BENSON
2
OIL UNIT HEATER
RANGE
INSTALLATI ON COMMISSION ING
SERVICING
USER INSTRUCTIONS
BENSON
Issue 3
October 2007
PART NO 33-65-190
1
BENSON OIL UNIT HEATER
1.5 Warranty 5
2.0 Installation 6
6.0 Commissioning 12
7.0 Servicing 15
12.0 Dimensions 29
2
BENSON OIL UNIT HEATER
3
BENSON OIL UNIT HEATER
4
BENSON OIL UNIT HEATER
(d That it is suitable for the electrical supply f) The main electrical supply input to the
heater has been interrupted during the
If any of the points are not satisfied then heating mode
contact should be made with the sales office
at Benson Heating as soon as possible by g) The heater has been subject to and
telephoning 01547 528534. in the case of affected by the ingress of water in any form
claims for damage, this must be reported in
writing within 24 hours of delivery, in order to h) The heater is not operated at the rating’s
comply with insurance criteria. laid down in the manufacturers technical
THE WARRANTY REGISTRATION CARD specifications
SUPPLIED WITH THE HEATER MUST BE
COMPLETED AND RETURNED IN THE i) The heater has not been operated or used
PRE PAID ENVELOPE TO BENSON within the normal scope of its intended
HEATING ON COMPLETION OF application
COMMISSIONING
Warranty claims made without this j) The manufacturer's recommended
condition being fulfilled will not be minimum service requirements have not
processed been complied with
5
BENSON OIL UNIT HEATER
Indirect fired heaters must not be located in Air pressure within the area heated and the
hazardous areas, however, it is permissible outside air pressure must remain the same,
for the heater to supply air to such areas. factors influencing this would be the
presence of extraction systems, ventilation
The heater must not be installed within an systems, and various types of process plant.
environment where there is a high OUHA 200-350 models can be installed to
concentration of chlorides, fluorides, salts, or allow the fans to work in opposite directions .
other aggressive or volatile chemicals / This enables the heater to be installed
compounds. centrally in the area to be heated and allows
Nor should the heater be positioned where warm air to be discharged to both the front
the burner could be adversely affected by and rear of the heater
high winds or draughts.
2.1 Installation Mounting Heights
The heater must be installed so that it is OUHA models
level. Supports for the heater must be
sufficiently robust to withstand the weight of The Heater must be installed within the
the heater and any ancillary equipment. Any mounting heights indicated below in metres
combustible material adjacent to the heater
or flue system must be so placed or shielded
so that its surface temperature does not
exceed 65C Model OUHA 100 140 200
6
BENSON OIL UNIT HEATER
7
BENSON OIL UNIT HEATER
Where combustion air ventilation is required For heaters with a rated input of more than
as dictated by the previous criteria then that 60 kW — 270 cm2 plus for each kW of rated
ventilation can be via permanent ventilation input over the 60 kW threshold an additional
openings / grilles situated at low level (I.e. 2.25 cm2
below the flue takeoff spigot ) and with the
free area of such grilles as :- Alternatively mechanical input (not extract)
For heaters with a rated input of less than ventilation may be used in association with
60 kW — 4.5 cm2 per kW of heat input either mechanical or natural extract and with
For heaters with a rated input of more than a ventilation flow rate of 2.16m3/h per kW of
60 kW — 270 cm2 plus for each kW of rated total rated input.
input over the 60 kW threshold an additional
4.5 cm2 Mechanical ventilation systems where fitted
must be provided with safety interlocks to
Or by mechanical input (not extract) prevent heater operation in case of air flow
ventilation in association with either failure
mechanical or natural extract and with a
ventilation flow rate of 1.08m3/h per kW of Where the combustion air intake is not
total rated input ducted to atmosphere heater installed in
flue only configuration then ventilation can
Where mechanical extract is used to be via a permanent ventilation opening /
complement the above then the extract rate grille situated at both Low level (Inlet) and
shall be 2.16m3/h per kW of rated heat input high Level (Outlet) and with the free area of
Mechanical ventilation systems where fitted such grilles as :-
must be provided with safety interlocks to Low level (Inlet)
prevent heater operation in the event of
airflow failure. For heaters with a rated input of less than
60 kW — 9.0 cm2 per kW of heat input
8
BENSON OIL UNIT HEATER
For heaters with a rated input of more than extend to not less than 100mm above the
60 kW — 540 cm2 plus for each kW of rated bottom of the tank. A non return valve with a
input over the 60 kW threshold an additional metal to metal seat should be fitted,
4.5 cm2 especially if the return pipe work is
terminated at a level above the draw off tube.
