Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide Issued: April 1999
Status: Update
Version: C/12.04.2006
Data subject to change without notice
Features • Sensitive low-set neutral overcurrent stage • Digital display of setting values, neutral
with definite time characteristic current measured, values recorded at relay
operation, indications, etc.
• High-set neutral overcurrent stage with def-
inite time characteristic • Powerful software support for parameter-
ization and supervision of the relay
• Output relay functions to be freely config-
ured • Continuous hardware and software self-
supervision including auto-diagnosis
• Flexible adaptation to different types of
application • Member of the SPACOM product family
and ABB’s Distribution Automation system
• 1 A and 5 A energizing inputs
• CE marking according to the EC directive
• Serial interface for connecting the relay to
for EMC
a fibre-optic serial bus and further to a sub-
station or network control system
Application The sensitive earth-fault relay SPAJ 111 C is circuit of the earth-fault relay is extremely
designed to be used as a neutral current mea- low which means that the relay can also be
suring feeder earth-fault relay, as generator energized from low output core-balance cur-
interturn fault protection, as capacitor bank rent transformers. Core-balance current trans-
unbalance protection and rotor earth-fault formers can be recommended when
protection. extremely sensitive earth-fault protection is
required. The earth-fault relay can also be
The sensitive earth-fault relay is suited for energized from a set of three phase current
both primary and back-up earth-fault protec- transformers connected in parallel, a so called
tion. The input impedance of the energizing residual current connection.
3
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
Design The sensitive earth-fault relay SPAJ 111 C is power source. The relay communicates with
a secondary relay which is connected to the higher-level data acquisition and control sys-
current transformers of the object to be pro- tems over the SPA bus.
tected. When an earth fault occurs, the relay
delivers an alarm signal, trips the circuit
breaker or starts an external auto-reclose
Self-supervision
relay, depending on the application and the The relay incorporates a sophisticated self-
supervision system with auto-diagnosis,
configuration of the relay.
which increases the availability of the relay
and the reliability of the system. The self-
When the energizing current exceeds the set
supervision system continuously monitors the
start value I0> of the low-set stage, the earth-
hardware and the software of the relay. The
fault relay starts. When the set operate time t>
system also supervises the operation of the
expires, the relay operates. In the same way
auxiliary supply module and the voltages
the high-set stage starts once the set start
generated by the module.
value I0>> is exceeded and, when the set
operate time t>> expires, the relay operates.
When the self-supervision system detects a
permanent internal relay fault, the IRF indica-
The start signal from the sensitive earth-fault
relay is received as contact function. The start tor on the relay front panel is lit. At the same
time the output relay of the self-supervision
signal can be used, for instance, for blocking
cooperating protection relays. system operates and a fault message is trans-
mitted to the higher-level system over the
serial bus. Further, in most fault situations, a
The relay contains one optically isolated logic
fault code is shown in the display of the pro-
input for external incoming control signals,
generally blocking signals. tection relay module. The fault code indicates
the type of the fault that has been detected.
Data communication
The relay is provided with a serial interface
Auxiliary supply voltage
The auxiliary supply of the relay is obtained
on the rear panel. By means of a bus connec-
from an internal plug-in type power supply
tion module type SPA-ZC 17 or SPA-ZC 21
module. Two auxiliary power module ver-
the relay can be connected to the fibre-optic
sions are available: type SPTU 240S1 for the
SPA bus. The bus connection module type
SPA-ZC 21 is powered from the host relay, supply voltage range 80…265 V ac/dc and
whereas the bus connection module SPA- type SPTU 48S1 for the supply voltage range
18…80 V dc. The power supply module
ZC 17 is provided with a built-in power unit,
forms the internal voltages required by the
which can be fed from an external secured
protection relay and the I/O module.
4
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
5
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
6
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
Block diagram
bspaj111
7
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
139 ±1
Panel cut-
136
162
out
dim100
Semi-flush mounting
a b
Raising frame a b
SFM100_1
SPA-ZX104 SPA-ZX110
SPA-ZX105 SPA-ZX115
SPA-ZX106
+0,4 158 263
482,6 –0 (19")
115
ø6
10
177 –0 (4U)
101,6
7
+0,4
312
292
21,5
6
115 98
104_6_10
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
8
Sensitive Earth-fault Relay SPAJ 111 C
1MRS750352-MBG
Product Guide
Order numbers
Earth-fault relay SPAJ 111 C without test adapter RS 421 011-AA, CA, DA, FA
Earth-fault relay SPAJ 111 C including test adapter RS 421 211-AA, CA, DA, FA
RTXP 18
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/dc
rated frequency fn and the auxiliary voltage Uaux of CA equals fn = 50 Hz and Uaux = 18…80 V dc
the relay as follows: DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc
9
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation