Q3: What are the applications for the following kinds of ducts?
Q3.1:Carbon steel?
A3.1:Brechings , Stacks , Hoods & Other high temperature duct syatems.
Q3.2:Aluminium?
A3.2:For moistyre laden air , Ornamental duct systems.
Q3.3:Stainless Steel?
A3.3:Kitchen Hood , Fume Exhaust , Moistuure Laden Air.
Q3.4:Copper ?
A3.4:For duct systems for exposure to outside elements and moisture laden air and
certain chemical exhaust.
Q3.5:F.R.P.?
A3.5:Chemical exhaust , Scrubbers and under ground duct systems.
Q3.6:Concret?
A3.6:For under ground ducts& Air shafts.
Q3.7:Asbestos Cement?
A3.7:For under ground duct systems , Kitchen Exhaust , Chemical Exhaust , High
Temperatue Duct Systems , Flues and Vents.
Q4: What is the maximum static presure rating for duct work?
A4:From 3” up to 10” For high and meduim pressure duct standard.
From 0.5” up to 2” For low pressure duct standard.
Q9: For 10 F Temp. Difference between IN and OUT of Chilled Water Chiller What
is the required rate of water flow rate?
A9:2.4 GPM/Ton refrigeration.
Q10:For Air Handling Unit What is the maximum coil face velocity?
A10: 500 Ft/min.
PLUMBING
Q1:What is the difference between Vent Stack & Stack Vent?
A1:Vent Stack: All the stack acting as a vent.
Stack Vent: The remaining portion between the highst drain / soil connection
and roof level.
Q2:How many Fixture units for the private and public lavatory?
A2:One for private and Two for public.
Q4:What is the maximum water velocity through a piping to avoid hummer and
pipe noises?
A4: 10 Ft/ sec.
Q5:When water is flowing at rate of 10 Ft/sec and the flow is stopped suddenly ,
What will happen?
A5:Apressure of 600 PSI will be created and a dangerous water hummer started.