High Level (Outlet) The non- return valve must be removable for
service and maintenance purposes, and the
For heaters with a rated input of less than return pipe from the pump must therefore be
60 kW — 4.5 cm2 per kW of heat input extended down into the tank to the same
level as the suction pipe. The use of a Fuel
For heaters with a rated input of more than Deaerator in this type of installation will
60 kW — 270 cm2 plus for each kW of rated reduce the need of a return pipe back to the
input over the 60 kW threshold an additional tank
2.25 cm2
Caution
Alternatively mechanical input (not extract) The Deareator must be fitted the burner
ventilation may be used in association with side of the inlet fuel filter
either mechanical or natural extract , and
with a ventilation flow rate of 3.24m3/h per Maximum lift should not exceed 3.5 metres,
kW of total rated input and the vacuum should not exceed 0.4 bar.
Where mechanical extract is used to Each heater must have a separate fuel
complement the above then the extract rate supply.
shall be 2.06m3/h per kW of rated heat input Note
It is strongly recommended that the separate
Mechanical ventilation systems where fitted manual concerning the operational details of
must be provided with safety interlocks to the burner supplied with the heater as part of
prevent heater operation in case of air flow the information package is studied prior to
failure installation
9
BENSON OIL UNIT HEATER
H I.D. I.D.
H m 8mm 10mm
Maximum 0 35.0 100.0
4 metres 0.5 30.0 100.0
1.0 25.0 100.0
1.5 20.0 90.0
2.0 15.0 70.0
3.0 8.0 30.0
3.5 6.0 20.0
BURNER
H The return line should terminate within the oil tank at the same level
as the suction line; in this case a non return valve is not required.
Should, however, the return line terminate over the fuel level,
a non return valve is essential.
This solution, however, is less safe than the previous one, due to
possibility of leakage of the valve.
Priming the pump: Start the burner and await priming.
Should lock-out occur prior to arrival of the fuel, wait at least 20 seconds
before repeating the operation.
BURNER
1 GATE VALVE
2 IN-LINE FILTER
3 PUMP
4 RELIEF VALVE
5 PRESSURE GAUGE
6 PRESSURE REDUCING VALVE
7 RETURN TO TANK 6 6
7 4 5
1 2
10
BENSON OIL UNIT HEATER
11
BENSON OIL UNIT HEATER
Flue terminals should be fitted on all flues, the make contact with any surfaces liable to be
terminal must be of the approved type, and subject to high temperatures or where the
have outlet grilles on all sides giving a total insulation of the wiring could be impaired as a
free area of at least double that of the flue. result of such contact.
Cables, conduit, and fittings that are used to (d) Check that the heater is installed correctly
make the connection between the isolator and and that the support is adequate.
the heater must conform to the appropriate
IEE regulations. (e) Ensure that warm air delivery outlets are
All heaters are supplied fused and pre-wired, open.
all must be earthed.
The Control fuse ratings are detailed on the (f) Check that fan is free to rotate and the
appliance data plate. guards are in place.
12
BENSON OIL UNIT HEATER
(h) Check that there is provision for flue gas (b) Ensure that the oil supply is turned off.
sampling and that this sample point can be
plugged and sealed after commissioning. (c) If CP2 supplied Select the following
switch settings on the control for the heater
(i) Remove cover from fan limit stat check
that fan limit stat settings have not been On/Standby - Standby
disturbed and are as follows Heat/Ventilation - Heat
(j) Ensure that the burner is securely (f) Check for the following burner sequence
attached to the heater.
13
BENSON OIL UNIT HEATER
14
BENSON OIL UNIT HEATER
(b) If the current drawn is greater than the Additionally, the fan and limit stat has been
stated running current, in most probability this factory set, and must not be re-set without
will be caused by insufficient static formal consent from the manufacturer.
pressure within the ductwork, in which case
system resistance should be increased Reference should be made to the separate
through the introduction of a damper placed as information covering the operational details of
close to the start of the ductwork as possible, the burner and remote controllers.
thereby resulting in a reduction in drawn Only approved spare/replacement parts can
current. be fitted, failure to comply with this can
compromise the safe and efficient running of
The damper should be adjusted until the the heater, and can also invalidate any
current is in accordance with that stated on the warranty claim
data plate.
