ES-CSM-91

For Balancing and Flow Measurement Applications


Job Name Job Location Engineer Approval Contractor Approval Contractors P.O. No. Representative

Series CSM-91
Sizes: 212" 10" (65 250mm)

Flow Measurement/Balancing Valves


Series CSM-91 Flow Measurement/Balancing Valves are designed for applications on medium or large flow rate HVAC systems, pump packages, and cooling towers. They feature a multi-turn adjustment range for maximum control. Pressure differential readout ports on both sides of the valve to allow for easier installation and positive shutoff for servicing equipment. In addition, these valves also incorporate a micrometer type handwheel adjustment, visually readable settings and a tamper-proof memory stop. The CSM-91s field-convertible design allows the valve to be changed from the factory-standard straight pattern to an optional angle pattern with standard tools and no additional parts. This allows the valve to be used as a replacement for angles or elbows and will not affect the valves accuracy. Maximum flow requires a one-foot pressure drop across the valve to obtain an accurate meter reading with the valve set point from 50% to 100% open for greatest accuracy. The valve should be installed with flow in the direction of the arrow on the valve body, and installed at least five pipe diameters downstream from any fitting, and at least ten pipe diameters downstream from any pump. Two pipe diameters downstream from the CSM-91 should be free of any fittings. When installed, easy and unobstructed access to the valve handwheel and metering ports for adjustment should be provided. Mounting of the valve in piping must prevent sediment buildup in metering ports.

Angle Pattern CSM-91 Straight Pattern

Specifications
A flow measurement valve shall be installed as shown on plans. Each valve shall have two 14 (6mm) NPT brass metering ports with Nordel check valves and gasketted caps located on both sides of valve seat. Two additional 14 (6mm) NPT connections with brass plugs are to be provided on the opposite side of the metering ports for use as drain connections. Drain connections and metering ports are to be interchangeable for measurement flexibility when valves are installed in tight locations. The valve body shall be ductile iron with industrial standard grooved ends. Valve stem and plug disc shall be bronze with ergonomically designed handwheel with multiturn handwheel adjustments. Sizes 212 and 3 (65 and 80mm) five turns, 4 6 (100 150mm) - six turns, and 8 and 10 (200 and 250mm). Flange adaptors shall be supplied to prevent rotation. The valve shall be a Watts Series CSM-91.

Features
Multi-turn adjustment Interchangeable metering and drain ports on both sides of valve Positive shutoff Tamper-proof memory stop  Micrometer type handwheel adjustment - visually readable from distance Field convertible for straight or angle pattern Grooved end connections with optional flange adaptors

Pressure-Temperature
Grooved Ends Only Maximum Working Pressure: 375psi (26.25 bar) Maximum Temperature: 230F (110C) Flange Maximum Working Pressure: Class 125: 175psi (12 bar) Maximum Temperature: 230F (110C)

Nordel is a registered trademark of DuPont Dow Elastomers. Viton is a registered trademark of DuPont Dow Elastomers.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Materials of Construction
Body Ductile Iron ASTM A536 GR65-45-12 Disc Bronze ASTM B584 C-84400 Seat 212" 6" Engineered Resin 8" 10" EPDM Stem  Brass ASTM B-16 212" 6" (65 150mm) Stainless Steel 8" 10" (200 250mm) O-ring Buna-N Memory Lock Brass ASTM B-16 Meter Ports NPT Brass body with Schrader Valve 14" Brass plug Drain Tappings (2)

Pressure Temperature
Temperature C
-46 -29 -18 400 375 300 250 200 100 0 -50 -20 0 50 100 150 200 230 10 38 66 93 110 2760 2585 2070 1724 1380 690 250

Pressure psi

Optional Equipment
Flange Adapters Ductile iron Flange Gaskets EPDM Insulation Fiberglass
Note: Series CSM-91 valves are shipped with grooved ends stan dard. For com pan ion flang es, please specify size and class rat ing when or der ing. In su la tion blocks are also or dered sep ar ate ly from valve. Please spec i fy size when or der ing.

Note:  For temperatures between 230F and 300F


Legend

Temperature F

(110C and 149C), specify Viton Elastomers

A  Ductile iron flange adapters for ANSI 150# flanges B Grooved end with 375psi rated pipe coupling

Flange Adapter Details


Valve size in. mm in. Pipe O.D. Bolt mm No. Size 125psi Bolt Circle Diam. in. mm

Installations
Generally locate the valve five pipe diameters downstream from a fitting; with two diameters downstream from the balancing valve free from fittings. If a balancing valve is located downstream from a circulation pump, allow a distance of ten (10) diameters between the pump and balancing valves (as illustrated below).

212 3 4 5 6

64 76 102 127 152

278 312 412 5916 658

73 89 114 140 168

4 4 8 8 8

x3 x3 58 x 3 34 x 312 34 x 312
58 58

512 6 712 812 912

140 152 191 216 214

DimensionsWeights

Flange Dia.

D Spacer A F

Straight Pattern (Stan dard)

Straight Pattern
Size (DN) A in. mm in. mm in. C mm in. Dimensions D mm in. F mm in. mm in. mm lbs kgs Flange Dia. 125# Spacer Weight

212 3 4 5 6 8 10

65 80 100 125 150 200 250

12 12 14 1712 201116 28316 30

305 305 356 445 525 716 762

958 1012 10916 13116 1334 2458 2612

245 267 268 332 349 625 673

234 2716 3 358 4716 51116 6916

70 62 76 92 113 144 167

2916 3 3716 41516 578 778 91532

65 76 87 125 149 200 241

7 712 914 10 11 1312 16

178 191 235 254 279 343 406

1 1 114 114 2 214 214

25 25 32 32 51 57 57

19 24 42 81 120 310 460

9 11 19 37 54 141 209

Pressure kPa

Spacer C

Flange Dia.

D F2

E F1

Angle Pattern (Convertible)

Angle Pattern (Field Convertible*)


Size (DN) A in. mm in. mm in. C mm in. D mm in. Dimensions E mm in. F1 mm in. F2 mm in. mm in. mm lbs kgs Flange Dia.125# Spacer Weight

212 65 1018 257 958 244 458 117 738 187 2916 65 234 70 7 178 1012 267 378 98 838 213 3 76 2716 62 712 191 3 80 101316 275 321 10916 268 438 111 958 244 3716 87 3 76 914 235 4 100 1258 397 13116 332 512 140 12 305 41516 125 358 92 10 254 5 125 1558 471 1334 349 658 168 1418 359 578 149 4716 113 11 279 6 150 18916 618 2458 625 9316 233 181516 481 778 200 51116 144 1312 343 8 200 24516 683 2612 673 934 248 20516 516 91532 241 6916 167 16 406 10 250 2678 *Note: Series CSM-91 valves are shipped as straight pattern from fac to ry. To convert to angle pattern refer to instruction sheet shipped with valve.

1 1 114 114 2 214 214

25 25 32 32 51 57 57

19 24 42 81 120 310 460

9 11 19 37 54 141 209

For additional information, visit our web site at: www.watts.com

A Watts Water Technologies Company

USA: Tel: (978) 688-1811 Fax: (978) 794-1848 www.watts.com Canada: Tel: (905) 332-4090 Fax: (905) 332-7068 www.wattscanada.ca

ES-CSM-91 1218

2012 Watts

You might also like