.11044) = .337, Ifault = 3(.337)/.11044 = 8.8 p.u. = 4056 amp. 
IV­ Motor starting study: 
Modifications will be made to the model given previously for the load flow study in order that 
the voltage levels at the different buses during the motor starting period can be obtained. The 
most simple method is used here "the snap shot". The motors (load) will be presented as 
constant impedance (equal to its transient reactance on the right base MVA). bb55 = bb45 + 
(1/motst), where motst is the motor (or equivalent reactance of all motors to be investigated) and 
is used with a negative sign. An approximate solution to obtain the starting duration of a motor 
was given in LESSON 1, using the acceleration­torque/time analysis method. 
A program simillar to the one to be written to solve for the load flow between the different 
buses for specific bus loads can be written to enable the completion of this special load flow 
study. 
V­ Reliabilty calculation for the utility side: 
This part of the example includes 2 overhead segments and 1 underground run. 
The elelments are : 
power transformer: .003(130) = .39 hours of downtime per year 
circuit breaker: .0034(26.8) = .09 hours/year 
overhead segment1: 120(.7)(.7)(.7)(.00005)(5) = .01 hours/year 
overhead segment2: .01 hours/year 
fuse cutout + fuse element: .005(3) = .015 hours/year 
splice: .0003(3)(25) = .0225 hours/year 
U/g cable (1000ft length): 1000(.15)(.1)(.7)(.00005)(5)(2) = .00525 hours/year 
The above numbers were based partially on IEEE standard # 493 and the following 
assumptions: 
total number of lines/cables network related failures per year = 26. 
the average downtime hours/failure = 5. 
the total length of the overhead conductors and underground cables = 524,800 ft. 
total failures/year/unit length (ft) = .00005. 
the exposure factor for overhead section = .7 
the exposure factor for underground cable = .15 
the conductor factor for overhead = .7 
the conductor factor for underground = .1 
the upstream protection device factor for both overhead and underground = .7 
cable factor = 2 (function of switching schemes, fault locating philosophy, method of 
laying/pulling of cables, cable splices types and cable trmination/elbows failure or replacement 
rates. 
Average hours of downtime/year .52 = 30 minutes to the unit substation and any other customers 
connected to the subject node (bus). A number proportion to the annual interruption time due to 
only the overhead and underground segments can be deducted from the above calculations. A 
program can be written to calculate the required numbers (failure time per year & weighed 
number of customer interruptions per year). The program can allow for any or all of the 
following factors: line disturbances effects, seasonal load variations or seasonal switching and 
automated zones vs. manual ones. 
VI­ User substation and downstream reliability analysis: 
m.v.c.b. + switchgear: .0036(83) + .0034(26.8) = .39 
2 l.v. c.b. + switchgear: 2(.0027)(4) + .0017(26.8) = .0672 
power transformer: .003(342) = 1.026 
Total number of hours of failure per year = 1.48 hours = 88 minutes. 
13)What are the essential computer programs for the power systems analyst? 
These programs are classified into two distinct types. The first set being the calculating 
programs, the second being the data providing ones. They may be written in any programming 
language or being built as an add­in to off­the­shelf software packages using their macro & 
native languages. Example for programming (or interpreting) languages are: Quickbasic, Visual 
Basic, Pascal, C++, SmallEiffel, Perl, Python, Tcl/Tk & Javascript. The software packages that 
can be used to run such studies or build the data bases (data providing programs) are: Quattro 
Pro, Excel, Access, Fox Pro & Access. 
Click here for a list of the calculating programs that are used often by the power systems 
analysts. 
Click here for a list of the data providing programs to the power systems analysts. 

SUMMARY: 
In this chapter, power systems studies were covered from the required data to perform the 
studies/analysis point of view. The answer to the first question gave the common requirements 
applicable to any power systems study. The answers to questions 2 up till 10 gave the specific 
data that have to be available in order that such specific calculations can be performed. In the 
answer to the question regarding motor starting effects studies, the different methods to 
investigate this condition were listed (snap shot, detailed voltage profile, motor 
torque/acceleration time).The answers to the questions regarding reliability analysis (utility and 
industrial systems), the major components to be considered for such studies were given. The 
other answers covered the specific data required to perform the following studies: TRV, stability, 
fault calculations/coordination, load flow and switching transients. In the answer to question 11, 
the list of the minimum required data to build a power distribution information system was data 
given from line/machine constants to conductors/cables properties to equipment 
ratings/testing/sizing. Question 12 was a numerical example. A hypothetical system was 
presented and the following studies were explained on this system: basic calculations (including 
line constants, base values, reactance/impedance diagrams and +ve/­ve/0 sequence reactances 
p.u. values), load flow, fault calculations, motor starting and reliability analysis. 

REFERENCES: 

1. Greenwood, Allan "Electrical Transients in Power Systems", Wiley . 
2. Wadhwa, C. "Electrical Power Systems", Wiley. 
3. Weedy, B. "Electric Power Systems", Wiley. 
4. Grainger & Stevenson "Power System Analysis", McGraw Hill. 
5. IEEE, "Application Guide for TRV for AC High Voltage Circuit Breakers", C37.011. 
6. IEEE, "Recommended Practice for Power System Analysis", std 399. 
7. IEEE, "Recommended Practice for Design of Reliable Industrial and Commercial Power 
Systems", std 493. 
8. IEEE, "Recommended Practice for Protection and Co­ordination of Industrial and Commercial 
Power Systems", std 242. 
9. IEEE, "Recommended Practice for Electric Power Distribution for Industrial Plants", std 141. 
10.O'Neil, P. "Advanced Engineering Mathematics", Wadsworth. 
11.Gonen, "Electric Power Distribution System Engineering", McGraw Hill. 
12.Kheir, "Automating Power Systems Analysis", Kheir. 
13.Kheir, "Computer Programming for Power Systems Analysts", Kheir. 
Home page of VePi

You might also like