7.1 Planned Servicing
(c) If the current drawn is too low the duct In order to maintain the efficient operation of
outlet grilles will require opening to reduce the heater it is recommended that the
static pressure and increase air volume, if this following planned servicing and preventative
is not the case overheat cut outs can be maintenance programme is adopted by the
caused user.
Quarterly Inspection
7.0 Servicing (a) Visual inspection of the burner
(b) Clean and check spark electrode
Warning (c) Clean and check photocell
Servicing must be carried out on a regular (d) Check overheat safety is operational
basis, the maximum interval between services
being 1 year. Bi-Annual Inspection
In certain applications the frequency of (a) As per quarterly inspection, plus...
servicing will have to be increased , this to a (b) Combustion check
large extent is governed by the working (c) Smoke test
environment.
It is a requirement that only suitably qualified Annual Inspection
and competent persons are allowed to (a) As per half year inspection, plus...
undertake servicing. (b) Heat exchanger and cleaning
(c) Electrical connections
Before any maintenance or servicing work (d) Main fan motor assembly
is carried out the heater must be shut (e) Oil supply including filter
down and allowed to cool, and have the oil (f) Burner
and electric supplies to it turned off at the (g) Air delivery system
supply valve and isolator (h) Flue
respectively.
Turbulator positions 100-250
Caution
Certain component parts are factory sealed
and are designed so as to be tamper proof.
Usually such items do not require servicing,
and therefore should not be tampered with.
Failure to comply with this can invalidate any
warranty, and can also lead to premature Turbulator positions 300-350
failure. The following parts fall within this
category: room thermostat, time clock, frost
thermostat, controller, and fan motor
assembly .
15
BENSON OIL UNIT HEATER
Burner Lockout
Burner
fails to Fan / Limit
Run Thermostat
Room
Thermostat
No Check Timer
Demand Controls
Heat / Ventilate
Switch
On / Off Switch
Fuel / Air
Problem Air in System Possible Fuel
Contamination
Restricted Fuel
Feed
Check Valves,
Fuel Feed, Filter
Nozzle for
Blockages or
Restrictions
No Spark
Check Check Control
Electrode
16
BENSON OIL UNIT HEATER
Adjust Air
Damper
Air / Fuel Mix Ratio
Incorrect
Check for Air in
Fuel Line
Check Nozzle
Fuel Feed
Restricted Check Filter
Check Fuel
Lines
Check Valves
Check Oil
Pressure
Check Nozzles
Check if Correctly
fitted
Burner
gives a Poor Check if Correct
smokey Combustion size
flame
Check if Damaged
or Worn
Inadequate Flue
Check Flue
Draught
17
BENSON OIL UNIT HEATER
Foreign Matter in
Check Burner
Fan
Fan Motor
Worn / Dry
Burner Suction Lift to Bearing
giving Great
excessive Insecure Burner
noise Fan
Fuel Feed
Restriction
Check for no
Check Fan and Loose
Insufficient Air Motor Contacts
Flow over the Assembly
Heat Exchanger
Check Fan and
Motor are
Secure
Check that
Limit Control
Reset to 100C Fan is not
Incorrectly Set
Blocked or
Check that
Impellor is not
Slipping
18
BENSON OIL UNIT HEATER
19
BENSON OIL UNIT HEATER
20
BENSON OIL UNIT HEATER
21
BENSON OIL UNIT HEATER
22
BENSON OIL UNIT HEATER
23
BENSON OIL UNIT HEATER
24
BENSON OIL UNIT HEATER
25
BENSON OIL UNIT HEATER
Comb Chamber press M/bar 0.14 0.14 0.14 0.14 0.14 0.14
Run Current Axial Amps 1.6 1.6 2.8 2.8 3.4 3.4
Run Current Centrif Amps 8.0 8.0 11.0 11.0 15.0 15.0
Electrical Protection IP 20 20 20 20 20 20
26
BENSON OIL UNIT HEATER
27
BENSON OIL UNIT HEATER
28
BENSON OIL UNIT HEATER
29
BENSON OIL UNIT HEATER
30
BENSON OIL UNIT HEATER
(g) Check for the following burner sequence 10.6 Ventilation only
Caution
Note Repeated or frequent lockouts must be
The time intervals within the ignition investigated and their cause determined by a
sequence may vary slightly between models. qualified and competent engineer.
31
BENSON OIL UNIT HEATER
BENSON HEATING
LUDLOW ROAD
KNIGHTON
POWYS
LD7 1LP
Telephone +44 (0) 1547 528534
Facsimile +44 (0) 1547 520399
email information@bensonheating.co.uk
Web www.bensonheating.com
32